VIKING PUMP, INC.• A Unit of IDEX Corporation•Cedar Falls, IA 50613 USA
1.0 SAFETY INFORMATION
INCORRECT INSTALLATION, OPERATION OR MAINTENANCE OF EQUIPMENT MAY CAUSE SEVERE
PERSONAL INJURY OR DEATH AND/OR EQUIPMENT DAMAGE AND MAY INVALIDATE THE WARRANTY.
This information must be read fully before beginning installation, operation or maintenance and must be
kept with the pump. All installation and maintenance must be undertaken by suitably trained or qualified
persons only.
Symbol
Legend :
Danger - Failure to follow the listed
precautionary measures identified by
this symbol may result in serious injury
!
or death.
WARNING
Warning - Safety instructions which
shall be considered for reasons of safe
operation of the pump or pump unit and/
or protection of the pump or pump unit
itself are marked by this symbol.
!
!
!
!
WARNING
!
!
WARNING
WARNING
WARNING
DO NOT OPERATE PUMP IF:
- The head is not installed correctly.
- Any guards are missing or incorrectly installed.
- The suction or discharge piping is not connected.
DO NOTplace ngers,etc. intothepumping chamber
or its connection ports or into any part of the gearbox if
there is ANY possibility of the pump shafts being rotated.
Severe injury will occur.
DO NOT exceed the pumps rated pressure, speed, and
temperature, or change the system/duty parameters
from those for which the pump was originally supplied,
the pump outside of its operation envelope can cause
mechanical contact, excessive heat and can represent a
serious risk to health and safety.
Installation and operation of the pump must always
comply with health and safety regulations.
A device must be incorporated into the pump, system,
or drive to prevent the pump exceeding its stated duty
pressure. It must be suitable for both directions of pump
rotation where applicable. Do not allow pump to operate
with a closed/blocked discharge unless a pressure
relief device is incorporated. If an integral relief valve is
incorporated into the pump, do not allow re-circulation
through the relief valve for extended periods (refer to
section 3.8).
The mounting of the pump or pump unit should be solid
and stable. Pump orientation must be considered in
relation to drainage/cavity ventilation requirements.
Once mounted, shaft drive elements must be checked for
correct alignment. Rotate pump shaft by at least one full
revolution to ensure smoothness of operation. Incorrect
alignment will produce excessive loading and will create
high temperatures and increased noise emissions. It
may also be necessary to earth the pump head to avoid
the build up of a potential charge difference that could
cause a spark.
The installation must allow safe routine maintenance and
inspection (to replenish lubricants, check for leakage,
monitor pressures, etc) and provide adequate ventilation
necessary to prevent overheating.
Fill all gearboxes with the recommended grades and
quantities of lubricant (refer to section 3.4 and 8.3).
cause the pump to overheat and mechanical damage
to occur.
Before operating the pump, be sure that it and all parts
of the system to which it is connected are clean and
free from debris and that all valves in the suction and
discharge pipelines are fully opened. Ensure that all
piping connecting to the pump is fully supported and
correctly aligned with its relevant connections. Misalignment and/or excess loads will cause severe pump
damage. This could result in unexpected mechanical
contact in the pump head and has the potential to be an
ignition source.
Be sure that pump rotation is correct for the desired
directionofow(refer to section 3.4).
WARNING
WARNING
!
!
!
!
!
!
WARNING
!
DO NOT install the pump into a system where it will run
dry (i.e. without a supply of pumped media) unless it is
running can cause excessive heat and seal failure.
Pressure gauges/sensors are recommended, next to
the pump suction and discharge connections to monitor
pressures.
Caution must be taken when lifting the pump. Suitable
lifting devices should be used as appropriate. Lifting eyes
installed on the pump must only be used to lift the pump,
not pump with drive and/or base plate. If pump is base
plate mounted, the base plate must be used for all lifting
purposes. If slings are used for lifting, they must be safely
and securely attached. For weights of bare shaft pumps,
refer to section 8.6.
DO NOT attempt any maintenance or disassembly of the
pump or pump unitwithoutrstensuringthat:
- The pump is fully isolated from the power source
(electric, hydraulic, pneumatic).
- The pumping chamber, pneumatic relief valve and
any shaft seal support system are depressurized and
purged.
