VEGA PULS41 User Manual

Operating Instructions
VEGAPULS 41 (Profibus PA)
PROF I
PROCESS FIELD BUS
BUS
Safety information ........................................................................ 3
Note Ex area ................................................................................ 3
1 Product description .................................................................. 4
1.1 Function................................................................................. 4
1.2 Application features ............................................................. 6
1.3 Profibus output signal .......................................................... 7
1.4 Adjustment ............................................................................ 8
1.5 Type survey ........................................................................ 12
1.6 Antennas............................................................................. 12
2 Mounting and installation ..................................................... 13
2.1 General installation instructions ........................................ 13
2.2 Measurement of liquids ..................................................... 16
2.3 Measurement in standpipe (surge or bypass tube) ...... 17
2.4 False echoes ...................................................................... 22
2.5 Common installation mistakes ........................................... 24
Contents
3 Electrical connection .............................................................. 26
3.1 Connection – Connection cable – Screening ................... 26
3.2 Sensor address ................................................................. 29
3.3 Connecting the sensor ...................................................... 31
3.4 Connecting the external indicating instrument ................ 32
3.5 Bus configuration ............................................................... 33
2 VEGAPULS 41 – Profibus PA
27292-EN-041227
Contents
4 Set-up ........................................................................................ 38
4.1 Adjustment media .............................................................. 38
4.2 Adjusting the sensor with the adjustment module
MINICOM ............................................................................ 38
6 Diagnostics............................................................................... 44
6.1 Simulation ............................................................................ 44
6.2 Error codes ........................................................................ 44
7 Technical data .......................................................................... 45
7.1 Technical data ..................................................................... 45
7.2 Approvals ........................................................................... 49
7.3 Data format of the output signal ........................................ 50
7.4 Dimensions ......................................................................... 51
7.5 CE conformity declaration ................................................. 53

Safety information

Please read this manual carefully, and also take note of country-specific installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and acci­dent prevention rules. For safety and warranty reasons, any internal work on the instruments, apart from that in­volved in normal installation and electrical con­nection, must be carried out only by qualified VEGA personnel.
27292-EN-041227
VEGAPULS 41 – Profibus PA 3

Note Ex area

Please note the attached safety instructions containing important information on installation and operation in Ex areas. These safety instructions are part of the oper­ating instructions manual and come with the Ex approved instruments.

1 Product description

Product description
Radar sensors usually come with horn or rod antennas. PTFE rod antennas are suitable for many applications with chemically aggres­sive products, but are unsuitable for small vessels due to their size. Also the reception efficiency of the rod antenna is lower than that of the (less resistant) horn antenna. The two new radar sensors, VEGAPULS 43 with DN 50 and DN 80 process fittings and the de­scribed VEGAPULS 41 with 1½“ process fitting, perfectly round out the instrument series. Horn and rod antennas that protrude into the vessel belong to the past. The an­tenna of VEGAPULS 41 consists of a small 40 mm TFM-PTFE cone that is suitable for chemically aggressive environments. Fluorothermoplasts and perfluoroelastomers (PTFE) have been known as the „Mercedes“ of plastic materials for many years. They are resistant to virtually all chemical media, such as e.g. amines, ketones, esters, acids (sul­phuric acid, phosphoric acid, hydrochloric acid, nitric acid), alkalis (caustic soda), oxi­dants, fuels and oils. These plastics do not become brittle or age and are suitable for temperatures up to 150°C. The only limits to these materials are applications with fluorine under high pressure or with liquid alkali met­als (sodium or potassium), where adverse reactions may occur. The cone acts like a lens that focuses short (0.15 mW) radar pulses into a beam and sends them towards the product. During the pulse breaks, the cones operate like a unidirectional micro­phone with optimum reception efficiency. The intelligent, extremely fast electronics converts the radar echo into a precise image of the environment and level, which is outputted as a 4 … 20 mA or Profibus signal.
Due to their small housing dimensions and process fittings, the compact sensors are unobtrusive and, above all, cost-effective monitors of your product levels. With their integrated display, they enable high­precision level measurements and can be used for applications in which the advantages of non-contact measurement could never before be realized.
VEGAPULS radar sensors are perfectly adapted to two-wire technology. The supply voltage and the output signal are transmitted via one two-wire cable. The instruments produce an analogue 4 … 20 mA signal as output, i.e. measuring signal.

1.1 Function

Radio detecting and ranging: Radar.
VEGAPULS radar sensors are used for non­contact, continuous distance measurement. The measured distance corresponds to a filling height and is outputted as level.
Measuring principle:
emission – reflection – reception
Extremely small 26 GHz radar signals are emitted from the antenna of the radar sensor as short pulses. The radar pulses reflected by the sensor environment and the product are received by the antenna as radar ech­oes. The running period of the radar pulses from emission to reception is proportional to the distance and hence to the level.
4 VEGAPULS 41 – Profibus PA
27292-EN-041227
Product description
Meas. distance
emission - reflection - reception
The radar pulses are emitted by the antenna system as pulse packages with a pulse duration of 1 ns and pulse intervals of 278 ns; this corresponds to a pulse package frequency of 3.6 MHz. In the pulse intervals, the antenna system operates as a receiver. Signal running periods of less than one bil­lionth of a second must be processed and the echo image evaluated in a fraction of a second.
1 ns
278 ns
Hence, it is possible for the radar sensors to process the slow-motion pictures of the sen­sor environment precisely and in detail in cycles of 0.5 to 1 second without using time­consuming frequency analysis (e.g. FMCW, required by other radar techniques).
Nearly all products can be measured
Radar signals display physical properties similar to those of visible light. According to the quantum theory, they propagate through empty space. Hence, they are not depend­ent on a conductive medium (air), and they spread out like light at the speed of light. Radar signals react to two basic electrical properties:
- the electrical conductivity of a substance
- the dielectric constant of a substance.
All products which are electrically conductive reflect radar signals very well. Even slightly conductive products provide a sufficiently strong reflection for a reliable measurement.
All products with a dielectric constant ε greater than 2.0 reflect radar pulses suffi­ciently (note: air has a dielectric constant εr of
1). Signal reflectivity grows stronger with increasing conductivity or increasing dielec­tric constant of the product. Hence, nearly all substances can be measured.
r
Pulse sequence
VEGAPULS radar sensors can achieve this through a special time transformation proce­dure which spreads out the more than 3.6 million echo images per second into a quasi slow-motion picture, then freezes and proc­esses them.
%
50 40 30 20 10
5 %
5
0
2
0
25 %
4 6 8 12 14 16 18
10
40 %
20
ε
Reflected radar power dependent on the dielectric constant of the measured product
tt
Time transformation
27292-EN-041227
VEGAPULS 41 – Profibus PA 5
r
Product description
With standard flanges of DN 50 to DN 150, ANSI 2“ to ANSI 6“ or G 1½ A and 1½“ NPT, the sensor antenna systems can be adapted to various products and measuring environ­ments.
The high-quality materials can also withstand extreme chemical and physical conditions. The sensors deliver stable, reproducible analogue or digital level signals with reliability and precision.
Continuous and reliable
Unaffected by temperature, pressure and individual atmosphere content, VEGAPULS radar sensors are used for quick and reliable continuous level measurement of widely vary­ing products.
%
0,03 0,02 0,01
0
100 500 1000 1300 ˚C
0
0,018 %
Temperature influence: Temperature error absolutely zero (e.g. at 500°C 0.018 %)
%
10
5
0,29 %
0
10
0
1,44 %
20 30 40 60
50
Pressure influence: Error with pressure increase very low (e.g. at 50 bar 1.44 %)
0,023 %
2,8 %
70 80 90 110 120 130 140
100
3,89 %
bar

1.2 Application features

Applications
• level measurement of any liquid
• measurement also in vacuum
• all slightly conductive materials and all substances with a dielectric constant > 2.0 can be measured
• measuring range 0 … 10 m.
Two-wire technology
• power supply and output signal on one two-wire cable (loop powered)
• Profibus PA (Profile 3).
Rugged and abrasionproof
• non-contact
• high-resistance materials
Exact and reliable
• accuracy 0.05 %.
• resolution 1 mm
• unaffected by noise, vapours, dusts, gas compositions and inert gas stratification
• unaffected by varying density and tem­perature of the medium
• measurement in pressures up to 3 bar and product temperatures up to 150°C.
Communicative
• integrated measured value display
• optional display module separate from sensor
• adjustment with detachable adjustment module, pluggable in the sensor or in the external display
• adjustment with HART
• adjustment with the PC.
®
handheld
Approvals
• CENELEC, ATEX, PTB, FM, CSA, ABS, LRS, GL, LR, FCC.
6 VEGAPULS 41 – Profibus PA
27292-EN-041227
Product description

1.3 Profibus output signal

PROPRO
PROcess
PROPRO sult of a joint project of thirteen companies and five universities. The companies Bosch, Klöckner-Möller and Siemens played a deci­sive role. The specifications of the bus are described in the protocol layers 1, 2 and 7 of the ISO/OSI reference model and are avail­able from the PNO (Profibus user organisa­tion). Since layers 3 … 5 have not yet been developed as a standard, Profibus still has a lot of far-reaching potential.
Today approx. 600 companies make use of Profibus technology and belong to the PNO. Profibus Specification, Profibus Periphery and Profibus mation.
As a process automation bus, Profibus PA also enables power supply over the bus. Up to 32 sensors can be operated on a shielded two-wire cable that carries both power sup­ply and measurement signal. In Ex areas, up to ten sensors can be connected from the PA level to one two-wire cable (EEx ia).
Bus structure
The Profibus DP and PA network consists of up to 126 master and slave participants. Data are always exchanged from point to point, with the data traffic being exclusively controlled and checked by master devices. Communication is carried out acc. to the Token-Passing procedure. This means that the master holding the Token can contact the slaves, give instructions, enquire data and cause the slaves to receive and transmit data. After the work is done or after a prede­termined time interval, the Token is passed on by the master to the next master.
FIFI
BUSBUS
FIeld
BUS (PROFIBUS) is the re-
FIFI
BUSBUS
FMSFMS
FMS stands for Fieldbus Messaging
FMSFMS
DPDP
DP for Decentralised
DPDP
PP
AA
P
A for Process Auto-
PP
AA
Master-Class 1
is the actual automation system, i.e. the proc­ess control computer or the PLC that en­quires and processes all measured values.
Master-Class 2
One or several Master-Class 2 can operate in a Profibus network. As a rule, Master-Class 2 devices are engineering, adjustment or visu­alisation stations. The VEGA adjustment soft­ware VVO (VEGA Visual Operating) operates as Master-Class 2 participant on the DP bus and can work on an engineering PC, on an adjustment PC or on the process control computer and can access any VEGA sensor on the PA level.
Instrument master file
A so-called GSD file is delivered with every VEGAPULS Profibus sensor. This file is re­quired to integrate the sensor into the bus system. The GSD (instrument master file) contains, beside the sensor name and the manufacturer, the sensor-specific communi­cation parameters which are necessary for a stable integration of the sensor in the bus.
Load the GSD file belonging to the sensor into your bus configuration program. If the GSD file is not available, it can be downloaded from the VEGA homepage: http:/ /www.vega.com.
Do not confuse the GSD file with the EDD (Electronic Device Description), a file which is necessary for the PDM environment (this can be also found on the VEGA homepage).
27292-EN-041227
VEGAPULS 41 – Profibus PA 7
Product description

