VEGA SCAN693 User Manual

0 (0)

Operating Instructions

Signal conditioning instrument for up to 15 HART sensors

VEGASCAN 693

15-channel HART signal conditioning instrument

Document ID: 29252

Contents

Contents

1 About this document

4

1.1

Function............................................................................................................................

1.2

Target group......................................................................................................................

4

1.3

Symbolism used...............................................................................................................

4

2 For your safety

5

2.1

Authorised personnel........................................................................................................

2.2

Appropriate use................................................................................................................

5

2.3

Warning about incorrect use.............................................................................................

5

2.4

General safety instructions................................................................................................

5

2.5

Safety label on the instrument...........................................................................................

5

2.6

CE conformity...................................................................................................................

6

2.7

Safety instructions for Ex areas.........................................................................................

6

2.8

Environmental instructions................................................................................................

6

3 Product description

7

3.1

Configuration....................................................................................................................

3.2

Principle of operation........................................................................................................

8

3.3

Adjustment........................................................................................................................

8

3.4

Packaging, transport and storage.....................................................................................

9

4

Mounting

10

 

4.1

General instructions........................................................................................................

 

4.2

Mounting instructions......................................................................................................

10

5

Electrical connection

12

 

5.1

Preparing the connection................................................................................................

 

5.2

Connection procedure....................................................................................................

12

 

5.3

Wiring plan......................................................................................................................

14

6

Setup with the integrated display and adjustment unit

16

 

6.1

Adjustment system..........................................................................................................

 

6.2

Setup steps.....................................................................................................................

17

 

6.3

Menu schematic.............................................................................................................

25

7

Setup with PACTware

30

 

7.1

Connect the PC...............................................................................................................

 

7.2

Parameter adjustment with PACTware............................................................................

32

 

7.3

Setup web server/e-mail, remote enquiry........................................................................

33

8

Application examples

34

 

8.1

Inventory enquiry via network and browser.....................................................................

 

8.2

Inventory enquiry/VMI via WEB-VV.................................................................................

35

9Maintenance and fault rectification

9.1

Maintenance...................................................................................................................

37

9.2

Rectify faults...................................................................................................................

37

9.3

Instrument repair.............................................................................................................

39

10 Dismounting

40

10.1

Dismounting steps..........................................................................................................

10.2

Disposal..........................................................................................................................

40

 

 

 

 

2

 

VEGASCAN 693 • 15-channel HART signal conditioning instrument

130701-EN-29252

29252-EN-130701

 

 

Contents

11 Supplement

 

11.1

Technical data.................................................................................................................

41

11.2

Overview applications/functionality.................................................................................

43

11.3

Dimensions.....................................................................................................................

44

Supplementary documentation

Information:

Supplementary documents appropriate to the ordered version come with the delivery.You can find them listed in chapter "Product description".

Editing status: 2013-06-18

VEGASCAN 693 • 15-channel HART signal conditioning instrument

3

1 About this document

1 About this document

1.1Function

This operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectification.Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.

1.2Target group

This operating instructions manual is directed to trained specialist personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3Symbolism used

Information, tip, note

This symbol indicates helpful additional information.

Caution: If this warning is ignored, faults or malfunctions can result.

Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result.

Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.

Ex applications

This symbol indicates special instructions for Ex applications.

List

The dot set in front indicates a list with no implied sequence.

Action

This arrow indicates a single action.

1Sequence of actions

Numbers set in front indicate successive steps in a procedure.

Battery disposal

This symbol indicates special information about the disposal of batteries and accumulators.

130701-EN-29252

4

VEGASCAN 693 • 15-channel HART signal conditioning instrument

29252-EN-130701

2 For your safety

2 For your safety

2.1Authorised personnel

All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator.

During work on and with the device the required personal protective equipment must always be worn.

2.2Appropriate use

VEGASCAN 693 is a universal signal conditioning instrument and power supply unit for connection of up to 15 HART sensors.

You can find detailed information on the application range in chapter "Product description".

Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.

For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbitrary conversions or modifications are explicitly forbidden.

2.3Warning about incorrect use

Inappropriate or incorrect use of the instrument can give rise to application-specific hazards, e.g.vessel overfill or damage to system components through incorrect mounting or adjustment.