- Any temperature control devices (jackets,
etc.) are fully isolated, that they are depressurized and
purged, and components are allowed to reach a safe
handling temperature.
DO NOT attempt to dismantle a pressure relief valve,
which has not had the spring pressure relieved, is still
connected to a pressurized gas/air supply or is mounted
on a pump that is operating. Serious personal injury or
death and/or pump damage may occur.
DO NOT loosen or undo the head, any connections to the
pump, shaft seal housings, temperature control devices,
or other components, until sure that such action will not
allow the unsafe escape of any pressurized media.
Pumps and/or drives can produce sound power levels
exceeding 85dB (A) under certain operating conditions.
When necessary, personal protection against noise must
be taken. Typical noise emission data can be found in
sections 8.7 and 8.8.
Avoid any contact with hot parts of pumps and/or drives
that may cause injury. Certain operating conditions,
temperature control devices (jackets, heat-tracing, etc.),
bad installation, or poor maintenance can all promote
high temperatures on pumps and/or drives.
When cleaning, either manually or by an in-line cleaning
method, the operator must ensure that a suitable
procedure is used in accordance with the system
requirements. During a in-line cleaning cycle, a pump
differential pressure of between 2 and 3 bar (30 and 45
psi) is recommended to ensure suitable velocities are
reached within the pump head. The exterior of the pump
should be cleaned periodically.
Surface temperature of pump is also dependent on the
temperature of pumped medium.
heat-tracing,
SECTION TSM 285ISSUE APAGE 2 OF 36
1.1 RISK ASSESSMENT RELATING
TO THE USE OF VIKING PUMP
CLASSIC+ ROTARY LOBE
PUMPS AND PUMP UNITS IN
POTENTIALLY EXPLOSIVE
ATMOSPHERES
NOTE
For a feature to be suitable for an application, the
feature must be t for its designated purpose and also
suitable for the environment where it is to be installed.
Source
of Hazards
Unvented
Cavities
Casing /
Rotors /
Head
Pump
External
Surfaces
Cover
O-Ring
Pump
Casing / Cover
Shaft Seals
Auxiliary
System for
Shaft
Sealing
Rotation
Direction
Test
Closed
Valve
Condition
Shaft
Mechanical
Shaft
Coupling
(Torque
Protection)
Mechanical
Shaft
Coupling
(Standard)
Potential
Hazards
Build up of explosive gas
Unintended mechanical
contact
Excess temperature.
Electrostatic charging
Pump liquid leakage.
Build up of explosive gas
Pump liquid leakage.
Build up of explosive gas
Excessive temperature.
Unintended mechanical
contact. Leakage.
up of explosive gas
Pump liquid leakage.
Build up of explosive gas
Excess Temperature
Excess Temperature.
Excess Pressure.
Mechanical Contact
Random induced current
Temperature from
friction. Sparks from
break up of shear pins.
Electrostatic charging
Break up of spider.
Unintended
mechanical contact.
Electrostatic charging
Build
Frequency
of Hazards
Very Rare
Rare
Rare
Very Rare
Very Rare
Rare
Rare
Very Rare
Rare
Very Rare
Rare
Rare
Recommended
Measures
Ensure that pump is totally
lled. Consider mounting
ports vertically.
See Chapter 1.0
Ensure that operating
pressures are not
exceeded. Ensure that
sufcient NPSH to prevent
cavitation. See Chapter
1.0 / 3.3.1 Service Plan
User must ensure
temperature limits. Do not
overll gearboxes with
lubricant. Provide a ground
contact for pump. See
Chapter 1.0 / Service plan
Check selection of
elastomers are suitable for
application. Ensure cover
retaining nuts are tight.
Service plan
Stainless Steel.
Corrosion Resistant
Selection of seal system
must be suitable for
application. See Chapter
5.0. Service plan. Seals
must never run dry
Selection of auxiliary seal
system must be suitable
for application. Seals must
never run dry
If ushed seals are
installed, ensure that
ush is applied to seal
assemblies. Only allow
pump to run for minimum
period - just a few seconds
Can cause excessive
pressure, heat and
mechanical contact.
See Chapter 1.0
Provide a ground contact
for pump. See Chapter 1.0
Coupling selection must
suit application.