1.4 Adjustment

Every measurement set-up is unique. For that reason, every radar sensor needs, be­side the adjustment, some basic information on the application and the environment, e.g. which level means "empty“ and which level "full“. Beside this "empty and full adjustment“, many other settings and adjustments are possible with VEGAPULS radar sensors. The output of echo curves and the calculation of vessel linearisation curves by means of ves­sel dimensions are only two examples.
Profibus adjustment structure
In the Profibus environment, there are differ­ent adjustment concepts and adjustment tools which often differ considerably from manufacturer to manufacturer. From the us­er’s point of view, the ideal solution would be a manufacturer-independent adjustment program which could be operated directly on the Profibus DP/PA, on the sensor, as well as at any system node (e.g. an engineering station or the process control center).
In the past, only the program „SIMATIC PDM“, based on the HART structure, could fulfil this wish (though with the limitations common to HART
®
HART
, the availability of an instrument-spe­cific database for a comprehensive adjust­ment with PDM (Process Device Managing) is a requirement. Otherwise, only the basic instrument functions, such as adjustment, are available. In the PDM environment, this instru­ment-specific database is called EDD (Elec­tronic Device Description), in perfect analogy to the HART
®
environment which also re­quires, except with VEGA HART ments, a DD (Device Description) for each sensor.
®
adjustment
®
). As with
®
instru-
The disadvantages of the HART
®
environment are well known: for each sensor/participant, an individual DD must be loaded, which in addition, must always be the latest and most up-to-date DD. Special adjustment options such as e.g. the output of an echo curve, are available neither with HART
®
nor with PDM. User-friendly adjustment is out of the ques­tion. With VEGA’s adjustment software VVO, those restrictions belong to the past.
The legitimate wish of many Profibus users for a manufacturer-independent adjustment tool without EDD has been realised in the form of PACTware number of process technology companies developed PACTware
CC
tion
Configuration
CC
TM
. An association of a
TM
PP
: a
Process
TT
Tool that can run different
TT
PP
AA
Automa-
AA
manufacturer software tools under a stand­ardized user interface and adjustment struc­ture. Specialists call this technology Field Device Transcription (FDT). Just as different Windows printer drivers enable operation of completely different printers under a single user interface, PACTware
TM
enables operation of all field instruments under a single user interface. Instrument-specific databases (EDD), like those for SIMATIC PDM, are not required.
As a result of this development, four adjust­ment media are available for VEGA Profibus sensors:
- adjustment with the PC and the adjustment
program VVO (VEGA Visual Operating) as stand-alone tool, on the segment coupler or directly on the sensor
- adjustment with the detachable adjustment
module MINICOM in the sensor
- adjustment with the SIMATIC PDM adjust-
ment program (requires EDD instrument databases) from process control
- adjustment with the manufacturer-inde-
pendent user interface PACTware
TM
on the sensor, from process control or on the segment coupler.
8 VEGAPULS 41 – Profibus PA
27292-EN-041227
Product description
Adjustment with the PC
Generally, the set-up and adjustment of radar sensors is most conveniently carried out on the PC with the adjustment program PAC Twa re leads quickly through adjustment and pa­rameter setting by means of pictures, graph­ics and process visualisations.
The adjustment software PACT the FDT concept (Field Device Tool) operates as an independent adjustment program on any PC, engineering station or process con­trol computer.
The adjustment program requires for com­munication with Profibus sensors either a Profibus-Master-Class2 interface card or the interface adapter VEGACONNECT 3. The PC with the Profibus interface card can be con­nected directly to any point on the DP bus with the standard RS 485 Profibus cable. In conjunction with the adapter VEGACONNECT, the PC can be connected directly to the sensor. VEGACONNECT com­municates via a small plug directly with the individual sensor.
The adjustment and parameter data can be saved at any time on the PC with the adjust­ment software and can be protected by passwords. If necessary, the adjustments can be transferred quickly to other sensors. In practice, the adjustment software PAC T engineering station or an operating station. As a Master-Class 2 operating via the Profibus interface card (e.g. from Softing), it accesses VEGA sensors directly over the bus, from the DP level to the PA via the seg­ment coupler.
TM
under Windows®. The program
TM
ware
is often installed as a tool on an
ware
TM
acc. to
Beside the instrument master file (GSD), with which a sensor is logged into the Profibus system, most Profibus sensors require, in addition, a so-called EDD (Electronic Device Description) for each individual sensor, to enable access and adjustment from the bus level.
27292-EN-041227
VEGAPULS 41 – Profibus PA 9
PACTware
SPS
Adr. 10
Master-Class 1
Adr. 1
Profibus DP interface card as Master-Class 2 (e.g. Softing)
3
Product description
Adr. 60
Adr. 59
Adr. 21
Adr. 22
3
Adr. 23
DP-Bus
Adr. 24
Adr. 57
Adr. 58
Segment coupler
Adr. 25
Adr. 25 … 56
PA-
Bus
Adr. 26
2
Adr. 27
(max. 32 participants)
Adr. 28
Adr. 29
Adjustment of the VEGAPULS radar sensors from process control via a Profibus interface card in the process control computer or in an additional PC. The adjustment software VEGA Visual Operating (VVO) accesses the sensors bidirectionally via the interface (interface card).
27292-EN-041227
10 VEGAPULS 41 – Profibus PA
Product description
Adjustment with the adjustment module MINICOM
The small (3.2 cm x 6.7 cm) 6-key adjustment module with display allows the adjustment to be carried out in clear text dialogue. The adjustment module can be plugged into the radar sensor or into the optional, external indicating instrument.
Tank 1 m (d)
12.345
Detachable adjustment module MINICOM
Unauthorised sensor adjustments can be prevented by removing the adjustment mod­ule.
ESC
+
-
OK
Adjustment with SIMA TIC PDM adjust­ment program
To adjust all essential functions of the VEGA sensor with the adjustment station SIMATIC PDM from Siemens, a so-called EDD is re­quired. Without this EDD, only the basic func­tions such as min./max. wet adjustment or integration time can be adjusted with the PDM adjustment program. Further important adjustment functions, such as the input of the meas. environment or a false echo storage are not available without EDD. After integra­tion of the EDD files in the Simatic PDM ad­justment software, all important adjustment functions are accessible. If it is not at hand, the obligatory GSD (instrument master file) as well as the EDD (Electronic Device De­scription) necessary for PDM can be downloaded from the VEGA homepage (www.vega.com).
ESC
+
-
Tank 1
m (d)
OK
12.345
2
-
Tank 1
m (d)
12.345
PA- Bus
ESC
+
OK
4
max. 25 m
Adjustment with detachable adjustment module. The adjustment module can be plugged into the radar sensor or into the external indicating instrument VEGADIS 50.
27292-EN-041227
VEGAPULS 41 – Profibus PA 11
Types and versions

1.5 T ype survey

VEGAPULS 41 sensors are manufactured with process connection G 1½ A or 1½“ NPT.
Features
• Application preferably for liquids in storage tanks and process vessels with increased accuracy requirements and in corrosive environments.
• Measuring range 0 … 10 m
• Ex approved in Zone 1 (IEC) or Zone 1 (ATEX) classification mark EEx ia [ia] IIC T6.
• Integrated measured value display.

1.6 Antennas

The antenna is the eye of the radar sensor. The shape of the antenna, however, doesn’t give a casual observer the lightest clue on how carefully the antenna geometry must be adapted to the physical properties of electro­magnetic waves. VEGAPULS 41 radar sen­sors are equipped with a completely encapsulated antenna.
PTFE is commonly found in hygienic applica­tions. The small plastic cone of the VEGAPULS 41 radar sensor, operating as antenna, consists of a TFM-PTFE material. This is a fluorothermoplast, which has addi­tional distinct advantages compared to PTFE, such as, e.g., reduced load deformation, denser polymer structure as well as a smoother surface (Ra < 0.8 µm). The other known advantages of PTFE, such as, e.g., high temperature resistance (up to 150°C), high chemical resistance as well as resist­ance to brittleness and ageing are still present or have even been enhanced. Perfluorelastomers and fluorothermoplasts are resistant to virtually all chemical media such as, e.g., amines, ketones, esters, acids (sulphuric acid, phosphoric acid, hydrochlo­ric acid, nitric acid), alkalis (caustic soda), oxidants, fuels and oils. Beside their use in the chemical industry, these materials are being applied more and more in sterilisation and pharmaceutical technologies. The only limits to these materials are in applications with fluorine under high pressure or with liquid alkali metals (sodium or potassium), where explosive reactions may occur.
12 VEGAPULS 41 – Profibus PA
27292-EN-041227
Mounting and installation

