Yaskawa L1000E User Manual

YASKAWA AC Drive-L1000E
AC Drive for Elevator Applications
Quick Start Guide
Type: CIMR-LEA Models:
To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual.
200 V Class: 3.7 to 110 kW (5 to 150 HP) 400 V Class: 4.0 to 132 kW (5 to 175 HP)
L E
DM
O
N
I TO
R
J V
R
O
U
P
N
­1 8
4
D
S
1
D S
2
P W
R
R U
N
D
S
1
D
S
2
S
R
T
E
A
ADY
T
U
R
S
U
N A L
A
R
M
P
(RU
G
O
N)
H
,
B
L
T
B
,
H
B
B E F
, S
E O V
, U
V OH
,OL
OC
, G
F
,S C PF,O
C
:LIG
,
P
GO
F
H
Ot
A
T
,O h e
F
r
B
:
F
B
,
a
O
L
u
F
I
lt
N
C
K
:
LI
G
H
TO
F
F
MANUAL NO. TOEP YAIL1E 01A
Receiving
Mechanical Installation
Electrical Installation
Start-Up Programming &
Operation
Troubleshooting
Periodic Inspection &
Maintenance
Option Card Installation
Specifications
Parameter Table
Standards Compliance
1
2
3
4
5
6
7
A
B
C
Copyright © 2014 YASKAWA ELECTRIC CORPORATION.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
2 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

Quick Reference

Drive a Synchronous PM Motor
L1000E can operate synchronous PM motors. Refer to Flowchart C: Auto-Tuning for PM Motors
on page 66.
Perform Auto-Tuning
Automatic tuning sets motor parameters. Refer to Types of Auto-Tuning on page 68.
Maintenance Check Using Drive Monitors
Use drive monitors to check fans, capacitors, and other components may require maintenance. Refer to Performance Life Monitors Maintenance
Monitors on page 144.
Fault Display and Troubleshooting
Refer to Troubleshooting on page 130.
Refer to UL Standards on page 219.
Standards Compliance
YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 3
4 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

Table of Contents

Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
i. Preface & General Safety ................................................................................................. 7
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
General Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
1. Receiving ......................................................................................................................... 15
Model Number and Nameplate Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
2. Mechanical Installation................................................................................................... 17
Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
3. Electrical Installation ...................................................................................................... 23
Standard Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Main Circuit Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Terminal Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
LED Monitor and Front Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Main Circuit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Control I/O Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Connect to a PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Wiring Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4. Start-Up Programming.................................................................................................... 52
LED Monitor JVOP-184 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Digital Operator JVOP-180 Keys and Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
The Drive and Programming Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Start-Up Flowcharts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Setup Procedure for Elevator Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
S: Elevator Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88
Setup Troubleshooting and Possible Solutions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123
5. Troubleshooting............................................................................................................ 130
Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130
Alarm Detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134
Operator Programming Errors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
Auto-Tuning Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138
Copy Function Related Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
6. Periodic Inspection & Maintenance ........................................................................... 141
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141
Periodic Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .143
Drive Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
7. Option Card Installation ............................................................................................... 148
Prior to Installing the Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Installing the Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .149
YASK AWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 5
Table of Contents
A. Specifications................................................................................................................ 159
Three-Phase 200 V Class Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .159
Three-Phase 400 V Class Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .160
Drive Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .161
B. Parameter Table ............................................................................................................ 163
Understanding the Parameter Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .163
Parameter Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .163
Defaults and Setting Ranges by Display Unit Selection (o1-03) . . . . . . . . . . . . . . . . .217
C. Standards Compliance ................................................................................................. 219
UL Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .219
Safe Disable Input Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .230
EN81-1 Compliant Circuit with one Motor Contactor. . . . . . . . . . . . . . . . . . . . . . . . . .233
Revision History ........................................................................................................................ 234
6 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

i Preface & General Safety

YEA_ com-
i Preface & General Safety

Preface

Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.
This manual is designed to ensure correct and suitable application of L1000E-Series Drives. Read this manual before attempting to install, operate, maintain, or inspect a drive and keep it in a safe, convenient location for future reference. Be sure you understand all precautions and safety information before attempting application.
Applicable Documentation
The following manuals are available for L1000E series drives:
L1000E Series AC Drive Quick Start Guide (This document)
Read this manual first. It contains basic information required to install and wire the drive, in addition
L1000E
CIMR-LE2A0012FAA
200V 3Phase 5.5kW/3.7kW
S/N:
WARNING
Risk of electric shock.
Read manual before installing.
Wait 5 minutes for capacitor discharge after disconnecting power supply.
To conform to requirements, make sure to ground the supply neutral for 400V class.
After opening the manual switch between the drive and motor, please wait 5 minutes before inspecting, performing maintenance or wiring the drive.
Hot surfaces
Top and Side surfaces may become hot. Do not touch.
RUN DS1 DS2
RUN DS1 DS2 STATUS
:LIGHT :BLINK :LIGHT OFF
AVERTISSMENT
Risque de décharge électrique.
Lire le manuel avant l'installation.
Attendre 5 minutes après la coupure de l'alimentation, pour permettre la décharge des condensateurs.
Pour répondre aux exigences , s assurer que le neutre soit relié à la terre, pour la série 400V.
Après avoir déconnécte la protection entre le driver et le moteur, veuillez patienter 5 minutes avain d’effectuer une opération de montage ou de câblage du variateur.
Surfaces Chaudes
Dessus et cotés du boitier Peuvent devenir chaud. Ne Pas toucher.
危 険
けが.感電のおそれがあります。
据え付け、運転の前には必ず取扱説明書を読むこと。
通電中および電源遮断後5分以内はフロントカバー を外さない事。
400V級インバータの場合は、電源の中性点が接地 されていることを確認すること。(対応)
保守・点検、配線を行う場合は、出力側開閉器を 遮断後5分待って実施してください。
高温注意
インバータ上部、両側面は高温になります。 触らないでください。
PWRLED MONITOR JVOP-184
READY RUN ALARM(RUN) PGOH,LT BB,HBB EF,SE OV,UV OH,OL OC,GF,SC,PGO CPF,OFA,OFB,OFC Other Fault
NPJT31470-1
to an overview of fault diagnostics, maintenance, and parameter settings. Use the information in this book to prepare the drive for a trial run with the application and for basic operation.
L1000E Series AC Drive Safety Precautions
This manual is packaged with the product and contains essential safety information and simplified information for the L1000E series AC drive. This document also provides basic instructions on mechanical installation, a connection diagram, main circuit and control circuit connections, switch and jumper configuration, basic troubleshooting, standards compliance and fusing, drive specifications and an abbreviated parameter list.
L1000E Series AC Drive Technical Manual
This manual provides detailed information on parameter settings, drive functions, and MEMOBUS/ Modbus specifications. Use this manual to expand drive functionality and to take advantage of higher performance features.

