VEGA SEL643 User Manual

Operating Instruction
VEGASEL 643
12 43
Level and Pressure
max.
5
6
++ –
min.
5
3
++
VEGASEL 643
56 78
9 1011121314
out
in
Contents
Safety information ........................................................................................ 2
1 Product description
1.1 Function and configuration ................................................................. 3
1.2 Approvals ............................................................................................ 3
1.3 Types and versions ............................................................................. 4
1.4 Technical data and dimensions .......................................................... 4
2 Mounting and installation instructions .......................................... 7
3 Electrical connection
3.1 Wiring instruction ................................................................................ 8
3.2 Wiring plan .......................................................................................... 8
4 Set-up
4.1 Indicating and operating elements ................................................... 10
4.2 Set-up sequence .............................................................................. 11
4.3 Switch point adjustment.................................................................... 11
Contents
5 Diagnosis
5.1 Maintenance ..................................................................................... 13
5.2 Repair ............................................................................................... 13
5.3 Failure removal ................................................................................. 13

Safety information

The described module must only be inserted and oper­ated as described in this operating instruction. Please note that other action can cause damage for which VEGA does not take responsibility.
2 VEGASEL 643
Product description

1 Product description

1.1 Function and configuration

VEGASEL 643 auxiliary level switch is a build-in instru­ment with terminal socket, suitable for carrier rail mounting (DIN 46 277). Together with a sensor or a VEGAMET… signal conditioning instrument it is used for level detection.
Typical applications are two-point controls, e.g. pump controls (ON/OFF) and monitoring functions such as overfill protection and protection against dry running of pumps.
The auxiliary level switch is provided with two passive inputs, a current and a voltage input as well as addi­tionally with an active current input. Hence VEGASEL 643 can be connected for control either with a VEGAMET… or a sensor (4 … 20 mA).
12 43
max.
5
6
++ –
min.
5
3
++
on
VEGASEL 643
56 78
91011121314
Sensor (4 … 20 mA)
Fig. 1.2 VEGASEL 643 with sensor
Function
VEGASEL 643, controlled by a VEGAMET…
- The continuous current or voltage course of the VEGAMET… signal processing instrument is processed into a switching command.
12 43
100
%
0/4 … 20 mA
50
0 … 10 V
0
!
on
VEGAMET 602EX
56 78
91011121314
Fig. 1.1 VEGASEL 643 on a VEGAMET
VEGASEL 643 with a 4 … 20 mA sensor
- VEGASEL 643 auxiliary level switch powers via the active current input the sensors and processes its continuous 4 … 20 mA current signal into a switch­ing command.
12 43
max.
5
6
or
++ –
min.
5
3
++
on
VEGASEL 643
56 78
91011121314
p
p
In both cases a relay output is available for process­ing.
Configuration
With a VEGASEL 643 an available measuring system, consisting of sensor and VEGAMET signal condition­ing instrument can be extended by a level detection.
Or an own measuring system can be created with a 4 … 20 mA sensor.

1.2 Approvals

If measuring systems are created according to the following approvals, the respective legal documents and their regulations have to be observed. These documents are supplied with the respective measur­ing system.
WHG-approval, VbF-approval
VEGASEL 643 auxiliary level switch together with a measuring system (sensor and VEGAMET) as part of an overfill protection acc. to WHG (test certificate applied) or acc. to the regulations for combustible liquids (test certificate applied).
CE-conformity
see „1.4 Technical data“.
VEGASEL 643 3
Product description
off
on

1.3 Types and versions

VEGASEL 643
Two-point auxiliary level switch with selectable mode; mode A (overfill protection) or mode B (protection against dry running of pumps) adjustable switching hysteresis Inputs: - passive current input 0/4 … 20 mA
- active current input (connections of a sensor 4 … 20 mA)
- passive voltage input 0/2 … 10 V
Outputs: 1 relay (spdt) Approvals: as part of an overfill protection acc. to WHG and
VbF
Application: level detection, overfill protection,
protection against dry running of pumps
Max.
Min.
Fig. 1.2 Two-point auxiliary level switch VEGASEL 643