See Chapter 1.0
Coupling selection must
suit application. Service
plan. See Chapter 1.0
2.0 INTRODUCTION
2.1 GENERAL
Classic+ rotary lobe pumps are manufactured by Johnson
Pump (UK) Ltd. a subsidiary of Viking Pump Inc., Cedar Falls,
USA, (a unit of the IDEX Corporation).
This manual includes all the necessary information for the
Classic+ and should be read prior to beginning installation,
operation, or maintenance.
Should you require any additional information regarding
the Classic+ contact Viking Pump or their local authorized
distributor, refer to section 2.2.
When asking for assistance please provide the pump model
and serial number. This information can be obtained from the
pump nameplate which is located on the side of the pump
gearbox cover, refer to section 2.6.
Should the nameplate be unreadable or missing, the serial
number is also stamped on either side of the casing refer to
section 2.6.
If the system or product characteristics are to be changed from
the original application for which the pump was selected, Viking
Pump or their authorized distributor should be consulted to
ensure the pump is suitable for the new application.
2.2 VIKING PUMP DISTRIBUTORS
Viking Pump distributes its products internationally via a network
of authorized distributors. Throughout this manual where
reference is made to Viking Pump, service and assistance will
also be provided by any Viking Pump authorized distributor for
Classic+.
2.3 RECEIPTS AND STORAGE
Upon receipt of the pump, immediately examine it for any signs
of visible damage. If any damage is noted, contact Viking
Pump or your Viking Pump distributor and clearly mark upon
the carriers’ paperwork that the goods have been received in a
damaged condition, with a brief description of damage.
If the pump is not required for immediate installation then it
should be stored in a clean, dry environment. It is recommended
that storage temperature should be between –10° and 40°C
(14°F and 105°F).
Further to the above, if the pump is not intended for installation
or use within 18 months or more then refer to Viking Pump,
or the Viking Pump authorized distributor for storage
recommendations.
2.4 CLEANING
The Classic+ pump series is suitable for both manual cleaning
and in-line cleaning, refer to section 3.3.2.
It is recommended that the exterior of the pump be cleaned
periodically with a non-aggressive, non-abrasive cleaning
solution.
SECTION TSM 285ISSUE APAGE 3 OF 36
2.5 PUMP MODEL DESIGNATION
The designations of pump models in the Classic+ range are
asfollows:
CP10S CP20S CP30S CP40S
CP50S
CP10M CP20L CP30L CP40L CP50L
CP10L
This information, together with the pump serial number, should
be provided when requesting additional information on the
pump or when ordering spare parts. The pump serial number
is stamped on the pump nameplate and the casing, (refer to
section 2.6, Figures 2 and 3).
For the maximum operating pressures, temperatures and
speeds refer to section 3.2, Figure 6.
CP 30 / 0069 / 12
2.6 PUMP MODEL AND SERIAL
NUMBER
Should you require any information regarding your Classic+
rotary lobe pump contact Viking Pump or your Viking Pump
distributor, providing the pump model and serial number as
Should this be damaged or missing, the pump serial number
is also stamped on opposite corners of the casing, (see
Figure 3).
Pump
Range
Model
Size
Displacement
(Ltrs/Rev)
Max Pressure
(Bar)
Figure 1
CP Designated Models Only
2.5.1 ATEX IDENTIFICATION PLATE
Unit is suitable
for environments
Temperature
Class
Group IICategory 2
containing dust
or gas
2.5.2 EQUIPMENT GROUPS
& CATEGORIES
Equipment-groups (Annex I of the EC-Directive 94/9/EC)
Group I
(mines, mine gas & dust)
Category MCategory 1Category 2Category 3
12
for equipment
providing a
very high level
of protection
when
endangered by
an explosive
atmosphere
for equipment
providing a
high level of
protection when
likely to
be endangered
by an explosive
atmosphere
(gas)
(Zone 0)
for equipment providing
a very high level of
protection when used
in areas where an
explosive atmosphere
is very likely to occur
(other explosive atmospheres gas/dust)
G
D
(dust)
(Zone 20)
Group II
G
(gas)
(Zone 1)
for equipment providing
a high level of
protection when used
in areas where an
explosive atmosphere
is likely to occur
D
(dust)
(Zone 21)
G
(gas)
(Zone 2)
for equipment providing
a normal level of
protection when used
in areas where an
explosive atmosphere
is less likely to occur
(dust)
(Zone 22)
VIKING P UMP, INC.
