Xantrex Technology DR2424, DR2424E, DR1524E, DR1512E, DR1524W User Manual

...
DR1512 DR2412 DR1524 DR2424 DR3624 DR1512W DR1524W DR1512E DR1524E DR1548E DR2424E
Installation and Operations Manual
DR Inverter/Charger
DR Inverter/Charger
Installation and Operation Manual
About Xantrex
Trademarks
DR Inverter/Charger is a trademark of Xantrex International. Xantrex is a registered trademark of Xantrex International.
Other trademarks, registered trademarks, and product names are the property of their respective owners and are used herein for identification purposes only.
Notice of Copyright
DR Inverter/Charger Installation and Operations Manual © March 2005 Xantrex International. All rights reserved.
Disclaimer
UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY INC. (“XANTREX”)
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.
Date and Revision
March 2005 Revision
Part Number
975-0012-01-02 Rev A
Contact Information
Telephone: 1 800 670 0707 (toll free North America)
1 360 925 5097 (direct)
Fax: 1 800 994 7828 (toll free North America)
1 360 925 5143 (direct)
Email: customerservice@xantrex.com
Web: www.xantrex.com
About This Manual
Purpose
The purpose of this Installation and Operation Manual is to provide explanations and procedures for installing, operating, maintaining, and troubleshooting the DR Inverter/Charger.
Scope
The Manual provides safety guidelines, detailed planning and setup information, procedures for installing the inverter, as well as information about operating and troubleshooting the unit. It does not provide details about particular brands of batteries. You need to consult individual battery manufacturers for this information.
Audience
The Manual is intended for anyone who needs to install and operate the DR Inverter/Charger. Installers should be certified technicians or electricians.
Organization
This Manual is organized into four chapters and three appendices.
Chapter 1, “Introduction” contains information about the features and functions of the DR Inverter/Charger.
Chapter 2, “Installation” contains information about how to plan for and install the DR Inverter/Charger.
Chapter 3, “Operation” contains information about how to operate the DR Inverter/Charger.
Chapter 4, “Troubleshooting” contains information about how to troubleshoot possible error conditions while using the DR Inverter/Charger.
Appendix A, “Specifications” contains information about the electrical specifications and environmental specifications of the DR Inverter/Charger.
Appendix B, “Appendix B, “Battery Information” supplies general information about batteries such as battery types, battery bank sizing, battery configurations, and battery care. For detailed information, see your battery manufacturer or your system designer.”
Appendix C, “Multi-wire Branch Circuit Wiring” supplies information about Multi-wire Branch Circuit Wiring Precautions when using stand-alone 120 Vac inverters or generators.
975-0012-01-02 Rev A iii
About This Manual
Conventions Used
The following conventions are used in this guide.
WARNING
Warnings identify conditions or practices that could result in personal injury or loss of life
CAUTION
Cautions identify conditions or practices that could result in damage to the unit or other equipment.
Important:
serious as a caution or warning.
These notes describe things which are important for you to know, but not as
Abbreviations and Acronyms
AC Alternating Current
ASC Authorized Service Center
AHJ Authority Having Jurisdiction
COM COMmunications Port
CW Clockwise (rotates to the right)
CCW Counter-clockwise (rotates to the left)
DC Direct Current
DR Inverter DR Inverter/Charger
DRI DR Interface (for stacking)
LED Light Emitting Diode
PV Photovoltaic
PVGFP PV Ground Fault Protection
RE Renewable Energy
RMA Return Material Authorization
Related Information
You can find more information about Xantrex Technology Inc. as well as its products and services at www.xantrex.com.
iv 975-0012-01-02 Rev A
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains important instructions for all DR Inverter/Charger models that shall be followed during installation and maintenance of the inverter.
General
1. Before installing and using the DR Inverter/Charger, read all instructions and cautionary markings on the DR Inverter/Charger and all appropriate sections of this guide. Be sure to read all instructions and cautionary markings for any equipment attached to this unit.
2. This unit is designed for indoor use only. Do not expose the DR Inverter/ Charger to rain, snow, or spray.
3. To reduce risk of fire hazard, do not cover or obstruct the ventilation openings. Do not install the DR Inverter/Charger in a zero-clearance compartment. Overheating may result.
4. Use only attachments recommended or sold by the manufacturer. Doing otherwise may result in a risk of fire, electric shock, or injury to persons.
5. To avoid a risk of fire and electric shock, make sure that existing wiring is in good condition and that wire is not undersized. Do not operate the DR Inverter/Charger with damaged or substandard wiring.
6. Do not operate the DR Inverter/Charger if it has received a sharp blow, been dropped, or otherwise damaged in any way. If the DR Inverter/Charger is damaged, see the Warranty section.
7. Do not disassemble the DR Inverter/Charger. It contains no user-serviceable parts. See Warranty for instructions on obtaining service. Attempting to service the DR Inverter/Charger yourself may result in a risk of electrical shock or fire. Internal capacitors remain charged after all power is disconnected.
8. The DR Inverter contains more than one live circuit (batteries and AC line). Power may be present at more than one source. To reduce the risk of electrical shock, disconnect both AC and DC power from the DR Inverter/Charger before attempting any maintenance or cleaning or working on any circuits connected to the DR Inverter/Charger. Turning off controls will not reduce this risk.
9. Use insulated tools to reduce the chance of short-circuits when installing or working with the inverter, the batteries, or a PV array.
975-0012-01-02 Rev A v
Safety
Wiring Requirements
1. All wiring methods and materials shall be in accordance with the National Electrical Code ANSI/NFPA 70 (Current Edition). When sizing conductors and conduits interfacing to the DR Inverter, both shall be in accordance with the National Electric Code ANSI/NFPA 70, as well as all state and local code requirements.
2. This product is intended to be installed as part of a permanently grounded electrical system per the National Electric Code ANSI/NFPA 70 (current edition). This is the single point earth ground for the inverter system.
3. Use copper conductors only with insulation rated for 75 °C.
4. The grounds on the DR Inverter are marked with this symbol:
5. The AC voltage and current on the DR Inverter is marked with this symbol:
6. The DC voltage and current on the DR Inverter is marked with this symbol:
7. Phase on the DR Inverter is marked with this symbol:
WARNING Fire Hazard:
Do not install 120 volt AC stand-alone inverters onto 120/240 volt AC multi-branch circuit wiring. This could pose a fire hazard due to an overloaded neutral return wire in this configuration. See “Multi-wire Branch Circuit Wiring” on page C–1 for details.
Explosive gas precautions
WARNING: Explosion Hazard
Working in the vicinity of lead-acid batteries is dangerous. Batteries generate explosive gases during normal operation. Therefore, you must read this guide and follow the instructions exactly before installing or using your DR Inverter/ Charger.
1. This equipment contains components which tend to produce arcs or sparks. To prevent fire or explosion, do not install the DR Inverter/Charger in compartments containing batteries or flammable materials, or in locations that require ignition-protected equipment. This includes any space containing gasoline-powered machinery, fuel tanks, as well as joints, fittings, or other connections between components of the fuel system.
2. To reduce the risk of battery explosion, follow these instructions and those published by the battery manufacturer and the manufacturer of the equipment in which the battery is installed.
vi 975-0012-01-02 Rev A
Precautions When Working With Batteries
WARNING: Explosion or Fire Hazard
Follow all instructions published by the battery manufacturer and the manufacturer of the equipment in which the battery is installed.
1. Make sure the area around the battery is well ventilated.
2. Never smoke or allow a spark or flame near the engine or batteries.
3. Use caution to reduce the risk or dropping a metal tool on the battery. It could spark or short circuit the battery or other electrical parts and could cause an explosion.
4. Remove all metal items, like rings, bracelets, and watches when working with lead-acid batteries. Lead-acid batteries produce a short circuit current high enough to weld metal to skin, causing a severe burn.
5. Have someone within range of your voice or close enough to come to your aid when you work near a lead-acid battery.
6. Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing, or eyes.
7. Wear complete eye protection and clothing protection. Avoid touching your eyes while working near batteries.
8. If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters your eye, immediately flood it with running cold water for at least twenty minutes and get medical attention immediately.
Safety
9. If you need to remove a battery, always remove the grounded terminal from the battery first. Make sure all accessories are off so you don’t cause a spark.
10. Always use identical types of batteries.
11. Never install old or untested batteries. Check each battery’s date code or label to ensure age and type.
12. Batteries are temperature sensitive. For optimum performance, the should be installed in a stable temperature environment.
13. Always recycle old batteries. Contact your local recycling center for proper disposal information.
975-0012-01-02 Rev A vii
viii
Contents
Important Safety Instructions
1
Introduction
Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2 Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2
AC Side - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–3 DC Side - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4 Optional Equipment - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4
Remote Control (RC8) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4 Stacking Interface (DRI) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4
Conduit Box (DRCB) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4 Unpacking and Inspection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4 Model Identification and Numbering Conventions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–5
2
Installation
Pre-installation Planning- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–2
Location - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–2 Mounting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–3 Ventilation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–3 Tools Required - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–3 Hardware / Materials Required - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4 Wiring Considerations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4
DC Terminal Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4 Grounding Considerations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4
AC Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4
DC Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4 Wire Routing - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4 Electrical Panels and Circuit Breaker Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–5
AC Distribution Panel (Sub-Panel) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–5
DC Disconnect - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–5 Battery Considerations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–5
Battery Location - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–6
Battery Temperature - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–6 Basic Configurations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–6 Generators - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10 Inverter Mounting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11
DC Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13
DC Circuit Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13 General DC Grounding Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -v
975-0012-01-02 Rev A ix
Contents
Batteries - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–15
Battery Types - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–15 Battery Bank Sizing - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–15 Battery Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–15 Battery Cable Sizing - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–16
DC Disconnect and Over-current Protection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–17
Battery Cable Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–18
Connecting the Battery Bank to the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–19
Installing a Battery Temperature Sensor - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–21
AC Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–22
AC Distribution Panel (Sub-panel) Mounting and Conduit Installation - - - - - - - - - - - - - - -2–22 Accessing the AC Terminals - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–22 AC Output Wiring to the AC Distribution Panel (Sub-panel) - - - - - - - - - - - - - - - - - - - - - -2–25 AC Input Wiring - On-Grid Applications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–26 AC Input Wiring using a Generator in an On-Grid Application - - - - - - - - - - - - - - - - - - - - -2–27 AC Input Wiring - Off-Grid Applications using a 120 Vac Generator - - - - - - - - - - - - - - - -2–28 AC Input Wiring - Off-Grid Applications using a 240 Vac Generator for 120 Vac Loads - - -2–29 Series Stacking (120 Vac/60 Hz Models only) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–30
3
Operation
Front Panel Controls and Indicators- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2
POWER ON/OFF Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2 Ports - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3
BATTERY SENSE Port - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3 COM Port - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3 Remote Controls (RC8/RC4) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3 Stacking Interface - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4
Controls - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4
Battery Type Selector - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4 SEARCH MODE WATTS Potentiometer - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–6
Battery Charger Rate - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–7
Over Discharge Protection/AC Transfer Voltage - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–8 Over Discharge Protection (ODP) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–9 AC Transfer Voltage - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–10 Battery Capacity - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–12
LED Indicators - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–13
Inverter Mode LED - Green - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–13 Over Temp / Overload LED - Red / Green (error condition) - - - - - - - - - - - - - - - - - - - -3–13 Battery High/Battery Low LED - Red/Green (error condition) - - - - - - - - - - - - - - - - - -3–13 Charger LED - Orange / Green - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–14 Audible Indicator (internal) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–14
Circuit Breakers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–15
x 975-0012-01-02 Rev A
Start-up - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–16 Charger Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–17
3-Stage Charging Process - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–17 Equalize Charging - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–18
4
Troubleshooting
Troubleshooting the DR Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–2 Problem Loads - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3
Ceiling Fans - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3 Cell Phones - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3 Computers and Sensitive Electronics - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3 Consumer Electronics - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3 Clocks - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4 Decreasing Loads - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4 Dimmer Switches - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4 Fluorescent Lights - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4 Heavy Loads - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4 Microwave Ovens - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4 Printers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–5 Rechargeable Devices - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–5 Undersized Loads - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–5
Contents
A
Specifications
Specifications of the DR Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -A–2
B
Battery Information
Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–2 Battery Types - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–2
Deep-cycle Flooded Lead Acid (FLA) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–2 Sealed Batteries (Gel and AGM) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–3 NiCad and NiFe Batteries - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–3
Understanding Battery Capacity Ratings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–4 Battery Bank Sizing - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–4
Understanding Amp-hour Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–5 Calculating Amp Hours - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–5
Amp Hour Example Worksheet - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–6
Battery bank size worksheet - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–7
Battery Configurations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–8
Wiring Batteries in Series - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–8 Wiring Batteries in Parallel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–9 Wiring Batteries in Series-Parallel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–10 Battery Connections for Stacked Inverters - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–12
975-0012-01-02 Rev A xi
Contents
Battery Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–13
Battery Charging - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–13 Equalization Charging - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–15 General Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–16
C
Multi-wire Branch Circuit Wiring
Multi-wire Branch Circuits - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–2 Identifying Multi-wire Branch Circuits - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–4 Correcting Multi-wire Branch Circuit Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–5
Warranty and Return Information
Index
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - IX–1
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - WA–1
xii 975-0012-01-02 Rev A
Figures
