Xylem AQCPCQR User Manual

QUICKSTART GUIDE
AQCPCQR
AQUAVAR® CPC
Centrifugal Pump Controller
Quick Start Guide
Overview
The installation of the AQUAVAR CPC adjust­able speed drive follows the outline below.
Task
PREPARE for installation
PREPARE mounting location
REMOVE the front cover
MOUNT the drive
INSTALL wiring
CHECK installation
REINSTALL the cover
APPLY power
START-UP Wizards
Application
This guide provides a quick reference for installing Aquavar CPC drives having a standard enclosure (NEMA 1).
NOTE: This guide does not provide detailed installation, safety or operational instructions. See the Installation Operation Manual for complete information.
Prepare for Installation
WARNING! The Aquavar should ONLY
be installed by a qualified electrician.
Check
• Motor Compatibility – Motor type, nominal current,
frequency and voltage range must match drive specifications (3 phase motor only).
• Suitable Environment – Drive requires heated,
indoor controlled environment that is suitable for the selected enclosure.
• Wiring – Follow local codes for wiring and fusing
requirements. Refer to NEC.
Refer to the Installation Operation Manual and confirm that all preparations are complete.
Tools Required
Screwdrivers, wire stripper, tape measure, mounting screws or bolts, and drill.
Use the following chart to interpret the type code found on the drive label.
CPC 4 370 1
AQUAVAR® (Series) Voltage
2 – 230 Volt 4 – 460 Volt
Amps
370 Amps *See Technical Section
NEMA Enclosure Rating
1 – NEMA 1 2 – NEMA 12 3 – NEMA 3R with disconnect 4 – NEMA 4 with disconnect 5 – NEMA 3R without disconnect 6 – NEMA 4 without disconnect
Options
A – Field Bus Card (Devicenet, Probus)
* Consult factory for other options, if available.
Not all combinations may be available.
Collect Motor Data
Collect the following data from the motor name­plate for later use in the Aquavar startup:
______________________________
• Voltage
• Nominal Motor Current
• Nominal Frequency
• Nominal Speed
• Nominal Power
_______________
___________________
______________________
_______________________
Unpack the Drive
NOTE: Lift the Aquavar by its chassis and not by
its cover.
1. Unpack the drive.
2. Check for any damage and notify the shipper immediately if damaged com­ponents are found.
3. Check the contents against the order and the shipping label to verify that all parts have been received.
Prepare the Mounting Location
The drive requires a smooth, vertical, solid surface, free from heat and moisture, with free
space for air ow – 200 mm (8
in.) above and below, and 25 mm (1 in.) around the sides of the drive.
1. Mark the mounting
points.
2. Drill the mounting holes.
1
Remove the Front Cover
1. Remove the control panel (display), if attached.
2. Loosen the captive screw at the top.
3. Pull near the top to remove the cover.
Mount the Drive
1. Position the AQUAVAR and use screws or bolts to securely tighten all four corners.
2. Attach a warning sticker in the appropriate language on the inside plastic shell.
Install the Wiring
1. Install thin-wall conduit clamps (not
supplied) in the conduit/gland box.
2. Install conduit/gland box.
Wiring Power
1. Connect conduit runs to box.
2. Route input power and motor
wiring through conduits.
3. Strip wires.
4. Connect power, motor and ground wires to the drive terminals. See “Power Connections” in the instruction manual.
Frame Sizes R1…R4
X0002
* Single phase input power must use U1, W1
and PE for wiring.
WARNING! For oating networks
remove screws at EM1 and EM3 on
Frame Sizes R1…R4.
Frame Size R5
Frame Size R6
WARNING!
For oating
networks remove
screws at F1 and F2 on Frame Sizes R5 or R6.
Wiring the Transducer
ON
ON
1. Route the transducer cable through the conduit.
2. Strip the transducer cable sheathing and twist the screen wire.
3. Connect the screen wire of the transducer to terminal X1-1.
4. Connect the power supply wire of the
transducer (red or brown) to terminal
X1-10.
5. Connect analog output wire from the transducer (white or black) to X1-5. See chart in next column.
Note 1. Jumper Setting: (Analog Input)
J1 AI1: 0…10 V
AI2: 0(4)…20 mA
Relay output 1, pro-
19 RO1C grammable. Default2
= run power to drive
20 RO1A
30 VDC, 2 A
21 RO1B
(12 V, 10 mA)
Relay output 2, pro-
22 RO2C
= ready, pump is running
23 RO2A
30 VDC, 2 A
24 RO2B
(12 V, 10 mA)
Relay Outputs
Relay output 3, pro-
25 RO3C grammable. Default2
= not used
26 RO3A
30 VDC, 2 A
27 RO3B
(12 V, 10 mA)
6. Install the conduit/gland box cover (1
Maximum: 250 VAC/
Minimum: 500 mW
grammable. Default2
Maximum: 250 VAC/
Minimum: 500 mW
Maximum: 250 VAC/
Minimum: 500 mW
screw).
3
5
1
X1 Control Wiring
Terminal for transducer
Trans-
1 SCR shield. (Connected inter-
ducer
nally to chassis ground.)
Screen/
Analog input channel 1,
Shield
2nd transducer. Default2
= frequency reference.