A Unit of IDE X Corporati on
CEDAR FAL LS, IOWA USA
Phone:( 319)266-17 41
Fax:(31 9)273-815 7
Figure 2
Nameplate
12345/A/67
Figure 3
Serial Number Position on Casing
D
SECTION TSM 285ISSUE APAGE 4 OF 36
2.7 STANDARD PUMP
ROTORS
FRONT COVER
ROTOR
RETAINER
ROTORCASE
BEARING
HOUSING
FRONT
BEARINGS
GEARBOX
COVER
BREATHER
/FILLER CAP
REAR
BEARINGS
DRIVE
SHAFT
DRIVEN
SHAFT
TIMING
GEARS
COMPONENT TERMS
Figure 4
Pump Component Terms
3.0 GENERAL
3.1 CLASSIC+ PUMPING PRINCIPAL
The pumping action of the rotary lobe pump principle is
generated by the contra rotation of two pumping elements
(rotors) within a chamber (casing) - see Figure 5. The rotors are
located on shafts, which in turn are mounted within an external
gearbox and supported by the bearings; the timing gears are
also located on the shafts. The timing gears transfer the energy
from the drive shaft to the driven shaft, synchronizing the rotors
such that they rotate without contact with each other.
As the rotors pass the suction port, see Figure 5a, the cavity
generated increases creating a pressure decrease, which
inducesthepumpedmediumtoowintothecasing.
The pumped medium is carried around the casing by the rotors;
see Figure 5b and 5c, to the discharge side of the pump, Figure
5d. Here the cavity decreases and the pumped medium is
discharged from the casing, Figure 5e.
For pump component terms, see Figure 4.
3.2 CLASSIC+ RANGE OPERATING
PARAMETERS
The maximum pressure and speed operating parameters are
given in Figure 6. In practice these may be limited due to the
nature of the product to be pumped and/or design of the system
in which the pump is to be installed. Consult Viking Pump or
your Viking Pump distributor for assistance.
The operating temperature limit of the pump is determined
by the rotor clearance. For the CP10, CP20, CP30 and CP40
series pumps there are three rotor clearance bands (class A,
B and C), and two (class B and D) for the CP50 series pumps.
WARNING
The pump should not be subjected to sudden temperature
changes to avoid the risk of damage from sudden expansion/
contraction of components. Care should be taken when
selecting pumps for handling liquids containing abrasive
particles as these may cause wear of pump head components.
For advice or assistance contact Viking Pump or your Viking
Pump distributor.
If the system or product characteristics are to
be changed from the original application for
which the pump was selected, Viking Pump or
their authorized distributor should be consulted
to ensure the pump is suitable for the new
application.
- Incorporation of a torque-limiting device in the
drive system.
It is recommended that all piping and associated
equipment from the tank to the discharge point
is thoroughly cleaned before installation of the
pump to avoid the possibility of debris entering
the pump and causing damage.
Pressure gauges should be installed adjacent to
the pump suction and discharge connections such
that system pressures can be monitored. These
gauges will provide a clear indication of changes
in operating conditions and where a relief valve
is incorporated in the system, will be necessary
for setting and checking the functioning of the
valve.
It is imperative that the suction condition at the
pump inlet meets the Net Positive Suction Head
required (NPSHr) by the pump. Failure to observe
this could cause cavitation, resulting in noisy
operation,reductioninowrateandmechanical
damage to the pump and associated equipment.
The Net Positive Suction Head available
(NPSHa) from the system must always exceed
the Net Positive Suction Head required (NPSHr)
by the pump.
3.3.1 SYSTEM DESIGN AND
INSTALLATION
When incorporating any pump into a system it is considered
good practice to minimize piping runs and the number of pipe
The following should be considered at the design stage of any
system.
Be sure ample room is provided around the pump
!
!
WARNING
Valves should be provided adjacent to the pump suction and
discharge connections to allow the pump to be isolated from
the system for routine inspection and maintenance.
!
SECTION TSM 285ISSUE APAGE 6 OF 36
toallowfor:
- Access to the pump and drive for routine
inspection and maintenance, i.e. to remove
pump head and rotors.
- Ventilation of the drive to prevent over
heating.