Figure 1-1 Front Panel Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–3 Figure 1-2 AC Side of the DR Inverter- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–3 Figure 1-3 DC Side of the DR Inverter- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–4 Figure 1-4 Product Identification - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–5 Figure 1-5 Model/Serial Number Sticker - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–6 Figure 2-1 On-Grid Basic Configuration (Utility Backup)- - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–7 Figure 2-2 Off-Grid Configuration (Generator only) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–7 Figure 2-3 On-Grid Configuration - with Renewable Energy Sources - - - - - - - - - - - - - - - - - - - - - 2–8 Figure 2-4 Off-Grid Configuration - with Renewable Energy Sources- - - - - - - - - - - - - - - - - - - - - 2–9 Figure 2-5 Charge Rate versus Peak AC Voltage - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10 Figure 2-6 Dimensions (not to scale) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11 Figure 2-7 Suggested Mounting Method - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12 Figure 2-8 Mounting on Plywood - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12 Figure 2-9 DC Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–14 Figure 2-10 Battery Cable Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–18 Figure 2-11 DC Terminals on the DR Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–19 Figure 2-12 Connecting the Battery Bank to the DR Inverter/Charger- - - - - - - - - - - - - - - - - - - - - 2–20 Figure 2-13 Battery Temperature Sensor (BTS) RJ11 Jack Location - - - - - - - - - - - - - - - - - - - - - 2–21 Figure 2-14 Connecting the BTS to the DR Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–21 Figure 2-15 AC Side Cover Panels - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–23 Figure 2-16 AC Terminals for AC Input to the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–24 Figure 2-17 AC Terminals for AC output to the Sub-panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–25 Figure 2-18 AC Wiring- On-Grid Application - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–26 Figure 2-19 AC Wiring using a Generator - On-Grid Application - - - - - - - - - - - - - - - - - - - - - - - 2–27 Figure 2-20 AC Wiring using a 120 Vac Generator - Off-Grid Application - - - - - - - - - - - - - - - - - 2–28 Figure 2-21 AC Wiring using a 240 Vac Generator with 120 Vac Loads only- Off-Grid Application2–29 Figure 2-22 AC Wiring for dual-inverters - On-Grid Application (120 Vac models only) - - - - - - - 2–31 Figure 2-23 Wiring for dual-inverters - On-Grid Application (120 Vac models only) - - - - - - - - - - 2–32 Figure 3-1 Front Panel Controls and Indicators - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2 Figure 3-2 Battery Type Selector Adjustment - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4 Figure 3-3 Battery Type Selector Adjustment - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–7 Figure 3-4 Battery Charger Rate Potentiometer (DR1512 values used) - - - - - - - - - - - - - - - - - - - - 3–8 Figure 3-5 ODP Enabled/Disabled Positions- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–9 Figure 3-6 Automatically Calculated Discharge Cutoff Voltage per Cell - - - - - - - - - - - - - - - - - - - 3–9 Figure 3-7 ODP Enabled/Disabled Positions- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–11 Figure 3-8 Typical Setting for Most Utility Application - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–11
975-0012-01-02 Rev A xiii
Figures
Figure 3-9 Battery Capacity Potentiometer (new) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–12 Figure 3-10 Battery Capacity Potentiometer (old)- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–12 Figure 3-11 LED Indicators - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–13 Figure 3-12 AC Pass-through and Charger AC Input Circuit Breakers- - - - - - - - - - - - - - - - - - - - -3–15 Figure 3-13 Startup Items - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–16 Figure 3-14 Charger Controls and Indicators - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–18 Figure 3-15 Equalize Positions on Battery Type Selector Switch - - - - - - - - - - - - - - - - - - - - - - - -3–19 Figure 3-16 Equalize 1 Battery Charger Rate Potentiometer (Position “1”)- - - - - - - - - - - - - - - - - -3–20 Figure 3-17 Equalize 2 Battery Capacity Rate Potentiometer (Position “0”) - - - - - - - - - - - - - - - - -3–20 Figure B-1 6-volt Battery Wiring - “Series” Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–8 Figure B-2 12-volt Battery Wiring - “Series” Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - - B–9 Figure B-3 Battery Wiring in Parallel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–9 Figure B-4 Battery Wiring 24-volt - Parallel Configuration - Step 1 - - - - - - - - - - - - - - - - - - - - - B–10 Figure B-5 Battery Wiring 24-volt - Parallel Configuration - Step 2 - - - - - - - - - - - - - - - - - - - - - B–10 Figure B-6 Battery Wiring 24-volt - Parallel Configuration - Step 3 - - - - - - - - - - - - - - - - - - - - - B–11 Figure B-7 Example of Battery Connections for Stacked Inverters (24 Vdc shown) - - - - - - - - - - B–12 Figure C-1 Conventional Home-type Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–2 Figure C-2 Multi-wire Branch Circuit Wiring and Current Flow - - - - - - - - - - - - - - - - - - - - - - - - C–3 Figure C-3 120 Vac Inverter Incorrectly Wired in a Multi-wire Branch Circuit - - - - - - - - - - - - - - C–3 Figure C-4 Multi-wire Branch Circuit Wiring- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–4 Figure C-5 Using a Step-down Autotransformer in Multi-wire Branch Circuit Wiring - - - - - - - - C–6S
xiv 975-0012-01-02 Rev A
Tables
Table 1-1 Model Identification and Numbering Conventions - - - - - - - - - - - - - - - - - - - - - - - - - - 1–5 Table 1-2 Letter Suffix Code Definitions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–6 Table 2-1 Peak Input Filtrate versus Charging Current - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10 Table 2-2 Safety Ground Conductor Size - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13 Table 2-3 Minimum Recommended Battery Cable Size versus Length - - - - - - - - - - - - - - - - - - 2–16 Table 2-4 Battery Cable to Maximum Breaker/Fuse Size- - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–17 Table 2-5 Minimum Recommended Wire Size, Torque Values (Input and Output),
and Maximum Output Breaker Size - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–23 Table 3-1 Battery Type Selector Switch Settings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–5 Table 3-2 Approximate Charge rate Setting/Amperage - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–8 Table 3-3 ODP/AC Transfer Voltage - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–10 Table 3-4 AC Pass-through Circuit Breakers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–15 Table 3-5 Battery Charger Circuit Breakers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–15 Table 4-1 Troubleshooting the DR Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–2 Table A-1 Electrical Specifications for the DR Inverter/Charger - 120 Vac/60 Hz Models- - - - - - -A–2 Table A-2 Electrical Specifications for the DR Inverter/Chargers - 220 Vac/60 Hz Models - - - - - -A–4 Table A-3 Electrical Specifications for the DR Inverter/Charger - 230 Vac/50 Hz Models- - - - - - -A–5 Table A-4 Environmental Specifications for the DR Inverter/Charger - - - - - - - - - - - - - - - - - - - -A–7 Table B-1 Determining Average Daily Load in Amp-hours (Example - - - - - - - - - - - - - - - - - - - -B–6 Table B-2 Determining Battery Bank Size - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–7 Table B-3 Typical Appliance Wattage- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–7 Table B-4 Variances in Charging Voltage based on Battery Temperature - - - - - - - - - - - - - - - - - B–14 Table B-5 Temperature Compensation Calculation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–14 Table B-6 Battery State-of-Charge - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–17
975-0012-01-02 Rev A xv
xvi
1
Introduction
Chapter 1, “Introduction” contains information about the features and functions of the DR Inverter/Charger.
Introduction
Introduction
Thank you for purchasing the DR Inverter/Charger from Xantrex Technology Inc. The DR Inverter is one of the finest inverter/chargers on the market today, incorporating state-of-the-art technology and high reliability.
The inverter features an AC pass-through circuit, powering your home appliances from utility or generator power while charging the batteries. When utility power fails, the battery backup system keeps your appliances powered until utility power is restored. Internal protection circuits prevent over-discharge of the batteries by shutting down the inverter when a low battery condition occurs. When utility or generator power is restored, the inverter transfers to the AC source and recharges the batteries.
The front panel features LEDs for reading system status, and controls to customize the inverter settings for your battery bank.
The DR Inverter is an economical product designed to provide a reliable supply of electricity to all the essential circuits in the home or business during a power outage. The critical loads can be powered for hours or days, depending on the size of the system battery bank. When utility grid power returns, the batteries are quickly recharged to ensure they will be ready to supply backup power during the next outage.
Accessories allow the DR Series to also serve as a central hub of a renewable energy system.
Modified Sine Wave P owe r
Battery Charger/AC Transfer Relay
Simplicity The DR Inverter is simple to operate. All inverter and battery charger controls are
High Efficiency The inverter/charger operates at over 90% efficiency through most of its power
Low Power Consumption
The DR Inverter provide a modified sine wave output which operates most AC appliances and equipment.
The inverter/charger includes a 3-stage battery charger designed to recharge any type of battery in the shortest possible time. The built-in, fully automatic AC transfer relay automatically transfers power from the utility to the inverter and handles a full 60 amps of current at 120 Vac (30 amps for pass-through plus 20 to 30 amps for charging - depending on the model).
located on the front panel.
range in Invert-mode.
DR Inverter use extremely low current while in the search mode, consuming less than 1 watt of power. In the O of power.
N mode, the inverter/charger uses less than 12 watts
Features
The following sections illustrate the features of the DR Inverter. Figure 1-1 shows the features of the front side of the DR Inverter and identifies the AC side from the DC side.
1–2 975-0012-01-02 Rev A
Features
Battery Caps
Figure 1-1
AC Side
DC End
COM Port
Front Panel Features
The AC side of the DR Inverter has one 30-amp breaker for pass-thru AC Input, and one 30-amp (20 amp in certain models) breaker for charger AC input.
Front Panel Controls
and Indicators
AC End
Battery Sense Port
30 Amp Breaker for Pass-thru AC Input
20 or 30 Amp Breaker for Charger AC Input
Ventilation Holes
Cover plate is not shown in this photo.
Figure 1-2
AC Side of the DR Inverter
975-0012-01-02 Rev A 1–3
Introduction
DC Side
The DC side of the DR Inverter has the equipment ground lug, the positive (+) battery terminal, and the negative (–) battery terminal.
Battery Positive (+) Terminal
Ventilation Holes
Figure 1-3
DC Side of the DR Inverter
Optional Equipment
The following options are available for the DR Inverter/Chargers.
Remote Control (RC8)
The RC8 allows the inverter to be switched ON or OFF remotely and includes an LED status indicator. This unit is also compatible with the RC4 (the predecessor to the RC8); although the RC4 is no longer available for purchase from Xantrex.
Ventilation Holes
Battery Negative (–) Terminal
Ground Lug
Stacking Interface (DRI)
The DRI stacking interface provides 3-wire 120/240 Vac at twice the power using dual DR Inverters (120 Vac/60 Hz units only).
Conduit Box (DRCB)
The DRCB conduit box connects to the DC side of the inverter and accepts a DC conduit run.
Unpacking and Inspection
Carefully unpack the inverter/charger from its shipping carton.
1–4 975-0012-01-02 Rev A
Features
Important:
additional help available if necessary, to assist in lifting the unit during installation.
The unit weighs 35–45 lb/15.9–20.4 kg (depending on model). Have
Verify all of the items listed on the packing material sheet are present. Please
call Xantrex Customer Service at (800) 670-0707 if any items are missing.
Save your proof-of-purchase. This is required if the unit should require
warranty service.
Save the original shipping carton and packing materials! If the inverter ever
needs to be returned for service, it should be shipped in the original carton. This is also a good way to protect the inverter if it ever needs to be moved.
Record the unit’s model, serial number and date of purchase in the appropriate
fields in section “Information About Your System” on page WA–4.
Important:
or illustrations used in this manual may not exactly match your unit. Xantrex Technology Inc. reserves the right to update this product without notice or releasing an updated manual when fit, form or function are not affected.
Due to continual improvement through product updates, photographs and/
Model Identification and Numbering Conventions
The DR Inverter is identified by the model/serial number labels. The Serial Number can be located on the mounting rail or inside the top cover. Model Number labels may be located on the bottom side of the front cover or possibly inside the front cover. All the necessary information is provided on the label such as AC output voltage, power and frequency (punch holes).
The inverter also has a letter designator followed by 4 or 5 digits (depending on revision). The model number describes the type of inverter, the output specifications, the required battery voltage and the output voltage and frequency
Table 1-1
DR
15
12
E
Product Family
Output Power
Figure 1-4
975-0012-01-02 Rev A 1–5
Model Identification and Numbering Conventions
indicates the type of inverter/charger - DR Series.
the first two digits of the numerical designator indicate the inverter’s output power - 1500 Watts.
the second two digits indicate the required nominal battery bank voltage ­12 Vdc.
the letter suffix code indicates the output voltage and frequency of the inverter ­230 Vac/50 Hz.
Country Code
(Letter Suffix)
Example: DR 1512 E
Battery Voltage
Product Identification
Introduction
Table 1-2
Letter Suffix Output Voltage Output frequency
(no letter) 120 Vac 60 Hz
E 230 Vac 50 Hz
J 105 Vac 50 Hz
K 105 Vac 60 Hz
W 220 Vac 60 Hz
Letter Suffix Code Definitions
Figure 1-5
Model Number Sticker
Regulatory
The 120 Vac/60 Hz models of the DR Series inverter/charger (models DR1512, DR1524, DR2412, DR2424, and DR3624) are ETL Listed to UL Standard 1741, (First Edition) Power Conditioning Units for use in Residential and Commercial Photovoltaic Power Systems.
These standards guarantee that the DR Inverter/Charger has been tested to nationally recognized safety standards (UL for the US) and have been found to be free from reasonably foreseeable risk of fire, electric shock and related hazards.
The DR Inverter/Charger is intended to be used for residential or commercial applications. Do NOT use this unit for applications for which it is not listed (i.e., land vehicles or marine craft). It may not comply with the safety code requirements or could possibly present other operational or safety hazards.
1–6 975-0012-01-02 Rev A
2
Installation
Chapter 2, “Installation” contains information about how to plan for and install the DR Inverter/Charger.
Installation
Pre-installation Planning
Location
Important:
and cautionary markings on the DR Inverter/Charger and all appropriate sections of this guide. Be sure to read all instructions and cautionary markings for any equipment attached to this unit.
Take some time prior to installing the equipment to pre-plan the installation. Location, mounting, and ventilation should be taking into consideration before any cabling can be done.
Before installing and using the DR Inverter/Charger, read all instructions
CAUTION: Personal Injury
The inverter/charger can weigh up to 45 lbs (20.4 kg) depending upon configuration. Always use proper lifting techniques during installation to prevent personal injury.
Inverters contain sophisticated electronic components and should be located in a well protected, dry environment away from sources of fluctuating or extreme temperatures and moisture. Exposure to saltwater is particularly destructive and potentially hazardous.
Locate the inverter as close to the batteries as possible in order to keep the battery cable length short. However, do not locate the inverter above the batteries or in the same compartment as vented batteries. Batteries generate hydrogen sulfide gas which is corrosive to electronic equipment. They also generate hydrogen and oxygen. If accumulated, an arc caused by connecting the battery cables or switching a relay could ignite this mixture. Mounting the inverter in a ventilated enclosure with sealed batteries is acceptable.
CAUTION: Corrosion Damage
If the inverter is installed in a location where it is exposed to a corrosive or condensing environment and fails due to corrosion, it will not be covered under warranty.
Important:
sensitive electronic equipment susceptible to RFI as far away from the inverter as possible. This includes radios and TVs.
2–2 975-0012-01-02 Rev A
Inverters can generate RFI (Radio Frequency Interference). Locate any
Mounting
Ventilation
Pre-installation Planning
The National Building Code requires the inverter be mounted on a vertical surface (or wall). The keyhole slots must not be used as the only method of mounting. The purpose of the wall mounting requirement is to orient the inverter so that its bottom cover, which has no holes, will not allow burning material to be ejected in the event of an internal fire. Use 0.25-inch diameter bolts for mounting. The mounting surface must be capable of supporting twice the weight of the inverter to comply with UL 1741.
Install the inverter in a well ventilated area/enclosure for proper operation. The inverter’s thermal shutdown point will be reached sooner than normal in a poorly ventilated environment, resulting in reduced peak power output and surge capability, as well as shorter inverter life.
The inverter contains an internal fan. Ensure the air vents and intakes are not obstructed in any way. Provide a minimum clearance of 6 inches around the top and sides of the inverter for ventilation.
Tools Required
The following tools may be required to complete this installation.
#2 Phillips screw driver Slotted screw driverAssorted open-end wrenches Socket wrench and fittingsMultimeter (True rms)Hole sawLevelWire strippersTorque wrenchElectrical tapePencilUtility knife
975-0012-01-02 Rev A 2–3
Installation
Hardware / Materials Required
The following hardware or materials may be required to complete this installation.
4 ft. x 4 ft. sheet of 3/4" plywood or 2 x 4’s studding material#12 wood screws (or 1/2" x 1-1/4" lag bolts)Conduit and appropriate fittingsWire nuts
Wiring Considerations
All wiring and installation methods should conform to applicable electrical and building codes.