General Safety

Supplemental Safety Information
General Precautions
• The diagrams in this manual may be indicated without covers or safety shields to show details. Replace the covers or shields before operating the drive and run the drive according to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual.
• When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative or the nearest Yaskawa sales office and provide the manual number shown on the front cover.
• If nameplate becomes worn or damaged, order a replacement from your Yaskawa representative or the nearest Yaskawa sales office.
YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 7
i Preface & General Safety
W ARNING
DANGER
W ARNING
CAUTION
NOTICE
DANGER
Read and understand this manual before installing, operating or servicing this drive. The drive must be installed according to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result in serious or fatal injury or damage to the products or to related equipment and systems.
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
WARNING! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
CAUTION! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
Indicates a property damage message.
NOTICE: may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
Safety Messages
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in this manual.
Electrical Shock Hazard
Do not connect or disconnect wiring or service the drive while the power is on.
Failure to comply will result in death or serious injury.
Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching any components.
8 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
i Preface & General Safety
W ARNING
Sudden Movement Hazard
The drive system or elevator may start unexpectedly upon application of power, resulting in death or serious injury.
• Clear all personnel from the drive, motor, and machine area before applying power.
• Secure covers, couplings, shaft keys, and machine loads before applying power to the drive.
Ensure there are no short circuits between the main circuit terminals (R/L1, S/L2, and T/L3) or between the ground and main circuit terminals before restarting the drive.
Failure to comply may result in serious injury or death and will cause damage to equipment.
System may start unexpectedly upon application of power when the Auto-restart function is enabled resulting in death or serious injury.
Use care when enabling Auto-restart as this function may cause unintended start of the elevator.
Use parameter S1-12 to enable/disable automatic switching of the Motor Contactor Control output signal during Auto-Tuning.
When using setting S1-12 = 1, ensure that the multi-function output terminals are properly wired and in the correct state before setting parameter S1-12.
Failure to comply could result in damage to the drive, serious injury or death.
Electrical Shock Hazard
Do not attempt to modify or alter the drive in any way not explained in this manual.
Yaskawa is not responsible for damage caused by modification of the product made by the user. Failure to comply could result in death or serious injury from operation of damaged equipment.
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual.
When a drive is running a PM motor, voltage continues to be generated at the motor terminals after the drive is shut off while the motor coasts to stop. Take the precautions described below to prevent shock and injury:
• In applications where the machine can still rotate even though the drive has fully stopped a load, install a switch to the drive output side to disconnect the motor and the drive.
• Do not allow an external force to rotate the motor beyond the maximum allowable speed or to rotate the motor when the drive has been shut off.
• Wait for at least the time specified on the warning label after opening the load switch on the output side before inspecting the drive or performing any maintenance.
• Do not open and close the load switch while the motor is running, as this can damage the drive.
If the motor is coasting, make sure the power to the drive is turned on and the drive output has completely stopped before closing the load switch.
Do not connect or disconnect wiring to the drive or motor while the power is on.
Failure to comply will result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 9
i Preface & General Safety
NOTICE
W ARNING
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual.
Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work on the drive.
Do not change wiring, remove covers, connectors or options cards, or attempt to service the drive with power applied to the drive.
Failure to comply could result in death or serious injury. Disconnect all power to the drive and check for unsafe voltages before servicing.
Do not allow unqualified personnel to use the equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives.
Fire Hazard
Drive Short-Circuit Current Rating
Install adequate branch circuit protection according to applicable local codes and this Installation Manual.
Failure to comply could result in fire and damage to the drive or injury to personnel.
The device is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 240 Vac maximum (200 V class) and 480 Vac maximum (400 V class) when protected by branch circuit protection devices specified in this manual.
Applications using a braking option should wire a thermal relay so that the output contactor opens when the thermal relay trips.
Inadequate braking circuit protection could result in death or serious injury by fire from overheating resistors.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
Equipment Hazard
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Failure to comply could result in damage to the drive or braking circuit.
Observe proper electrostatic discharge procedures (ESD) when handling the drive, circuit boards, and option cards.
Failure to comply may result in ESD damage to the drive circuitry.
10 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
i Preface & General Safety
NOTICE
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Do not lift the drive up while the cover is removed.
This can damage the terminal board and other components.
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the drive.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
General Application Precautions
Motor Selection Drive Capacity
The output current should not exceed 133% for 30 s of the drive rated current. Select a drive that can output enough current when accelerating a load at 100%.
For specialized motors, make sure that the motor rated current is less than the rated output current for the drive.
Starting Torque
The startup and acceleration characteristics of the motor are restricted to the drive's overload current rating (150% rated current for 60 s).
The overload rating for the drive determines the starting and accelerating characteristics of the motor. Expect lower torque than when running from line power. To get more starting torque, use a larger drive or increase both the motor and drive capacity.
Stopping Fast Stop
When the drive faults out, a protective circuit is activated and drive output is shut off. This, however, does not stop the motor immediately. A mechanical brake may be required to stop the motor if Fast Stop deceleration is insufficient.
Mechanical Brake
A mechanical brake is required to prevent the elevator from free falling during a drive fault condition.
Repetitive Starting/Stopping
Elevators and other applications with frequent starts and stops often approach 150% of their rated current values. Heat stress generated from repetitive high current will shorten the life span of the IGBTs.
Yaskawa recommends lowering the carrier frequency, particularly when audible noise is not a concern. It is beneficial to reduce the load, increase the acceleration and deceleration times, or switch to a larger drive to help keep peak current levels under 133%. Be sure to check the peak current levels when starting and stopping repeatedly during the initial test run, and make adjustments accordingly.
Installation Enclosure Panels
Keep the drive in a clean environment by installing the drive in an enclosure panel or selecting an installation area free of airborne dust, lint, and oil mist. Be sure to leave the required space between drives to provide for cooling, and take proper measures so the ambient temperature remains within allowable limits and keep flammable materials away from the drive. Yaskawa offers protective designs for drives that must be used in areas subjected to oil mist and excessive vibration. Contact Yaskawa or your Yaskawa agent for details.
YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 11
i Preface & General Safety
Installation Direction
NOTICE: Install the drive upright as specified in the manual. Refer to Mechanical Installation on page 17 for more information on
installation. Failure to comply may damage the drive due to improper cooling.
Settings DC Injection Braking
NOTICE: Excessive current during DC Injection Braking and excessive duration of DC Injection Braking can cause motor overheating.
Adjust DC Injection parameters to prevent motor overheating.
Acceleration/Deceleration Ramp
Acceleration and deceleration times are affected by the amount of torque generated by the motor, the load torque, and the inertia moment. Set a longer accel/decel time when Stall Prevention is enabled. The accel/decel times are lengthened for as long as the Stall Prevention function is in operation. Install one of the available braking options or increase the capacity of the drive for faster acceleration and deceleration.
General Handling Selecting a Molded Case Circuit Breaker or Ground Fault Circuit Interrupter (GFCI)
Select an appropriate GFCI. This drive can cause a residual current with a DC component in the protective earthing conductor. Where a residual current operated protective or monitoring device is used for protection in case of direct or indirect contact, always use an GFCI of type B according to IEC 60755.