1.4 Technical data and dimensions

General data
Power supply
Operating voltage 20 … 250 V AC, 50/60 Hz
Power consumption max. 1,7 W (4,5 VA) Fuse T 1 A, 250 V
Measuring data inputs
Input 1 1 current input
Kind of input active two-wire input analog Range 4 … 20 mA Application connection of sensors (4 … 20 mA) Sensor supply voltage 16 … 24 V DC Switching threshold adjustable via coded key Min. hysteresis 1 % Current limitation appr. 25 mA, permanently shortcircuit proof Temperature error 0,05 %/10 K of range Switch point error 0,5 % of adjusted switch point Connection cable 2 wire (standard line) Resistor per conductor max. 35 Interlock diode for connection of a measuring instrument
20 … 72 V DC
max. load 15
Level
Time t
Input 2 1 additional current input Kind of input passive two-wire input analog Range 0/4 … 20 mA Inner resistor Ri = 50 Application direct connection to active current output of e.g.
VEGAMET 601, 602 Ex Switching threshold adjustable via coded key Min. hysteresis 1 % Temperature error 0,05 %/10 K of range Switch point error 0,5 % of adjusted switch point
4 VEGASEL 643
Product description
Input 3 1 voltage input Kind of input passive two-wire input analog Range 0/2 … 10 V DC Inner resistor Ri 100 k Application direct connection to active voltage output of
Switching threshold adjustable via coded key Min. hysteresis 1 % Temperature error 0,05 %/10 K of range Switch point error 0,5 % of adjusted switch point Connection cable 2-wire (standard line) Resistor per conductor max. 100
Electrical connection
Screw terminal max. 1,5 mm
Electrical protective measures
Protection
- instrument IP 30
- terminal socket IP 20 Protection II Overvoltage category II
Mechanical data
Series module instrument with terminal socket incl.
Mounting carrier rail mounting acc. to DIN 46 277, Bl. 3 Dimensions unassembled W = 36 mm, H = 118,5 mm, D = 134 mm Weight appr. 170 g
e.g. VEGAMET 601, 602 Ex
2
transparent cover, cover of the sensor terminals, coded pin, two connection bridges
Ambient conditions
Permissible ambient temperature -20°C … +60°C Storage and transport temperature -40°C … +70°C
Relay output
Number 1 output Contact 1 spdt (open 12 - 13, closed 12 - 14)
AgCdO and Au plated
Turn-on voltage min. 10 mV DC
max. 250 V AC, 60 V DC
Switching current min. 10 µA DC
max. 2 A AC, 1 A DC
Breaking capacity max. 125 VA, 54 W
Indicating elements
LED in front plate green on: operating voltage on
yellow on: relay energized
Functions
Mode overfill protection (A)
protection against dry running of pumps (B)
Adjustments of the inputs 0 … 20 mA or 4 … 20 mA
0 … 10 V or 2 … 10 V
VEGASEL 643 5
Product description
Operating elements
Front plate 2 coded key
Laterally on top 1 DIL-switch for adjustment
Electrical separating measures
Reliable separation acc. to VDE 0106, part 1 between power supply, meas. data inputs
- limit voltage 250 V
- isolation resistance 3 kV
CE-conformity
VEGASEL signal conditioning instruments meet the protective regulations of EMVG (89/336/EWG) and NSR (73/23/EWG). The conformity has been judged acc. to the following standards: EMVG Emission EN 50 081 - 1
Immission EN 50 082 - 2
NSR EN 61 010
Carrier rail 35 x 7,5 or 35 x 15 acc. to EN 50 022
Transparent cover
0 … 99 %
- mode A/B (overfill protection/protection against dry
running of pumps)
- adjustment possibility of the inputs 0 … 20 mA or 4 … 20 mA 0 … 10 V or 2 … 10 V
and level relais
12 4
3
118,5
54,5
134
VEGA
56 78
9 1011121314
36
6 VEGASEL 643
Mounting and installation instructions

2 Mounting and installation instructions

Mounting
Each series 600 signal conditioning instrument con­sists of a terminal socket for carrier rail mounting DIN 46 277 and a module instrument.
The supply voltage can be connected to terminals 9 and 10.
For neighbouring series 600 signal conditioning instruments it is possible to provide and loop the connection L1 and N directly via the supplied bridges.
The same is valid for the connection VEGAMET­voltage output 0 … 10 V to VEGASEL-voltage input 0 … 10 V /terminals 7 and 8).
Note, danger!
Never use the bridges with single instrument or at the end of an instrument row. They may come in touch with the operating voltage or cause a shortcircuit.
Coding
The terminal socket must be provided with pins and the signal conditioning instrument with appropriate gaps (mechanical coding) to avoid interchanging of the individual signal conditioning instruments.
An instrument coding ensures that interchanging among the signal conditioning instruments is avoided by differently positioned coded keys.
Instrument coding VEGASEL 643 (pin 4)
Direct connection for voltage input 0 … 10 V
Direct connection for supply voltage
12 4
A o B o C o 1 o 2 o 3 o
o o o
7 o 8 o 9 o
o o o
3
VEGA
0…10 V
N
L1
56 78
9 1011121314
VEGASEL 643 7

3 Electrical connection

Electrical connection

3.1 Wiring instruction

The following wiring plan and the extension examples 1 and 2 are valid for standard as well as for Ex-ver­sions of the signal conditioning instruments. Please note the following instructions:
- the relay contact is shown in unpressurized condition
- if strong electromagnetic interferences are ex­pected, we recommend to use screened cable for the signal lines
- the screening must only be earthed at one sensor side
- in case of overvoltages we recommend the use of VEGA-overvoltage arresters
- the connection must be made according to the appropriate national installation standards (e.g. in Germany according to VDE-regulations).