Pre-plan the wire and conduit runs.
The AC terminals accept cable sizes up to #6 AWG.
The DC terminals accept cable sizes up to #4/0 AWG that use ring terminals with 5/16" holes.
For maximum safety, run both AC and DC cables in conduit.
DC Terminal Connections
Battery-to-inverter cabling should be only as long as required.
For Example: If #4/0 AWG cables are used, do not exceed 5 feet (one way) in 12 Vdc systems; do not exceed 10 feet (one way) in 24 Vdc systems.
For optimum performance, use pre-assembled battery cables designed specifically for this application (available from Xantrex).
Grounding Considerations
AC Grounding
The inverter/charger should be connected to a grounded, permanent wiring system. Neutral and ground conductors should only be bonded at the main electrical service panel.
DC Grounding
The negative battery conductor should be bonded to the grounding system at only one point in the system. The size for the conductor is usually based on the size of the largest conductor in the DC system.
2–4 975-0012-01-02 Rev A
Wire Routing
Pre-installation Planning
Determine all wire routes both to and from the inverter and which knockouts are best suited for connecting the AC conduits. Possible routing scenarios include:
AC input wiring from the main electrical service panel to the inverter/charger (if used)
AC input wiring from the generator to the inverter/charger (if used)
DC input wiring from the RE to the inverter/charger (if used)
DC input wiring from the batteries to the inverter/charger
AC output wiring from the inverter/charger to the sub-panel
Battery Temperature Sensor cable from the batteries to the inverter/charger (if used)
Remote control cable to the inverter/charger (if used)
DC ground from the batteries to an external ground rod
Load circuit wiring rerouted from the main service panel to the sub-panel
Check for existing electrical or plumbing prior to making cuts in the walls. Cut holes in the walls at appropriate locations for routing wiring/cables.
Electrical Panels and Circuit Breaker Requirements
The following electrical panels and circuit breakers may be required for this installation.
AC Distribution Panel (Sub-Panel)
Loads backed up by the inverter will need to be rerouted from the main electrical panel to a sub-panel. This can be done several different ways, depending upon the installation. Always refer to electrical codes for safe wiring practices.
DC Disconnect
Install a DC disconnect breaker or fuse in the positive battery line. This breaker protects the DC wiring in the event of an accidental short. Size the breaker in accordance with the battery cables. Switch this breaker OFF whenever servicing the batteries.
Battery Considerations
The DR Inverter can support either 12-volt battery banks or 24-volt battery banks. The battery voltage MUST match the voltage requirements of the inverter. To determine the correct voltage for the system, check the last two digits on the inverter’s model number. For example, the DR1512 is a 12-volt inverter and requires a 12 Vdc battery system. The DR2424 is a 24-volt inverter and requires a 24 Vdc battery system.
975-0012-01-02 Rev A 2–5
Installation
Battery Location
Locate the batteries in an accessible location. Two feet clearance above the batteries is recommended for access to the battery caps. They should be located as close to the inverter as possible without limiting access to the inverter’s disconnects. Install the batteries to the left of a wall mounted inverter for easy access to the DC side of the inverter and shorter cable runs.
For safety and to limit access to the batteries, a lockable, ventilated, battery enclosure or dedicated room should be used. If an enclosure is used, it should be vented to the outside via a one inch vent pipe located at the top of the enclosure. Install an intake vent at the bottom of the enclosure to promote air circulation. These vents exhaust explosive hydrogen gases and must not be overlooked when designing an enclosure.
The enclosure should be made of an acid resistant material or have a finish that resists acid to prevent corrosion. It should be capable of holding the electrolyte from at least one battery should a leak occur.
Place a layer of baking soda on the shelves to neutralize any acid that may be spilled in the future (lead-acid batteries only).
Enclosures located outside must be rainproof and screened to prevent access by rodents or insects.
Battery Temperature
The battery enclosure should provide a fairly stable temperature for the batteries. If it is installed in a cold environment, insulation should be used to protect the batteries from the cold. The insulation also provides a more consistent temperature and better system performance.
The battery enclosure should not be installed in direct sunlight where the summer sun can overheat the batteries. Locate the enclosure where it will be protected from the afternoon sun and provide vents in the top and bottom of the enclosure to provide air flow. High battery temperatures greatly shortens the life of the batteries.
Basic Configurations
The following illustrations show basic applications for the DR Inverter/Charger. They include the following configurations.
On-Grid Configuration - Utility Backup
Off-Grid Configuration - Generator only
On-Grid Configuration with Renewable Energy Sources
Off-Grid Configuration with Renewable Energy Sources and a Generator
Consult with your system design for other possible configurations depending on site and code requirements.
2–6 975-0012-01-02 Rev A
Pre-installation Planning
Figure 2-1
On-Grid Basic Configuration (Utility Backup)
Figure 2-2
975-0012-01-02 Rev A 2–7
Off-Grid Configuration (Generator only)
Installation
Figure 2-3
2–8 975-0012-01-02 Rev A
On-Grid Configuration - with Renewable Energy Sources
Pre-installation Planning
Figure 2-4
975-0012-01-02 Rev A 2–9
Off-Grid Configuration - with Renewable Energy Sources
Installation
Generators
An AC generator can be used as an input source instead of the utility power, or can be connected (using additional hardware) to power the loads when utility is not present (utility outage), and to charge the batteries. The generator must be of the permanently installed type and not a portable type unit used for emergency power. Small emergency type (lower power) generators may not have a stable enough voltage for the inverter to synchronize to or provide enough current to fully charge the batteries.
The maximum charge rate the battery charger can deliver is dependant upon the peak AC voltage available. Since the battery charger uses only the top portion of the input sine wave, small variations in peak voltage result in large variations in the amount of energy to the charger. The charger’s rated output is based on a utility voltage of 120 Vac RMS (the usual measured value). This should have a peak voltage of 169 Vac
(230 Vac has a peak voltage of 325 Vac). For every 10
p
p
volts of peak lost, the charge rate is reduced by approximately half.
Size the generator appropriately for the system, including battery charge and load current (typically twice the wattage output of the inverter).
Table 2-1 and Figure 2-5 demonstrates how the peak voltage available affects the charging current.
Table 2-1
Peak Voltage Available DR1512 DR2412 DR1524 DR242 DR3624
170 Vac
160 Vac
145 Vac
Peak Input Filtrate versus Charging Current
p
p
p
70 amps 120 amps 35 amps 70 amps 70 amps
35 amps 60 amps 17.5 amps 35 amps 35 amps
15 amps 25 amps 7 amps 15 amps 15 amps
Figure 2-5
2–10 975-0012-01-02 Rev A
Charge Rate versus Peak AC Voltage
Inverter Mounting
Pre-installation Planning
The DR Series inverter can weigh as much as 45 lb. (20.4 kg). Wallboard is not strong enough to support its weight so additional support must be used or added. The inverter can be mounted directly to the wall studs if the wall studs are 16" apart. If not, then 2x4’s or plywood can be used.
WARNING: Personal Injury
Use appropriate lifting techniques. Have extra people on hand to assist in lifting the inverter into position while it is being secured.
To secure the DR Inverter to the wall studs:
1. Locate the studs and mark their location on the wall.
2. Measure the desired height from the floor for the inverter to be mounted.
3. Using a level, run a horizontal line. The length of the line must span at least three studs.
4. Using the dimensions illustrated in Figure 2-6, drill mounting holes into the center of the studs for the inverter.
5. Secure the inverter to the studs using ¼ x 1½ inch lag bolts and washers.
Figure 2-6
975-0012-01-02 Rev A 2–11
Dimensions (not to scale)
To secure the DR Inverter to the mounting location using 2 x 4’s or plywood:
1. Repeat steps 1 through 3 above.
2. Place a pre-cut 2 x 4 (flat side against the wall) on the marked location and drill pilot holes through the 2 x 4’s and studs.
Installation
3. Secure the 2 x 4 with #10 wood screws (length to penetrate 1½ inches into the studs) as shown in Figure 2-7.
4. Measure 7 5/8" from the center of the first 2 x 4 and draw another level line. Place the center of the second 2 x 4 over this line and secure to the wall as described in Step 5.
5. Using the dimensions illustrated in Figure 2-6, drill mounting holes into the center of the 2 x 4’s for the inverter.
6. Secure the inverter to the 2 x 4’s using ¼ x 1½ inch lag bolts and washers.
Figure 2-7
Figure 2-8
2–12 975-0012-01-02 Rev A
Suggested Mounting Method
Ensure the plywood spans across a minimum of three wall studs for adequate support.
Mounting on Plywood
DC Wiring
This section describes the DC wiring requirements and how to make the connections. It provides the required cable and wire sizes, recommended lengths for cables, and disconnect/circuit breaker requirements.
DC Circuit Grounding
Grounding is an important part of the system installation and must be performed correctly to ensure safe operation of the equipment. Grounding requirements vary by country and application. Consult the NEC for specific requirements.
The ground conductor should be sized appropriately for the over-current protection device being used and according to NEC 250-95 (Ninth Edition) (see Table 2-2 below for a portion of the NEC code).
DC Wiring
Table 2-2
Size of Over-current Device Protecting the Conductor
30 or 60 amp #10 AWG
100 amp #8 AWG
200 amp #6 AWG
300 amp #4 AWG
400 amp #3 AWG
Safety Ground Conductor Size
General DC Grounding Requirements
This product is intended to be installed as part of a permanently grounded electrical system per the National Electric Code ANSI/NFPA 70 (current edition). This is the single point earth ground for the inverter system.
To ground the DC circuits:
1. Connect the negative (-) terminal of the battery bank to an appropriately sized conductor and connect it to the ground bus in the DC Disconnect.
2. Connect an appropriately sized conductor to the Ground bus in the DC Disconnect and connect it to the primary system ground.
The system ground is the same ground used by the AC side of the system.
Minimum Size of the Copper Ground Wire
975-0012-01-02 Rev A 2–13
Installation
Figure 2-9
2–14 975-0012-01-02 Rev A
DC Grounding
Batteries
Battery Types
Battery Bank Sizing
DC Wiring
The DR Inverter can support either 12-volt battery banks or 24-volt battery banks. Before proceeding, ensure you have the appropriate sized batteries for this inverter.
Batteries are available in different sizes, amp-hour ratings, voltage, liquid or gel, vented or non-vented, chemistries, etc. They are also available for starting applications (such as an automobile starting battery) and deep discharge applications. Only the deep discharge types are recommended for inverter applications. Choose the batteries best suited for the inverter installation and cost. Use only the same battery type for all batteries in the bank. For best performance, all batteries should be from the same lot and date. This information is usually printed on a label located on the battery.
Additional information regarding batteries can be found in the Appendix B, “Battery Information”.
Battery Configuration
The size of the battery bank determines how long the AC loads will operate in a backup mode without utility power. The larger the battery bank, the longer the run time. Size the battery bank to the AC load requirements and length of time required to run from the batteries. In general, the battery bank should not be discharged more than 50%. Additional DC charging devices such as solar, wind, hydro, etc., can provide longer run times by recharging the batteries in the absence of AC utility or generator power.
Additional details on estimating battery bank size and capacity can be found in “Battery Bank Sizing” on page B–4.
The battery bank must be wired to match the inverter’s DC input voltage specifications (12 Vdc, 24 Vdc, or 48 Vdc). In addition, the batteries can be wired to provide additional run time. The various wiring configurations are:
SERIES - Wiring batteries in series increases the total bank output voltage (to match the inverter’s DC requirements).
PARALLEL - Wiring the batteries in parallel increases the total run time the batteries can operate the AC loads.
SERIES-PARALLEL - Series-parallel configurations increase both the battery voltage (to match the inverter’s DC requirements) and run-time for operating the AC loads.
For additional information on how to wire these battery-bank configurations, see “Battery Configurations” on page B–8.
975-0012-01-02 Rev A 2–15
Installation
Battery Cable Sizing
Proper cable sizing (diameter and length) is critical to the safe and efficient operation of an inverter system. Larger diameter cables (smaller AWG number) have less voltage drop and are, therefore, more efficient when transferring power to and from the batteries. If a cable is undersized (diameter too small), it could potentially overheat, creating a fire hazard.
Cable length is another important factor. Runs should be kept as short as practical. Longer cable runs increase resistance, thus lowering the overall efficiency of the system. This is especially true in lower voltage systems (i.e., 12 Vdc) where, depending upon the length of the cable run, it may be necessary to oversize the diameter of the wire, or parallel (double) the cables.
Table 2-3
Inverter Model
DR1512 150 A
DR2412 240 A
DR1524 75 A
DR2424 120 A
DR3624 180 A
Minimum Recommended Battery Cable Size versus Length
Typical Amperage 1 to 3 feet (one-way) 3 to 5 feet (one-way) 5 to 10 feet (one-way)
Important:
for the amperage of the inverter and batteries.
Only use copper cables. Always use a properly sized cable and length rated
WARNING: Fire Hazard
Undersized cables can overheat and melt, creating a fire hazard when subjected to heavy (peak) loads.
Table 2-3 provides recommended minimum cable sizes for various cable lengths and inverter amperages. These recommendations may not meet all local or NEC requirements.
Important:
possible by taping them together. This reduces the effects of inductance and produces a better waveform thus increasing efficiency. See Xantrex Technical Note 008 on the
Xantrex website for additional information on Battery Cable Inductance.
#2/0 AWG (67.4 mm
#4/0 AWG (107 mm
#2/0 AWG (67.4 mm
#2/0 AWG (67.4 mm
#4/0 AWG (107 mm
Run the positive and negative battery cables as close to each other as
2
) #2/0 AWG (67.4 mm2) #4/0 AWG (107 mm2)
2
) #2/0 AWG (67.4 mm2) #2/0 AWG (67.4 mm2)
2
) #2/0 AWG (67.4 mm2) #2/0 AWG (67.4 mm2)
2
) #4/0 AWG (107 mm2) #4/0 AWG (107 mm2)
2
) #4/0 AWG (107 mm2) #4/0 AWG (107 mm2)
Important:
micro-hydroelectric plant or wind generator), increasing the size of the cables and disconnects will greatly reduce the number of nuisance outages associated with breaker tripping and open fuses.
2–16 975-0012-01-02 Rev A
If the system includes a large battery bank or large DC source (such as a
DC Disconnect and Over-current Protection
For safety and to comply with regulations, battery over-current protection is required. Fuses and disconnects must be sized to protect the wiring in the system and are required to open before the wire reaches its maximum current carrying capability.
The National Electrical Code (NEC) requires both over-current protection and a disconnect switch for residential and commercial electrical systems. These items are not supplied as part of the inverter. However, Xantrex offers a DC rated, ETL Listed, circuit breaker disconnect module specifically designed for use with Xantrex™ inverters to meet NEC compliance. Two amperage ratings are available: a DC250 (250 amps) and a DC175 (175 amps) in either single or dual breaker configurations for single- or dual-inverter installations.