Select a MCCB (Molded Case Circuit Breaker) with a rated current that is 1.5 to 2 times higher than the rated current of the drive in order to avoid nuisance trips caused by harmonics in the drive input current.
WARNING! Sudden Movement Hazard. Install a properly controlled contactor on the input-side of the drive for applications where power should be removed from the drive during a fault condition. Improper equipment sequencing could result in death or serious injury.
WARNING! Fire Hazard. Shut off the drive with a magnetic contactor (MC) when a fault occurs in any external equipment such as braking resistors. Failure to comply may cause resistor overheating, fire, and injury to personnel.
To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the drive power supply off and on more than once every 30 minutes. Frequent use can damage the drive. Use the drive to stop and start the motor.
Inspection and Maintenance
WARNING! Electrical Shock Hazard. Capacitors in the drive do not immediately discharge after shutting off the power. Wait for at least
the amount of time specified on the drive before touching any components after shutting off the power. Failure to comply may cause injury to personnel from electrical shock.
CAUTION! Burn Hazard. Because the heatsink can get very hot during operation, take proper precautions to prevent burns. When replacing the cooling fan, shut off the power and wait at least 15 minutes to be sure that the heatsink has cooled down. Failure to comply may cause burn injury to personnel.
WARNING! Electrical Shock Hazard. When a drive is running a PM motor, voltage continues to be generated at the motor terminals after the drive is shut off while the motor coasts to stop. Take the precautions described below to prevent shock and injury:
• In applications where the machine can still rotate after the drive has fully stopped a load, install a load disconnect switch on the drive output side to disconnect the motor and the drive.
• Do not allow an external force to rotate the motor beyond the maximum allowable speed or to rotate the motor when the drive is powered off.
• Wait for at least the time specified on the warning label after opening the load switch on the output side before inspecting the drive or performing any maintenance.
• Do not open and close the load switch while the motor is running.
• If the motor is coasting, make sure the power to the drive is turned on and the drive output has completely stopped before closing the load switch to reconnect the drive to the motor.
Wiring
Yaskawa recommends using ring terminals on all drive models for UL/cUL compliance. Use only the tools recommended by the terminal manufacturer for crimping.
12 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
i Preface & General Safety
Transporting the Drive
NOTICE: Never steam clean the drive. During transport, keep the drive from coming into contact with salts, fluorine, bromine, phthalate
ester, and other such harmful chemicals. Failure to comply may damage the drive.
Motor Application Precautions
Standard Induction Motors Insulation Tolerance
NOTICE: Consider motor voltage tolerance levels and motor insulation in applications with an input voltage of over 440 V or particularly
long wiring distances.
NOTICE: Ensure that the motor is suitable for inverter duty and/or the motor service factor is adequate to accommodate the additional heating with the intended operating conditions. A motor connected to a PWM drive may operate at a higher temperature than a utility­fed motor and the operating speed range may reduce motor cooling capacity.
High-Speed Operation
NOTICE: Mechanical damage may occur with the motor bearings and dynamic balance of the machine when operating a motor
beyond its rated speed. Operate the motor within specifications to prevent motor damage.
Low-Speed Range
The cooling fan of a standard motor should sufficiently cool the motor at the rated speed. As the self-cooling capability of such a motor reduces with the speed, applying full torque at low speed will possibly damage the motor. Reduce the load torque as the motor slows to prevent motor damage from overheat. Use a motor designed specifically for operation with a drive when 100% continuous torque is needed at low speeds.
Torque Characteristics
Torque characteristics differ compared to operating the motor directly from line power. The user should have a full understanding of the load torque characteristics for the application.
Vibration and Shock
The drive allows selection of high carrier PWM control and low carrier PWM control. Selecting high carrier PWM can help reduce motor oscillation.
If resonance occurs, install shock-absorbing rubber mounts around the base of the motor and utilize the Jump frequency selection to prevent continuous operation in the resonant frequency ranges.
Audible Noise
Noise created during run varies by the carrier frequency setting. When using a high carrier frequency, audible noise from the motor is comparable to the motor noise generated when running from line power. Operating above the rated r/min, however, can create unpleasant motor noise.
Precautions for PM Motors
NOTICE: Damage to Equipment. Improper sequencing of output motor circuits could result in damage to the drive. Do not connect
electromagnetic switches or magnetic contactors to the output motor circuits without proper sequencing. Do not open the main circuit between the drive and the motor while the PM motor is rotating.
• Contact Yaskawa or your Yaskawa agent if you plan to use any PM motor not endorsed by Yaskawa.
• When using a holding brake, release the brake prior to starting the motor. Failure to set the proper timing can result in speed loss.
WARNING! Sudden Movement Hazard. Use the Initial Pole Search Status Signal (H2-= 61) to interlock the brake to ensure the brake is not released before the Initial Magnetic Pole Search is completed. Failure to comply may cause inadvertent elevator movement resulting in serious injury. This safety message is applicable under these conditions:
• When applying a PM motor, with an external brake sequence, and the PG-F3 option is not being used.
WARNING! Electrical Shock Hazard. The motor must be at a complete stop before performing any maintenance, inspection, or wiring.
• With a PM motor, drive output must be fully interrupted when the power is shut off and the motor is still rotating. Failure to comply can result in personal injury from electrical shock.
YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 13
i Preface & General Safety
YEA_co mmon
Drive Label Warnings
Always heed the warning information listed in Figure 1 in the position shown in Figure 2.
Figure 1
WARNING
Risk of electric shock.
Read manual before installing.
Wait 5 minutes for capacitor discharge after disconnecting power supply.
To conform to requirements, make sure to ground the supply neutral for 400V class.
After opening the manual switch between the drive and motor, please wait 5 minutes before inspecting, performing maintenance or wiring the drive.
Hot surfaces
Top and Side surfaces may become hot. Do not touch.
Figure 1 Warning Information
Figure 2
PWRLED MONITOR JVOP-184
RUN DS1 DS2
L1000E
RUN DS1 DS2 STATUS
READY RUN ALARM(RUN) PGOH,LT BB,HBB EF,SE OV,UV OH,OL OC,GF,SC,PGO CPF,OFA,OFB,OFC Other Fault
:LIGHT :BLINK :LIGHT OFF
CIMR-LE2A0012FAA
200V 3Phase 5.5kW/3.7kW
S/N:
WARNING
Risk of electric shock.
Read manual before installing.
Wait 5 minutes for capacitor discharge after disconnecting power supply.
To conform to requirements, make sure to ground the supply neutral for 400V class.
After opening the manual switch between the drive and motor, please wait 5 minutes before inspecting, performing maintenance or wiring the drive.
Hot surfaces
Top and Side surfaces may become hot. Do not touch.
AVERTISSMENT
Risque de décharge électrique.
Lire le manuel avant l'installation.
Attendre 5 minutes après la coupure de l'alimentation, pour permettre la décharge des condensateurs.
Pour répondre aux exigences , s assurer que le neutre soit relié à la terre, pour la série 400V.
Après avoir déconnécte la protection entre le driver et le moteur, veuillez patienter 5 minutes avain d’effectuer une opération de montage ou de câblage du variateur.
Surfaces Chaudes
Dessus et cotés du boitier Peuvent devenir chaud. Ne Pas toucher.
危 険
けが.感電のおそれがあります。
据え付け、運転の前には必ず取扱説明書を読むこと。
通電中および電源遮断後5分以内はフロントカバー を外さない事。
400V級インバータの場合は、電源の中性点が接地 されていることを確認すること。(対応)
保守・点検、配線を行う場合は、出力側開閉器を 遮断後5分待って実施してください。
高温注意
インバータ上部、両側面は高温になります。 触らないでください。
NPJT31470-1
Warning Label
Figure 2 Warning Information Position
Warranty Information
Restrictions
The drive is not designed or manufactured for use in devices or systems that may directly affect or threaten human lives or health.
Customers who intend to use the product described in this manual for devices or systems relating to transportation, health care, space aviation, atomic power, electric power, or in underwater applications must first contact their Yaskawa representatives or the nearest Yaskawa sales office.
WARNING! Injury to Personnel. This product has been manufactured under strict quality-control guidelines. However, if this product is to be installed in any location where failure of this product could involve or result in a life-and-death situation or loss of human life or in a facility where failure may cause a serious accident or physical injury, safety devices must be installed to minimize the likelihood of any accident.
14 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
Receiving
1
1 Receiving
YEA_c om-
Quick Start Guide
P W
R
L E D
M O
N I T
O R JV
O P
-1 8 4
R U N
DS
1
D S2
R UN
D
S 1
D
S 2
S TA
T U
S
R E A
D
Y R U
N A L A
RM
( R
U N)
P GO
H
,
L T
B B ,
H
B
B E F ,S
E
O t h
er
Fa
u
l t
O V
, U V
OH
, O
L O C
,
G
F
, SC
, P G
O
C P F
,
O
F
A ,
O F B
, O F C
: L IG
H T
: B
L I N
K
: L IGH
T
O F
F
PRG : 3580
IND.CONT.EQ.
7J48 B
CIMR-LE2A0018DAC
REV: A
YASKAWA ELECTRIC CORPORATION
MADE IN JAPAN
: : CIMR-LE2A0018DAA : AC3PH 200-240V 50/60Hz 15.6A : AC3PH 0-240V 0-120Hz 17.5A : 3.5 kg : :
: E131457 IP00
PASS
MODEL C / C INPUT OUTPUT MASS O / N S / N
FILE NO
AC drive model
Input specifications Output specifications
Lot number Serial number
Software version
Enclosure type
YEA_comm