3.2 Wiring plan

Sensor
+
+–
10 V
78
111213 14
43
+
12
VEGASEL 643
910
L1
N 
+
Supply voltage
active current input for connec­tion of a sensor (4 … 20 mA)
passive current input for connection of a signal condi­tioning instrument (VEGAMET…)
passive voltage input for connection to the voltage output of a signal conditioning instrument (VEGAMET…)
Relay output
8 VEGASEL 643
Electrical connection
Extension example 1
Instrument 1: VEGASEL 643 actively switched Instrument 2 up to max. instrument 5: VEGASEL 643 passively switched
Note:
The voltage inputs (7, 8) must not be used when the current inputs are switched.
Sensor (4 … 20 mA)
active
+
12 43
+
VEGASEL
passive
Current inputs
+
12
VEGASEL
+
Current inputs
43
+
12
VEGASEL
+
passive
43
Current inputs
Instrument 1 Instrument 2 .................... up to max. . instrument 5
Extension example 2
Instrument 1: VEGAMET 601 or 602 Ex Instrument 2 up to max. instrument 10: VEGASEL 643 each switched to passive voltage input (parallel switching)
Note:
Current inputs (3, 4) must not be used when the voltage inputs are switched.
Sensor
10 V
+
+
43
87
Voltage input
+
12
10 V
VEGASEL
+
43
+
87
Voltage input
+
12
VEGAMET
10 V
+
+
43
87
Voltage input
+
12
VEGASEL
Instrument 1 Instrument 2 .................... up to max. . instrument 10
According to the extension examples it is possible to control several signal conditioning instruments with one sensor and hence to detect different levels.
This kind of switching can be extended each up to 5 or 10 instruments.
VEGASEL 643 9

4 Set-up

4.1 Indicating and operating elements

Set-up
1 2 3
4
5 6
VEGASEL 643
Top view, laterally
12 43
max.
5
6
++ –
min.
5
3
++
on
56 78
9 1011121314
7
8
9
11
12
1 Key for value falling 2 Coded key for max. switch point 3 Key for value raising 4 Coded key for min. switch point 5 Status indication of the output 6 LED-supply voltage 7 Separating wall 8 Terminals current input 9 Terminals voltage input 10 Terminals supply and relay output
11 Bar code, series number 12 DIL-switch block 13 Screws 14 Ventilation opening 15 Transparent cover
13








10 VEGASEL 643
14
15
Set-up
Coded key
Coded keys (2 and 4) are located in the front plate by which the switch point (with single point level switches) as well as the switching hysteresis (with double point level switches) can be adjusted.
The figures are given in % and relate to the current or voltage input. By pushing the buttons „+“ or „–“ you can adjust the requested values raising or falling in 1 % or 10 %-steps.
Signal lamps
Green (6)
- Supply voltage on, ready for operation Yellow (5)
- Status indication of the relay output (LED lights = relay energized, LED extinguished = relay de-energized)
DIL-switch (13)
Laterally on top. When the signal conditioning instru­ment is mounted, covered by the terminal socket.
Description of the individual functions
2..10V
4..20mA
0.. A
B
Adjustment possibility
- Current input 0 … 20 mA or 4 … 20 mA voltage output 0 … 10 V or 2 … 10 V
- Mode A or B A = overfill protection, B = protection against dry running of pumps
• Mount the terminal socket.
• Wire the input terminals of the terminal socket acc. to the above mentioned conditions.
• Cover the input terminals with the separating chamber.
• Switch the output of the auxiliary level switch acc. to the technical requirements.
• Adjust on the DIL-switch (11) the range of the inputs.
• When connecting a sensor to the active current input (terminals 1 and 2) set the DIL-switch to 4 … 20 mA.
• Select on the DIL-switch (11) the desired mode.
• Adjust the switch points acc. to “section 4.3”.
• Mount the module unit to the terminal socket.
• Switch on the supply voltage, the green LED (6) lights.