DC Wiring
Important:
Xantrex™ DC disconnects are not designed to accept doubled (paralleled) cables which may be required for long cable runs. Also, the plastic red and black covers on the DC inverter inputs are not designed to accommodate dual cables. If dual cables are used, the optional conduit box (DRCB) must be used.
Some installations may not require conduit or a disconnect device, although over-current protection is still required. Xantrex offers a fuse block (TFB) providing the code required inverter over-current protection for these applications. Refer to the table below for the proper size disconnect device for specific cable diameters.
Table 2-4
Cable Size Required Rating in Conduit
#2 AWG 115 amps max N/A 170 amps max TFB200
#2/0 AWG 175 amps max DC175 265 amps max TFB300
#4/0 AWG 250 amps max DC250 360 amps max TFB400
Battery Cable to Maximum Breaker/Fuse Size
Maximum Breaker Size
Important:
rating (i.e., 150 amp cable size rounds up to a standard 175 amp size). The term “free air” is defined by the NEC as cabling that is not enclosed in a conduit or a raceway. Cables enclosed in conduit or raceways have substantially lower continuous current carrying ability due to heating factors.
The NEC allows rounding to the next standard fuse size from the cable
Rating in “Free Air”
Maximum Fuse Size
975-0012-01-02 Rev A 2–17
Installation
Battery Cable Connections
Battery cables must have crimped (or preferably, soldered and crimped) copper compression lugs unless aluminum mechanical lugs are used. Soldered connections alone are not acceptable. High quality, UL-listed battery cables are available from Xantrex in an assortment of lengths: 1½ to 10 feet, and in #2/0 AWG or #4/0 AWG sizes. These cables are color-coded with pressure crimped, sealed ring terminals.
Figure 2-10 illustrates the proper method to connect the battery cables to the DR Inverter’s DC terminals.
Do not place anything
between battery cable lug
and terminal surface.
Assemble exactly as shown.
2/0 Copper Compression Lug 2/0 Aluminum Mechanical Lug
Figure 2-10
Battery Cable Connections
CAUTION: Equipment Damage
The inverter is not reverse polarity protected. Reversing the battery polarity on the DC input connections will cause permanent damage to the inverter which is not covered under warranty. Always check polarity before making connections to the inverter.
WARNING: Shock Hazard
Ensure the inverter is off before disconnecting the battery cables, and that AC power is disconnected from the inverter input.
2–18 975-0012-01-02 Rev A
Positive (+) Battery Terminal
DC Wiring
Torque the Positive (+) Battery terminal to 10-15 ft-lbs (13.6 to 20.3 nm)
Torque value for the Ground Lug is 10-15 in-lbs (1.1 to 1.7 nm)
Figure 2-11
DC Terminals on the DR Inverter
Ground Lug
Connecting the Battery Bank to the Inverter
Follow the procedure below to connect the battery bank to the inverter.
WARNING: Shock Hazard
:
Ensure the inverter is off before connecting or disconnecting the battery cables and that all AC power is disconnected from the inverter’s inputs.
Negative (–) Battery Terminal
Torque the Negative (–) Battery terminal to 10-15 ft-lbs (13.6 to 20.3 nm)
To connect the battery bank to the inverter:
1. Determine the correct size battery cable to use for installation from Table 2-3
on page 2–16.
2. Determine the correct size disconnect/fuse for installation from Table 2-4 on
page 2–17.
3. Color code the cables with tape or heat shrink tubing. The standard colors are
red for positive (+) and black for negative (–). (NEC requires white for the negative conductors.)
4. Connect the negative (–) cable to the battery’s negative terminal (torque to
manufacturer’s recommendations).
5. Install the over-current device (fuse or circuit breaker) between the battery’s
positive terminal and the inverter’s positive terminal (as close to the batteries as possible).
6. Connect the (short) positive cable to the battery’s positive terminal (torque to
manufacturer’s recommendations).
7. Ensure the correct polarity of the cables with a DC voltmeter (DVM).
975-0012-01-02 Rev A 2–19
Installation
8. Observing battery polarity, connect the positive battery cable (from the over-current device) to the inverter’s positive terminal.
Important:
connecting the cable to the inverter. This is normal, and is caused by the inverter’s capacitors charging up.
The next step may cause a small spark and snapping sound when
9. Observing battery polarity, connect the negative battery cable to the inverter’s negative terminal.
10. Use an insulated ½ inch wrench or socket to tighten the 5/16 SAE nuts to 10-15 ft-lb (13.6 to 20.3 nm) for each inverter input terminal.
CAUTION: Equipment Damage
: Equip
Do not put anything between the cable ring terminal and the flat metal part of the terminal. overheating of the terminal may occur. Do not apply any type of antioxidant paste until after the battery cable wiring is tightened.
11. Apply antioxidant paste to the battery and inverter terminals.
12. Install the battery terminal connection covers (red for positive, black for negative) over the inverter’s DC terminals and secure with the screws and washers provided.
Figure 2-12
2–20 975-0012-01-02 Rev A
Connecting the Battery Bank to the DR Inverter/Charger
Installing a Battery Temperature Sensor
A battery temperature sensor (BTS) option can easily be installed in the system to ensure proper charging of the batteries based on temperature. Installing a BTS extends battery life by preventing overcharging in warm temperatures and undercharging in cold temperatures.
To install the Battery Temperature Sensor:
1. Run the battery temperature sensor wire in the DC conduit (if used) and route the RJ11 connector end to the BATTERY SENSE port located on the front of the inverter.
2. Secure the sensor to one of the batteries located in the center of the battery pack.
DC Wiring
Battery Sense (RJ11) port
Figure 2-13
Figure 2-14
Battery Temperature Sensor (BTS) RJ11 Jack Location
Connecting the BTS to the DR Inverter
975-0012-01-02 Rev A 2–21
Installation
AC Wiring
This section describes the AC wiring requirements and how to make the connections. It provides the required wire sizes, recommended lengths for conductors, and disconnect/circuit breaker requirements.
Important:
qualified person or a licensed electrician following all local and NEC codes.
The installation of sub-panels and wiring should be performed by a
AC Distribution Panel (Sub-panel) Mounting and Conduit Installation
WARNING: Shock Hazard
Disconnect the power from the utility’s main breaker box before proceeding.
1. Determine the location of the sub-panel and install it according to the manufacturer’s directions.
2. Install the AC conduit between the sub-panel (output) and inverter.
3. Install conduit between the inverter (input) and the main breaker box.
4. Determine which circuits require backup. Install the appropriate circuit breakers into the sub-panel.
5. Install an appropriately sized circuit breaker (30 amp maximum) in the sub-panel. This will later be wired to the inverter’s output. If two inverters are being used in a stacked configuration, install a double-pole circuit breaker for 240 Vac service.
Accessing the AC Terminals
CAUTION: Equipment Damage
The inverter’s AC output must never be wired to the utility or generator output. This will cause severe damage to the inverter which is not covered under warranty.
All AC wiring connects to the terminal block located on the right-hand side of the inverter.
To make the AC connections to the inverter:
1. To access the terminal block, remove the side cover panels (if installed) by removing the two (or three) Phillips screws. Units are shipped without the covers installed (packed in a small plastic bag with additional hardware).
2. Locate the AC input and output terminals on the block. Refer to Figure 2-15 on page 2–23.
2–22 975-0012-01-02 Rev A
AC Wiring
Figure 2-15
Important:
DR36XX models are equipped with a conduit box and not a plate. The conduit box is required for the larger diameter wire providing ample bending radius.
Standard Cover Plate
DR15XX
AC Side Cover Panels
Before wiring the input of the inverter, refer to Table 2-5 below for the minimum recommended wire size.
Important:
The lower AC cover varies depending on the model. DR24XX and
Screws
High Power Conduit Box
DR24XX and DR36XX models
Refer to the NEC for actual wire sizes for specific installations.
Table 2-5
Minimum Recommended Wire Size, Torque Values (Input and Output), and Maximum Output
Breaker Size
AC Input AC Output Torque Value
Inverter Model
DR1512 #8 or 6 AWG #10 AWG #10 AWG #16 AWG 16 in-lbs
DR2412 #6 AWG #10 AWG #10 AWG #14 AWG 16 in-lbs
DR1524 #8 or 6 AWG #10 AWG #10 AWG #16 AWG 16 in-lbs
DR2424 #6 AWG #10 AWG #10 AWG #14 AWG 16 in-lbs
DR3624 #6 AWG Not Available #8 AWG Not Available 16 in-lbs
for Terminal Connections
(1.8 nm)
(1.8 nm)
(1.8 nm)
(1.8 nm)
(1.8 nm)
WARNING: Fire Hazard
To reduce the risk of fire, connect only to a circuit provided with the maximum branch-circuit overcurrent protection noted above in accordance with the National Electrical Code, ANSI/FFPA70.
Maximum Output Breaker Size120 Vac 220-240 Vac 120 Vac 220-240 Vac
30 amps AC
30 amps AC
30 amps AC
30 amps AC
30 amps AC
975-0012-01-02 Rev A 2–23
Installation
Important:
NEC and local codes. Conduit fittings can be replaced with strain reliefs where code permits.
The U.S. requires conduit be used in this type of installation. Refer to the
WARNING: Shock Hazard
Disconnect the battery cables from the inverter if they are already connected.
To connect the AC Input to the Inverter:
1. Disconnect the main breaker at the main electrical service panel (if used) or disconnect the AC generator.
2. Install an appropriately sized circuit breaker in the electrical service panel. This will serve as both an AC disconnect and over-current protection. If using a generator only, use the circuit breaker in the generator.
3. Feed the HOT, NEUTRAL, and GROUND wires (using conduit) from the inverter to the AC source. Leave several inches of extra wire at each end.
4. Make the connections to the inverter first. Wiring to the AC source is performed after all connections have been made in the inverter.
a) Connect the GROUND (green) wire to the inverter’s AC GROUND
terminal.
b) Connect the NEUTRAL (white) wire from the AC source to the inverter’s
NEUTRAL INPUT terminal.
c) Connect the HOT (black) wire from the AC source to the inverter’s AC
HOT INPUT terminal.
5. Torque all connections to 16 in-lbs (1.8 nm).
Torque the terminal connections to 16 in-lbs (1.8 nm)
GROUND
Figure 2-16
2–24 975-0012-01-02 Rev A
HOT IN
AC Terminals for AC Input to the Inverter
NEUTRAL IN
AC Output Wiring to the AC Distribution Panel (Sub-panel)
AC Wiring
Important:
the system. If the generator is the main source of power, (i.e., no utility grid power) then the neutral and ground connections are bonded at the generator. If the generator is acting as a backup for the utility grid, then the bond should be at the main utility service entrance box. In this case, ensure that no bond exists at the generator output.
The ground and neutral must be bonded at one place, and only one place, in
To connect the AC output wiring to the sub-panel:
1. Connect the GROUND wire to the inverter’s AC GROUND chassis terminal. Connect the other end of this wire to the GROUND bus in the sub-panel.
2. Connect the NEUTRAL (white) wire to the inverter’s NEUTRAL OUTPUT terminal. Connect the other end of this wire to the NEUTRAL bus in the sub-panel.
3. Connect the HOT (black) wire to the inverter’s terminal labeled AC HOT OUTPUT. Connect the other end of this wire to the sub-panel’s input circuit breaker.
4. Torque all inverter terminal block connections to 16 in-lbs (1.8 nm).
5. Refer to the sub-panel manufacturer’s specifications for wire torque requirements to sub-panel terminals.
Torque the terminal connections to 16 in-lbs (1.8 nm)
GROUND HOT
Figure 2-17
Important:
and may be used in any combination.
975-0012-01-02 Rev A 2–25
AC Terminals for AC output to the Sub-panel
The two neutral connections (input and output) are common to one another
NEUTRAL
OUT
OUT
Installation
The following diagrams illustrate the AC wiring for the following basic 120/240 Vac scenarios. Consult your system design for other possible configurations.
On-Grid Application (See Figure 2-18)
On-Grid using with a generator Backup (See Figure 2-19)
On-Grid Dual-Inverter Application (See Figure 2-20)
Off Grid Application using a 120 Vac Generator (See Figure 2-21)
Off-Grid Application using a 240 Vac Generator (See Figure 2-22)
Off-Grid Dual-Inverter Application (see Figure 2-23)
AC Input Wiring - On-Grid Applications
Follow the example below to complete the wiring for an on-grid application.
Figure 2-18
2–26 975-0012-01-02 Rev A
AC Wiring- On-Grid Application
AC Input Wiring using a Generator in an On-Grid Application
If a generator is used as a backup for the utility, then a manual transfer switch must be added to provide a means to switch the generator power to the inverter’s inputs. The generator can be used during extended outages to recharge the batteries and provide pass through power for the loads. Start and stop the generator manually using the generator’s pull-cord, ON/OFF switch, etc.
AC Wiring
Figure 2-19
975-0012-01-02 Rev A 2–27
AC Wiring using a Generator - On-Grid Application
Installation
AC Input Wiring - Off-Grid Applications using a 120 Vac Generator
Follow the example below to complete the wiring for an off-grid application.
Figure 2-20
2–28 975-0012-01-02 Rev A
AC Wiring using a 120 Vac Generator - Off-Grid Application
AC Input Wiring - Off-Grid Applications using a 240 Vac Generator for 120 Vac Loads
Follow the example below to complete the wiring for an off-grid application.
AC Wiring
Figure 2-21
975-0012-01-02 Rev A 2–29
AC Wiring using a 240 Vac Generator with 120 Vac Loads only- Off-Grid Application
Installation
Series Stacking (120 Vac/60 Hz Models only)
This COM port allows two DR Inverters (120 Vac/60 Hz models only) to be used in the same system in a “SERIES” configuration to operate 240 Vac loads. Series stacking can also be used to connect to 240 Vac only power systems providing both 120 and 240 Vac outputs. A series stacking interface cable (DRI) is required to connect the series stacking port of the inverters.
In this mode, one of the inverters will function as the “primary” and the other inverter becomes the “secondary.” The first unit switched ON becomes the primary and ensures the secondary’s output is 180 degrees out of phase for 240 Vac operation. Both units can charge the batteries or provide battery backup power during a utility outage.
The following illustrations provide a general overview of AC configurations using stacked inverters. Detailed wiring and operating instructions are provided with the DRI interface kit available from Xantrex Technology Inc.
The following diagrams illustrate the AC Wiring for a basic On-Grid and Off-Grid application.
2–30 975-0012-01-02 Rev A
AC Wiring
Figure 2-22
975-0012-01-02 Rev A 2–31
AC Wiring for dual-inverters - On-Grid Application (120 Vac models only)
Installation
Figure 2-23
2–32 975-0012-01-02 Rev A
Wiring for dual-inverters - On-Grid Application (120 Vac models only)
3
Operation
Chapter 3, “Operation” contains information about how to operate the DR Inverter/Charger.
Operation
Front Panel Controls and Indicators
All operating controls, indicators and sense connectors are located on the front panel of the unit. The controls are easily accessible, and the LEDs provide inverter/charger status at a glance.