Model Number and Nameplate Check

Please perform the following tasks after receiving the drive:
• Inspect the drive for damage. If the drive appears damaged upon receipt, contact the shipper immediately.
• Verify receipt of the correct model by checking the information on the nameplate.
• If you have received the wrong model or the drive does not function properly, contact your supplier.

1 Receiving

Description Drive
L E D M
O N I T
O R J V
R
O
U
P
N
­1
8
4
D S
1
D S 2
P W R
R U N
D S 1
D S
2
ST R E
A
A
T
D
U
Y
R
S
U
N A L
A
R
M P
(
G
R
O
UN
H
)
,
B
L T
B
,
H
B
B E F
, S E
O
V , U V
O
H , O L
O
C , G F
, C
SC P
:
F
L
,
,
I
P
O
G
G
F
H
O
O
A
T
t
,
h
O
er
FB
:
F B
,
a
O
L
u
F
I
l
NK
C
t : L
I
G
H
T
O
F F
Controller Power Supply Cable
for Rescue Operation
Quick Start Guide
Quantity 111
Nameplate
Figure 3
YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 15
Figure 3 Nameplate Information
1 Receiving
YEA_common
Refer to Table 1
Model Number
CIMR- L E 2 A 0018 D A C
Drive
L1000 Series
Region
No.
Code
South
E
America
No. Voltage Class
4
Customized
No.
Specifications
A Standard model
3-phase, 200-240 Vac 2
3-phase, 380-480 Vac
Enclosure Type
No.
IP00
A
IP00 with top
D
protective cover
No.
A Standard
Environmental Specification
<1>
Design Revision Order
<1> Drives with these specifications do not guarantee complete protection for the environmental conditions
indicated.
Table 1 Model Number and Specifications
Three-Phase 200 V Three-Phase 400 V
No.
Max. Motor Capacity
kW (HP)
2A0018 3.7 (5) 17.5 4A0009 3.7 (5) 9.0
2A0022 5.5 (7.5) 21.9 4A0012 5.5 (7.5) 11.5
2A0031 7.5 (10.0) 31.3 4A0019 7.5 (10.0) 18.5
2A0041 11.0 (15.0) 41.3 4A0023 11.0 (15.0) 22.5
2A0059 15.0 (20.0) 58.8 4A0030 15.0 (20.0) 30.0
2A0075 18.5 (25.0) 75.0 4A0039 18.5 (25.0) 38.8
2A0094 22.0 (30.0) 93.8 4A0049 22.0 (30.0) 48.8
2A0106 30.0 (40.0) 106.3 4A0056 30.0 (40.0) 56.3
2A0144 37.0 (50.0) 143.8 4A0075 37.0 (50.0) 75.0
2A0181 45.0 (60.0) 181.3 4A0094 45.0 (60.0) 93.8
2A0225 55.0 (75.0) 225.0 4A0114 55.0 (75.0) 113.8
2A0269 75.0 (100.0) 268.8 4A0140 75.0 (100.0) 140.0
2A0354 90.0 (125.0) 353.8 4A0188 90.0 (125.0) 187.5
2A0432 110.0 (150.0) 432.5 4A0225 110.0 (150.0) 225.0
- - - 4A0260 132.0 (175.0) 260.0
Figure 4
3 minute 50% Duty
Rated Output
Current A
No.
Max. Motor Capacity
kW (HP)
3 minute 50% Duty
Rated Output
Current A
16 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