2.4General safety instructions

This is a high-tech instrument requiring the strict observance of standard regulations and guidelines. The user must take note of the safety instructions in this operating instructions manual, the country-specific installation standards as well as all prevailing safety regulations and accident prevention rules.

The instrument must only be operated in a technically flawless and reliable condition. The operator is responsible for trouble-free operation of the instrument.

During the entire duration of use, the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regulations.

2.5Safety label on the instrument

The safety approval markings and safety tips on the device must be observed.

VEGASCAN 693 • 15-channel HART signal conditioning instrument

5

2 For your safety

2.6CE conformity

The device fulfills the legal requirements of the applicable EC guidelines.By affixing the CE marking, we confirm successful testing of the product.

You can find the CE Certificate of Conformity in the download section of our homepage.

Electromagnetic compatibility

The instrument is designed for use in an industrial environment. Nevertheless, electromagnetic interference from electrical conductors and radiated emissions must be taken into account, as is usual with a class A instrument according to EN 61326-1. If the instrument is used in a different environment, its electromagnetic compatibility with other devices must be ensured by suitable measures.

2.7Safety instructions for Ex areas

Please note the Ex-specific safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex-approved instruments.

2.8Environmental instructions

Protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental protection.The environment management system is certified according to DIN EN ISO 14001.

Please help us fulfill this obligation by observing the environmental instructions in this manual:

Chapter "Packaging, transport and storage"

Chapter "Disposal"

130701-EN-29252

6

VEGASCAN 693 • 15-channel HART signal conditioning instrument

29252-EN-130701

Scope of delivery

Constituent parts

Type plate

3 Product description

3 Product description

3.1Configuration

The scope of delivery encompasses:

VEGASCAN 693 signal conditioning instrument

Terminal socket

Coded pins and bridges

RS232 modem connection cable (optional)

Documentation

––this operating instructions manual

––Supplementary instruction 30325 "RS232/Ethernet connection"

(optional)

––Supplementary instructions manual 30768 "Modbus-TCP, VEGA ASCII protocol" (optional)

––Ex-specific "Safety instructions" (with Ex versions)

––if necessary, further certificates

The VEGASCAN 693 consists of the components:

VEGASCAN 693 signal conditioning instrument with display and adjustment unit in the front

Terminal socket

 

 

 

 

 

 

 

1

 

 

 

 

 

 

1

2

 

3

4

5

6

 

 

7

8

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

COM

 

 

 

 

 

 

 

 

 

 

 

 

 

ESC

 

 

 

 

OK

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

6

on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ser. No.

 

 

VEGASCAN 693

 

 

 

 

 

12345678

 

 

9

10

 

11

12

13

14

 

 

15

16

 

5

17 18

20

21

22

23 24

25

26

27

28

 

Fig. 1: VEGASCAN 693

1Ex separating chamber with Ex version

2VEGASCAN 693

3Display and adjustment unit

4Communication interface for VEGACONNECT (I²C)

5RS232 or Ethernet interface

6Terminal socket

The nameplate contains the most important data for identification and use of the instrument:

Article number

Serial number

Technical data

Article numbers, documentation

VEGASCAN 693 • 15-channel HART signal conditioning instrument

7

3 Product description

The order data and the documentation of the instrument can be retrieved by means of the instrument serial number on the type label. To do this, go to www.vega.com, "VEGA Tools" and "serial number search".

 

3.2 Principle of operation

Application area

VEGASCAN 693 is a universal signal conditioning instrument for a

 

number of applications such as level, gauge and process pressure

 

measurement. At the same time, it can serve as power supply unit for

 

connected sensors. VEGASCAN 693 is designed for connection of 15

 

independent VEGA HART sensors (5 with Ex applications). Hence 15

 

(5 with Ex) independent measurements can be carried out.

 

On instruments with one of the optional interfaces (RS232/Ethernet),

 

the measured values can be retrieved via modem or network and

 

displayed by means of a web browser, Visual VEGA or WEB-VV. It is

 

also possible to send measured values and messages via e-mail. The

 

use of VEGASCAN 693 is particularly suitable for stocktaking, VMI

 

(Vendor Managed Inventory) and remote enquiry.