2 Mounting and installation

2.1 General installation instructions

Measuring range
The reference plane for the measuring range of the sensor is the lower edge of the flange.
Keep in mind that in measuring environments where the me­dium can reach the sensor flange, buildup can form on the antenna, possibly causing measurement errors.
Note: Series 40 sensors are suitable for measurement of solids only under certain con­ditions.
empty
full
Measuring range (operating range) and max. measuring distance Note: Use of the sensors for applications with solids is limited.
max.
Meas. range
Reference plan
max.
min.
False echoes
Flat obstructions and struts cause strong false echoes. They reflect the radar signal with high energy density.
Interfering surfaces with rounded profiles scatter the radar signals into the surrounding space more diffusely and thus generate false
If flat obstructions in the range of the radar signals cannot be avoided, we recommend diverting the interfering signals with a deflec­tor. The deflector prevents the interfering signals from being directly received by the radar sensor. The signals are then so low­energy and diffuse that they can be filtered out by the sensor.
echoes with a lower energy density. Hence, those reflections are less critical than those from a flat surface.
Round profiles diffuse radar signals
Profile with smooth interfering surfaces cause large false signals
Cover smooth, flat surface with deflectors
27292-EN-041227
VEGAPULS 41 – Profibus PA 13
Mounting and installation
Emission cone and false echoes
The radar signals are focused by the an­tenna system. The signals leave the antenna in a conical path similar to the beam pattern of a spotlight. This emission cone depends on the antenna used. Any object in this beam cone will reflect the radar signals. Within the first few meters of the beam cone, tubes, struts or other installations can interfere with the measurement. At a distance of 6 m, the false echo of a strut has an amplitude nine times greater than at a distance of 18 m.
At greater distances, the energy of the radar signal distributes itself over a larger area, thus causing weaker echoes from obstruct­ing surfaces. The interfering signals are therefore less critical than those at close range.
If possible, orient the sensor axis perpen­dicularly to the product surface and keep vessel installations (e.g. pipes and struts) out of the emission cone.
The illustrations of the emission cones are simplified and represent only the main beam
- a number of weaker beams also exist. Un-
der difficult measuring conditions, the an­tenna location and alignment must be chosen with the objective of reducing false echoes. Only giving attention to the size of the useful echo is not adequate when measuring condi­tions are unfavourable.
In a difficult measuring environment, search­ing for a mounting location with the lowest possible false echo intensity will bring the best results. In most cases, the useful echo will then be present with sufficient strength. With the adjustment software PACT
ware
TM
on the PC, you can have a look at the echo im­age and optimise the mounting location.
If possible, provide a "clear view“ to the product inside the emission cone and avoid vessel installations in the first third of the emission cone.
Optimum measuring conditions exist when the emission cone reaches the measured product perpendicularly and when the emis­sion cone is free from obstructions.
Examples of vessel echoes
The following vessel images show a typical echo pattern in a vessel. This is the example of a process vessel with a slow double­bladed stirrer. In the lower par t, the vessel is equipped with heating spirals. A thin, angled inlet tube ends in the vessel centre between the stirrer blades.
14 VEGAPULS 41 – Profibus PA
27292-EN-041227
Mounting and installation
Empty vessel ¼ filling
When the vessel is empty, you see the ech­oes of the vessel installations around the emission cone. Beside the large bottom echo, you see a number of additional false echoes. The false echoes of the vessel installations are saved during a false echo recording. For this reason, the false echo recording must be carried out when the vessel is empty.
False echoes from the top down:
- first inlet tube fastening
- upper stirrer blade
- second inlet tube fastening
- angled inlet tube
- upper heating tubes
- lower stirrer blade
- remaining heating tubes
- vessel bottom
After filling, the bottom echo is replaced by the product echo.
½ filling
The product echo moves to the centre of the meas. range. At the end of the meas. range, you now see an echo at a position where the bottom echo previously was in the empty vessel. This echo is a multiple echo of the product echo and is located at twice the distance of the product echo.
27292-EN-041227
VEGAPULS 41 – Profibus PA 15
Mounting and installation
Filled vessel
In a completely filled vessel, you see addi­tional multiple echoes at two, three or four times the distance of the product surface echo.

2.2 Measurement of liquids

Radar sensors are usually mounted on short DIN socket pieces. The lower side of the instrument flange is the reference plane for the measuring range. - The socket piece should be as short as possible, max. 70 mm.
When mounting on dished vessel tops, the antenna length should correspond at least to the length of the sockets.
In vessels with dished or rounded tops, please do not mount the instrument in the centre or close to the vessel wall.
Dished tank tops can act as paraboloidal reflectors. If the radar sensor is placed in the focal point of the parabolic tank, the radar sensor receives amplified false echoes. The radar sensor should be mounted outside the focal point. Parabolically amplified echoes are thereby avoided.
Antenna directly on the vessel top
If the stability of the vessel will allow it (sensor weight), flat mounting directly on the vessel top is a good and cost-effective solution. The top side of the vessel is the reference plane.
Screwed antennas, especially when used on small vessels, are mounted in sockets. The antenna fits into even the smallest vessel connection openings with 1½“ socket. The socket must not be longer than 70 mm.
Reference plane
< 70 mm
Screwed antenna on 1½“ mounting boss
16 VEGAPULS 41 – Profibus PA
27292-EN-041227
Mounting and installation

2.3 Measurement in standpipe (surge or bypass tube)

General instructions
Pipe antennas are preferred in vessels which contain many installations, e.g. heating tubes, heat exchangers or fast-running stirrers. Measurement is then possible where the product surface is very turbulent, and vessel installations can cause no false echoes.
Due to the concentration of the radar signals within the measuring tube, even products with small dielectric constants (ε
3) can be reliably measured in surge or by-
pass tubes.
Surge pipes which are open at the bottom must extend over the full measuring range (i.e. down to 0% level), as measurement is only possible within the tube. The tube inner diameter should be max. 100 mm or corre­spond to the size of the antenna horn.
Make sure the required upper vent hole in the surge pipe is aligned with the sensor type label.
As an alternative to a surge pipe in the ves­sel, a pipe antenna system outside the ves­sel in a bypass tube is also possible. The surge and bypass tubes must generally be made of metal. For plastic tubes, a closed, conductive jacket is always required. When using a metal tube with plastic inner coating, make sure that the thickness of the coating is minimal (approx. 2 … 4 mm).
Align the sensor so that the type label lies on the same axis as the tube holes or the tube connection openings. The polarisation of the radar signals enables a considerably stabler measurement with this alignment.
= 1.6 up to
r
When mounting a VEGAPULS 41 sensor on a bypass tube (e.g. on a previous floating or displacer unit), the radar sensor should be placed approx. 300 mm or more from the max. level.
For products with small dielectric constants (< 4), a much longer bypass tube than would otherwise be required by the lower tube connection should be used. Products with small dielectric constants are partly pen­etrated by the radar signals, allowing the tube bottom to produce a stronger echo than the product (when the bypass tube is nearly empty). By extending the tube downward, some liquid remains at the bottom even when the vessel is completely empty.
Type label
> 300 mm
100 %
0 %
Tube flange system as bypass tube
300 ... 800 mm
If enough liquid (300 … 800 mm) remains in the blind lower end of the tube, the portion of the signal that penetrates the liquid and re­flects from the tube bottom is sufficiently damped - the sensor can then easily distin­guish it from the echo of the liquid surface. A deflection plate located at the bottom of a vertical pipe has a similar function. It deflects signals that reach the tube bottom into the standard connection opening.
27292-EN-041227
VEGAPULS 41 – Profibus PA 17
Connections to the bypass tube
The connections to the bypass tubes must be fashioned in such a way that only minimal reflections are caused by the walls of the connecting tubes. This is especially important for the breather connection in the upper part of the tube. Observe the following points:
• Use small openings for the connection.
• The diameter of the connecting tubes should not exceed 1/3 of the bypass diam­eter.
• The tube connections must not protrude into the bypass tube.
• Large welding beads in the tubes should be avoided.
• Additional connections to the bypass tube are more suitable if they lie on the same plane as the upper and lower vessel con­nection (above each other or displaced by 180°).
Optimum connection to the bypass tube
Mounting and installation
Tube connection protrudes
Additional connection in the bypass tube in one plane
Use of guide tubes
In case of very rough inner surfaces in exist­ing bypass tubes (e.g. due to corrosion), large connecting tube openings as well as bypass tubes with more than 100 mm inner diameter, the use of a guide tube inside the existing bypass tube is recommended. This reduces the noise level and increases meas­urement reliability considerably. The flange of the guide tube can be easily mounted as a sandwich flange between vessel and sensor flange.
Welding beads too large
18 VEGAPULS 41 – Profibus PA
27292-EN-041227
Mounting and installation
Seals on tube connections and tube ex­tensions
Microwaves are very sensitive to gaps in flange connections. If connections are made without proper care, distinct false echoes as well as increased signal noise can result. Observe the following points:
• The applied seal should correspond to the tube inner diameter.
• If possible, conductive seals such as con­ductive PTFE or graphite should be used.
• There should be as few seal positions as possible in the guide tube.
Flange connections on bypass tubes
Adhesive products
In non-adhesive or slightly adhesive prod­ucts, use a surge pipe with a nominal width of e.g. 50 mm. VEGAPULS 41 radar sensors with 26 GHz technology are for the most part insensitive to buildup in the measuring tube. However, buildup should not block the meas­uring tube.
Standpipe measurement of inhomoge­neous products
ø 5...15
homogeneous liquids
inhomogeneous liquids
Openings in a surge pipe for mixing of inhomogene­ous products
If you want to measure inhomogeneous prod­ucts or stratified products in a surge pipe, it must have holes, elongated holes or slots. These openings ensure that the liquid is mixed and corresponds to the liquid in the vessel.
The more inhomogeneous the measured product, the closer the openings should be spaced.
slightly inhomogeneous liquids
ø 5...15
For products with somewhat heavier buildup, the use of a DN 80 to max. DN 100 standpipe or surge pipe can make the measurement possible despite buildup. But with extremely adhesive products, measurement in a stand-
Due to radar signal polarisation, the holes or slots must be positioned in two rows offset by 180°. The radar sensor must then be mounted so that the type label of the sensor is aligned with the rows of holes.
pipe is not possible at all.
Every wider slot causes a false echo. The slots should therefore not exceed a width of 10 mm in order to keep the signal noise level to a minimum. Round slot ends are better than rectangular ones.
27292-EN-041227
VEGAPULS 41 – Profibus PA 19
Mounting and installation
Type label
ø 5...15
Row of holes in one axis with the type label
Surge pipe with ball valve
If a ball valve is mounted in the surge pipe, maintenance and servicing can be carried out without opening the vessel (e.g. if it con­tains liquid gas or toxic products).
Ball valve
> 300 mm
Vent hole
ø50
Deflector
Tube antenna system with ball valve cutoff in measur­ing tube
A prerequisite for trouble-free operation is a ball valve throat that corresponds to the pipe diameter and provides a flush surface with the pipe inner wall. The valve must not have any rough edges or constrictions in its chan­nel. The distance to the sensor flange should be min. 300 mm.
Guidelines for standpipe construction
The measuring pipe must be smooth inside (average roughness Rz ≤ 30). Use stainless steel tubing (drawn or welded lengthwise) for construction of the measuring pipe. Extend the measuring pipe to the required length with welding neck flanges or with connecting sleeves. Make sure that no shoulders or projections are created during welding. Be­fore welding, join pipe and flange with their inner surfaces flush and exactly fitting.
Avoid welding through the pipe wall. The pipe must remain smooth inside. Roughness or welding beads on the inner surfaces must be carefully removed and burnished, as they cause false echoes and encourage product adhesion.
If the vessel contains agitated products, fasten the measuring pipe to the vessel bot­tom. Provide additional fastenings for longer measuring pipes.
In products with lower dielectric values (< 4), a part of the radar signal penetrates the medium. If the vessel is nearly empty, echoes are generated by both the product and the vessel bottom. In some cases, the vessel bottom generates a stronger echo than the product surface. If a deflector is installed below the open end of the measuring tube, the radar signals are scattered and pre­vented from reaching the vessel bottom. This ensures that, in nearly empty vessels or with products of low dielectric value, the product delivers a more distinct echo than the vessel bottom.
Due to the deflector, the useful echo (and thus the measured value) remains clearly detectable in a nearly empty vessel, and the 0 % level can be reliably measured.
27292-EN-041227
20 VEGAPULS 41 – Profibus PA
0 %
Mounting and installation
The standpipe or surge pipe can be equipped with a quadrant pipe at the end instead of a deflector. The quadrant pipe reflects the radar signals that penetrate the medium diffusely to the side and reduces strong echoes from the tube end or the ves­sel bottom.
Connecting sleeve
Welding neck flanges
Deburr the holes
Deflector
0 %
100 %
150...500
~45û
2,9...6
5...10
2,9
ø 51,2
Welding of the connect­ing sleeves
0,0...0,4
Welding of the welding neck flanges
1,5...2
0,0...0,4
Meas. pipe fastening
0 %
Quadrant pipe on the bypass tube end
Vessel bottom
Quadrant pipe on the standpipe end
27292-EN-041227
VEGAPULS 41 – Profibus PA 21
Mounting and installation