2 Mechanical Installation

Mechanical
Installation
2
2 Mechanical Installation

Mechanical Installation

This section outlines specifications, procedures, and the environment for proper mechanical installation of the drive.
CAUTION! Crush Hazard. Carrying the drive by the front cover may cause the main body of the drive to fall, resulting in minor or moderate injury. Always hold the case when carrying the drive.
Installation Environment
Install the drive in an environment matching the specifications below to help prolong the optimum performance life of the drive.
Table 2 Installation Environment
Environment Conditions
Installation Area Indoors
IP00 enclosure with top protective cover: -10 to +40°C (14 to 104°F) IP00 enclosure: -10 to +50°C (14 to 122°F)
Ambient Temperature
Humidity 95% RH or less and free of condensation
Storage Temperature -20 to 60°C (-4 to 140°F)
Surrounding Area
Altitude 1000 m (3280 ft.) or lower, up to 3000 m (9842 ft.) with derating (Refer to Altitude Derating on page 162)
Vibration
Orientation Install the drive vertically to maintain maximum cooling effects.
Drive reliability improves in environments without wide temperature fluctuations. When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclosure does not exceed the specified levels. Do not allow ice to develop on the drive.
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
10 to 20 Hz at 9.8 m/s 20 to 55 Hz at 5.9 m/s2 (2A0018 to 2A0225 and 4A0009 to 4A0188) or 2.0 m/s2 (2A0269 to 2A0432 and 4A0225 to 4A0260)
2
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the noise created can lead to erroneous operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary cover before startup, as the cover will reduce ventilation and cause the drive to overheat.
YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 17
2 Mechanical Installation
A
A
BB
Side Clearance Top/Bottom Clearance
C
C
D
D
PWRLED MONITOR JVOP-184
RUN DS1 DS2
RUN DS1 DS2 STATUS
READY RUN ALARM(RUN) PGOH,LT BB,HBB EF,SE
Other Fault
OV,UV OH,OL OC,GF,SC,PGO CPF,OFA,OFB,OFC
:LIGHT :BLINK :LIGHT OFF
PW RL
E D
M
O N
I T O
R J
V O
P
-18 4
RU N
D
S 1
D S
2
RU
N
D S1
D S
2
S
T A T
US
R E
A D Y
R U
N
AL A
R M
( R UN
)
PG
OH ,
L T
BB
, H B B
E F ,
S E
O t h
e r F
a u lt
O V,
U V
O H
, O L
O C
, G F ,
S C , P
G O
C PF
, O F
A , O
F B
,O
F C
: L
I G H
T
: B LI
N K
: L
I G
H T O
F F
YEA_comm
Installation Orientation and Spacing
WARNING! Fire Hazard. Provide sufficient cooling when installing the drive inside an enclosed panel or cabinet. Failure to comply could result in overheating and fire. When drives are placed inside the same enclosure panel, install proper cooling to ensure air entering the enclosure does not exceed 40°C (104°F).
Installation Orientation
Install the drive upright as illustrated in Figure 4 to maintain proper cooling. Refer to Mechanical Installation on
page 17 for details on installing the drive.
Figure 5
Figure 4 Correct Installation Orientation
Installation Spacing
Figure 5 shows the installation distance required to maintain sufficient space for airflow and wiring.
Figure 6
A – 50 mm (1.97 in.) minimum C – 120 mm (4.72 in.) minimum B – 30 mm (1.18 in.) minimum D – Airflow direction
Figure 5 Correct Installation Spacing
18 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
2 Mechanical Installation
Mechanical
Installation
2
Instructions on Installation
Eye bolts are used to install the drive or to temporarily lift the drive when replacing it. The drive can be installed in an enclosure panel or on a wall. Do not leave the drive suspended by the wires in a horizontal or vertical position for long periods of time. Do not transport the drive over long distances. Read the following precautions and instructions before installing the drives.
WARNING! Be sure to observe the following instructions and precautions. Failure to comply could result in minor or moderate injury and damage to the drive from falling equipment.
Before using wires to suspend the drive vertically and horizontally, make sure that the drive front cover, terminal blocks and other drive components are securely fixed with screws.
Do not subject the drive to vibration or impact greater than 1.96 m/s wires.
Do not overturn the drive while it is suspended by the wires.
Do not leave the drive suspended by the wires for long periods of time.
2
(0.2 G) while it is suspended by the
Horizontal Suspension of the Drive (CIMR-LE2A0432 and 4A0260)
To make a wire hanger or frame for use when lifting the drive with a crane, lay the drive in a horizontal position and pass a wire through the holes of the four eye bolts.
When lifting the drive, confirm that the spring washer is fully closed. If not, the drive may become deformed or damaged when lifted.
Figure 7
B
A
A – No space between drive and washer C – Space between drive and washer B – Spring washer: Fully closed D – Spring washer: Open
Figure 6 Details of Spring Washers
D
C
Vertical Suspension of the Drive (CIMR-LE2A0432 and 4A0260)