Functional principle

VEGASCAN 693 signal conditioning instrument can power up to

 

15 HART sensors and also evaluates their measuring signal via the

 

same cable. The measured value transmission is carried out via a

 

digital bus system (HART multidrop). The requested parameter is

 

shown in the display and, in addition, outputted to the integrated

 

interface and the web server for further processing. On request, the

 

measured values can be sent event or time-controlled via e-mail to

 

different addressees.

Voltage supply

Wide-range power supply unit with 20 … 253 V AC/DC for world-wide

 

use.

 

Detailed information about the power supply can be found in chapter

 

"Technical data".

3.3 Adjustment

The instrument can be adjusted with the following adjustment media:

With integrated display and adjustment unit

an adjustment software according to FDT/DTM standard, e.g.

 

PACTware and a Windows PC

 

 

 

 

The entered parameters are generally saved in VEGASCAN 693,

 

 

 

 

when used with PACTware and PC also optionally in the PC.

 

 

 

 

Information:

 

 

 

 

When using PACTware and the corresponding VEGA DTM, additional

 

 

 

 

settings can be carried out which are not possible or only partly pos-

 

 

 

 

 

 

 

 

sible with the integrated display and adjustment unit. When using an

 

 

 

 

adjustment software, you either need one of the integrated interfaces

 

 

 

 

(RS232/Ethernet) or the interface converter VEGACONNECT.

 

 

 

 

Further instructions for setting up the web server and e-mail functions

 

 

 

 

can be found in the online help of PACTware or the VEGASCAN 693

 

 

 

 

 

 

8

 

 

 

VEGASCAN 693 • 15-channel HART signal conditioning instrument

130701-EN-29252

 

 

 

3 Product description

 

 

DTMs as well as the operating instructions manual "RS232/Ethernet

 

 

connection".

 

 

3.4 Packaging, transport and storage

Packaging

Your instrument was protected by packaging during transport. Its

 

 

capacity to handle normal loads during transport is assured by a test

 

 

based on ISO 4180.

 

 

The packaging of standard instruments consists of environment-

 

 

friendly, recyclable cardboard. For special versions, PE foam or PE

 

 

foil is also used. Dispose of the packaging material via specialised

 

 

recycling companies.

Transport

Transport must be carried out under consideration of the notes on the

 

 

transport packaging. Nonobservance of these instructions can cause

 

 

damage to the device.

Transport inspection

The delivery must be checked for completeness and possible transit

 

 

damage immediately at receipt. Ascertained transit damage or con-

 

 

cealed defects must be appropriately dealt with.

Storage

Up to the time of installation, the packages must be left closed and

 

 

stored according to the orientation and storage markings on the

 

 

outside.

 

 

Unless otherwise indicated, the packages must be stored only under

 

 

the following conditions:

 

 

Not in the open

 

 

Dry and dust free

 

 

Not exposed to corrosive media

 

 

Protected against solar radiation

 

 

Avoiding mechanical shock and vibration

Storage and transport

Storage and transport temperature see chapter "Supplement -

temperature

Technical data - Ambient conditions"

 

 

Relative humidity 20 … 85 %

29252-EN-130701

VEGASCAN 693 • 15-channel HART signal conditioning instrument

9

4 Mounting

4 Mounting

4.1General instructions

Installation possibilities Each series 600 instrument consists of the actual signal conditioning instrument as well as a plug-in socket for carrier rail mounting (tophat rail 35 x 7.5 according to DIN EN 50022/60715). Because it has protection class IP 30 or IP 20, the instrument is intended to be used in switching cabinets.

 

4.2 Mounting instructions

Mounting

The plug-in socket is designed for carrier rail mounting. The operat-

 

ing voltage is connected to terminals 17 and 18. For neighbouring

 

series 600 instruments it is possible to continue connection L1 and

 

N directly via the supplied bridges.Max.five instruments can be con-

 

nected through in this way.

 

Danger:

 

Looping through via bridges is only allowed for operating voltage

 

(sockets L1 and N). The bridges must never be used with single

 

instruments, at the end of a row of instruments or with other sockets.

