1 Area of applicability
These safety instructions apply to VEGADIS 176 Ex (DIS176.ICSI) according to the Certicate of
Conformity IECEx PTB 15.0002 X (certicate number on the type label) and to all instruments with
the number of the safety instruction (50016) on the type label.
2 General information
The VEGADIS 176 Ex (DIS176.ICSI) is an intrinsically safe, scalable, digital indicating instrument
without external energy for installation in hazardous areas of zone 1. It is looped into intrinsically
safe 4 … 20 mA circuits. The voltage supply for power supply of the electronics is taken from the
4 … 20 mA circuit.
The VEGADIS 176 Ex (DIS176.ICSI) is suitable for use in hazardous atmospheres of all combustible materials of explosion group IIA, IIB and IIC for applications requiring EPL-Gb instruments.
If the VEGADIS 176 Ex (DIS176.ICSI) are installed and operated in hazardous areas, the general Ex
installation regulations IEC 60079-14 as well as these safety instructions must be observed.
The operating instructions as well as the installation regulations or standards that apply for explosion protection of electrical systems must generally be observed.
The installation of explosion-endangered systems must always be carried out by qualied person-
nel.
EPL-Gb instrument
The VEGADIS 176 Ex (DIS176.ICSI) is installed in hazardous areas requiring an EPL-Gb instrument
of category 2G (EPL-Gb). The VEGADIS 176 Ex (DIS176.ICSI) can be looped in an intrinsically safe
circuit of EPL-Ga instruments.
3 Technical data
Electrical connection values
VEGADIS 176 Ex (DIS176.ICSI)
Voltage supply: (terminals + and - or +
and LED or + and auxiliary terminal Π)
Temperature classAmbient temperature
T6-40 … +60 °C
Ui ≤ 30 V DC
Ii ≤ 200 mA
Pi ≤ 900 mW
Li = 35.1 µH
Ci = negligibly small
50016-EN-150325
VEGADIS 176 Ex (DIS176.ICSI)
3
Page 4
Hazardous area
Zone 0, 1, 2
EPL-Ga, Gb, Gc
e.g. sensor
Connection without background lighting
Hazardous area
Zone 1, 2
EPL-Gb, Gc
Local potential equalization
Local potential equalization
Safe area
Associated, intrinsically safe
+
instrument with max.
electrical connection
–
values (see tables)
LED
–
+
–
I
Y
+
+
–
1
LED
–
+
–
I
Y
+
+
–
1
LED
–
+
+
–
I
2
Y
Connectionwith background lighting
LED
–
+
–
I
Y
+
+
–
1
LED
–
+
–
I
Y
+
+
–
1
LED
–
+
+
–
I
2
Y
1 Transmitter power supply 2 Current source 4...20mA
4 Installation/construction
No potential equalisation on the complete circuit between VEGADIS 176 Ex (DIS176.ICSI) and the
sensor(s), associated instrument required.
The required isolation voltage is > 500 V AC.
For applications requiring instruments of EPL-Gb, the intrinsically safe power supply and signal
circuit can correspond to protection class ia or ib. For connection to a circuit with protection class ib,
the ignition protection type identication is Ex ib IIC T6.
For applications requiring EPL-Ga instruments, the intrinsically safe power supply and signal circuit
50016-EN-150325
4
VEGADIS 176 Ex (DIS176.ICSI)
Page 5
must be in conformity with protection class ia.
The permitted category of the intrinsically safe circuit for the sensor depends on the ame proong
of the associated instrument used.
5 Grounding/Potential equalization
In order to avoid the danger of electrostatic charging of the housing, the VEGADIS 176 Ex (DIS176.
ICSI), used as EPL-Gb instrument, must be electrostatically connected to the local potential equalisation (transfer resistance ≤ 1 MΩ), e.g. via the ground terminal.
6 Material resistance
The VEGADIS 176 Ex (DIS176.ICSI) must only be used in media against which the materials of the
wetted parts are suciently resistant.
7 Impact and friction sparks
The VEGADIS 176 Ex (DIS176.ICSI) in light metal versions (e.g. aluminium/titanium/zircon) must be
mounted in such a way that sparks from impact and friction between light metals and steel (except
stainless steel, if the presence of rust particles can be excluded) cannot occur.
50016-EN-150325
VEGADIS 176 Ex (DIS176.ICSI)
5
Page 6
Notes
50016-EN-150325
6
VEGADIS 176 Ex (DIS176.ICSI)
Page 7
Notes
50016-EN-150325
VEGADIS 176 Ex (DIS176.ICSI)
7