2.4 False echoes

The radar sensor must be selected must be installed at a location where no installations or inflowing material cross the radar impulses. The following examples and instructions show the most frequent measuring problems and how to avoid them.
Vessel protrusions
Vessel forms with flat protrusions can make measurement very difficult due to their strong false echoes. Baffles mounted above these flat protrusions scatter the false echoes and guarantee a reliable measurement.
Correct Incorrect
Vessel protrusions (ledge)
Intake pipes, i.e. for the mixing of materials ­with a flat surface directed towards the sen­sor - should be covered with a sloping shield that will scatter false echoes.
Vessel installations
Vessel installations such as, e.g. ladders, often cause false echoes. Make sure when planning your measuring location that the radar signals have free access to the meas­ured product.
Correct Incorrect
Ladder
Vessel installations
Ladder
Struts
Struts, like other vessel installations, can cause strong false echoes that are superim­posed on the useful echoes. Small shields effectively hinder a direct false echo reflec­tion. These false echoes are scattered and diffused in the area and are then filtered out as "echo noise“ by the measuring electronics.
Correct Incorrect
Correct Incorrect
Shields
Struts
Vessel protrusions (intake pipe)
22 VEGAPULS 41 – Profibus PA
27292-EN-041227
Mounting and installation
Inflowing material
Do not mount the instrument in or above the filling stream. Ensure that you detect the product surface and not the inflowing mate­rial.
Correct
Inflowing material
Incorrect
Buildup
If the sensor is mounted too close to the vessel wall, buildup and adhesions of the measured product to the vessel wall cause false echoes. Position the sensor at a suffi­cient distance from the vessel wall. Please also note chapter "3.1 General installation instructions“.
Correct
Incorrect
Strong product movements
Strong turbulence in the vessel, e.g. caused by powerful stirrers or strong chemical reac­tions, can seriously interfere with the meas­urement. A surge or bypass tube (see illustration) of sufficient size generally allows reliable and problem-free measurement even if strong turbulence occurs in the vessel, provided there is no buildup of the product in the tube.
Correct
Strong product movements
Incorrect
100 %
75 %
0 %
Buildup
27292-EN-041227
VEGAPULS 41 – Profibus PA 23
Mounting and installation

2.5 Common installation mistakes

Socket piece too long
If the sensor is mounted in a socket exten­sion that is too long, strong false echoes arise which interfere with the measurement. Make sure that the horn antenna projects out of the socket piece.
Correct
Reference plane
Flange antenna: Correct and unfavourable socket length
Wrong orientation to the product
Weak measuring signals are caused if the sensor is not directly pointed at the product surface. Orient the sensor axis perpendicu­larly to the product surface to achieve opti­mum measuring results.
Unfavourable
Parabolic effects on dished or arched vessel tops
Round or parabolic tank tops act like a para­bolic mirror on the radar signals. If the radar sensor is placed at the focal point of such a parabolic tank top, the sensor receives am­plified false echoes. The optimum mounting location is generally in the range of half the vessel radius from the centre.
Correct
Unfavourable
Unfavourable
Correct Incorrect
Ladder
Ladder
Mounting on a vessel with parabolic tank top
Sensor too close to the vessel wall
If the radar sensor is mounted too close to the vessel wall, strong false echoes can be caused. Buildup, rivets, screws or weld joints superimpose their echoes onto the product
Direct sensor vertically to the product surface
24 VEGAPULS 41 – Profibus PA
i.e. useful echo. Please ensure a sufficient distance from the sensor to the vessel wall.
27292-EN-041227
Mounting and installation
If there are good reflection conditions (liquid medium, no installations), we recommend locating the sensor where there is no vessel wall within the inner emission cone. For prod­ucts in less favourable reflection environ­ments, it is a good idea to also keep the outer emission cone free of interfering installations. Note chapter "3.1 General installation instruc­tions“.
Foam generation
Conductive foam is penetrated by radar signals to different depths and generates a number of individual (bubble) echoes. In addition, the signals are damped in foam, which is comparable to the damping of heat radiation by Styrofoam. Thick, dense, creamy and conductive foam can cause incorrect measurements.
Conductive foam
Liquid
Standpipe installation mistakes
Pipe antenna without ventilation hole
Pipe antenna systems must be provided with a ventilation hole on the upper end of the surge pipe. If this hole is absent, incorrect measurements will result.
Correct
Pipe antenna: The surge pipe open to the bottom must have a ventilation or equalisation hole on top
Wrong polarisation direction
When measuring in a surge pipe, especially if there are holes or slots for mixing in the tube, it is important that the radar sensor is aligned with the rows of holes.
The two rows of holes (displaced by 180°) of the measuring tube must be in the same plane as the polarisation direction of the radar signals. The polarisation direction is always in the same plane as the type label.
Incorrect
Foam generation
Provide preventative measures against foam
Correct
Type label
Incorrect
or measure in a bypass tube. Check, if nec­essary, the possibility of using a different measurement technology, e.g. capacitive electrodes or hydrostatic pressure transmit­ters. In many cases, VEGAPULS 54 radar sensors with 5.8 GHz operating frequency achieve considerably better and more reli­able measuring results in foam applications than series 40 sensors with 26 GHz technol­ogy.
27292-EN-041227
VEGAPULS 41 – Profibus PA 25
VEGAPULS on the surge pipe: The sensor type plate must be aligned with the rows of holes