The exterior of the pump unit may exceed 68°C
(154°F); Appropriate measures must be taken to
warn or protect operators.
The pump must not be used to support piping.
All piping to and from the pump unit must be
independently supported. Failure to observe
this may distort the pump head components
or assembly and cause serious consequential
damage to the pump.
Rotary lobe pumps are of the positive displacement
type and therefore an overload protection device
mustbeprovided.Thiscantaketheformof:
- An in-line pressure relief system, i.e. external
to the pump.
Figure 7
NPSH
Observing the following general guidelines should ensure the
best possible suction condition is created.
- Suction piping is at least the same diameter
connections.
- The length of suction piping is kept to the
minimum.
- The minimum number of bends, tees and
restrictions are used.
- Calculations to determine system NPSHa are
the worst condition see below.
Should advice on pump or system NPSH characteristics be
required contact the factory or their authorized distributor.
When installing a pump complete with base plate, motor and
drive,thefollowingguidelinesmustbeobserved:
a) The preferred drive arrangement for any
is in-line direct coupled. If an alternative is required please
contact Viking Pump or your Viking Pump distributor.
b) Flexible couplings must always be
!
!
!
!
f) When using electric motor drives, ensure
supply is compatible with the drive and controls and that the
method of wiring is correct for the type of starting required
by the motor i.e. Direct On Line, or other similar method.
Ensure all components are correctly grounded.
incorporated and correctly aligned within
the limits recommended by the coupling
manufacturer. To check coupling alignment
rotate the shaft by at least one full revolution
and ensure that the shaft rotates smoothly.
Couplings of a non-flexible design must never
be used.
c) Couplings must always be enclosed in a
suitable guard to prevent contact with rotating
parts, which could result in personal injury.
Guards should be of suitable material, (see d)
and of sufciently rigid design to prevent
contact with rotating parts under normal
operating conditions.
d) Whenthepumpisinstalledinaammableor
explosive environment, or is used for handling
ammable or explosive materials, special
consideration must be given. Not only to the
safety aspects of the drive unit enclosure
but also to the materials used for both the
coupling and the guard to eliminate the risk of
explosion.
surface such that distortion and misalignment
are avoided. Once base plates are fastened
in position the drive alignment must be rechecked, (see b).
as the pump
absolute
pipework
carried out for
rotary lobe pump
that the electrical
When installing a pump complete with base plate, motor and
drive,thefollowingguidelinesmustbeobserved:
a) The preferred drive arrangement for any
is in-line direct coupled. If an alternative is required please
contact Viking Pump or your Viking Pump distributor.
b) Flexible couplings must always be
!
!
!
!
f) When using electric motor drives, ensure
supply is compatible with the drive and controls and that the
method of wiring is correct for the type of starting required
by the motor i.e. Direct On Line, or other similar method.
Ensure all components are correctly grounded.
incorporated and correctly aligned within
the limits recommended by the coupling
manufacturer. To check coupling alignment
rotate the shaft by at least one full revolution
and ensure that the shaft rotates smoothly.
Couplings of a non-flexible design must never
be used.
c) Couplings must always be enclosed in a
suitable guard to prevent contact with rotating
parts, which could result in personal injury.
Guards should be of suitable material, (see d)
and of sufciently rigid design to prevent
contact with rotating parts under normal
operating conditions.
d) Whenthepumpisinstalledinaammableor
explosive environment, or is used for handling
ammable or explosive materials, special
consideration must be given. Not only to the
safety aspects of the drive unit enclosure
but also to the materials used for both the
coupling and the guard to eliminate the risk of
explosion.
surface such that distortion and misalignment
are avoided. Once base plates are fastened
in position the drive alignment must be rechecked, (see b).
rotary lobe pump
that the electrical
3.3.2 Installations with
CIP SYSTEMS
The Classic+ pump range is designed to be effectively cleaned
by the CIP procedures recommended for in place cleaning of
process plant. It is recommended that a differential pressure
of 2 to 3 Bar (30 to 45 psi) be developed across the pump
- Before beginning operation, it is considered
to momentarily start/stop the pump to check the direction of
rotation and ensure that the pump is free of obstructions.
Once this has been carried out, begin operation keeping a
visual check on suction and discharge pressure gauges and
monitor the pump temperature and absorbed power where
possible.