4.3 Switch point adjustment

Single point control
With a single point control it is possible to generate at one point of the input signal (0…10 V or 0/4…20 mA) a switching signal.
Coded key
max. 80
min. 79
t
12 13 14
12 13 14
Hysteresis 1 %
Mode A
Mode B
79/80
%
100
0
Procedure

4.2 Set-up sequence

• Adjust the switch point on both coded keys.
• As example min. = 79 %, max. = 80 %, with this
The following list states the essential set-up steps in short
Pre-requirement:
adjustment there is a hysteresis of 1 %.
• Possible adjustment range 1 % … 99 %.
• The auxiliary level switch is hence ready for opera­tion. Please cover with the transparent cover (15).
VEGASEL 643 auxiliary level switch is connected with a measuring system (sensor and VEGAMET…) or directly with a sensor (4 … 20 mA).
VEGASEL 643 11
Set-up
Double point control
With a double point control it is possible to generate switching signals at two different points of the input signal (0/2 … 10 V or 0/4 … 20 mA).
Procedure
%
100
60
20
0
Mode A
Mode B
• Adjust the coded key with different values.
• Possible adjustment range 1 % … 99 %.
• As example min. = 20 %, max. = 60 %, with this adjustment there is a hysteresis of 40 %.
• The auxiliary level switch is hence ready for opera­tion. Please cover with the transparent cover (15).
Note: Adjust the percentage values with the coded keys which relate to the input signal.
Example 1
- Voltage input 0 … 10 V
- Two-point control
- Switch points min. = 20 %, max. = 60 %
0 … 10 V corresponds to 0 % … 100 %, = 10 V
20 % of 10 V = 2 V 60 % of 10 V = 6 V
Switch point 20 % corresponds to 2 V Switch point 60 % corresponds to 6 V
Coded key
max. 60
min. 20
t
12 13 14
12 13 14
^ Hysteresis 40 %
Example 2
- Voltage input 2 … 10 V
- Two-point control
- Switch points min. = 20 %, max. = 60 %
2 … 10 V corresponds to 0 % … 100 %, = 10 V – 2 V = 8 V
20 % of 8 V = 1,6 V 60 % of 80 V = 4,8 V
Switch point 20 % corresponds to 1,6 V + 2 V = 3,6 V Switch point 60 % corresponds to 4.8 V + 2 V = 6,8 V
Example 3
- Current input 0 … 20 mA
- Two-point control
- Switch points min. = 20 %, max. = 60 % 0 … 20 mA corresponds to 0 % … 100 %, = 20 mA
20 % of 20 mA = 4 mA 60 % of 20 mA = 12 mA
Switch point 20 % corresponds to 4 mA Switch point 60 % corresponds to 12 mA
Example 4
- Current input 4 … 20 mA
- Two-point control
- Switch points min. = 20 %, max. = 60 %
4 … 20 mA corresponds to 0 % … 100 %, = 20 mA – 4 mA = 16 mA
20 % of 16 mA = 3,2 mA 60 % of 16 mA = 9,6 mA
Switch point 20 % corresponds to 3,2 mA + 4 mA = 7,2 mA Switch point 60 % corresponds to 9,6 mA + 4 mA = 13,6 mA
The calculation and information examples are valid in the same way for the single point control.
12 VEGASEL 643
Diagnosis

5 Diagnosis

5.1 Maintenance

The instrument is maintenancefree.

5.2 Repair

For safety and guarantee reasons repairs on the instrument must only be carried out by VEGA-staff.
In case of a defect please return the respective instru­ment along with a short description of the fault to our repair department.
Occurring faults, possible reasons and their removals are stated under „5.3 Failure removal“.

5.3 Failure removal

Failure Removal / Measure
Instrument does not function, the green mains control lamp extinguishes Check the supply voltage and the mains connection by means of the „Connection
Instrument does not switch correctly Check the position of the coded keys. The switch points for min. and max. must not
instructions“. When the instrument still does not function, contact our service department.
be set to the same values. Correct if necessary the values.
Instrument does not switch when using the active input Check the connected measuring data input
VEGASEL 643 13
- Check wiring, see „3.3 Wiring plan and extension examples“
- Check voltage or current values on their nominal range, see „1.4 Technical data“.
- The auxiliary level switch is internally provided with an interlock diode. A measuring instrument connected to terminal 2 and 3 is hence automatically switched into the circuit of the measuring line (switching in series). Hence it is possible to check the measuring line. The measuring instrument indicates the actual current.
Load of the measuring
mA
instrument max. 15
12 43
Notes
14 VEGASEL 643
Notes
VEGASEL 643 15
VEGA Grieshaber KG Am Hohenstein 113 D-77761 Schiltach Phone (0 78 36) 50 - 0 Fax (0 78 36) 50 - 201 Fax (0 78 36) 50 - 203
ISO 9001
Technical data subject to alterations 2.19 955 / Sept. 1996
Loading...