3 Electrical connection

Electrical connection
3.1 Connection – Connection cable – Screening
Safety information – Qualified person­nel
Instruments which are not operated with protective low voltage or DC voltage must only be connected by qualified personnel. This also applies to the configuration of measuring systems planned for Ex environ­ment.
As a rule, do all connecting work in the com­plete absence of line voltage. Always switch off the power supply before you carry out connecting work on the radar sensors. Pro­tect yourself and the instruments.
Connection cables and bus configura­tion
Note the Profibus specification. The connec­tion cables must be specified for the ex­pected operating temperatures in your systems and must have an outer diameter of 6 … 12 mm, to ensure the seal effect of the cable entry on the sensor.
For power supply and bus communication, a two-wire cable acc. to the Profibus specifica­tion (up to max. 2.5 mm of conductor) is used. The electrical connec­tion on the sensor is made by spring-loaded terminals.
In a laboratory set-up, a Profibus system will also work with standard, unshielded two-wire cable. In practice, however, an automation network and bus system can only be pro­tected reliably against electromagnetic inter­ference by using screened cable. Acc. to the Profibus specification (IEC 1158-2), screened and twisted cables are prescribed.
2
cross-section area
All participants are connected in one line (serially). At the beginning and end points of a segment, the bus is terminated by an ac­tive bus termination. On the DP bus level, most participants already have a bus termi­nation implemented. With more than 32 par­ticipants on the DP level, a so-called repeater must be used to open and combine another DP level with a max. of 32 additional partici­pants. On the PA bus branch of the segment coupler, the PA radar sensors also work with a max. of 32 participants (Ex max. 10 partici­pants).
A PA sensor can work only in conjunction with a Profibus DP system, to which a Profibus PA subsystem is connected. A PA Profibus par­ticipant must consume at least 10 mA of sup­ply current.
Connection cable and cable length
Connection cables must correspond to the Profibus specification and the FISCO model. The sensor cable must be in conformity with the values of the reference cable acc. to IEC 61158-2:
2
0.8 mm
; R
= 44 Ω/km;
Z
31.25kHz
C
asymmetric
The max. cable length first of all depends on the transmission speed: up to 32 kbit/s: 1900 m Prup to 32 kbit/s: 1900 m Pr
up to 32 kbit/s: 1900 m Pr
up to 32 kbit/s: 1900 m Prup to 32 kbit/s: 1900 m Pr up to 94 kbit/s: 1200 m Profibus DP up to 188 kbit/s: 1000 m Profibus DP up to 500 kbit/s: 500 m Profibus DP up to 1500 kbit/s: 200 m Profibus DP up to 12000 kbit/s: 100 m Profibus DP
DCmax.
= 80 … 120 ; damping = 3 dB/km;
= 2 nF/km.
ofibus Pofibus P
ofibus P
ofibus Pofibus P
AA
A
AA
27292-EN-041227
26 VEGAPULS 41 – Profibus PA
Electrical connection
The distributed resistance of the cable, in conjunction with the output voltage of the segment coupler and the current requirement (VEGAPULS 10 mA) or the voltage require­ment (VEGAPULS 9 V) of the sensors, deter­mines the max. cable length.
In a practical application of a PA bus branch, the max. length of the cable is also deter­mined (beside the required supply voltage and max. current consumption of all partici­pants on the PA bus branch) by the structure and the type of segment coupler used.
The cable length results from the sum of all cable sections and the length of all stubs. The length of the individual stubs must not exceed the following lengths: 1 … 12 stubs 120 m (Ex: 30 m) 13 … 18 stubs 60 m (Ex: 30 m) 19 … 24 stubs 30 m (Ex: 30 m)
More than 24 stubs are not permitted, whereby each branch longer than 1.2 m is counted as a stub. The total length of the cable must not exceed 1900 m (in Ex version 1000 m).
Ground terminal
The electronics housings of the sensors have a protective insulation. The ground terminal in the electronics housing is galvanically con­nected with the metallic process connection. For sensors with a plastic thread as process fitting, the sensor must be grounded through a ground connection to the exterior ground terminal.
Screening
„Electromagnetic pollution“ caused by elec­tronic actuators, energy cables and transmit­ting systems has become so pervasive that shielding for normal two-wire bus cable is usually a necessity. According to the Profibus specification, the screening should be grounded on both ends. To avoid potential equalisation currents, a potential equalisation system must be provided in addition to the screening.
According to the specification, we recom­mend the use of twisted and screened two­wire cable, e.g.: SINEC 6XV1 830-5AH10 (Siemens), SINEC L26XV1 830-35H10 (Sie­mens), 3079A (Belden).
Alternatively, when grounding at both ends in non-Ex areas, the cable shielding can be connected on one ground side (in the switch­ing cabinet) via an Y capacitor
1)
to ground potential. Make sure that the ground connec­tion has the lowest possible resistance (foun­dation, plate or mains earth).
Profibus PA in Ex environment
When used in Ex area, the PA bus (including all connected instruments) must be configured as intrinsically safe protection class „i“. Four-wire instruments requiring separate supply must at least have an intrin­sically safe PA connection. VEGA sensors for PA Ex environment are generally „ia two-wire instruments“.
1)
max. 10 nF, e.g. voltage resistance 1500 V,
27292-EN-041227
VEGAPULS 41 – Profibus PA 27
ceramic
Electrical connection
In the so-called Fieldbus Intrinsically Safe Concept (FISCO), the boundary conditions for an Ex safe bus configuration have been laid down. Therein the participants and the bus cables with their electrical data have been determined, ensuring that the linking of these components always meets Ex require­ments. A more time-consuming Ex calculation is therefore not necessary. You can build your Ex bus according to the IEC standard 1158-2.
The Ex segment coupler delivers a controlled power supply to the PA bus. It acts as source in the PA branch. All other compo­nents (field instruments and bus terminators) are only consumers. A field instrument must consume at least 10 mA. Ideally, an individual sensor should not consume more than 10 mA, so that the number of instruments can be as large as possible.
VEGA PA sensors, whether Ex or non-Ex, consume a constant current of 10 mA. Ac­cording to the Profibus specification, this is the minimum participant current. With VEGA sensors, it is therefore possible to connect 10 sensors (also in Ex environment) even with a limited energy supply from the Ex segment couplers.
Watch out for potential losses
Due to potential losses, grounding on both ends without a potential equalisation system is not allowed in Ex applications. If an instru­ment is used in hazardous areas, the re­quired regulations, conformity and type approval certificates for systems in Ex areas must be noted (e.g. DIN 0165). Please also note the approval documents (as well as the enclosed safety data sheet) that come with each Ex sensor.
Electrical data of the cables
R
DC
No. of A in Z cores mm
2
31.25kHz
C in Damping Screen nF/km
SINEC 6XV1 44 Ω/km 2 0.75 100 Ω < 90 < 3 dB/km Cu braiding 830-5AH10 +/- 20 39 kHz (Siemens)
SINEC L26XV1 44 Ω/km 2 0.75 100 Ω < 90 < 3 dB/km Cu braiding 830-35H10 +/- 20 39 kHz (Siemens)
3079A 105 /km 2 0.32 150 29.5 < 3 dB/km Foil (Belden) 39 kHz
28 VEGAPULS 41 – Profibus PA
27292-EN-041227
Electrical connection

3.2 Sensor address

In a Profibus system composed of Profibus DP and Profibus PA subsystem, each partici­pant must have a unique address. Each participant, whether master or slave, is accessed by means of its own address in the bus system. The address of a partici­pant, whether on DP or PA level, should be assigned before connecting to the bus, be­cause an address can be used only once. If an address is used twice, bus interference will result.
The address of a radar sensor can be set in two ways:
- with the adjustment software VVO (software addressing) or
- with the DIP switch block in the sensor (hardware addressing).
VEGA Profibus sensors are delivered with the address set at 126 (all DIP switches to „ON“). Remember, in a Profibus system there are max. 126 participants possible. When the DIP switch is set to address 126 (or higher), the address can be adjusted with the adjust­ment software VVO, the adjustment module MINICOM or another configuration tool (e.g. PDM). However, there can be only one sen­sor on the bus with address 126 (delivery status) during address assignment via soft­ware. For that reason, hardware addressing (DIP switch) before connection to the bus is recommended.
Hardware addressing
The DIP switches generate an address number in the binary system. This means that, from right to left (ascending), any switch represents a number twice as high as the previous switch on the right. The corre­sponding number in the decimal system results from the sum of all switches set to „ON“. In the illustration you see the decimal number that corresponds to each individual DIP switch.
DIP switch 8 corresponds to the number 128, switch 1 corresponds to the number 1 and switch 3 corresponds to the decimal number
4.
1
2
8765 4
128
64
32
Example 1
The switches 3, 5 and 7 are set to „ON“. The address is then: DIP switch 3 to „ON“ means 4 DIP switch 5 to „ON“ means 16 DIP switch 7 to „ON“ means 64
The sum is: 4 + 16 + 64 = Address 84
3
1
2
4
8
16
ON
1
2
8765 4
64
64 + 16 + 4 = 84
27292-EN-041227
VEGAPULS 41 – Profibus PA 29
3
16
4
Electrical connection
Example 2
You want to set address 27. 16 + 8 + 2 + 1 = 27
You must set the DIP switches 5 = 16 4 = 8 2 = 2 1 = 1 to „ON“.
Example 3
You want to set address 99 64 + 32 + 2 + 1 = 99
You must set the DIP switches 7 = 64 6 = 32 2 = 2 1 = 1 to „ON.
Software addressing
The DIP switches must be set to an address of 126 … 255, i.e.
- either all DIP switches are set to „ON“, corresponding to address 255 (delivery status)
OFF
1
2
64
3
ON
8765 4
32
16
1
2
3
1
2
4
8
8765 4 Addr.
- or only DIP switch 8 is set to „ON“, corre­sponding to address 128.
128
Of course, software addressing is also pos­sible if the switches 7 … 2 are set to „ON“ (address 126).
The adjustment of the address with software VVO is described in chapter „5.2 Adjustment with VVO“ under the heading „Software ad­dressing“ or in chapter „5.3 Sensor adjust­ment with the adjustment module MINICOM“.
30 VEGAPULS 41 – Profibus PA
27292-EN-041227
Electrical connection
ESC
OK

3.3 Connecting the sensor

After mounting the sensor at the measure­ment location according to the instructions in chapter "3 Mounting and installation“, loosen the closing screw on top of the sensor. The sensor lid with the optional indication display can then be opened. Unscrew the sleeve nut and slip it over the connection cable (after removing about 10 cm of insulation). The sleeve nut of the cable entry has a self-lock­ing ratchet that prevents it from opening on its own.
Version with aluminium housing
Power supply and Profibus signal
+
To the indicating instrument in the sensor lid or to the external indicating instrument VEGADIS 50
M20 x 1.5 (diameter of the connection cable 6…9 mm)
Now insert the cable through the cable entry into the sensor. Screw the sleeve nut back onto the cable entry and clamp the stripped wires of the cable into the proper terminal positions.
The terminals hold the wire without a screw. Press the white opening levers with a small screwdriver and insert the copper core of the connection cable into the terminal opening. Check the hold of the individual wires in the terminals by lightly pulling on them.
Version with plastic housing
To the display in the lid or the external indicating instrument
Power supply and Profibus signal
+-
M20 x 1.5 (diameter of the connection cable 6…9 mm)
1
2
3
8 7654
+1 2- 5 6 7 8
Addr.
Bus
Display
ON
Spring-loaded terminals (max. 2.5 mm cross-section)
2
wire
+1 2- 5678
Addr.
Bus
Display
ON
1
2
3
87654
Opening tabs
ESC
-
+
OK
Pluggable adjustment module MINICOM
Tank 1 m (d)
12.345
ESC
+
-
OK
27292-EN-041227
VEGAPULS 41 – Profibus PA 31

3.4 Connecting the external indicating instrument

Loosen the four screws of the housing lid on VEGADIS 50. The connection procedure can be facilitated by fixing the housing cover during connec­tion work with one or two screws on the right of the housing.
OUTPUT (to the sensor)
3
2
1
4
5
8
6
7
Adjustment module
VEGADIS 50
Tank 1 m (d)
12.345
Electrical connection
ESC
+
-
OK
Power supply and digital meas. signal
-
+
8 7654
+1 2- 5 6 7 8
Addr.
Bus
Tank 1 m (d)
12.345
DISPLAY (in the lid of the indicating instrument)
1
2
3
Display
ON
ESC
+
-
OK
Screws
32 VEGAPULS 41 – Profibus PA
27292-EN-041227
Types and versions