- Check that all piping and associated equipment
are clean and free from debris and that all pipe
connections are secure and leak free.
of the oil sight glass - refer to section 8.3 for
pump oil capacities and grades.
- If an external relief valve is incorporated in the
system, check that it is set correctly. For start up
purposes, it is considered good practice to set
the relief valve lower than the system design
pressure. On completion of start up, the relief
valve should be reset to the required setting
for the application. The required setting should
never exceed the lower of either the pumps
maximum pressure rating or the system design
pressure. For setting integral relief valves refer
to sections 3.8.1 and 3.8.2.
- Be sure both suction and discharge valves are
fully opened and that pipe work is free from
all obstructions. The Classic+ is a positive
displacement type pump and should therefore
never be operated against a closed valve as this
would result in pressure overload, resulting in
damage to the pump and possibly the system.
- Make sure that the drive shaft rotation is correct
forthedirectionofowrequired.SeeFigure8.
- Be sure product is available in the suction
vessel before starting the pump. This is very
important for pumps tted with un-ushed
product seals, as these sealing arrangements
must never be allowed to run dry.
good practice
3.5 SHUTDOWN PROCEDURE
When shutting the pump down, stop pump, close
!
both the suction and discharge valves and ensure
thatthenecessarysafetyprecautionsaretaken:
- The prime mover power source has been
isolated.
- If installed, pneumatically operated integral
relief valve has been depressurized.
- Flushed product seal auxiliary services have
been isolated and depressurized.
- Pump head and piping have been drained and
purged.
- Before undertaking any work on the pump refer
to sections 4, 5, 6 and 7.
3.6 ROUTINE MAINTENANCE
WARNING
- Change the oil every 12 months or 3000
whichever is the sooner.
- For lubricant capacities and grades refer to
- Check oil levels regularly.
operating hours,
section 8.3.
3.7 HEATING AND COOLING
JACKETS
SeeFigure9andFigure10.
The Classic+ can be supplied with a jacketed head and casing
for circulation of a heating/cooling media.
The jacketed head and casing ports are strategically positioned
such that the required thermal effect acts on the pumping
chamber.
The pressure rating of the Classic+ series jacketed
!
Heating/cooling of the pump head is used to maintain, rather
than increase/decrease the temperature of the pumped media
and should be used as part of a complete system where suction
and discharge lines and vessels are also heated/cooled.
Where heating/cooling devices are employed, the heating/
cooling media should be circulated 15-20 minutes prior to pump
start-up and should be allowed to continue for a similar period
of time after the pump has been shut down. Where an in-line
cleaning cycle is employed as part of the process, then the
heating/cooling media should continue to be circulated during
the cleaning cycle.
head and casing is 3 Bar (50 psi) and this should
not be exceeded without consulting Viking Pump
or your local Viking Pump distributor.
The Classic+ models CP10, CP20, CP30 and CP40 can be
supplied with integral pressure relief valves. For the CP10,
CP20 and CP30 both spring and air loaded versions are
available. The function of the valves can be further enhanced
with the option of manual or airlift override, offering particular
of the cleaning media through the pump chamber, thereby
avoiding the need for manual cleaning or external bypass.
Where the pump is mounted onto a portable base plate,
complete with motor and drive to be used as a mobile set, an
integral pressure relief valve should be installed.
- Valve can be set to the required pressure relief setting.
Spring Loaded with Manual Lift - see Figure 12.
- Valve can be set to the required pressure relief setting.
Manual lift override can be used to open valve without
disturbing pressure relief setting.
Spring Loaded with Air Lift - see Figure 13.
- Valve can be set to the required pressure relief setting. Air
override, which operates on an air supply of up to 7 Bar (102
psi) depending on pressure relief setting, can be used to
open valve without disturbing pressure relief setting.
Air Loaded with Air Lift - see Figure 14.
- Valve, which operates on an air supply of up to 7 Bar
psi) regulated for required setting, can be set to the required
pressure relief setting. Airlift override, which operates on an
air supply of up to 7 Bar (102 psi) depending on pressure
relief setting, can be used to open valve without disturbing
pressure relief setting.
Air actuated relief valves can be operated remotely and interfaced with other elements of the system or process control.
either a pressurised system or one incorporating a vessel under
vacuum then the application of the valve should be referred to
Viking Pump.