When vertical suspension of the drive is required in an enclosure panel, the orientation of the eye bolts for these drive models can be easily changed by turning the eye bolts counterclockwise 90 degrees.
Figure 8
Figure 7 Adjusting Angle of Eye Bolts (CIMR-LE2A0432 and 4A0260)
YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 19
2 Mechanical Installation
YEA_com
Exterior and Mounting Dimensions
IP00 Enclosure Drive with Top Protective Cover
W1
RUN DS1 DS2
RUN DS1 DS2 STATU S
READY RUN ALARM(RUN) PGOH,LT BB,HBB EF,SE OV,UV OH,OL OC,GF,SC,PGO CPF,OFA,OFB,OFC Other Fault
:LIGHT :BLINK :LIGHT OFF
4-d
1.5 (0.06)
PWRLED MONITOR JVOP-184
W1
RUN DS1 DS2
RUN DS1 DS2 STATUS
:LIGHT :BLINK :LIGHT OFF
READY RUN ALARM(RUN) PGOH,LT BB,HBB EF,SE OV,UV OH,OL OC,GF,SC,PGO CPF,OFA,OFB,OFC Other Fault
4-d
PWRLED MONITOR JVOP-184
t2
W
Drive Model Figure
2A0018
2A0022
2A0031
2A0041
2A0059
2A0075
2A0094
2A0106
2A0144
1
2
2A0181
2A0225
H
H1
H2
Figure 1
t1
Max 8
D
D1
(0.31)
W
H1
H2
Max 8 (0.31)
Figure 2
H
Table 3 Dimensions: 200 V Class
Dimensions mm (in)
W H D W1 H1 H2 D1 t1 t2 d
140
(5.50)
140
(5.50)
140
(5.50)
140
(5.50)
180
(7.10)
221
(8.70)
221
(8.70)
249
(9.80)
274
(10.80)
325
(12.80)
325
(12.80)
259
(10.20)
259
(10.20)
259
(10.20)
259
(10.20)
300
(11.80)
351
(13.80)
351
(13.80)
399
(15.70)
450
(17.70)
551
(21.70)
551
(21.70)
165
(6.50)
165
(6.50)
168
(6.60)
168
(6.60)
188
(7.40)
198
(7.80)
198
(7.80)
259
(10.20)
259
(10.20)
284
(11.10)
284
(11.10)
122
(4.80)
122
(4.80)
122
(4.80)
122
(4.80)
160
(6.30)
193
(7.60)
193
(7.60)
196
(7.70)
221
(8.70)
259
(10.20)
259
(10.20)
249
(9.80)5(0.20)56(2.20).5(0.20)
249
(9.80)5(0.20)56(2.20).5(0.20)
249
(9.80)5(0.20)56(2.20).5(0.20)
249
(9.80)5(0.20)56(2.20).5(0.20)
284
(11.20)8(0.30)76(3.00).5(0.20)
335
(13.20)8(0.30)79(3.10).5(0.20)
335
(13.20)8(0.30)79(3.10).5(0.20)
386
(15.20)8(0.30)99(3.90)
434
(17.10)8(0.30)99(3.90)
536
(21.10)8(0.30)
536
(21.10)8(0.30)
109
(4.30)
109
(4.30)
.25
(0.10)
.25
(0.10)
.25
(0.10)
.25
(0.10)
D
–M5
–M5
–M5
–M5
–M5
–M6
–M6
.25
(0.10)
.25
(0.10)
.25
(0.10)
.25
(0.10)
M6
M6
M6
M6
t1
D1
Weight
kg (lbs)
3.5
(7.7)
3.5
(7.7)
4.0
(8.8)
4.0
(8.8)
5.6
(12.3)
8.7
(19.2)
9.7
(21.4)
21.0
(46.3)
25.0
(55.1)
37.0
(81.6)
38.0
(83.8)
20 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
Mechanical
Installation
2
Table 4 Dimensions: 400 V Class
2 Mechanical Installation
Drive Model Figure
4A0009
4A0012
4A0019
4A0023
4A0030
4A0039
4A0049
4A0056
4A0075
4A0094
1
2
4A0114
4A0140
4A0188
Dimensions mm (in)
W H D W1 H1 H2 D1 t1 t2 d
140
(5.50)
140
(5.50)
140
(5.50)
140
(5.50)
180
(7.10)
180
(7.10)
221
(8.70)
249
(9.80)
274
(10.80)
325
(12.80)
325
(12.80)
325
(12.80)
325
(12.80)
259
(10.20)
259
(10.20)
259
(10.20)
259
(10.20)
300
(11.80)
300
(11.80)
351
(13.80)
399
(15.70)
450
(17.70)
511
(20.10)
511
(20.10)
551
(21.70)
551
(21.70)
165
(6.50)
165
(6.50)
168
(6.60)
168
(6.60)
168
(6.60)
188
(7.40)
198
(7.80)
259
(10.20)
259
(10.20)
259
(10.20)
259
(10.20)
282
(11.10)
282
(11.10)
122
(4.80)
122
(4.80)
122
(4.80)
122
(4.80)
160
(6.30)
160
(6.30)
193
(7.60)
196
(7.70)
221
(8.70)
259
(10.20)
259
(10.20)
259
(10.20)
259
(10.20)
249
(9.80)5 (0.20)56(2.20)5(0.20)
249
(9.80)5 (0.20)56(2.20)5(0.20)
249
(9.80)5 (0.20)56(2.20)5(0.20)
249
(9.80)5 (0.20)56(2.20)5(0.20)
284
(11.20)8(0.30)56(2.20)5(0.20)
284
(11.20)8(0.30)76(3.00)5(0.20)
335
(13.20)8(0.30)79(3.10)5(0.20)
–M5
–M5
–M5
–M5
–M5
–M5
–M6
386
(15.20)8(0.30)99(3.90)3(0.10)3(0.10)
434
(17.10)8(0.30)99(3.90)3(0.10)3(0.10)
495
(19.50)8(0.30)
495
(19.50)8(0.30)
536
(21.10)8(0.30)
536
(21.10)8(0.30)
104
(4.10)3(0.10)3(0.10)
104
(4.10)3(0.10)3(0.10)
109
(4.30)3(0.10)3(0.10)
109
(4.30)3(0.10)3(0.10)
M6
M6
M6
M6
M6
M6
Weight
kg (lbs)
3.5
(7.7)
3.5
(7.7)
4.0
(8.6)
4.0
(8.9)
5.4
(11.9)
5.4
(11.9)
8.0
(18.3)
22.0
(46.3)
25.0
(55.1)
36.0
(79.4)
36.0
(79.4)
41.0
(90.4)
42.0
(92.6)
YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 21
2 Mechanical Installation
YEA_com
IP00 Enclosure Drive
W1
RUN DS1 DS2
RUNDS1 DS2 STATUS
:LIGHT :BLINK :LIGHT OFF
4-d
H
PWRLED MONITOR JVOP-184
READY RUN ALARM(RUN) PGOH,LT BB,HBB EF,SE OV,UV OH,OL OC,GF,SC,PGO CPF,OFA,OFB,OFC Other Fault
H1
t2
Drive Model Figure
2A0269
2A0354
2A0432
1
Drive Model Figure
4A0225
1
4A0260
t1
D1
D
Max 8 (0.31)
H2
W
Max 8 (0.31)
Figure 1
Table 5 Dimensions: 200 V Class
Dimensions mm (in) Weight
W H D W1 H1 H2 D1 t1 t2 d
450
(17.70)
450
(17.70)
500
(19.70)
706
(27.80)
706
(27.80)
800
(31.50)
330
(13.00)
330
(13.00)
330
(13.00)
325
(12.80)
325
(12.80)
371
(14.60)
681
(26.80)13(0.50)
681
(26.80)13(0.50)
772
(30.40)13(0.50)
130
(5.10)3(0.10)3(0.10)
130
(5.10)3(0.10)3(0.10)
130
(5.10)5(0.20)5(0.20)
Table 6 Dimensions: 400 V Class
Dimensions mm (in) Weight
W H D W1 H1 H2 D1 t1 t2 d
450
(17.70)
500
(19.70)
706
(27.80)
800
(31.50)
330
(13.00)
330
(13.00)
325
(12.80)
371
(14.60)
681
(26.80)13(0.50)
772
(30.40)13(0.50)
130
(5.10)3(0.10)3(0.10)
130
(5.10)5(0.20)5(0.20)
M10
M10
M12
M10
M12
kg
(lbs)
76
(167.6)
80
(176.4)
98
(216.1)
kg
(lbs)
79
(174.2)
96
(211.6)
22 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