3.5 Bus configuration

The type of radar sensor you use depends on your process requirements and mounting conditions, as well as on the requirements of your control, regulative, or process manage­ment system.
VEGAPULS 42, 44 and 45 Profibus radar sensors are sensors for use in Profibus PA environment. Profile 3 has been implemented in the sensors. A measuring system consists of one or several sensors, one or several segment couplers and one DP master com­puter, such as e.g. an S7 PLC with Profibus interface or a process management system with Profibus DP-Master-Slot. The processing unit (e.g. the PLC) evaluates the level-propor­tional, digital measuring signals in a number of evaluation routines and puts them to use process-specifically.
On the following four pages you will see schematic illustrations of the bus configura­tion.
The automation system as Master-Class 1 takes over bus control completely. It reads out all signals cyclically and, if necessary, gives instructions to the participants (e.g. sensors). Beside this, additional master sys­tems (e.g. visualisation systems or adjust­ment tools) can be connected to the DP bus. These systems operate as so-called Master­Class 2 participants. Like the Master-Class 1 system, they can read out signals, give in­structions and operate in the acyclical mode.
A DP bus does not allow power supply via signal cable, whereas the PA bus does. Both, DP and PA, require at a minimum a screened two-wire cable. The DP bus can additionally have up to 8 cores (screened), of which some can be supply cables (see also „Instal­lation Guides PA + DP“ of the Profibus User Organisation (PNO).
Each participant on the bus mast have a unique address. The addressing covers both bus levels. A Profibus DP network can have max. 126 participants on the PA level. In practice, each Master-Class 1 computer gets address 1 and the Master-Class 2 computer address 10 … 20. As a rule, the slaves or participants get the addresses 21 … 126. On the Profibus PA network segment, max. 32 sensors can be connected on one PA seg­ment coupler.
Ex environment
In Ex environment, intrinsically safe (EEx ia) PA sensors are used with Ex segment cou­plers. Generally, the number of PA sensors on a segment coupler (Ex or non-Ex) de­pends on the current requirement of the sensors and on the current supplied by the segment coupler. Segment couplers for EEx ia environment provide 90 … 110 mA. The number of sensors results from the sum of:
- the basic current intake of all sensors
- plus 9 mA communication signal
- plus the leakage currents of all sensors
- plus a recommended current reserve (approx. 10 mA)
The min. basic current has been set at 10 mA according to the Profibus specification. VEGA Profibus radar sensors constantly consume a basic current of 10 mA and oper­ate without leakage current requirements, so that in Ex environment, up to max. ten VEGA sensors can be operated on one segment coupler.
27292-EN-041227
VEGAPULS 41 – Profibus PA 33
Profibus PA sensors on Profibus network
1
Types and versions
Master-Class 1
Bus terminator
3...9
Profibus PA (31,25 kBit/s)
Profibus DP
21
Profibus interface card
RS 232
22...54
3
RS 485
10
Master-Class 2
Segment coupler
Bus terminator
2
22
23
24
53
54
VEGACONNECT 3
PA segment on segment coupler: 1 … 32 sensors on one two-wire cable (Ex: 10 sensors)
34 VEGAPULS 41 – Profibus PA
27292-EN-041227
Types and versions
Profibus DP segment level 1 … 126 participants including all DP and PA participants. Due to segment couplers and PA segments in the com­plete system on PA and DP level, the transmission rate is determined by the slowest coupler/participant.
Bus terminator
3...9
55
M
Segment coupler
56...88
Bus terminator
2
Profibus PA
3~M
3...9
89
90
Bus terminator
2
56
57
87
88
PA segment: 1 … 32 sensors on one two-wire cable (Ex: 10 sensors)
27292-EN-041227
VEGAPULS 41 – Profibus PA 35
Profibus PA sensors with 4 … 20 mA sensors on Profibus network
1
Types and versions
Master-Class 1
Bus terminator
VEGALOG
Profibus PA (31,25 kBit)
3~M
3…9
Profibus DP
Profibus interface card
21
3
RS 485
22
10
Master-Class 2
VEGACONNECT 3
4
RS 232
1
2
3
5
11
12
4
1 … 15 PA sensors per two-wire cable
13
15
14
with independent address zone (Ex: 10 sensors)
36 VEGAPULS 41 – Profibus PA
27292-EN-041227
Types and versions
Profibus DP segment level 1 … 126 participants including all DP and PA participants. Up to 12 MBit/s transmission rate on DP level. In the PA segments, 31.25 kBit/s transmission rate.
VEGACONNECT 3
4 … 20 mA (HART )
2
4
4
4
2
2
2
Profibus PA (31,25 kBit)
3…9
23
M
3…9
24
25
VEGALOG
VBUS
Outputs
2
2
2
2
®
2
2
2
2
2
0/4…20 mA
0…10 V
2
VBUS
Bus termi­nator
Profibus PA: 1 … 15 sensors per two-wire cable (Ex: 10 sensors) with independent address zone
VBUS: 1 … 15 sensors per two­wire cable Exd: also 15 Ex ia: 5 sensors
27292-EN-041227
VEGAPULS 41 – Profibus PA 37
Set-up

4 Set-up

4.1 Adjustment media

In chapter „1.4 Adjustment“ the Profibus adjustment structure was briefly explained and the adjustment media for VEGA Profibus sensors were shown. All VEGA Profibus sensors operate in profile 3 and can be ad­justed with:
- the adjustment software PACT
- the Siemens software PDM in conjunction with an EDD (Electronic-Device-Descrip­tion)
- the adjustment module MINICOM in the sensor.
Adjustment with the PC
The adjustment software PACT user-friendly adjustment of VEGA Profibus PA sensors. All functions and options of sensor adjustment are accessible. The program runs under Windows Profibus-Master-Class 2 interface card on Profibus DP level as Master-Class 2 tool. The adjustment software accesses the VEGA PA sensors via the DP bus, the segment coupler and the PA bus.
®
on a PC with a
ware
ware
TM
TM
enables