POWER ON/OFF
COM Port
Figure 3-1
Front Panel Controls and Indicators
POWER ON/OFF Switch
The POWER ON/OFF control is a momentary contact switch that turns the inverter/charger ON or OFF by pressing it once. When the inverter is first connected to the batteries, it will run through a self test consisting of flashing the LEDs in sequence, operating the cooling fan momentarily and switching the transfer relay three times. Once the self test has successfully completed, the POWER ON/OFF switch is activated. Pressing the switch once turns the inverter ON. Another press turns the inverter OFF.
LED Status Indicators
Inverter Mode Controls (Search Watts)
Inverter Mode Indicator
Battery Charge Control
Battery Type Selector
Battery Sense Port
3–2 975-0012-01-02 Rev A
Ports
BATTERY SENSE Port
Front Panel Controls and Indicators
There are two ports on the inverter/charger. Both ports are RJ11 type telephone style connectors. One is used for connecting a remote control to the inverter. The other is used for regulating the charger voltage based on the temperature of the battery bank.
The BATTERY SENSE Port is used for connecting a battery temperature sensor (BTS) to control the charging rate based on battery temperature. The sensor should be taped onto the side of one of the batteries. The information received in this port adjusts the charger’s output higher in cold temperatures, assuring the batteries receive a full charge, and lowers it during warm temperatures, reducing battery gassing and providing overcharge protection.
Important:
charger.
Refer to the Installation section for the BTS location on the battery.
COM Port
COM PORT (J1) is a dual function RJ11 (6-pin) connector. Its primary function is to provide serial communications to an optional Xantrex™ remote control unit (RC4 or RC8). The port also acts as a stacking interface control when two DR Inverters are used in a series configuration. When two inverters are stacked, a remote control cannot be used with either unit.
Remote Controls (RC8/RC4)
DR Inverter are designed to operate with either an RC8 or RC4 remote control units. Both remotes incorporate a membrane switch with a single red LED display combination to start and stop the inverter, as well as provide overall system operating status.
Solid - With AC line power present, the unit is charging the batteries while directing AC to the load. With no AC line power present, the inverter is running on the batteries and supplying AC to the load.
Blinking Slow (1 to 3 flashes @ 1 second intervals) - The inverter is in search mode (no load connected).
Blinking Fast (3 to 5 flashes @ 1 second intervals) - The inverter is charging the batteries.
Flickering (3 to 5 flashes @ 1 second intervals) - The inverter has detected an over-current error. The LED (and inverter) will turn OFF whenever an over­current condition exceeds eight seconds.
The Battery Sense only adjusts charging voltage. It does not disable the
975-0012-01-02 Rev A 3–3
Operation
Stacking Interface
Controls
Erratic Blinking (0 to 3 and 2 to 5 flashes @ 2 second intervals) - The inverter has detected an error condition caused by overheating, low battery voltage, or high battery voltage.
OFF - The inverter is OFF.
The remote control must be connected prior to switching the inverter ON; otherwise, the micro-controller will not recognize (or respond to) the remote. If the remote is not recognized, switch the inverter OFF and then ON using the inverter’s front panel POWER ON/OFF switch.
Whenever two DR Series inverters are used in a series (stacked) configuration, one unit (primary) controls the other unit (secondary). Communication between the two inverters is done via the COM port (J1). The first unit switched ON, using its front panel POWER ON/OFF switch, becomes the controlling (primary) inverter.
There are several controls on the inverter’s front panel that provide adjustments for the battery charger, and AC output energy saving mode.
Battery Type Selector
The Battery Type Selector is a 10 position rotary switch used to set the inverter’s charger for the proper Float and Bulk voltage levels. These levels are selected depending on the type of batteries used.
There are also 2 positions (0 and 1) which allow the batteries to be equalized. Equalizing batteries should only be done on liquid lead acid batteries and never on gel batteries. Refer to the table below for the charge voltages in the various switch positions. Consult the battery manufacturer for optimum battery voltage charging settings.
Battery Type Selector Enlargement
(pointing to Setting 7)
Figure 3-2
3–4 975-0012-01-02 Rev A
Battery Type Selector Adjustment
Front Panel Controls and Indicators
Table 3-1
Switch Position
Battery Type Selector Switch Settings
Description
0 Equalize 1 -
equalizes at a rate equal to the battery bank capacity (in amp­hours) divided by
40.
1 Equalize 2 -
charges at a rate set by the BATTERY CHARGER RATE control.
2 Deep Cell Lead
Acid 2
12-volt Models 24-volt Models Charge Function
Bulk/ Float Voltage
Equalize*
Voltage
Float Voltage
13.2 *15.0 26.4 *30.0 Battery Capacity
13.2 *15.5 26.4 *31.0 Battery Charger
Bulk/ Equalize* Voltage
Equalize Charge Rate Equalize Time
6 hrs. minimum
Setting (C/40)
12 hrs. maximum
6 hrs. minimum
Rate Setting
12 hrs. maximum
(manual)
13.3 15.0 26.6 30.0 Provides an additional Float and Bulk
settings for deep cycle, lead acid batteries. Refer to the battery manufacturer’s recommendation for Float and Bulk settings.
3 Not Specified 13.6 14.3 27.2 28.6 Provides an additional setting of Bulk and
Float voltages.
4 Gel Cel 2 13.7 14.4 27.4 28.8 Recommended for gel cell batteries that
specify high float voltages. Check with the battery’s manufacturer.
5 Gel Cell 1 13.5 14.1 27.0 28.2 Typical gel cell setting.
6 PcCa-lead
Calcium
7 Deep Cycle
Lead Acid 1
13.2 14.3 26.4 28.6 Use this setting for sealed type car
batteries.
13.4 14.6 26.6 29.2 Factory setting for typical deep cycle
lead acid batteries.
(Default Setting)
8 NiCad 1 14.0 16.0 28.0 32.0 Use for NiCad battery systems.
9 NiCad 2 14.5 16.0 29.0 32.0 Recommended for use with nickel iron
batteries.
See Important notes that follow.
975-0012-01-02 Rev A 3–5
Operation
Important:
1. Switch positions “0” and “1” are for monthly battery maintenance only. Return the switch to the appropriate position for the system’s batteries when Equalize charging has completed. NEVER EQUALIZE GEL BATTERIES! Use together with BATTERY CHARGER RATE potentiometer (position1) or BATTERY CAPACITY potentiometer (position 0).
2. Equalize voltages are displayed in the table with an asterisk (*) - Switch positions “0” and “1” only.
3. Switch position “7” is the default values as shipped from the factory.
4. Always refer to the battery manufacturer’s specifications for equalization.
SEARCH MODE WATTS Potentiometer
The Search Mode Watts potentiometer adjusts the current threshold required to bring the inverter out of search mode into full wave operation. With search mode enabled, the inverter pulses the AC output looking for an applied load. With no load detected, the inverter goes into the search mode to minimize energy consumption. When a load is applied, the load current is sensed, bringing the inverter into full power operation. Disabling the threshold (setting the potentiometer fully CCW) causes the inverter to remain ON (in full power operation) regardless of an applied load.
To set the Search Mode Watts:
1. Remove the AC input source from the inverter. The inverter switches to battery operation. Ensure all inverter supported appliances are switched OFF.
2. Turn the potentiometer completely CW (to MAX).
3. Switch on the load which will trigger the inverter to full power. This could be a lamp located in a convenient location if the power goes out. The light may flicker as the inverter searches the line for a load. The green INVERTER MODE LED blinks 2-3 times a second, indicating the inverter is in the SEARCH MODE.
4. Slowly turn the potentiometer CCW (toward MIN) when the proper setting is found, the lamp and INVERTER MODE LED will light steady.
5. Turn the lamp OFF for a moment. The inverter should switch back to the SEARCH MODE. Turn the lamp ON. Ensure the inverter comes out of the Search Mode. Adjust the potentiometer up or down as necessary.
Important:
mode (from batteries) to prevent unnecessary battery discharge when electrical power is not required. If the inverter is supporting loads that must constantly be powered, turn the search mode OFF by setting the potentiometer fully CCW to the DEFEAT position.
3–6 975-0012-01-02 Rev A
The Search Mode only activates when the unit is operating in the inverter
Front Panel Controls and Indicators
Important:
These include: TVs with instant-ON circuits, microwaves with digital displays, VCRs, etc. It is best to operate these devices from another circuit or install a switch to turn these OFF completely or don’t use the Search Mode.
Important:
120 Vac loads connected to the “master” inverter will bring the unit out of the search mode. See “AC Transfer Voltage” on page 3–10.
Some loads constantly draw power even though they are switched OFF.
When the SEARCH MODE is used with series stacked inverters, only
Lower wattage device
turns ON inverter
Search Mode
Potentiometer
Figure 3-3
Battery Type Selector Adjustment
Battery Charger Rate
The Battery Charger Rate potentiometer sets the maximum charge current supplied to the battery bank and is also used to regulate constant current in the Bulk Charge Mode. The level should be adjusted to provide a charge rate less than or equal to the amp-hour capacity of the battery bank divided by a factor of five.
Example:
1. Inverter DR1512 has a maximum charge rate of 70 amps.
2. Inverter DR1512 has maximum charge rate of 70 amps.
Higher wattage device DEFEAT Switches Search Mode OFF
turns ON inverter
a) Battery bank amp-hour capacity = 500 amp-hours using gel cell batteries. b) Divide the amp-hour capacity by 5 (500/5 = 100). c) Set the potentiometer to MAX (70 amps) as it is less than 100.
a) Battery bank amp/hour capacity is 250 amp-hours using gel cell batteries. b) Divide the amp-hour capacity by 5 (250/5 = 50). c) Set the potentiometer to approximately 71% (50 amps).
975-0012-01-02 Rev A 3–7
Operation
Use Table 3-2 to find the approximate setting of the Battery Charge Rate potentiometer. The settings do not need to be exact, but should be as close as possible to the actual value required.
Important:
small blade screwdriver and rotate the control completely CCW to find the start position. Rotate the potentiometer CW to the desired position (i.e., halfway between the stops for a 50% setting).
Table 3-2
Model
DR1512 DR2424 DR3624
DR2412 0 amps 30 amps 60 amps 90 amps 120 amps
DR1524 0 amps 8.75 amps 17.5 amps 26.25 amps 35 amps
The potentiometer does not have an arrow to indicate its position. Use a
Approximate Charge rate Setting/Amperage
Percent of Potentiometer Rotation (between stops)
100%
0% Min. 25% 50% 75%
0 amps 17.5 amps 35 amps 52.5 amps 70 amps
25%
(17.5 amps
50%
(35 amps
Max
75%
(50 amps)
0%
(0 amps
Figure 3-4
Battery Charger Rate Potentiometer (DR1512 values used)
Example 2
100%
(70 amps)
Example 1
Over Discharge Protection/AC Transfer Voltage
The Over Discharge Protection/AC Transfer Voltage potentiometer performs two related functions. When set between the 2 and 5 o’clock position (right), both ODP and the AC Transfer Voltage function simultaneously (see table on next page). When the potentiometer is set between the 9 and 1 o’clock position (left), only the AC Transfer Voltage is functional (ODP is disabled).
Important:
refer the AC transfer function.
3–8 975-0012-01-02 Rev A
The ODP is not scaled. It is either on or off. The min/max settings only
Over Discharge Protection (ODP)
When enabled, ODP shuts down the inverter at a specified voltage (low battery cutoff) to protect the batteries from over discharge damage. The inverter circuitry calculates the lowest (safe) DC voltage (leaving approximately 20% battery capacity) based on the position the Battery Type Selector switch and the amount of current drawn by the load. Under no-load conditions this level is typically between 11.8 and 12.0 Vdc (for a 12-volt battery bank).
Front Panel Controls and Indicators
Figure 3-5
Important:
The range of set points between 2 and 5 o’clock also determine the low AC Transfer Voltage. This must be considered when adjusting this potentiometer with ODP enabled (see Table 3-3).
Important:
When ODP is disabled (set points between 9 and 1 o’clock), the inverter is programmed to shut OFF when the batteries reach approximately 8.5 Vdc (1.4166 V/cell) for 12-Vdc systems (17 Vdc for 24-volt systems).
ODP Disabled
Range
ODP Enabled/Disabled Positions
2
1.95
1.9
1.85
1.8
1.75
1.7
Cell Voltage
1.65
1.6
1.55
1.5 1
0.1
Discharge Rate/Battery Capacity
0.01
ODP Enabled
Range
12 Vdc
12.0
11.4
10.8
10.2
9.6
9.0
0.001
24 Vdc
24.0
22.8
21.6
20.4
19.2
18.0
Figure 3-6
Automatically Calculated Discharge Cutoff Voltage per Cell
975-0012-01-02 Rev A 3–9
Operation
AC Transfer Voltage
During normal operation, the inverter supplies AC power to the applied loads through the pass-through circuit and simultaneously charges the system batteries. Whenever the external AC source drops below the AC Transfer Voltage (set by the potentiometer), the inverter switches to battery power in order to maintain the connected load.
Examples (120 Vac inverter system):
1. The AC Transfer Voltage potentiometer is set to 9:00 o’clock with ODP disabled. Whenever the incoming AC voltage drops to 40 volts or below, the inverter will switch to battery power.
2. The AC Transfer Voltage potentiometer is set to 2:00 o’clock with ODP enabled. Whenever the incoming AC voltage drops to 105 volts or below, the inverter will switch to battery power.
Important:
either ON or OFF, depending upon the position of the potentiometer.
Important:
OFF and ON as shown in the Table 3-3 below.
Important:
Transfer Voltage potentiometer near the 2:00 o’clock position (with the ODP enabled); or, near the 1:00 o’clock position (with the ODP disabled). If a high number of “nuisance transfers” caused by transients on the AC line occur, adjust the potentiometer from the maximum position toward the minimum position (i.e., 2 o’clock toward 5 o’clock with ODP enabled; or 1 o’clock toward 9 o’clock with ODP disabled).
Table 3-3
ODP Disabled ODP Enabled
9:00
Approximate Approximate
Approximate
ODP/AC Transfer Voltage
ODP Adjustment AC Transfer Voltage
5:00
Approximate
ODP does not affect the operation of the AC Transfer Voltage. ODP is
There are 6 settings available for the AC Transfer Voltage for both ODP
To achieve the fastest transfer time (typically less than 16 ms), set the AC
100 to 105 Vac (-J/-K Models) 120 Vac Models
30 Vac 45 Vac 90 Vac
77 Vac 85 Vac 170 Vac
81 Vac 90 Vac 180 Vac
220 to 230 Vac (-W /-E Models)
Approximate Approximate
Approximate Approximate
Approximate Approximate
3–10 975-0012-01-02 Rev A
86 Vac 95 Vac 190 Vac
90 Vac 100 Vac 200 Vac
95 Vac 105 Vac 210 Vac
AC Transfer Voltage (Adjustable)
with ODP Disabled
Minimum
(45 Vac for 120 Vac models)
Front Panel Controls and Indicators
Maximum
(105 Vac for 120 Vac models)
Maximum
(105 Vac for 120 Vac models)
AC Transfer Voltage (Adjustable)
with ODP Enabled
Minimum
(45 Vac for 120 Vac models)
Figure 3-7
ODP Enabled/Disabled Positions
Important:
voltage between 95 and 105 volts. Setting the AC Transfer Voltage potentiometer between these values will allow the incoming source voltage to drop to this level and still operate the connected appliances (load). If the appliances do not operate properly at the lower AC utility pass-through voltage, increasing the setting of the potentiometer (toward MAX) allows the inverter to transfer to battery power (providing full AC output) during these periods.