 

If this rule is not heeded, there is a danger of coming into contact with

 

the operating voltage or causing a short circuit.

 

A VEGASCAN 693 in Ex version is an auxiliary, intrinsically safe

 

instrument and may not be installed in explosion-endangered areas.

 

Before setup, the Ex separating chamber must be attached (as shown

 

below) with Ex versions. Safe operation can be only ensured if the

 

operating instructions manual and the EG type approval certificate

 

are observed. VEGASCAN 693 must not be opened.

Instrument coding

All signal conditioning instruments are provided with different gaps

 

dependent on type and version (mechanical coding).

 

The plug-in socket is provided with coded pins that can be inserted to

 

prevent accidental interchanging of the various instrument types.

 

With a VEGASCAN 693 in Ex version, the supplied coded pins (type

 

coded pin and Ex coded pin) must be inserted by the user according

 

to the below chart.

130701-EN-29252

10

VEGASCAN 693 • 15-channel HART signal conditioning instrument

VEGA SCAN693 User Manual

4 Mounting

1

1

2

3

4

5

6

7

8

A o

VEGA

B o

 

C o

 

1 o

 

2 o

 

3 o

 

o

 

o

 

o

 

A o

VEGA

B o

 

C o

 

1 o

 

2 o

 

3 o

 

4 o

 

5 o

 

6 o

 

 

7 o

 

7 o

 

 

8 o

 

8 o

 

4

9 o

N

9 o

N

o

10 o

o

L1

11 o

L1

 

12 o

 

12 o

 

2

3

4

Fig. 2: Plug-in socket VEGASCAN 693

1Ex separating chamber

2Ex coding with Ex version

3Type coding for VEGASCAN 693

4Bridges for looping the operating voltage

29252-EN-130701

VEGASCAN 693 • 15-channel HART signal conditioning instrument

11

5 Electrical connection

5 Electrical connection

5.1Preparing the connection

Note safety instructions Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

If overvoltage surges are expected, overvoltage arresters should be installed

Take note of safety instructions for Ex applications

Select power supply Select connection cable

Cable screening and grounding

Select connection cable for Ex applications

In hazardous areas you must take note of the respective regulations, conformity and type approval certificates of the sensors and power supply units.

The voltage supply can be 20 … 253V AC/DC, 50/60 Hz.

The operating voltage of VEGASCAN 693 is connected with standard cable according to the national installation standards.

Standard two-wire cable can be used for connecting the sensors. The screening is absolutely necessary to ensure interference-free operation with HART sensors.

Connect the cable screen on both ends to ground potential. In the sensor, the screen must be connected directly to the internal ground terminal. The ground terminal on the outside of the sensor housing must be connected to the potential equalisation (low impedance).

If potential equalisation currents are expected, the screen connection on the side of VEGASCAN 693 must be made via a ceramic capacitor (e. g. 1 nF, 1500 V). The low frequency potential equalisation currents are thus suppressed, but the protective effect against high frequency interference signals remains.

Take note of the corresponding installation regulations for Ex applications. In particular, make sure that no potential equalisation currents flow over the cable screen.In case of grounding on both sides this can be achieved by the use of a capacitor or a separate potential equalisation.

5.2Connection procedure

Note:

Before the actual setup, each HART sensors must be assigned an address (address range 1-15), (see chapter "Setup").Address 0

(mode 4 … 20 mA) must not be used. When assigning an address, only one sensor should be connected to VEGASCAN 693. If connection is completed already, the wiring must be briefly cancelled for addressing. Depending on the installation location of the sensors, it can be advantageous to carry out this addressing before installing and connecting the sensors. This can be conveniently carried out e.g. in the workshop.You just need a 24 Volt power supply as well as an indicating and adjustment module PLICSCOM or the adjustment software PACTware with VEGACONNECT.