4.2 Adjusting the sensor with the adjustment module MINICOM

Tank 1 m (d)
12.345
Beside the PC, you can use the small, de­tachable adjustment module MINICOM to carry out the adjustments directly in the sen­sor.
With the adjustment module MINICOM, only the sensor-relevant adjustments such as e.g. scaling of the sensor display, operating range, meas. conditions, sensor display scaling or false echo storage are possible. Not possible, however, are all adjustment steps relating to configuration, conditioning and signal processing (configuration of the inputs and outputs, linearisation curves, simulation …). This is only possible with the PC.
The adjustment module MINICOM is oper­ated with 6 keys. A small display shows you apart from the measured value, a short mes­sage on the menu item or the value entered in a menu.
ESC
+
-
OK
Adjustment with PDM
The sensors can be adjusted completely with PDM. However, some convenient functions and many special features, like e.g. display of an echo curve, are not available. In addi­tion to the PDM software, an EDD (available on request from VEGA) is required for each sensor type. The adjustment instructions for
however, cannot be compared with that of the adjustment program VVO. Nevertheless with the help of the menu schematic for MINICOM you will be able to quickly find your way through the adjustment structure. In time, you might even be able to carry out your adjust­ments with the small module faster and more efficiently than with the PC.
PDM are described in the PDM documenta-
The volume of information of the small display,
tion.
Error codes:
E013 No valid measured value
- Sensor in the warm-up phase
Adjustment with the adjustment module MINICOM
With the adjustment module MINICOM, you adjust the individual sensor directly in the sensor or in the external indicating instrument VEGADIS 50. The adjustment module MINICOM enables (with the 6-key adjustment field with text display) all essential functions of parameter setting and adjustment.
38 VEGAPULS 41 – Profibus PA
- Loss of the useful echo E017 Adjustment span too small E036 Sensor program not operating
- Sensor must be reprogrammed
(service)
- Failure message also appears
during programming
E040 Hardware failure, electronics
defective
27292-EN-041227
Set-up
Adjustment steps
On the following pages you will find the com­plete menu schematic of the adjustment mod­ule MINICOM. Set up the sensor in the numbered sequence:
1.Address
2. Measuring tube adjustments (only for measurement in a standpipe)
3. Operating range
4. Adjustment
5. Conditioning
6. Meas. conditions
7. False echo storage (only required when errors occur during operation)
8. Indication of the useful and noise level
9.Outputs
Outputs Short explanations to the setup steps 1 … 9 follow.
1. Address
Choose a free bus address with the DIP switch (see chapter „3.2 Sensor address“).
2. Measurement in a standpipe
Adjustment is only necessary if the sensor is mounted in a standpipe (surge or bypass tube). When measuring in a standpipe, do a sounding of the distance and correct the measured value display (which can differ several percent from the sounded value) according to the sounding. From then on, the sensor corrects the running time shift of the radar signal and displays the correct value of the level in the standpipe (measuring tube).
3. Operating range
Without special adjustment, the operating range corresponds to the measuring range. It is generally advantageous to set the oper­ating range slightly larger (approx. 5 %) than for measuring range.
Example: Min./max. adjustment: 1.270 … 5.850 m; adjust operating range to approx.
1.000 … 6.000 m.
4. Adjustment
Max.
Min.
Under the menu item " the sensor of the measuring range it should operate in.
You can carry out the adjustment with or without medium. Generally, you will carry out the adjustment without medium, as you can then adjust without a filling/emptying cycle.
Adjustment without medium
(adjustment independent of the level)
Key Display indication
OK
OK
OK
OK
100 % (1.270 m) correspond to 1200 liters
Span (4.58 m)
0 % (5.850 m) corresponds to 45 liters
Adjustment
Sensor
m(d)
4.700
Para­meter
Adjust­ment
w.o medium
Ad­just­ment in
m(d)
(min. adjustment)
“ you inform
27292-EN-041227
VEGAPULS 41 – Profibus PA 39
Set-up
+
The distance indication flashes and you can choose "feet“ and "m“.
OK
+
or
Confirm the adjustment with "
OK
“.
Ad­just­ment in
With "
+
“ and "–“ you adjust the
m(d)
0.0%
at
m (d)
XX.XXX
percentage value for the min. value (example 0.0 %).
The entered percentage value is written in the sensor and the
OK
min. distance value corres­ponding to that percentage value flashes.
+
or
With the " assign a level distance (ex-
+
“ or "–“ key you can
ample 5.85 m) to the previ­ously adjusted percentage value. If you do not know the distance, you have to do a sounding.
OK
The adjusted product dis­tance is written in the sensor and the display stops flash­ing.
You thereby adjusted the lower product dis­tance as well as the percentage filling value corresponding to the lower product distance.
Note:
For level detection outside the operating range, the operating range must be corrected accord­ingly in the menu "
ing range“
.
Sensor optimisation/Operat-
100.0%
at
m (d)
XX.XXX
(max. adjustment)
Now you make the max. adjustment (upper product distance) (example: 100 % and
1.270 m product distance). First, enter the percentage value and then the product dis­tance corresponding to that percentage value.
Note:
The difference between the adjustment val­ues of the lower product distance and the upper product distance should be as large as possible, preferably at 0 % and 100 %. If the values are very close together, e.g. lower product distance at 40 % (3.102 m) and upper product distance at 45 % (3.331 m), the measurement will be less accurate. A characteristic curve is generated from the two points. Even the smallest deviations between actual product distance and en­tered product distance will considerably influence the slope of the characteristic curve. If the adjustment points are too close together, small errors inflate to considerably larger ones when the 0 % or the 100 % value is outputted.
Adjustment with medium
with medium
XXX.X
Max. adjust at %
XXX.X
Min. adjust at %
Fill the vessel e.g. to 10 % and enter 10 % in the menu "
Min. adjust
“ with the "+“ and "–“ keys. Then fill the vessel, e.g. to 80 % or 100 % and enter 80 % or 100 % in the menu "
Max. adjust
“ with the "+“ and "–“ keys.
5. Conditioning
Signal condit ioning
Scal ing
0 %
100 %
Deci-
prop.
corres
corres ponds
XXXX
mal point
888.8
Conditioning
ponds
XXXX
Under the menu item " assign a product distance at 0 % and at 100 % filling. Then, you enter the parameter and the physical unit as well as the decimal point. Enter in the menu window "
0 % corresponds
Unit
to
Mass
Kg
“, you
27292-EN-041227
40 VEGAPULS 41 – Profibus PA
Set-up
the numerical value of the 0 % filling. In the example of the adjustment with the PC and the adjustment software VVO, this would be 45 for 45 liters.
• Confirm with "
OK
“.
With the "—>“ key you switch to the 100 % menu. Enter here the numerical value of your parameter corresponding to a 100 % filling. In the example 1200 for 1200 liters.
• Confirm with "
OK
“.
If necessary, choose a decimal point. How­ever, note that only max. 4 digits can be displayed. In the menu "
prop. to
“ you choose the physical quantity (mass, volume, dis­tance…) and in the menu "
Unit
“ the physical
unit (kg, l, ft3, gal, m3 …).
Linearisation:
A linear correlation between the percentage
Adjust ment
Signal condit ioning
Scal ing
Lin. curve
Linear
Integra tion time
0 s
to record the false echoes and save them in an internal database. The sensor electronics treats these (false) echoes differently from the useful echoes and filters them out.
8. Useful level, noise level
In the menu
Ampl.:
XX dB
S-N:
XX
you get important information on the signal quality of the product echo. The greater the "S-N“ value, the more reliable the measure­ment (menu plan MINICOM).
Ampl.: means amplitude of the level echo in
S-N: means Signal-Noise, i.e. the useful
The greater the "S-N“ value (difference be­tween the amplitudes of the useful signal level and the noise level), the better the measure­ment: > 50 dB Measurement excellent 40 … 50 dB Measurement very good 20 … 40 dB Measurement good 10 … 20 dB Measurement satisfactory 5 … 10 dB Measurement sufficient < 5 dB Measurement poor
dB
dB (useful level)
level minus the level of the back­ground noise
value of the product distance and percent­age value of the filling volume has been pre­set. With the menu "Lin. curve“ you can choose between linear, spherical tank and cylindrical tank. The generation of a custom-
Example:
Ampl. = 68 dB S-N = 53 dB
68 dB – 53 dB = 15 dB
ized linearisation curve is only possible with the PC and the adjustment program VVO.
This means that the noise level is only 68 dB – 53 dB = 15 dB.
6. Meas. conditions
(see menu schematic)
7. False echo storage
A false echo storage is always useful when unavoidable false echo sources (e.g. struts) must be minimised. By creating a false echo memory, you authorise the sensor electronics
27292-EN-041227
VEGAPULS 41 – Profibus PA 41
A 15 dB noise level and a 53 dB signal differ­ence yield a high degree of measurement reliability.
9. Outputs
Under the menu "Outputs“ you determine, for example, whether the current output should be inverted, or which unit of measurement should be shown on the sensor display.
Menu schematic for the adjustment module MINICOM
Sensor
m(d)
4.700
Para­meter
Sensor opti­mize
Meas. enviro nment
PULS 42
After switching on, the sensor
P
type and the software version are
3.00
displayed for a few seconds.
Confi­gura­tion
Sensor Tag
Verdam
pfer
1.
Sensor addr.
(•–/ –•)
126
Set-up
Sensor address:
• Sensor address here from 1 … 126 only adjustable, if the DIP switch in the sensor is set to address greater than/equal to 126.
• For adjustment of the sensor with the DIP switch to address 128, switch 8 must be set to „ON“.
Meas. unit
m (d)
3.
Opera­ting range
Begin
4. 5.
Adjust ment
w.out medium
m (d)
0.50
End
m (d)
6.00
6. 2.
Meas. condit ions
Condit ion
solid
Condit ion
liquid
Fast change
No
Fast change
No
with medium
High dust level No
Agitat ed sur face No
Foam­ing prod. No
Large angle repose No
Multi ple echo No
Low DK pro­duct No
Signal condit ioning
Sca­ling
Meas­ure in tube
No
Lin. curve
Linear
Multi ple echo No
Integr ation time
Tube diamet
0 s
Correc tion Now!
Measur ing in tube
mm (d)
OK?
Correc tion factor
2.50 %
50
Correc tion Now!
OK ?
0.0 %
at
m (d)
XX.XXX
100.0%
at
m (d)
XX.XXX
Min­adjust at %
XXX.X
Max­adjust at %
XXX.X
0 % corres ponds
XXXX
100 % corres ponds
XXXX
Deci­mal point
888.8
Prop. to
Mass
Unit
Kg
Adjust ment in
m(d)
42 VEGAPULS 41 – Profibus PA
27292-EN-041227
Set-up
With these keys you move in the menu field to the left, right, top and bottom
ESC
7. 8.
9.
act. dist.
m (d)
4.700
Update
Meas. dist.
m (d)
X.XX
Update Now!
Lear­ning!
OK?
False echo memory
Create new
Meas. dist.
m (d)
X.XX
Create new
OK?
Lear­ning!
Out­puts
Add’l func­tions
Info
Ampl.:
XX dB
S-N:
XX
dB
Delete
Delete Now!
OK?
Delet­ing!
Simulation:Simulation:
Simulation:
Simulation:Simulation:
Sensor Tag
Sensor
One hour after the last simulation adjustment, the sensor returns automatically to normal operating mode.
Simu­lation
Sensor type
PULS42 P
Reset to de fault
Reset Now!
OK?
Reset ing!
Serial no.
1094 0213
Act. dist. m
X,XX
Lan­guage
Eng­lish
Softw.
Softw.
vers.
date
3.00
15.09. 1999
Act.
max.
dist.
range
m (d)
m (d)
4.700
7.000
Menu items in bolt print provide sensor and measured value information and cannot be modified in this position.
OK
Sensor addr.
(•–/ –•)
Ampl.:
XX dB
S-N:
XX
126
dB
PA output
Fail-
Prop.
ure
to
mode
di-
Value
stance
27292-EN-041227
Sensor displ.
Prop. to
di­stance
Simu­lation Now!
Simu­lation
XXX.X
OK ?
High dust level No
%
Fast change
Ye s
Light grey menu fields are only displayed if required (dependent on the adjustments in other menus).
White menu items can be modified with the "+“ or "–“ key and saved with the "OK“ key .
VEGAPULS 41 – Profibus PA 43

6 Diagnostics

Diagnostics

6.1 Simulation

To simulate a certain filling, you can call up the function „Simulation“ on the adjustment module MINICOM or in the adjustment soft­ware PACT
With this function, you simulate a real vessel filling. Please note that connected instru-
ware
TM
.
Simulation with PACT
If you start the simulation mode with PAC T
TM
ware
on the PC, the simulated level is
outputted until you quit the simulation mode.
Simulation with MINICOM
If you start the simulation mode on the adjust­ment module MINICOM, the sensor returns to standard operating mode after one hour.
ware
TM
ments, such as e.g. a PLC, react acc. to their adjustments and will probably activate alarms or system functions.