Important:
applications, the setting may need to be lowered if high powered loads cause the generator voltage to momentarily drop.
Typical Setting Range for Utility
Application (ODP OFF)
Most AC appliances will operate properly with an AC pass-through
When setting the AC Transfer Voltage potentiometer for generator
Typical Setting Range for Utility
Application (ODP ON)
Figure 3-8
Typical Setting for Most Utility Application
975-0012-01-02 Rev A 3–11
Operation
Battery Capacity
The Battery Capacity potentiometer is used to set the correct charge profile for the battery capacity (amp-hours) used with the inverter (see illustration below). The setting allows the inverter to calculate over-discharge protection values and also the end of the Bulk/Absorption charge mode, at which point the inverter switches to the Float mode of battery charging.
The potentiometer should be adjusted as close as possible to the actual capacity of the battery bank for optimum charging. If the system’s battery bank is larger than 1000 amp-hours, set the potentiometer for 1K.
Important:
Important:
50 amp-hours
(small battery bank)
Figure 3-9
Important:
between the minimum value of 50 Ah and 1 kAh. Please use the photo that matches your unit.
If using dual inverters configurations, set each charger for half the value.
Most battery manufacturers list the amp/hour rating on the battery label.
1000 amp-hours
(1000 amp-hour or larger
battery banks)
Battery Capacity Potentiometer (new)
The Battery Capacity (Amp/Hrs) potentiometer values have changed
250 amp-hours
125 amp-hours
50 amp-hours
(small battery bank)
(1000 amp-hour or larger battery banks)
Figure 3-10
3–12 975-0012-01-02 Rev A
Battery Capacity Potentiometer (old)
370 amp-hours
500 amp-hours
1000 amp-hours
LED Indicators
Front Panel Controls and Indicators
There are four LEDs on the inverter’s front panel, indicating inverter status, battery condition, over temperature/overload conditions and charger status. These LEDs blink or change color depending on the condition or function they are displaying.
OVER TEMP/OVERLOAD
INVERTER
MODE
Figure 3-11
LED Indicators
Inverter Mode LED - Green
The green Inverter Mode LED lights (solid) to indicate the inverter is running on batteries (full wave operation). When the inverter is in search mode (no load applied) the LED flashes 2 to 3 times per second. During AC line operation, with AC passing directly through to the connected load, the LED remains OFF.
Over Temp / Overload LED - Red / Green (error condition)
The Over Temp / Overload LED is a dual color, dual function indicator. When the inverter’s temperature is too high for safe operation, the LED lights (red) to indicate the Over Temp condition. When the temperature returns to a safe level, the LED turns OFF. If the condition persists, the inverter will shut down, cool and then restart.
Whenever the current draw exceeds a value programmed into the micro­controller, the LED lights (green) to indicate the Overload condition. The LED can remain ON for up to one hour (before inverter shutdown) if the condition is caused by a fault in the charger circuit. When the fault condition clears, the LED turns OFF. If the condition is caused by backfeed (connecting the AC line to the inverter’s output) the LED will remain ON for approximately 10 seconds before the inverter shuts down.
BATTERY HIGH/LOW
BATTERY CHARGER
Battery High/Battery Low LED - Red/Green (error condition)
The Battery Hi / Battery Low LED is a dual-color, dual-function indicator. Whenever battery voltage exceeds a safe value, the LED lights red to indicate the condition. This value is typically 15.5 volts DC for a 12 volt system (31 volts DC for a 24 volt system). If the condition persists, the inverter will shut down until the battery voltage returns to a safe level and then restart.
975-0012-01-02 Rev A 3–13
Operation
Important:
controllers must be set to a level below the inverter’s maximum input voltage or the inverter shuts OFF.
Whenever the battery voltage drops to its lowest (safe) level (as calculated by the ODP), the LED lights green to indicate the condition. If the condition persists, the inverter will shut down until the battery voltage returns to a safe level and then restart.
Important:
detected: LOW/HIGH BATTERY, OVER TEMPERATURE, or a quick duration SHORTED OUTPUT or OVER-CURRENT. The inverter shuts OFF and requires a MANUAL restart if the following conditions are detected: a prolonged overload condition (approximately 10 seconds) or the inverter’s output is connected directly to an AC power source (utility grid or generator).
Charger LED - Orange / Green
The Charger LED is a dual color (red/green), triple function indicator.
When the charger is in Bulk mode, the LED lights orange.
When the charger is in Absorption mode, the LED blinks orange.
When the charger is in Float mode, the LED lights green.
In renewable energy applications (solar, wind, hydro, etc.) the DC charge
The inverter automatically restarts when the following error conditions are
Important:
on the angle at which the LED is viewed. It should never be a solid red.
Important:
battery voltage falls below 7 volts, the inverter/charger will not operate. The batteries must first be recharged using a stand-alone charger to bring the voltage up to a level where the inverter/charger can operate.
Audible Indicator (internal)
A buzzer is located on the control board as an audible alert to fault conditions such as Battery High/Battery Low, or Overload. Steady buzzing indicates an impending inverter shut down. A pulsing chirp indicates the inverter is temporarily off-line due to a fault condition (either within the inverter or related to the system).
Orange is a flickering mix of red and green. It can look different depending
The battery charger control circuit operates from the battery voltage. If the
3–14 975-0012-01-02 Rev A
Circuit Breakers
Front Panel Controls and Indicators
The DR Inverter contains two circuit breakers located on the right-hand side of the chassis, directly above the AC input terminal block. The pass-through AC input circuit breaker protects the AC wiring and connected load. The charger AC input circuit breaker protects the charger circuit. The breakers are rated for the maximum charge rate and pass-through current allowed according to the rating of the internal relay.
Table 3-4
Models DR15XX DR24XX DR36XX
120 Vac 30 amps 30 amps 30 amps
210-230 Vac 15 amps 15 amps N/A
Table 3-5
Models DR15XX DR24XX DR36XX
120 Vac 20 amps 30 amps 30 amps
210-230 Vac 8 amps 15 amps N/A
AC Pass-through Circuit Breakers
Battery Charger Circuit Breakers
AC Pass-through Circuit Breaker
Charger AC Input Circuit Breaker
Figure 3-12
975-0012-01-02 Rev A 3–15
AC Pass-through and Charger AC Input Circuit Breakers
Operation
Start-up
Once the inverter is properly connected to the batteries, AC source, and loads (using a sub-panel) the inverter is ready for operation. Recheck the controls and ensure they are in the proper position. Recheck all wiring and ensure it is correct.
Starting the inverter:
1. Apply DC power to the inverter by switching on the DC disconnect circuit breaker. The inverter will go through a self-test and then shut OFF.
2. Press the ON/OFF button once. The inverter will sound an audible chirp.
3. Apply AC power to the inverter.
4. The inverter starts charging the batteries in the Bulk mode, indicated by the CHARGER LED illuminating a solid orange.
5. Using a true RMS AC voltmeter, check the output voltage of the inverter. This voltage can be checked at either the AC terminal block or in the sub-panel (between the HOT and NEUTRAL lines). The voltage should be 120 Vac (230 Vac for “E” models, 220 Vac for “W” models, or 105 Vac for “J” and “K” models). (Non-true RMS meters register from 90 to 110 Vac.)
6. Switch the AC disconnect circuit breaker to OFF. The inverter will go into the inverter mode (if a sufficient load is applied to the AC output while in the search mode). The green INVERTER MODE LED will light solid indicating the inverter is active. The voltage on the AC output of the inverter will remain the same as above (± 5% maximum).
Important:
flashing) and a sufficient load is not available to bring the inverter up to full voltage, turn the SEARCH MODE WATTS potentiometer fully CCW to defeat the search function.
If the inverter is in the SEARCH MODE (INVERTER MODE LED
7. Reapply the AC power by switching the AC disconnect to ON. Allow the batteries to fully recharge.
POWER ON/OFF Switch
INVERTER MODE LED
Figure 3-13
Important:
(utility or generator) is available to the inverter.
Startup Items
The unit will not use renewable energy for AC output as long as AC input
Charger LED
SEARCH MODE WATTS Potentiometer
3–16 975-0012-01-02 Rev A
Charger Mode
3-Stage Charging Process
The charging cycle uses a 3-stage charging process to maintain the batteries. Whenever nominal AC is present at the inverter’s input, it passes power through to the connected load and begins charging the batteries, indicated by the dual color BATTERY CHARGER LED.
Bulk Charge
Bulk charge is the first stage in the charging process and provides the batteries with a controlled, constant current. A solid orange BATTERY CHARGER LED indicates bulk charge. The bulk charge level is adjustable using the BATTERY CHARGER RATE potentiometer. Once the battery voltage rises to the bulk voltage threshold, the charger then switches to the absorption mode.
Absorption Charge
Absorption charge is the second stage of battery charging and provides the batteries a controlled, constant voltage for a set period of time. A blinking orange BATTERY CHARGER LED indicates absorption charge.
Charger Mode
During this stage the current supplied to the batteries slowly decreases. When the current equals the programmed return amps value (battery bank capacity/40) set with the BATTERY BANK CAPACITY potentiometer, the charger switches to the third stage–float.
Important:
decrease to the level to initiate the float stage. The inverter/charger incorporates a timer circuit which starts counting when AC voltage is applied. To ensure that the charger does not stay indefinitely in the absorption charge mode, the timer automatically switches to the float charge mode when 12 hours have elapsed.
If there are DC loads connected to the battery, the current may never
Float Charge
Float charge, the final stage of battery charging, maintains a charge to the batteries whenever AC is present on the inverter’s input. A solid green BATTERY CHARGER LED indicates float charging which reduces battery gassing, minimizes watering requirements (for flooded batteries) and ensures the batteries are in a constant state of readiness.
A new 3-stage charging cycle is initiated after an AC source is reapplied to the inverter’s AC input terminals such as after a utility outage.
Important:
charge”. Some batteries may require higher current. Consult the battery manufacturer to determine if the batteries being used can handle a float charge. The inverter will adjust its charge rate to meet the battery requirement.
The Float Charge is a very low-current charge, also called a “trickle-
975-0012-01-02 Rev A 3–17
Operation
Equalize Charging
Battery Charger LED
Solid Orange = Bulk Blinking Orange = Absorption Solid Green = Float
Figure 3-14
Charger Controls and Indicators
Battery Capacity
Equalize charging is a special mode of battery charging. During use, the battery’s cells can become unequal in the voltage and current they can deliver. This is due to a buildup of sulfate on the plates as well as stratified electrolyte. Sulfate prevents the cells from receiving or delivering full power. If the sulfate is left on the plates, it will harden, and permanently reduce the battery’s capacity. Stratification separates the heaver acid from the water, and the concentrated acid remains at the lower portion of the plates, eventually corroding them.
Equalize charging holds the battery at the Equalize voltage for a minimum of 6 hours. This stirs up the electrolyte, distributing the acid, and removing the sulfate from the plates. Equalizing the batteries every month or two (depending on usage) prolongs the life of the batteries and provides better battery performance.
CAUTION: Explosion Hazard
Only unsealed or vented batteries should be equalize charged. Since Hydrogen and oxygen gases are produced when equalized, provide adequate ventilation and remove all sources of ignition to prevent explosion. Remove DC loads while equalizing as they can be damaged by the higher battery voltage. Consult the battery manufacturer’s recommendation for equalize charging settings.
To Set the Equalize Charge:
1. Remove all DC loads connected to the batteries.
2. Remove all battery vent caps.
3. Check the battery water level, it should be just over the top of the plates (do not overfill). Use only distilled water for filling batteries.
3–18 975-0012-01-02 Rev A
Charger Mode
Important:
Recheck the water the level after equalize charging and refill if necessary.
4. Set the BATTERY TYPE SELECTOR switch to position “0” or “1”. To start the equalization charging process, cycle the AC power (i.e., disconnect and then reconnect the AC source). A solid orange BATTERY CHARGER LED indicates equalize charge.
a) Position “0” equalizes the batteries at the rate of the battery bank capacity
divided by 40 (C/40) at a voltage of 15 volts for 12-volt systems or 30 volts for 24-volt systems. This is set with the BATTERY CAPACITY potentiometer.
b) Position “1” equalizes the batteries at the rate set with the BATTERY
CHARGER RATE CONTROL at a voltage of 15.5 volts for 12-volt systems or 31 volts for 24-volt systems.
When the voltage condition is met and 6 hours have elapsed, the charger will switch to the float mode. If the condition is not met (i.e., the current draw is above the rate set with the BATTERY CAPACITY potentiometer (position “0”) or BATTERY CHARGER RATE potentiometer (position “1”)), the charger will continue until the condition is met, or for a maximum of 12 hours. At this point the charger switches to float at the equalize 1 or 2 voltage setting (see Figure 3-1, “Battery Type Selector Switch Settings” on page 3–5).
5. Reset the BATTERY TYPE SELECTOR potentiometer to the appropriate setting for the system’s batteries when the Equalize charge has completed.
Important:
Figure 3-15
975-0012-01-02 Rev A 3–19
Refer to “Battery Maintenance” on page B–13 for additional information.
Equalize 1
Equalize 2
Equalize Positions on Battery Type Selector Switch
Operation
See Table 3-1 Switch Position “1”.
Figure 3-16
Figure 3-17
Equalize 1 Battery Charger Rate Potentiometer (Position “1”)
See Table 3-1 Switch Position “0”.
Equalize 2 Battery Capacity Rate Potentiometer (Position “0”)
3–20 975-0012-01-02 Rev A
4
Troubleshooting
Chapter 4, “Troubleshooting” contains information about how to troubleshoot possible error conditions while using the DR Inverter/Charger.
Troubleshooting
Troubleshooting the DR Inverter
Table 4-1 provides a list of possible error conditions that may occur, their possible causes, and possible solutions to resolve the error condition.
Table 4-1
Error Condition Possible Cause Solution
No AC output voltage and no warning LEDs on ON.
AC output voltage is low and the inverter turns loads ON and OFF.
AC output is low. Loose or corroded battery
Charger is inoperative. AC voltage has dropped
Charger is supplying a lower charge rate.
Troubleshooting the DR Inverter
Battery voltage at the inverter terminals is too high or low.
Low Battery. Check the condition of the batteries
connections.
Loose AC output connections.
Wrong voltmeter is being used.
out-of-tolerance
Loose AC input connections.
Charger controls are improperly set.
Check the battery voltage, fuses or breakers, and cable connections.
and recharge if possible.
Replace the batteries.
Check and clean all DC connections.
Check all AC output connections.
Use a True RMS voltmeter.
Check the AC voltage for proper voltage and frequency (depending on model).
Check all AC output wiring connections
Refer to the section on adjusting the “Charger Rate”.
Low peak AC input voltage (169 Vac required for full charger output)
Loose or corroded battery connections.
Loose AC input connections.
Generator is unstable - charger is losing synchronization.