3 Electrical Installation

Electrical Installation
3
3 Electrical Installation

Standard Connection Diagram

Connect the drive and peripheral devices as shown in Figure 8. It is possible to set and run the drive via the digital operator without connecting digital I/O wiring. This section does not discuss drive operation; Refer to Start-Up
Programming on page 52 for instructions on operating the drive.
WARNING! Sudden Movement Hazard. Ensure holding brake circuits are properly configured, load equipment may fall or drop during power loss or drive fault, which could result in death or serious injury.
Provide a separate holding brake if necessary.Always construct the external sequence to confirm that the holding brake is activated in the event of an emergency, a power failure, or
an abnormality in the drive.
When using the drive with an elevator, provide safety measures on the elevator to prevent the elevator from dropping.
NOTICE: Equipment Hazard. Separate motor and/or braking circuit wiring (terminals, U/T1, V/T2, W/T3, +3, +2, +1,(-), B1, B2, from all other wiring. Place motor wiring within its own conduit or cable tray with appropriate divider, and use shielded motor cable where appropriate. Improper wiring practices could result in malfunction of drive due to electrical interference.
NOTICE: Inadequate wiring could result in damage to the drive. Install adequate branch circuit short circuit protection per applicable codes. The drive is suitable for circuits capable of delivering not more than 100,000 RMS symmetrical amperes, 240 Vac maximum (200 V Class) and 480 Vac maximum (400 V Class).
NOTICE: When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters (328 ft.), pay special attention to the motor insulation voltage or use a drive rated motor. Failure to comply could lead to motor insulation breakdown.
Note: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction.
NOTICE: The minimum load for the multi-function relay output MA-MB-MC is 10 mA. If a circuit requires less than 10 mA (reference value), connect it to a photocoupler output (P1-C1, P2-C2). Improper application of peripheral devices could result in damage to the photocoupler output of the drive.
YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 23
3 Electrical Installation
Shield ground terminal
+−+
DM
DM
H
1
H2
HC
<10>
R/L1
S/L2
T/L3
Fuse
MC
2MCCB
MB
ON
OFF
THRX
SA
1
2
TRX
MC
MA
TRX
Fault relay contact
Braking resistor unit Thermal relay trip contact
MC
MC
SA
SA
THRX
ELCB (MCCB)
R
T
S
Three-phase power supply
200 to 240 V 50/60 Hz
<14>
2MCCB
r1 s1 t1
MC
Wiring sequence should shut off power to the drive when a fault output is triggered.
If running from a 400 V power supply, a step-down transformer is needed to reduce the voltage to 200 V.
P1
P2
C1
C2
Photo Coupler 1 (During Frequency Output)
Photo Coupler 2 (not used)
Digital output 5 to 48 Vdc 2 to 50 mA (default setting)
+
+
++
Terminals -, +1, +2, B1, B2 are for connecting options. Never connect power supply lines to these terminals
DC link choke
(option)
UX
Thermal relay
(option)
+
+
++
+
UX
S
1
S2
S3
S4
S5
S6
S7
A1
A2
0
V
AC
R
R
S
S
IG
Drive
B112
B2
2
kΩ
S8
SC
0 V
FM
AM
AC
E (G)
<1>
<8>
<8>
<9>
<2><3>
+24 V
+V
MA
M
1
M2
MB
MC
Jumper
Braking resistor (option)
Up command / Stop
External Fault
Fault Reset
Multi-step Speed 1
Not Used
Multi-function
digtial inputs
(default setting)
Sink / Source mode selection wire jumper (default: Sink)
Multi-function analog inputs
Power supply +10.5 Vdc, max. 20 mA
Analog Input 1 (Speed Bias)
-10 to +10 Vdc (20 kΩ)
Analog Input 2 (Not used)
-10 to +10 Vdc (20 kΩ)
V
Power supply, -10.5 Vdc, max. 20 mA
MEMOBUS/Modbus
comm. RS485/422
max. 115.2 kBps
Termination resistor
(120 Ω, 1/2 W)
DIP Switch S2
Fault relay output 250 Vac, max. 1 A 30 Vdc, max 1 A (min. 5 Vdc, 10 mA)
Multi-function relay output (Brake Release Command) 250 Vac, max. 1 A 30 Vdc, max 1 A (min. 5 Vdc, 10 mA)
Multi-function analog output 1 (Output Speed)
-10 to +10 Vdc (2mA)
Multi-function analog output 2 (Output Current)
-10 to +10 Vdc (2mA)
Main Circuit
Control Circuit
shielded line
twisted-pair shielded line
main circuit terminal
control circuit terminal
M3
M4
Multi-function relay output (Motor Contactor Close Command) 250 Vac, max. 1 A 30 Vdc, max 1 A (min. 5 Vdc, 10 mA)
M5
M6
Multi-function relay output (Drive Ready) 250 Vac, max. 1 A 30 Vdc, max 1 A (min. 5 Vdc, 10 mA)
SP
SN
FM
+
AM
<7>
Down command / Stop
Multi-step Speed 2
Multi-step Speed 3
FE
SD
NC
a+ a-
b-
z-
b+
z+
IP IG
IP12
IP5
IG
SG
TB2
A pulse monitor signal
B pulse monitor signal
Z pulse monitor signal
CN3
PG
<4>
<2>
A+ A
B
Z
B+
Z+
TB1
PGX3
CN5-C
CN5-B
CN5-A
Option card connector
M
U/T
1
V/T2
W/T
U/T1
V/T2
W/T3
3
Ground
Cooling fan
<6>
<5>
M
r1
s1
t1
FU
FV
FW
<12>
<13> <14>
<15>
EDM (Safety Electronic Device Monitor)
Safe Disable inputs
<11>
YEA_com
Figure 9
Figure 8 Drive Standard Connection Diagram (example: CIMR-LE2A0041)
<1> Remove the jumper when installing a DC link choke. Models 2A0106 through 2A0432 and 4A0056 through
4A0260 come with a built-in DC link choke.
<2> Set L8-55 to 0 to disable the protection function of the built-in braking transistor of the drive when using an
optional regenerative converter or dynamic braking option.
<3> Set up a thermal relay sequence to disconnect drive main power in the event of an overheat condition on the
dynamic braking option.
<4> Self-cooling motors do not require the same wiring necessary for motors with separate cooling fans.
24 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
3 Electrical Installation
Electrical Installation
3
<5> Supplying power to the control circuit separately from the main circuit requires a 24 V power supply (option). <6> For control modes that do not use a motor speed feedback signal, PG option card wiring is not necessary. <7> This figure illustrates an example of a sequence input to S1 through S8 using a non-powered relay or an NPN
transistor. Install the wire link between terminals SC-SP for Sink mode, between SC-SN for Source mode, or leave the link out for external power supply. Never short terminals SP and SN, as it will damage the drive.
<8> The maximum output current capacity for the +V and -V terminals on the control circuit is 20 mA. Never short
terminals +V, -V, and AC, as it can cause erroneous operation or damage the drive.
<9> Set DIP switch S2 to the ON position to enable the termination resistor in the last drive in a MEMOBUS/
Modbus network.
<10>The sink/source setting for the Safe Disable input is the same as with the sequence input. Jumper S3 has the
drive set for an external power supply. When not using the Safe Disable input feature, remove the jumper shorting the input and connect an external power supply. Refer to Sinking/Sourcing Mode Selection for Safe
Disable Inputs on page 50 for instructions.
<11>Disconnect the wire jumper between H1 - HC and H2 - HC when utilizing the Safe Disable input. <12>Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters.
They are not intended for use as a feedback-type of signal.
<13>When the drive is set to trigger a fault output upon activation of the fault reset function (L5-02 = 1), a
sequence to interrupt power when a fault occurs will shut off the power to the drive when the drive attempts a reset. The default setting for L5-02 is 0 (fault output not active during reset attempt).
<14>Wire fault contact outputs MA, MB, and MC. Wire so that a fault will open the safety circuit and interrupt
drive output.
<15>When using the Programming Mode to edit parameter settings, the drive will not accept an Up/Down
command. If the drive still will not run when an Up/Down command has been entered and no fault is present, then use the "Drive ready" signal (the default setting for terminal M5-M6) to interlock components.
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before energizing the drive. Failure to comply could result in death or serious injury from moving equipment.
NOTICE: When using the automatic fault reset function with wiring designed to shut off the power supply upon drive fault, make sure the drive does not trigger a fault output during fault reset (L5-02 = 0, default). Failure to comply will prevent the automatic fault reset function from working properly.
YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 25
3 Electrical Installation
+1
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
B1 B2
DC link
choke
+
Relay
Gate board
Control
board
Operator
Current sensor
YEA_ com-
YEA_ com-
YEA_ com-

Main Circuit Connection Diagram

Refer to the Figure 9 when wiring the main circuit of the drive. Connections may vary based on drive capacity. The DC power supply for the main circuit also provides power to the control circuit.
NOTICE: Do not use the negative DC bus terminal “-” as a ground terminal. This terminal is at high DC voltage potential. Improper wiring connections could damage the drive.
NOTICE: Equipment Hazard. Separate motor and/or braking circuit wiring (terminals, U/T1, V/T2, W/T3, +3, +2, +1,(-), B1, B2, from all other wiring. Place motor wiring within its own conduit or cable tray with appropriate divider, and use shielded motor cable where appropriate. Improper wiring practices could result in malfunction of drive due to electrical interference.
+1
+2
R/L1
S/L2
T/L3
2A0018 to 2A0094 4A0009 to 4A0049
B1 B2
Relay
+
Gate board
Control
board
Current sensor
Operator
U/T1
V/T2
W/T3
2A0181 and 2A0225
4A0094 to 4A0140
+3
2A0106 and 2A0144
4A00456 and 4A0075
2A0269 to 2A0432 4A0188 to 4A0260
+3
R/L1
S/L2
T/L3
+1
DC link
choke
Relay
24 V Power Supply
+
Gate board
Control
board
Current sensor
Operator
U/T1
V/T2
W/T3
+1
R/L1
S/L2
T/L3
26 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
DC link
choke
Relay
+
Gate board
Control
board
Current sensor
U/T1
V/T2
W/T3
Operator
Figure 9 Drive Main Circuit Configurations
3 Electrical Installation
Electrical Installation
3
YEA_common
YEA_common
YEA_common