6.2 Error codes

Error codes Fault rectification
E013 No valid measured value Message is displayed during the warm-up
- Sensor in the warm-up phase phase.
- Loss of the useful echo If the message remains, a false echo storage (with the adjustment software on the PC - see „Echo curve“ under „Sensor optimisation“) must be carried out together with a modification of mounting location and orientation to achieve the lowest possible false echo background.
E017 Adjustment span too small Carry out a readjustment.
Make sure that the difference between min. and max. adjustment is at least 10 mm.
E036 Sensor software does not run Sensor requires a software update (service).
Message appears during a software update.
E040 Hardware failure/Electronics defec- Check all connection cables.
tive Contact our service department.
E113 Communication conflict Service or sensor exchange
44 VEGAPULS 41 – Profibus PA
27292-EN-041227
Technical data

7 Technical data

7.1 Technical data

Power supply
Supply voltage 9 … 32 V DC Supply voltage dependent on
output voltage U segment coupler (see PA specification) e.g.
- non-Ex 22 V DC (max. 32 sensors on one
- E x 15 V DC (max. 10 sensors on one
Current consumption constantly 10 mA (no leakage current output) Resistance of the signal cable dependent on segment coupler, see
Unit and measuring range
Unit distance between product surface and
Measuring range 0 … 10 m
Output signal
Signal output digital output signal in two-wire technology
Resistance/Load of the signal cable dependent on the segment coupler (see
Integration time (adjustable) 0 … 999 seconds
of the
O
two-wire cable)
two-wire cable)
technical data of the segment coupler and Profibus specification
process fitting (e.g. lower flange side of the sensor)
(PA): The digital output signal (meas. signal) is superimposed on the power supply and further processed in the PLC or processing system, max. 32 sensors on one two-wire cable (Ex: max. 10)
technical data of the segment coupler) and the existing bus cable (see Profibus­cable parameters)
Two-wire technology: The digital output signal (meas. signal) is superimposed on the power supply and further processed in the signal conditioning instrument or in the processing system. Up to 15 sensors can be operated on one two-wire cable (in Ex area up to 5 sensors).
Four-wire technology: Separate power supply. The digital output signal (meas. signal) is transmitted in a cable separate from the power supply.
27292-EN-041227
VEGAPULS 41 – Profibus PA 45
Technical data
Measured value display (optional)
Liquid crystal display
- in the sensor scalable measured value output as a graph and as a number
- external, powered by the sensor scalable measured value output as a graph and as a number. Measured value display can be mounted up to 25 m away from the sensor (max. cable length 25 m).
Adjustment
- PC and adjustment software VEGA Visual Operating
- adjustment module MINICOM
- SIMATIC-PDM
-PACTware
Accuracy
TM
1)
(typical values under reference conditions, all statements relate to the nominal range)
Characteristics linear Accuracy see diagram
10 mm
5 mm
-5 mm
0,5 m 10 m
-10 mm
Resolution in general max. 1 mm Resolution of the output signal 1 mm or 0.005 %
Ambient conditions
Ambient temperature on the housing -40°C … +80°C Process temperature (flange temp.) -40°C … +130°C Storage and transport temperature -60°C … +80°C Vessel pressure -1 … 3 bar (-100 … 300 kPa) Protection IP 66 and IP 67 Protection class
- two-wire sensor II
- four-wire sensor I
Overvoltage category III
46 VEGAPULS 41 – Profibus PA
27292-EN-041227
Technical data
Characteristics
1)
(typical values under reference conditions, all statements relate to the nominal measuring range)
Min. span between
full and empty > 10 mm (recommended > 50 mm) Frequency 26 GHz Intervals
- two-wire sensor 0.6 s
- four-wire sensor 0.5 s Beam angle (at -3 dB) 22° Adjustment time (response time)
2)
> 1 s (depending on parameter setting)
Influence of the process temperature at 0 bar not measurable;
at 5 bar 0.004 %/10 °K;
at 40 bar 0.03 %/10 °K Influence of the process pressure 0.0265 %/bar Emitted radar power (average) 0.717 µW Received average emitted power
3)
- distance 1 m 0.4 … 3.2 nW per cm² (0.4 … 3.2 x 10-9W/cm²)
- distance 5 m 0.02 … 0.13 nW per cm²
Ex technical data
Comprehensive data in separate approval documents
Connection cables
Two-wire sensors power supply and signal via one two-wire
cable Four-wire sensor power supply and signal separate Electrical connection
- cable entry for Aluminium and plastic housing: one cable entry (four-wire: two cable entries) and spring-loaded terminal connection up to max. 2.5 mm
2
wire cross-section
- plug connection optional for plastic housing: four-pole, polarity reversal-proof screw connection (four-wire: two plug connections)
Cable entry
- ia terminal compartment 1 … 2 x M20 x 1.5 (cable-ø 5 … 9 mm) or 1 … 2 x ½“ NPT EEx d (cable-ø 3.1 … 8.7 mm or 0.12 … 0.34 inch)
- Exd terminal compartment
(pressure-tight encapsulated) 1 x½“ NPT EEx d (cable-ø 3.1 … 8.7 mm or
0.12 … 0.34 inch)
Ground connection max. 4 mm² Intermediate housing between
process flange and housing 1.4435
1)
Similar to DIN 16 086, reference conditions acc. to IEC 770, e.g. temperature 15 °C … 35 °C; moisture 45 % … 75 %; pressure 860 mbar … 1060 mbar
2)
The adjustment time (also actuating time, response time or adjustment period) is the time required by the sensor to output the correct level (with max. 10% deviation) after a sudden level change.
3)
Average emitted power (electromagnetic energy) received by a body per cm² directly in front of the antenna. The received emitted power depends on the antenna version and the distance.
27292-EN-041227
VEGAPULS 41 – Profibus PA 47
Technical data
Materials
Housing PBT (Valox) or
Aluminium die-casting (GD-AlSi 10 Mg) Housing with Exd version Aluminium chill casting (GK-AlSi 7 Mg) Process flange 2.25901 (PVDF) Wetted materials
(antenna) 2.25901 (PVDF) and TFM
TM
-PTFE
Weights
Weights dependent on the housing materials and Ex concepts.
VEGAPULS 41 1.8 … 2.5 kg
WHG approvals
VEGAPULS 41 radar sensors are approved as part of an overfill protection system for stationary vessels storing water-endangering liquids.
CE conformity
VEGAPULS 41 radar sensors meet the protective regulations of EMC (89/336/EWG), NSR (73/23/EWG) and R & TTE regulation (1999/5/EC). Conformity has been judged acc. to the following standards:
EN 300 683 - 1: 1997 EN 300 440 - 1: 1995 IETS 300-440 Expert opinion No. 0043052-02/SEE, Notified Body
No. 0499 EMC Emission/Susceptibility EN 61 326: 1997/A1: 1998 ATEX EN 50 020: 1994
EN 50 018: 1994
EN 50 014: 1997 NSR EN 61 010 - 1: 1993
48 VEGAPULS 41 – Profibus PA
27292-EN-041227
Technical data

7.2 Approvals

When radar sensors are used in Ex areas or on ships, the instruments must be suitable and approved for the explosion zones and applications. The suitability is checked by the approval authorities and is certified in approval docu­ments.
Please note the attached approval docu­ments when using a sensor in Ex area.
Test and approval authorities
VEGAPULS radar sensors are tested and approved by the following monitoring, test and approval authorities:
- PTB
(Physikalisch Technische Bundesanstalt ­Physical Technical Approval Authority)
- FM
(Factory Mutual Research)
- ABS
(American Bureau of Shipping)
- LRS
(Lloyds Register of Shipping)
- GL
(German Lloyd)
- CSA
(Canadian Standards Association)
27292-EN-041227
VEGAPULS 41 – Profibus PA 49
Technical data

7.3 Data format of the output signal

Byte4 Byte3 Byte2 Byte1 Byte0
Status Measured value (IEEE-754 format, see below)
Status byte:
The status byte corresponds to Profile 3.0 „Profibus PA Profile for Process Control Devices“ coded. The status „Measured value OK“ is coded as 80 (hex) (Bit7 = 1, Bit 6 … 0 = 0).
Measured value:
The measured value is transmitted as 32 Bit floating point number in the IEEE-754 format.
Byte n Byte n+1
Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit
7654321076543210
VZ 27262524232221202-12-22-32-42-52-62
Sign
Exponent Mantissa
Byte n+2 Byte n+3
Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit
7654321076543210
2-82-92
-102-112-122-132-142-152-162-172-182-192-202-212-222-23
-7
Mantissa Mantissa
Formula: Meas. value = (-1)VZ • 2
Examples: 41 70 00 00 (hex) = 0100 0001 0111 0000 0000 0000 0000 0000 (bin)
Meas. value = (-1)
= 1 • 2
(Exponent - 127)
0
(130 - 127)
• 2
3
• (1 + 0.5 + 0.25 + 0.125)
• (1 + Mantissa)
• (1 + 2-1 + 2-2 + 2-3)
= 1 • 8 • 1.875 = 15.0
50 VEGAPULS 41 – Profibus PA
27292-EN-041227
Technical data

7.4 Dimensions

External indicating instrument VEGADIS 50
85 38
ø5
48
10
Pg 13,5
Mounting on carrier rail 35 x 7.5 acc. to EN 50 022 or flat screwed
118
108
135
Flange dimensions acc. to ANSI (RF)
d
2
f
d
1
k D
82
b
Note:
The diameter of the connection cable should be min. 5 mm and max. 9 mm. Otherwise the seal effect of the cable entry
85
would not be ensured.
D=outer flange diameter
b = flange thickness k = diameter of hole circle d
= seal ledge diameter
1
f = seal ledge thickness
1
/16" = approx. 1.6 mm
d
= diameter of holes
2
Size Flange Seal ledge Holes
Db k d1No. d
2
2" 150 psi 152.4 20.7 120.7 91.9 4 19.1 3" 150 psi 190.5 25.5 152.4 127.0 4 19.1 4" 150 psi 228.6 25.5 190.5 157.2 8 19.1 6" 150 psi 279.4 27.0 241.3 215.9 8 22.4
Adjustment module MINICOM
ESC
+
-
Tank 1 m (d)
12.345
67,5
74
27292-EN-041227
VEGAPULS 41 – Profibus PA 51
32,5
OK
Adjustment module for insertion into sensors or into the external indicating instrument VEGADIS 50
Sensor dimensions
Technical data
PBT Aluminium
201
165
1
0
˚
322
182
M20x1,5
125
101
0 7 3
5 0 2
SW 60
83
185
G1½ A
1½" NPT
Aluminium with Exd terminal compartment
215
25
116
0 7 3
M20x1,5
135
130
20
215
185
5 0 2
116
25
½" NPT
52 VEGAPULS 41 – Profibus PA
27292-EN-041227
Technical data

7.5 CE conformity declaration

27292-EN-041227
VEGAPULS 41 – Profibus PA 53
Technical data
54 VEGAPULS 41 – Profibus PA
27292-EN-041227
Technical data
27292-EN-041227
VEGAPULS 41 – Profibus PA 55
VEGA Grieshaber KG Am Hohenstein 113 77761 Schiltach Germany Phone (07836) 50-0 Fax (07836) 50-201 E-Mail info@de.vega.com
www.vega.com
ISO 9001
All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing sys­tems correspond to the information available at the time of printing.
Technical data subject to alterations
27292-EN-041227
Loading...