AC LEDs flicker while charging. Generator is unstable and charger is
losing synchronization.
4–2 975-0012-01-02 Rev A
Use larger generator (increasing AC
p
voltage/RPM’s may help).
Check and clean all DC connections.
Check all AC output wiring connections.
Turn BATTERY CHARGER RATE potentiometer down to less than halfway until problem is gone.
Turn BATTERY CHARGER RATE potentiometer down to less than halfway until problem is gone.
Problem Loads
Table 4-1
Error Condition Possible Cause Solution
CHARGER LED:
- indicates charging, but no charge is going to the batteries.
- is ON, but there is no output power.
Charger turns OFF while charging from a generator
Troubleshooting the DR Inverter
Circuit Breaker on the side of the inverter is open.
No AC voltage on inverter’s AC terminal block.
Good AC voltage on inverter’s AC terminal block.
High peak AC input voltages from the generator
Reset the AC CHARGER circuit breaker on the side of the unit.
Check “AC PASS-THRU” Circuit Breaker on the side of the inverter.
Check for open AC output breakers or uses and AC wiring connections.
Load the generator down with a heavy load.
Turn the generator output voltage down.
Problem Loads
The inverter can drive most loads, however, there are special conditions that can cause a load to behave differently than expected. The following describes some of the common problems encountered when using an inverter.
Ceiling Fans
Most large diameter, slow turning fans run correctly, but generate more noise than when connected to utility power. High speed fans tend to operate normally.
Cell Phones
Some cellular telephones experience interference in the form of a clicking sound.
Computers and Sensitive Electronics
Some computers and sophisticated electronics have power supplies that do not present a load until correct line voltage is available. When this occurs, each unit waits for the other to begin. This can usually be solved by plugging in an additional load (such as a lamp) to bring the inverter out of its search mode. Also, when using a computer, avoid starting large loads.
Consumer Electronics
AM radios tend to pick up inverter noise, especially on the lower half of their band. Inexpensive tape recorders are likely to experience noise as well. When using sensitive electronic devices, avoid starting large loads.
975-0012-01-02 Rev A 4–3
Troubleshooting
Clocks
Decreasing Loads
Dimmer Switches
The inverter’s crystal controlled oscillator keeps the frequency accurate to within a few seconds a day; however, external loads in the system may alter the inverter’s output waveform causing clocks to run at different speeds. There may be periods where clocks keep time and then mysteriously do not. This is because most clocks do not draw enough power to trigger the load sensing circuit. In order to operate, especially with no other loads present, the inverter’s load sensing circuit will have to be defeated. Refer to the Operation/Search Mode Watts.
If the amount of power a load draws decreases after it has been switched on (such as with a small motor) and its current draw becomes less than the load sensing threshold, it will be turned alternately ON and OFF by the inverter. This can usually be solved by plugging in an additional load (such as a lamp).
Most dimmer switches lose their ability to dim the lights when used with an inverter and operate only in the fully ON or OFF position. Newer, microprocessor controlled dimmers tend to work better in inverter applications.
Fluorescent Lights
Heavy Loads
Microwave Ovens
Some devices cannot be detected by the inverter’s load sensor and will not operate. Small fluorescent lights are the most common example. This can usually be solved by plugging in an additional load. Also, try turning the lamps AC plug over.
If the battery bank cannot deliver the necessary amperage to drive a heavy load, the inverter will shut OFF. The battery voltage will then slowly rise back above the low voltage threshold causing the inverter to resume operation. As soon as the heavy load draws the batteries down, the cycle will continue unless the load is reduced or an additional source of power is added.
Microwave ovens are sensitive to peak output voltages. The higher the voltage, the faster they cook. Since the inverter’s peak output voltage is dependent upon battery voltage and load size, the microwave’s cook time may need to be increased.
4–4 975-0012-01-02 Rev A
Printers
Most inkjet type printers work well in inverter applications. Laser printers, however, require high current for their fusing circuit and are not recommended for use with an inverter.
Rechargeable Devices
When first using a rechargeable device, monitor its temperature for 10 minutes to ensure it does not become abnormally hot. Excessive heat will indicate that it is incompatible with the inverter.
Undersized Loads
If the power consumed by a device is less than the inverter’s search mode circuitry threshold, it will not run. This can usually be solved by plugging in an additional load such as a 100 watt light bulb.
Problem Loads
CAUTION: Equipment Damage
Some products can be damaged when used with modified sine-wave power. If in doubt, check with the product’s manufacturer.
975-0012-01-02 Rev A 4–5
4–6
A
Specifications
Appendix A, “Specifications” contains information about the electrical specifications and environmental specifications of the DR Inverter/Charger.
Specifications
Specifications of the DR Inverter
Table A-1 provides the electrical specifications for the DR Inverter/Charger (120 Vac/60 Hz. models).
Table A-2 provides the electrical specifications for the DR Inverter/Charger (220 Vac/60 Hz. models).
Table A-3 provides the electrical specifications for the DR Inverter/Charger (230 Vac/50 Hz. models).
Table A-4 provides the environmental specifications for all models of the DR Inverter/Charger.
Table A-1
Model DR1512 DR2412 DR1524 DR2424 DR3624
AC Input Voltage 120 Vac 120 Vac 120 Vac 120 Vac 120 Vac
AC Input Low Transfer Voltage
AC Input Current
Continuous Power (@ 25°C)
Continuous Output (@25 °C)
Efficiency 94% max 94% max 94% max 95% max 95% max
AC Output Voltage (rms)
Frequency: (± 0.04% Crystal controlled)
Surge Capability:
Electrical Specifications for the DR Inverter/Chargera - 120 Vac/60 Hz Models
40-105 Vac 40-105 Vac 40-105 Vac 40-105 Vac 40-105 Vac
b
45 amps 55 amps 45 amps 55 amps 55 amps
1500 VA 2400 VA 1500 VA 2400 VA 3600 VA
12.5 amps AC 20 amps AC 12.5 amps AC 20 amps AC 30 amps AC
120 Vac 120 Vac 120 Vac 120 Vac 120 Vac
60 Hz 60 Hz 60 Hz 60 Hz 60 Hz
5 sec Rating 2400 watts 4200 watts 3500 watts 6200 watts 7500 watts
1 mSec Rating 38 amps AC 77 amps AC 412 amps AC 80 amps AC 100 amps AC
100 mSec Rating 27 amps AC 55 amps AC 29 amps AC 58 amps AC 72 Amps AC
DC Input Current:
Search Mode 0.045 amps 0.055 amps 0.030 amps 0.030 amps 0.030 amps
Full Voltage 0.700 amps 0.900 amps 0.350 amps 0.450 amps 0.500 amps
DC Current at Rated Power
Short Circuit Current
A–2 975-0012-01-02 Rev A
165 amps 280 amps 80 amps 140 amps 210 amps
400 amps 800 amps 280 amps 560 amps 720 amps
Specifications of the DR Inverter
Table A-1
Electrical Specifications for the DR Inverter/Chargera - 120 Vac/60 Hz Models
Model DR1512 DR2412 DR1524 DR2424 DR3624
DC Input Voltage
(nominal)
c
DC Input Voltage
12.6 Vdc 12.6 Vdc 25.2 Vdc 25.2 Vdc 25.2 Vdc
10.8 to 15.5 Vdc 10.8 to 15.5 Vdc 21.6 to 31.0 Vdc 21.6 to 31.0 Vdc 21.6 to 31.0 Vdc
Range
Auto Low Battery
11 V 11 V 22 V 22 V 22 V
Protection enabled
DC Charger Rate
0 to 70 amps 0 to 120 amps 0 to 35 amps 0 to 70 amps 0 to 70 amps
(Adjustable)
Common Specifications:
Voltage Regulation
± 5%
(maximum)
Voltage Regulation
±2. 5%
(Typical)
Waveform modified sine wave
Load Power Factor
0.5 to 1.0 (leading or lagging)
(allowed)
Adjustable Load
5 watts minimum to 100 watts maximum
Sensing Range
Series Operation Yes
Force Air Cooling Variable speed fan
Automatic Transfer
30 amps
Relay
Number of
10
Charging Profiles
Three-stage
Yes (float, absorption, bulk)
Charging
Temperature Comp
optional
Probe (BTS)
Remote Control
d
(RC8)
optional
a.Specifications subject to change without notice. b.This is the minimum AC current required to obtain full pass-through and maximum battery charging. c.Product may not meet voltage regulation specifications at other than "Input Nominal" at full-rated load. d.Also compatible with the RC4.
975-0012-01-02 Rev A A–3
Specifications
Table A-2
Electrical Specifications for the DR Inverter/Chargersa - 220 Vac/60 Hz Models
Model DR1512W DR2412W
AC Input Voltage 220 Vac 220 Vac
AC Input Low Transfer Voltage 80 to 210 Vac 80 to 210 Vac
AC Input Current
b
45 amps 55 amps
Continuous Power (@ 25°C) 1500 VA 2400 VA
Continuous Output (@25 °C) 6.8 amps AC 6.8 amps AC
Efficiency 94% max 94% max
AC Output Voltage (rms) 220 Vac 220 Vac
Frequency: (± 0.04% Crystal controlled) 60 Hz. 60 Hz.
Surge Capability:
1 mSec Rating 20 amps AC 20 amps AC
DC Input Current:
Search Mode 0.045 amps 0.055 amps
Full Voltage 0.700 amps 0.900 amps
DC Current at Rated Power 150 amps 80 amps
Short Circuit Current 400 amps 800 amps
DC Input Voltage (nominal)
c
12.6 Vdc 12.6 Vdc
DC Input Voltage Range 10.8 to 15.5 Vdc 10.8 to 15.5 Vdc
Auto Low Battery Protection enabled 11 V 11 V
Charger Rate (Adjustable) 0 to 70 amps 0 to 120 amps
Common Specifications:
Voltage Regulation (maximum) ± 5%
Voltage Regulation (Typical) ±2. 5%
Waveform modified sine wave
Load Power Factor (allowed) 0.5 to 1.0 (leading or lagging)
Adjustable Load Sensing Range 5 watts minimum to 100 watts maximum
Series Operation NO
Force Air Cooling Variable speed fan
Automatic Transfer Relay 20 amps
Number of Charging Profiles 10
Three-stage Charging Yes (float, absorption, bulk)
A–4 975-0012-01-02 Rev A
Specifications of the DR Inverter
Table A-2
Electrical Specifications for the DR Inverter/Chargersa - 220 Vac/60 Hz Models
Model DR1512W DR2412W
Temperature Comp Probe (BTS) optional
Remote Control (RC8)
d
optional
a.Specifications subject to change without notice. b.This is the minimum AC current required to obtain full pass-through and maximum battery charging. c.Product may not meet voltage regulation specifications at other than "Input Nominal" at full-rated load. d.Also compatible with the RC4.
Table A-3
Electrical Specifications for the DR Inverter/Chargera - 230 Vac/50 Hz Models
Model DR1512E DR1524E DR1548E DR2424E
AC Input Voltage 230 Vac 230 Vac 230 Vac 230 Vac
AC Input Low Transfer
80 to 210 Vac 80 to 210 Vac 80 to 210 Vac 80 to 210 Vac
Voltage
AC Input Current
Continuous Power
b
55 amps 55 amps 55 amps 55 amps
1500 VA 1500 VA 1500 VA 2400 VA
(@ 25°C)
Continuous Output
12.5 amps AC 20 amps AC 12.5 amps AC 20 amps AC
(@25 °C)
Efficiency 94% max 94% max 94% max 95% max
AC Output Voltage
230 Vac 230 Vac 230 Vac 230 Vac
(rms)
Surge Capability:
1 mSec Rating 20 amps AC 20 amps AC 20 amps AC 40 amps AC
DC Input Current:
Search Mode 0.045 amps 0.055 amps 0.030 amps 0.030 amps
Full Voltage 0.700 amps 0.900 amps 0.350 amps 0.450 amps
DC Current at Rated
165 amps 280 amps 80 amps 140 amps
Power
Short Circuit Current 400 amps 800 amps 280 amps 560 amps
DC Input Voltage
(nominal)
c
DC Input Voltage
12.6 Vdc 25.2 Vdc 50.4 Vdc 25.2 Vdc
10.9 to 15.5 Vdc 21.8 to 31 Vdc 43.6 to 62 Vdc 21.8 to 31 Vdc
Range
975-0012-01-02 Rev A A–5
Specifications
Table A-3
Model DR1512E DR1524E DR1548E DR2424E
Auto Low Battery Protection enabled
DC Charger Rate (Adjustable)
Common Specifications:
Voltage Regulation (maximum)
Voltage Regulation (Typical)
Waveform modified sine wave
Load Power Factor (allowed)
Adjustable Load Sensing Range
Series Operation NO
Force Air Cooling Variable speed fan
Electrical Specifications for the DR Inverter/Chargera - 230 Vac/50 Hz Models
11 V 11 V 22 V 22 V
0 to 70 amps 0 to 35 amps 0 to 17.5 amps 0 to 70 amps
± 5%
±2. 5%
0.5 to 1.0 (leading or lagging)
5 watts minimum to 100 watts maximum
Automatic Transfer Relay
Number of Charging Profiles
Three-stage Charging Yes (float, absorption, bulk)
Temperature Comp Probe (BTS)
Remote Control (RC8)
a.Specifications subject to change without notice. b.This is the minimum AC current required to obtain full pass-through and maximum battery charging. c.Product may not meet voltage regulation specifications at other than "Input Nominal" at full-rated load. d.Also compatible with the RC4.
d
20 amps
10
optional
optional
A–6 975-0012-01-02 Rev A
Specifications of the DR Inverter
Table A-4
Environmental Specifications for the DR Inverter/Charger
a
Model DR1512 DR2412 DR1524 DR2424 DR3624
Dimensions
b
8.5" w x 7.25" H x 21" D (21.6 cm W x 18.4 cm H x 54.6 cm D
Unit Weight 35 lbs (16 kg) 45 lbs (21 kg) 35 lbs (16 kg) 40 lbs (16 kg) 45 lbs (21 kg)
“E” Models 38 lbs (18 kg) N/A 39 lbs (18 kg) (45 lbs (21 kg) N/A
Ambient Temp Range (rated 0 to 25 °C):
Operating 0 °C to +50 °C
Storage -55 °C to +75 °C
Altitude:
Operating 15,000 feet
Non-operating 50,000 feet
Mounting Wall-mount (with 16" mounting centers)
Shelf Mount
a.Specifications subject to change without notice. b.Allows for hardware extensions such as mounting rails, DC terminals, and front panel controls.
975-0012-01-02 Rev A A–7
A–8
B
Battery Information
Appendix B, “Battery Information” supplies general information about batteries such as battery types, battery bank sizing, battery configurations, and battery care. For detailed information, see your battery manufacturer or your system designer.
Battery Information
Introduction
Batteries Batteries are available in different sizes, amp-hour ratings, voltage, liquid or gel,
vented or non-vented, chemistries, etc. They are also available for starting applications (such as an automobile starting battery) and deep discharge applications.
Recommendations Consider the following recommendations for battery use.
Use only the deep discharge types for inverter applications.