Resolution 0.1%, 2 AI1 accuracy ±1%.
J1:AI1 OFF: 0…10 V (Ri =
312 kΩ)
J1:AI1 ON: 0…20 mA (Ri = 100 Ω)
Analog input circuit com-
Jumper
mon. (Connected inter-
Wire
3
AGND
nally to chassis gnd. through 1 MW. Jumper wire to X1-11.)
(–) Trans­ducer
input potentiometer,
(4 -20
accuracy ±2%. (Not used.)
mA)
Analog input channel 2.
Conn-
Resolution 0.1%,
ection
5 AI2 accuracy ±1%.
Analog I/O
(White
Transducer input
or
4–20 mA
Black)
nally to chassis gnd.
10 V/10 mA reference
4 +10V
6 AGND
voltage output for analog
Analog input circuit com-
mon. (Connected inter-
through 1 MΩ)
used. Current 0…20 mA
(–)
(load < 500 Ω)
Trans­ducer Power
used. 0…20 mA
Supply
(load < 500 Ω)
(Brown
or Red)
internally to chassis gnd.
Analog output, program-
7 AO1
8 AO2
9 AGND
mable. Default2 = Not
Analog output, program-
mable. Default2 = Not
Analog output circuit
common (Connected
through 1 MΩ)
1
Auxiliary voltage output
10–15
24 VDC / 250 mA
E-stop or Jump­er
Jump­er Wire 11 and 12
Xylem, Inc.
2881 East Bayard Street Ext., Suite A, Seneca Falls, NY 13148
Phone: (800) 453-6777 • Fax: (888) 322-5877 www.xyleminc.com/brands/gouldswatertechnology
10
Short circuit protected. Transducer/digital input power supply.
Auxiliary voltage output 11 GND common. (Connected internally as floating.)
Digital Inputs
(reference to GND).
+24V
ON
ON
X1 Control Wiring
Jump-
Digital input common.
er Wire
To activate a digital input,
11 and
there must be +10V
12
(or -10V) between that 12 may be provided by the
AQUAVAR (X1-10) or by an external 12…24V
source of either polarity.
10–15
E-stop
Digital input 3,
or
15 DI3 programmable. Default2
Jump-
= E-stop or jumper
er
Digital input 4, 16 DI4 programmable. Default2
E-stop
= set point selection
/start Jump to
+24V
for en­able (15
to 10
Jump­er)
Check Installation
Before applying power, perform the following checks.
Check
Environment conforms to specifications. The drive is mounted securely. Proper cooling space around the drive. Motor and driven equipment are ready for start.
Floating networks: Internal RFI filter disconnected. Drive is properly grounded, with pump/motor.
Input power (mains) voltage matches the drive nominal input voltage.
The input power (mains) terminals, U1, V1, W1, are connected and tightened as specified.
The input power (mains) fuses / mains switch installed. The motor terminals, U2, V2, W2, are connected and
tightened as specified. Motor cable is routed away from other cables. NO power factor compensation capacitors are connected
to the motor cable. Control terminals are wired and tightened as specified. NO tools or foreign objects (such as drill shavings) are
inside the drive. NO alternate power source for the motor is connected
– no input voltage is applied to the output of the drive.
DCOM
input and DCOM. The 24V
1
13 DI1
14 DI2
Digital input 1, program­mable. Default2 = run enable
Digital input 2, program­mable. Default2 = low water
Digital Inputs
17 DI5
18 DI6
1
Digital input impedance 1.5 kΩ. Maximum voltage for
digital inputs is 30 V.
2
Default values depend on the macro used. Values
specified are for the default macro, single/multi-pump.
NOTE: Jumper Wires between 3 and 11, 10 and
15, 11 and 12.
Digital input 5, program­mable. Default2 = not used
Digital input 6, program­mable. Default2 = not used
Goulds is a registered trademark of Goulds Pumps, Inc. and is used under license. Aquavar is a trademark of Xylem, Inc. or one of its subsidiaries.
© 2012 Xylem, Inc. AQCPCQR November 2004
Reinstall the Cover
1. Align the cover and slide it on.
2. Tighten the captive screw.
3. Reinstall the control panel.
Apply Power
Always reinstall the front cover before turn­ing power on.
WARNING! The AQUAVAR will start up automatically at power up, if the external run command is on.
1. Apply input power.
When power is applied to the
AQUAVAR, the green LED comes on.
NOTE! Before increasing motor speed, check that the motor is running in the desired direction.
Start-Up
In Start-Up, enter motor data (collected earlier) and, if needed, edit parameters that define how the drive operates and communicates.
Wizards
The Start-Up Wizard steps through typical start-up selec­tions and runs auto­matically upon the initial power up. At other times, use the steps be­low to run the Start-Up Wizard.
1. Use the MENU key to access the Menu list.
2. Select Wizards.
3. Select Start-Up Wizards.
4. Follow the screen instructions to configure
the system.
NOTE! For common parameters and menu
items, use the Help Key to display descriptions. If you encounter Alarms or
Faults, use the Help Key or refer to the Diagnostic section of the instruction manual.
REM
40.2 PSI sp
0.0 PSI ac
0.0 HZ
DIR MENU
LOC REM
11.1%
Loading...