Terminal Cover

Follow the procedure below to remove the terminal cover for wiring and to reattach the terminal cover after wiring is complete.
Removing/Reattaching the Terminal Cover
Removing the Terminal Cover Models 2A0018 to 2A0094 and 4A0009 to 4A0049
1. Loosen the terminal cover screw using a #2 Phillips screwdriver. Screw sizes vary by drive model.
Figure 10
Figure 10 Removing the Terminal Cover
2. Push in on the tab located on the bottom of the terminal cover and gently pull forward to remove the terminal
Figure 11
cover.
Figure 11 Removing the Terminal Cover
Models 2A0106 to 2A0432 and 4A0056 to 4A0260
1. Loosen the screws on the terminal cover, then pull down on the cover.
CAUTION! Do not completely remove the cover screws, just loosen them. If the cover screws are removed completely, the terminal
cover may fall off causing an injury.
Note: The shape of the terminal covers and the numbers of screws differ depending on the drive models.
Figure 12
Figure 12 Removing the Terminal Cover
YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 27
3 Electrical Installation
YEA_common
Connect ground wiring first, followed by the main circuit, and then wire the control circuit. Power lines and signal wiring exit through the opening provided.
YEA_common
Connect ground wiring first, followed by the main circuit, and then wire the control circuit.
YEA_common
2. Pull forward on the terminal cover to free it from the drive.
Figure 13
Figure 13 Removing the Terminal Cover
Reattaching the Terminal Cover Models 2A0018 to 2A0094 and 4A0009 to 4A0049
Power lines and signal wiring should pass through the opening provided. Refer to Wiring the Main Circuit Terminal on
page 42 and Wiring the Control Circuit Terminal on page 46 for details on wiring.
NOTICE: Equipment Hazard. Separate motor and/or braking circuit wiring (terminals, U/T1, V/T2, W/T3, +3, +2, +1,(-), B1, B2, from all other wiring. Place motor wiring within its own conduit or cable tray with appropriate divider, and use shielded motor cable where appropriate. Improper wiring practices could result in malfunction of drive due to electrical interference.
Reattach the terminal cover after completing the wiring to the drive and other devices.
Figure 14
Figure 14 Reattaching the Terminal Cover
Models 2A0106 to 2A0432 and 4A0056 to 4A0260
After wiring the terminal board and other devices, double-check connections and reattach the terminal cover. Refer to
Wiring the Main Circuit Terminal on page 42 and Wiring the Control Circuit Terminal on page 46 for details on
wiring.
Figure 15
Figure 15 Reattaching the Terminal Cover
28 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
3 Electrical Installation
Electrical Installation
3
YEA_common
P W
R
L ED
M O
N I T O
R J
V O
P
­1
84
R U
N
D S 1
D S
2
R U N
D
S 1
D S2
STA
T U
S
R
E A DY
R
UN
A
L A R
M (
R UN)
P
G OH,
LT
B
B , H B
B
EF,S
E
O
t h e
r Fa
u
l t
O
V , U
V
O
H,O
L
O
C , GF
, SC
,
P G
O
C
PF , O
F A
,O
F B
, OFC
:L
IG H
T
: B
L I N K
:
LIGH
T
O F F
PW R
L E D M O
N I T O
R J V O
P
­1 8
4
R U N
D S 1
D
S 2
R U N D
S 1
D S 2
S
TA T U
S
R E
A D Y
R U
N A L A
R
M(
R U N )
PG
O
H
,
L
T
B B ,
H
B
B
E F ,
S
E
O t h
e
r
Fau
l t
O V
,
U
V O H
,
O
L O C
,
G
F
,
S C , P G
O
C P F
,
O
F
A , O F B
, O F C
:
L I G H
T
: B L I N
K
: L I G
H T OF
F
YEA_common
P W
R
L E D
M O N I T O
R J V O P
­1 8 4
R U N
D S1
D S 2
R UN
DS 1
D S 2
ST
A T U
S
RE A D Y
R U N A L A R M (
R UN
)
P G O H , L
T
B B, H BB E F , S E
O
t h er F a
u l t
O V , UV O H , O L O C , G F , SC
, P G
O
C
P F , O F A,
O FB
, O F
C
: L I G H
T : B
L I N K
:L I G
H T
O F F
YEA_commo

LED Monitor and Front Cover

Detach the LED monitor from the drive for remote operation or when opening the front cover to install an option card.
Note: Be sure to remove the LED monitor prior to opening or reattaching the front cover. Leaving the LED monitor plugged into the
drive when removing the front cover can result in erroneous operation caused by a poor connection. Firmly fasten the front cover back into place before reattaching the LED monitor.
Removing/Reattaching the LED Monitor
Removing the LED Monitor
While pressing on the tab located on the right side of the LED monitor, pull the LED monitor forward to remove it from the drive.
Figure 16
Figure 16 Removing the LED Monitor
Reattaching the LED Monitor
Insert the LED monitor into the opening in the top cover while aligning it with the notches on the left side of the opening.
Next, press gently on the right side of the LED monitor until it clicks into place.
Figure 17
Figure 17 Reattaching the LED Monitor
Removing/Reattaching the Front Cover
Removing the Front Cover Models 2A0018 to 2A0094 and 4A0009 to 4A0049
After removing the terminal cover and the LED monitor, loosen the screw that affixes the front cover (models 2A0059, 4A0030, and 4A0039 do not use a screw to affix the front cover). Pinch inwards on the tabs found on each side of the front cover, then pull forward to remove it from the drive.
Figure 18
Figure 18 Remove the Front Cover (Models 2A0018 to 2A0094 and 4A0009 to 4A0049)
YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide 29
3 Electrical Installation
HookHook
Front cover installation screw
Free hooks on both sides of the cover
Models 2A0106 to 2A0432 and 4A0056 to 4A0260
1. Remove the terminal cover and the LED monitor.
2. Loosen the installation screw on the front cover.
3. Use a straight-edge screwdriver to loosen the hooks on each side of the cover that hold it in place.
Figure 19
Figure 19 Remove the Front Cover (Models 2A0106 to 2A0432 and 4A0056 to 4A0260)
4. Unhook the left side of the front cover then swing the left side towards you as shown in Figure 20 until the cover
Figure 20
comes off.
Figure 20 Remove the Front Cover (Models 2A0106 to 2A0432 and 4A0056 to 4A0260)
Reattaching the Front Cover Models 2A0018 to 2A0094 and 4A0009 to 4A0049
Reverse the instructions given in Remove the Front Cover (Models 2A0018 to 2A0094 and 4A0009 to 4A0049) on
page 29 to reattach the front cover. Pinch inwards on the hooks found on each side of the front cover while guiding it back
into the drive. Make sure it clicks firmly into place.
30 YAS KA WA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
Loading...
+ 206 hidden pages