Use the same battery type for all batteries in the bank.
Use only batteries from the same lot and date in your battery bank. This information is usually printed on a label located on the battery.
Battery Types
There are two principal types of batteries: starting and deep-discharge (with several different types of chemistries). Batteries can be either sealed or non-sealed (vented).
Deep discharge The battery types recommended for use in an inverter system are: Flooded Lead
Acid (FLA), Sealed Gel Cells (GEL), Sealed Absorbed Glass Mat (AGM); and alkaline types Nickel-iron (NiFe) and Nickel-Cadmium (NiCad).
Starting Automotive (starting) batteries are designed to provide high starting current for
short periods of time and are not appropriate for inverter applications.
Deep-cycle Flooded Lead Acid (FLA)
Description A flooded lead acid battery is designed to be deep-discharged before being
recharged, making it suitable for inverter applications. Flooded batteries require periodic maintenance consisting mainly of adding distilled water to the cells.
Attributes
Types of FLA Batteries Attributes
Golf Cart Popular for smaller off-grid home
systems
Many medium sized inverter systems use “L16” batteries
Rugged, long lasting
Typically rated at 6 volts (220 to 350 amp hours)
Industrial (electric forklift) Popular in large inverter systems
Extremely rugged - lasts up to 10 years or more in an inverter system
Typically 2 volt cells (1,000 amp hours or more)
B–2 975-0012-01-02 Rev A
Battery Types
Sealed Batteries (Gel and AGM)
Description Gel Cell and absorbed glass mat (AGM) batteries are sealed and do not require the
addition of distilled water. Since these batteries are valve regulated, over-charging can cause irreversible damage.
Attributes Attributes of sealed batteries are:
Types of Sealed Batteries Attributes
Gel Cell Gelled electrolyte instead of
liquid
Long life (up to 1500 cycles, typical)
Low self-discharge
Absorbed Glass Mat Electrolyte is contained in
glass-fibre mats between battery plates
• Similar to gel cells in characteristics
Good low temperature performance
NiCad and NiFe Batteries
Disadvantages These types of batteries can be used but are not optimized for the DR Inverter for
the following reasons:
Alkaline batteries, such as NiCad and NiFe types, have a nominal cell voltage of 1.2 volts per cell.
Xantrex inverters and battery chargers are optimized for use with lead acid batteries having a nominal 2.0 volts per cell (that is, 12 cells for a 24-volt system and 24 cells for a 48-volt system).
The number of cells required in a battery bank for alkaline batteries must, therefore, be adjusted for a 24- and 48-volt system (i.e, 20 cells for a 24-volt system and 40 cells for a 48-volt system).
Alkaline batteries require a higher charge voltage to fully recharge, and drop to a lower voltage during discharge compared to a similarly sized lead-acid type battery.
Other options Another option for 24 volt (only) alkaline battery banks is to use only 19 cells
instead of 20. Fewer cells allow the battery charger to operate more closely to the settings used for lead-acid batteries. However, the battery voltage will drop to as low as 18 volts when discharging the batteries.
Consult the battery manufacturer or supplier regarding system requirements and battery charger settings for alkaline type batteries.
975-0012-01-02 Rev A B–3
Battery Information
Understanding Battery Capacity Ratings
Discharge rate Deep cycle batteries have their amp-hour rating expressed as “at the x-hour rate”.
The hour rating refers to the time it takes to discharge the batteries. A faster hour rate (6 hour rate) means more current is withdrawn from the batteries during their discharge period. There is an inevitable amount of heat associated with the flow of current through a battery and the higher amount of current the greater the amount of heat will be generated. The heat is energy which is no longer available to the battery to power loads. a relatively long discharge rate (72 hour rate) will result in a larger number of amp-hours being available for electrical loads.
Calculation This calculation shows how to determine the level of current drawn from a battery
at any given hour rate—battery capacity divided by the hour rate equals the current drawn from the battery. For example, a battery rated 220 Ah at a 6 hour rate would be discharged at 36 amps (220/6).
For most residential applications of the DR Inverter the 72 hour rate is appropriate because on average a household uses low amounts of current (lights, TV, radio for example) with occasional bursts or higher consumption appliances like toasters or washing machines. For those installations where high continuous electrical consumption rates are anticipated it is more appropriate to use the 20 hour rate.
CCA rating The CCA rating (cold cranking amps) shown on starting batteries expresses
battery capacity in terms of its ability to provide large amounts of current for intervals measured in minutes, not hours. This is why starting batteries are not appropriate for inverter systems.
Battery Bank Sizing
Running time and size
Depth of discharge In general, the battery bank should be designed so the batteries do not discharge
Days of autonomy For off-grid, stand-alone applications, design a battery bank that can power the
The battery bank’s size determines the length of time the inverter can supply AC output power. The larger the bank, the longer the inverter can run.
more than 60% of their capacity on a regular basis. Discharging up to 80% is acceptable on a limited basis, such as a prolonged utility outage. Totally discharging a battery can reduce its effective life or permanently damage it.
loads for three to five days without requiring recharging. This design calculation assumes a worst case scenario where there is no recharging taking place during these days of autonomy.
Days of autonomy may vary depending upon the availability of other charging sources, the critical nature of the load and other factors. If the system is to be powered by renewable energy sources such as solar, wind, and micro-hydro, determine the appropriate number of days of autonomy by allowing for cloudy or calm weather as well as other seasonal variations in available energy.
If an engine generator is part of the system design, the days of autonomy can be determined by simply deciding how often you are prepared to run the generator. Significant battery cost reductions can be achieved by shortening the days of autonomy and allowing a generator to run for a schedule time period daily.
B–4 975-0012-01-02 Rev A
Battery Bank Sizing
Back up power systems which use utility power for recharging should use the estimated number of days of maximum power outage for determining days of autonomy.
Understanding Amp-hour Requirements
Amp-hours To estimate the battery bank requirements, you must first calculate the amount of
power you will draw from the batteries during your period of autonomy. This power draw is then translated into amp hours (Ah)—the unit of measure to express deep-cycle battery capacity.
Amp hours are calculated multiplying the current drawn by the load by the length of time it will operate.
Watts to amps To calculate amps when the power consumption is expressed in watts, use the
following equation:
A = W/V
where W = watts and V = volts DC
For example:
A 100 watt light bulb will draw approximately 8.33 amps
8.33 = 100 /12
If the light runs for three hours it will consume (8.33 x 3) or 25 Ah of power.
Time and power The length of time a load is operated will affect the power draw. In some cases, an
appliance which draws a large wattage may not consume as many amp hours as a load drawing fewer watts but running for a longer period of time.
For Example:
A circular saw draws 1500 watts or 125 amps. It takes 5 seconds to complete a cross cut. Twelve such cuts would take a minute and you would consume 125 A x 0.016* hour = 2 Ah
*1/60 = 0.016
Observation The circular saw, while it draws more power, consumed fewer amp hours of electricity because it ran for a short period of time.
Calculating Amp Hours
Calculations To determine the amp hours you will consume, you need to list your anticipated
loads and the length of time you will operate each one. Determine the number of hours per day and the number of days during the week you will use the appliance. For example, you use the microwave every day, but a breadmaker only once a week. If you use an appliance for less than an hour, express the time as a decimal portion of an hour.
Amps to watts All electrical appliances have labels which state their energy consumption. Look
for an amps rating on motors and a watts rating on other appliances.
If the label plate has expressed power consumption in amps, multiply by volts for the watts required. (watts = volts x amps).
975-0012-01-02 Rev A B–5
Battery Information
Considerations When calculating battery bank size, consider the following:
Motors typically require 3 to 6 times their running current when starting. Check the manufacturer’s data sheets for their starting current requirements. If you will be starting large motors from the inverter, increase the battery bank size to allow for the higher start-up current.
Refrigerators and ice-makers typically run only about 1/3 of the time, therefore, the running wattage is 1/3 of the total wattage of the appliance. Divide the total wattage of the appliance by 3 when determining the battery requirements.
Amp Hour Example Worksheet
Complete the following steps to calculate the amp-hour requirements per day for your system. Use and Table B-2 as examples to complete your own.
To calculate amp-hour requirements:
1. Determine the loads the inverter will power and enter their wattage in the watts column.
2. Determine the number of hours (or decimal portion of hours) the appliance is used each day. Enter this figure in the Hours column.
3. Determine the number of days the appliance will be used during the week. Enter this figure in the Days column.
4. Multiply Hours x Days for each load identified to determine the watt/hours per week.
5. Add the total watt/hours per week for all loads then divide by 7 to obtain the average total watt/hours per day.
6. Divide the total average per day by the DC nominal voltage.
This figure represents the average amp-hours per day that you will use.
Table B-1
Load Watts Hours per Day
5 lights: 15 W CFL 75 W 5 7 2625
Breadmaker 1200 0.75 2 1800
Energy-efficient refrigerator
Laptop computer 50 6 5 1500
B–6 975-0012-01-02 Rev A
Determining Average Daily Load in Amp-hours (Example
Days per week used
200 x 0.3 24 10080
Total weekly watt-hours of AC load 16005 Wh
Divided by days per week 7
Average total watt-hours per day 2286
Divided by DC nominal voltage 24
Average amp-hours per day (Ah/d) 95
Weekly watt-hours
Battery Bank Sizing
Battery bank size worksheet
Calculation To calculate the battery bank size, use the average amp-hours per day that you
calculated using Table B-1, then make the other calculation shown in Table B-2 to calculate the battery bank size you need to support your loads.
Table B-2
Average amp hours per day 95
Divided by inverter efficiency (90%) for DR Inverter 0.9
Divided by battery efficiency (usually 0.75) 0.75
Adjusted hours per day 140
Divided by Depth of Discharge (usually 60%) 0.6
Multiplied by days of autonomy 5
Battery bank size required 1173 Ah
Determining Battery Bank Size
Worksheets Table B-1 and Table B-2 are examples only. Use the specifications noted on the
label of each AC appliance and fill in the values specific for the appliances used in this installation on the a work sheet.
Table B-3 provides a typical wattage for selected appliances. However, you should try to find the exact wattage on the appliance label.
Table B-3
Appliance Watts Appliance Watts
Fluorescent Type Light 10 Blender 400
Computer 200-300 Toaster 1000
Microwave (compact) 600-800 Hot Plate 1800
Microwave (full-size) 1500 Washer/Dryer 375-1000
Stereo or VCR 50 3/8" Drill 500
Color Television (19") 150 Hair Dryer or Iron 1000
Refrigerator (3 cu ft) 180 Vacuum Cleaner 1200
Refrigerator (12 cu ft) 480 Coffee Maker 1200
Typical Appliance Wattage
975-0012-01-02 Rev A B–7
Battery Information
Battery Configurations
The battery bank must be wired to match the inverter’s DC input voltage specifications (12 or 24 Vdc). In addition, the batteries can be wired to provide additional run time. The various wiring configurations are:
Series Wiring batteries in series increases the total bank output voltage. This voltage
MUST match the DC requirements of the inverter or inverter and/or battery damage may occur.
Parallel Wiring the batteries in parallel increases the total run time the batteries can
operate the AC loads. The more batteries connected in parallel the longer the loads can be powered from the inverter.
Series-Parallel Series-parallel configurations increase both the battery voltage (to match the
inverter’s DC requirements) and run-time for operating the AC loads. This voltage must match the DC requirements of the inverter.
Batteries with more than two or three series strings in parallel often exhibit poor performance characteristics and shortened life.
Wiring Batteries in Series
Effect Wiring the batteries in a series configuration increases the voltage of the battery
string. Six-volt batteries can be combined to form 12-volt, 24-volt, or 48-volt battery banks. In the same way, 12-volt batteries connected in series form 24-volt battery banks. The total current capacity of the bank does not increase and remains the same amp-hour rating as it does for a single battery.
Important The voltage must match the DC requirements of the inverter.
Each battery’s amp-hour
rating is 100 Ah.
+ - +
6 V 6 V
+ -
24 V INVERTER
(Total bat tery capac ity = 100 Ah)
-
SHUNT
DC Disconnect (either a circuit
breaker or a
fuse with a
disconnect)
Figure B-1
Each battery's amp-hour
rating is 100 Ah.
+ - + -
6 V 6 V
SHUNT
+ -
12 V INVERTER
(Total bat tery capacit y = 100 Ah)
+ - + -
6 V 6 V
DC Disconnect (either a circuit
breaker or a
fuse with a
disconnect)
6-volt Battery Wiring - “Series” Configuration
B–8 975-0012-01-02 Rev A
Battery Configurations
+ - + -
12 V 12 V
SHUNT
Each battery's
amp-hour rating
is 100 Ah.
DC Disconnect
(either a circuit
breaker or a
+ -
fuse with a
disconnect)
Figure B-2
12-volt Battery Wiring - “Series” Configuration
24 V INVERTER
(Total battery capacity = 100 Ah)
Wiring Batteries in Parallel
Effect Wiring the batteries in a parallel configuration increases the current of the battery
string. The voltage of the battery bank remains the same as an individual battery. “Parallel” configurations extend the run times of the AC loads by providing increased current for the inverter to draw from. In a parallel configuration, all the negative battery terminals are connected together and all the positive battery terminals are connected together.
Wiring example Figure B-3 is an example of how to wire batteries in a parallel configuration.
+ - + -
12 V 12 V
SHUNT
Each battery's
amp-hour rating
is 100 Ah.
DC Disconnect
(either a circuit
breaker or a
+ -
fuse with a
disconnect)
Figure B-3
Battery Wiring in Parallel
12 V INVERTER
(Total battery capacity = 200 Ah)
975-0012-01-02 Rev A B–9
Battery Information
Wiring Batteries in Series-Parallel
Effect Wiring the batteries in a series-parallel configuration increases the current and
voltage of the battery bank. “Series-parallel” wiring is more complicated and care should be taken when wiring these banks.
Steps It is done in three steps; wiring the batteries in series, wiring them in parallel, then
wiring the string to the inverter.
Series wiring To wire in series:
1. First wire the batteries in “series” (voltage adds) with the positive terminal of one battery connected to the negative terminal of the next battery to meet the inverter’s DC input requirements (24 volts shown in Figure B-4 and Figure B-5.)
2. Repeat this step for the next battery string.
Two identical strings of batteries are now wired in series.
+ +
6 V 6 V
+ +
6 V 6 V
Figure B-4
Battery Wiring 24-volt - Parallel Configuration - Step 1
+ +
6 V 6 V
+ +
6 V 6 V
Parallel wiring To wire the batteries in parallel:
1. Connect the positive terminal of the first battery string to the positive terminal of the second battery string.
2. Connect the negative terminal of the first battery string to the negative terminal of the second battery string.
Each b att er y's amp- hou r
rating is 100 Ah.
+
6 V 6 V
Para llel
Connection
+
Series String 1
Each battery's amp-hour
Series String 2
+ +
6 V 6 V
rating is 100 Ah.
Series String 1
Para llel
Connection
Figure B-5
+ +
6 V 6 V
Battery Wiring 24-volt - Parallel Configuration - Step 2
+ +
6 V 6 V
Series String 2
B–10 975-0012-01-02 Rev A
Loading...