Integral pressure relief valves are normally used
to protect the pump from the effects of increases
in system pressure caused, for example, by a
restricted or closed discharge line. In response
to a pressure increase, the valve opens and
internally circulates the pumped media within the
pump chamber. When the valve opens, because
the volume of liquid circulating is relatively small,
the temperature of the liquid in the pump chamber
may rise if the pump continues to operate for
an extended period. In severe cases, this may
result in temperatures in excess of the pumps
operating limits, or vaporisation of the liquid, both
of which should be avoided. For these reasons
when the valve is activated the cause of the
system pressure increase should be eliminated
as continuous operation of the pump with the
valve open is not recommended and may cause
severe damage to the pump.
lift
(102
The selection, setting and application of integral relief valves is
pumps operating speed and the required pressure relief setting
and mode of operation. For these reasons and to cover the
diverse range of products, the conditions under which they are
pumped and application demands, it is not practical to factoryset integral relief. Valves and the setting of the valves should
be carried out on site, under the proposed duty conditions for
which the pump and valve were selected.
For setting and operating Classic+ integral relief valves refer
to sections 3.8.1 and 3.8.2. Before beginning the relief valve
setting procedure the pump should be installed, refer to section
3.3.1, paragraph (vi), with a pressure gauge in the discharge
line adjacent to the pump discharge port.
3.8.1 SETTING AND OPERATING
SPRING LOADED VALVES
See Figures 11, 12 and 13.
- Remove cover (108). For integral relief valve with manual lift,
For Integral Relief Valve with Manual Lift - see Figure 12.
- To operate the manual lift, turn the hand wheel (111)
which will lift the valve head (102/128). To resume normal
relief valve operation, turn the hand wheel (111) counterclockwise.
For Integral Relief Valve with Air Lift - see Figure 13.
- To actuate the airlift, connect an air supply not exceeding
7 Bar (102 psi) to the cylinder (123), connection ‘B’, which
will lift the valve head (112). To resume normal relief valve
operation, exhaust the cylinder (123).
provided to relieve spring compression. For
integral relief valve with airlift, see Figure 13,
the air cylinder must be exhausted prior to
unscrewing the nut (107).
Note: Care should be taken not to exceed the
lower of either the pump’s maximum pressure
rating or the system design pressure.
clockwise,
3.8.2 SETTING AND OPERATING
AIR LOADED INTEGRAL
PRESSURE RELIEF VALVES
See Figure 14.
- Connect an air supply, not exceeding 7 Bar (102 psi), via
a regulating valve to the relief valve connection ‘A’ in the
cylinder (114). Do not turn on the air supply.
- Start the pump, refer to section 3.4.
- Using the regulating valve, gradually increase the air
pressure until required pressure relief setting is reached. The
air pressure must not exceed 7 Bar (102 psi).
- The relief valve is now set.
SECTION TSM 285ISSUE APAGE 10 OF 36
WARNING
!
!!
Note: Care should be taken not to exceed the
lower of either the pump’s maximum pressure
rating or the system design pressure.
- To use the air lift system, the regulated air
supply must be routed through a change-over
valve in order to transfer air from the relief valve
load air chamber, connection ‘A’, to the lift air
chamber, connection ‘B’, while depressurizing
the load chamber and vice versa. The changeover valve will actuate the air lift which will lift
when the air supply is diverted to connection
‘B’, and will close, restoring normal relief valve
operation, when the air supply is diverted back
to connection ‘A’.
DANGER !
Under no circumstances should any
attempt be made to dismantle a pressure
relief valve which has not had the spring
pressure relieved, is still connected to a
pressurized air supply, or is mounted on a
pump that is operating. Serious personal
injury or pump damage may occur.
Figure 12
Spring Loaded Integral Pressure Relief Valve
with Manual Lift
CP10, CP20 and CP30
Figure 11
Spring Loaded Integral Pressure Relief Valve
CP10, CP20, CP30, CP40
Figure 13
Spring Loaded Integral Pressure Relief Valve with Air Lift
CP10, CP20 and CP30
Figure 14
Air Loaded Integral Pressure Relief Valve with Air Lift
CP10, CP20, CP30 and CP40
SECTION TSM 285ISSUE APAGE 11 OF 36
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.