Move on to electrical connection and proceed as follows:

1. Snap the socket without VEGASCAN 693 onto the carrier rail

12

VEGASCAN 693 • 15-channel HART signal conditioning instrument

130701-EN-29252

5 Electrical connection

2.Connect sensor cable to terminal 1/2 (active input) or 3/4 (passive input), provide a screening

3.When using several sockets, loop the power supply by means of bridges

4.Connect power supply (switched off) to terminal 17 and 18

5.If necessary, connect relays or other outputs

6.Insert VEGASCAN 693 into the plug-in socket and screw it down tightly

Note:

If the addressing of the sensors is not yet carried out, only one sensor must be connected.Then the addressing (see chapter "Setup") is carried out.Afterwards, the first sensor must be disconnected again and the next sensor must be connected as well as the addressing must be carried out. Carry out this procedure as long as all sensors have an own, unambiguous address. Then all sensors can be connected and setup can be carried out.

Before setting up Ex versions, make sure the Ex separating chamber is plugged on the left housing side (above the sensor terminals). The pins for type and Ex coding must also be inserted correctly.

Information:

 

 

 

On the active input (terminal 1/2), VEGASCAN 693 provides

 

 

 

 

 

 

power for the connected sensors. Power supply and measurement

 

 

 

 

 

 

 

data are transmitted over the same two-wire cable. This mode is

 

 

 

 

provided for connection of measuring transducers without sepa-

 

 

 

rate operating voltage (sensors in two-wire version).

 

 

 

On the passive input (terminals 3/4), the sensors are not supplied

 

 

 

with energy - only the measured value is transmitted. This input is

 

 

 

 

for instruments with their own separate operating voltage (sensors

 

 

 

 

in four-wire version or separators such as VEGATRENN 149). On

 

 

 

 

a VEGASCAN 693 in Ex version, the passive input is not available

 

 

 

 

due to approval/technical reasons.

Note:

VEGASCAN 693 is designed for connection of up to 15 HART sensors (5 with Ex).Because they are accessed via different addresses in the HART multidrop mode, all sensors must be connected to the same sensor input. These are either terminals 1/2 (active input) or terminals 3/4 (passive input). Mixed operation of active and passive input is not possible. Since this is a digital bus system, only one two-wire cable should lead to the sensors. A distributor can then be connected directly forward of the sensors. As an alternative, the connection cable can be looped through the second cable entry on the sensor housing. The address assignment of the sensors should be carried out before connection, see chapter "Set up".

29252-EN-130701

VEGASCAN 693 • 15-channel HART signal conditioning instrument

13

5 Electrical connection

Wiring plan for two-wire sensors

5.3Wiring plan

3

+ -

2

3

4

5

6

7

8

2

4

 

 

9

10

 

 

11

12

13

14

 

 

15

16

 

 

17

18

19

20

21

22

23

24

25

26

27

28

8

6

+

-

 

 

 

 

 

 

 

 

 

 

L1

N

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

Fig. 3: Connection example VEGASCAN 693 with two-wire sensors

1Measurement data input with sensor supply (active input)

2Measurement data input (passive input), not in Ex ia

3Internal fail safe relay

4Distributor

5Voltage supply of VEGASCAN 693

6HART two-wire sensor with Multidrop address 1

7HART two-wire sensor with Multidrop address 2

8HART two-wire sensor with Multidrop address 3

130701-EN-29252

14

VEGASCAN 693 • 15-channel HART signal conditioning instrument

5 Electrical connection

Wiring plan for four-wire sensors

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

+

-

 

 

 

 

 

 

 

 

 

2

 

 

3

4

5

6

 

 

7

8

 

 

 

 

 

 

2

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

10

 

 

11

12

13

14

 

 

15

16

 

 

17

18

19

20

21

22

23

24

25

26

27

28

 

6

+

-

 

 

 

 

 

 

 

 

 

 

 

L1

N

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 4: Connection example VEGASCAN 693 with four-wire sensors

1Measurement data input with sensor supply (active input)

2Measurement data input (passive input), not in Ex ia

3Internal fail safe relay

4Distributor

5Voltage supply of VEGASCAN 693

6HART four-wire sensor with Multidrop address 1

7HART four-wire sensor with Multidrop address 2

8HART four-wire sensor with Multidrop address 3

9Power supply for four-wire sensors

29252-EN-130701

VEGASCAN 693 • 15-channel HART signal conditioning instrument

15