FOR NEW REFRIGERANT R410A
Installation Manual
Branch Pipes
Model RBC-TWP 30•50
Toshiba Carrier Corporation
For “Cautions on Safety”, please read “Cautions on Safety” contained in the
installation manual of the air conditioner and follow the precautions.
Important
Read the following cautions carefully before installing your air conditioner.
The two indoor units of TOSHIBA simultaneous twin packaged air conditioning system are the same units.
Set and install the main and sub units taking the installation site into consideration. (Be certain to use the new
refrigerant R410A in the indoor units.) The indoor unit connected to the remote control switch will be the
main unit.
1. Installation
● These branch pipes are for new HFC refrigerant R410A that does not destroy the ozone layer.
1) Compared with the previous refrigerants, pressure of Refrigerant R410A is about 1.6 times higher and is
easily affected by impurities such as moisture, oxidized films and oil. The new refrigerant also requires
new refrigerating machine oil. Make certain to prevent mixing of moisture, rubbish, old refrigerant and
refrigerating machine oil into the refrigeration cycle of the air conditioner with the new refrigerant when
installing the air conditioner.
2) The sizes of the air conditioner charge port and connection part of the installation tool are different from
those of the previous refrigerant to prevent mixing of the refrigerant and refrigerating machine oil. A
special tool dedicated to the new refrigerant R410A is need. (For the complete information, read the
installation manual for air conditioner outdoor units.)
3) Use clean, new pipe fittings when connecting the connection pipe. Install the pipe carefully avoiding
mixing of moisture and rubbish.
2. Wiring
1) The remote control switch cannot be connected to both of the two indoor units (main and sub units).
Connect it only to the indoor unit that will become the main indoor unit (Unit A). Connecting the remote
control switch to the sub indoor unit will cause malfunction.
1
3. Refrigerant Piping (Branch piping system is used for refrigerant piping)
1) Compared with R22, pressure of R410A is about 1.6 times. Unless the piping is installed correctly, gas
leak may be caused during operation such as pressure boosting. Conduct a leak test of the pipe connecting
parts correctly.
2) In case the actual length of the piping exceeds the standard piping length, accurately add the refrigerant
referring to Additional Refrigerant Amount .
3) Thermal insulation materials for the branch pipes are not supplied as accessories. Provide thermal
insulation correctly using fitting covers or other materials sold on the market. For further information,
read Refrigerant Piping and Piping Thermal Insulation .
Improper thermal insulation work will result in a failure and a claim.
Components
The following parts are supplied as accessories of the branch pipes. Check them when opening the carton
box.
Part Quantity Shape Use
Installation Instructions 1 This booklet For installation works
Gas side 1
Branch pipe
Liquid side 1
Refrigerant Piping
Tolerance of Pipe Length Tolerance of Pipe Head
Indoor Unit B
Outdoor unit
Indoor Unit A
Branch pipe
Model
(RAV-)
SM1100AT-E
SM1400AT-E
Pipe Length (One Direction) Height Defference
Full length
L+a or
L+b
Below 50m
(actual length)
Branch
piping
a, b
Below
15m
(actual
length)
Difference
of branch
piping
length
b-a, or a-b
Below 10m
For refrigerant pipe branching
and collection
Outdoor Unit -
Indoor Unit
Outdoor
Unit
Installed
Above
Indoor
Unit
Below
30m
H
Outdoor
Unit
Installed
Below
Indoor Unit
Below 15m
Between
Indoor
Units
∆h
Below
0.5m
Remarks
Less
than 10
bends
Refrigerant Piping
Cautions
When planning a layout for Units A and B, comply with the following:
1. The lengths after branching (“a” and “b”) should be equal if feasible. Install Units A and B so that the
difference of the branching lengths becomes less than 10m if the lengths cannot be equal due to the branch
pipe position.
2. Install Units A and B on the same level. If Units A and B cannot be installed on the same level, the
difference in level should be limited to 0.5m or less.
3. Be certain to install Units A and B in the same room. Units A and B cannot be operated independently each
other.
2
Piping Materials and Sizes
● Use copper tube of Type 1220 in JIS H
3300 (Copper and copper alloy
seamless pipes and tubes) with
40mg/10m or less in the amount of oil
stuck on inner walls of pipe and
0.8mm in pipe wall thickness for
diameters 6.4, 9.5 and 12.7mm and
1.0mm, for diameter 15.9mm. Never
Pipe
side
Model
(RAV-)
side
Liquid
side
In parentheses ( ) are wall thickness [unit: mm]
SH1100AT-E SH1400AT-E
Main piping Ø15.9 (1.0) Gas
Branch piping Ø 12.7 (0.8) Ø 15.9 (1.0)
Main piping Ø 9.5 (0.8)
Branch piping Ø 6.4 (0.8) Ø 9.5 (0.8)
use pipes of thin wall thickness such as
0.7mm.
Branch Pipe
Now the refrigerant pipe is installed using branch pipes supplied as accessories.
● Bend and adjust the refrigerant piping so that the branch pipes and pipe after branching become horizontal.
● Fix the branch pipes onto a wall in a ceiling or onto a column.
● Provide a straight pipe longer than 500mm in length as the main piping of the branches.
Horizontal
Inclination
Horizontal
Inclination
500mm or more
Air Purging
For the complete information, read the installation instructions for outdoor units of air conditioner.
● Purge air using a vacuum pump.
Additional Refrigerant Amount
Cautions
● Be certain to write the additional refrigerant amount, pipe length (actual length), head and other
specification on the nameplate put on the outdoor unit for recording.
● Seal the correct amount of additional refrigerant in the system.
3