Toshiba RBC-TRP100E INSTALLATION MANUAL

AIR CONDITIONER (SPLIT TYPE)
Installation manual
Branch kit 1:3
Model name:
RBC-TRP100E
Installation manual Air conditioner
Manuel d’installation Climatiseur
Manuale di installazione Condizionatore d’aria
Manual de instalación Aire acondicionado
Manual de Instalação Ar condicionado (Tipo split) 116
Installatiehandleiding Airconditioner
Εγχειρίδιο εγκατάστασης Κλιματιστικό
Руководство по установке Кондиционер воздуха
(сплит-система)
(Split type) 1
(Type split) 24
(Tipo split) 70
(Tipo split) 93
(Gesplitst type) 139
(Τύπ ου Split) 162
185
English
Français
Deutsch
Italiano
Español
Português
Nederlands
Ελληνικά
Русский
Montaj Kılavuzu
(Split tip) 208
Klima
Türkçe
Branch Kit 1:3
Please read this Installation Manual carefully before installing the Air Conditioner.
This Manual describes the installation method of the indoor unit.
For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit.
ADOPTION OF NEW REFRIGERANT
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.
Contents
1 PRECAUTIONS FOR SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 COMPONENT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 WIRING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5 PIPING HEAT INSULATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6 TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7 DELIVERY TO CUSTOMER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
1EN
Branch Kit 1:3
1 PRECAUTIONS FOR SAFETY
The three indoor units of TOSHIBA simultaneous triple packaged air conditioning system are the same units. Set and install the header and follower units taking the installation site into consideration. (Be certain to use the new refrigerant R410A in the indoor units.) The indoor unit connected to the remote controller will be the header unit.
Ensure that all Local, National and International regulations are satisfied.
Read indoor, outdoor installation manual and this manual carefully before Installation.
The precautions described below include the important items regarding safety. Observe them without fail.
After the installation work, perform a trial operation to check for any problem. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
Turn off the main power supply switch (or breaker) before the unit maintenance.
Ask the customer to keep the Installation Manual together with the Owner’s Manual.
WARNING
Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner.
Inappropriate installation may result in water leakage, electric shock or fire.
Turn off the main power supply switch or breaker before attempting any electrical work.
Make sure all power switches are off. Failure to do so may cause electric shock.
Connect the connecting cable correctly.
If the connecting cable is connected in a wrong way, electric parts may be damaged.
When moving the air conditioner for the installation into another place, be very careful not to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle.
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high and it resultantly causes pipe burst and injuries on persons.
Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlock switches.
Exposure of unit to water or other moisture before installation may cause a short­circuit of electrical parts.
Do not store it in a wet basement or expose to rain or water.
After unpacking the units, examine them carefully if there are possible damage.
Do not install in a place that might increase the vibration of the unit.
To avoid personal injury (with sharp edges), be careful when handling parts.
Perform installation work properly according to the Installation Manual.
Inappropriate installation may result in water leakage, electric shock or fire.
When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level.
EN
2
EN
Branch Kit 1:3
Install the air conditioner securely in a location where the base can sustain the weight adequately.
Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might generate.
Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.
Use the specified cables for wiring connect the terminals securely fix. To prevent external forces applied to the terminals from affecting the terminals.
Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.
If a combustible gas leaks, and stays around the unit, a fire may occur.
3EN
Branch Kit 1:3
CAUTION
New Refrigerant Air conditioner Installation
THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the outdoor unit and installation tools are changed from those for the conventional refrigerant.
Accordingly the exclusive tools are required for the new refrigerant. (R410A)
For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter. Moreover, do not use the existing piping because there are problems with pressure-resistance force and impurity in it.
The three indoor units of TOSHIBA simultaneous triple packaged air conditioning system are the same units.
Set and install the header and follower units taking the installation site into consideration. (Be certain to use the new refrigerant R410A in the indoor units.) The indoor unit connected to the remote controller will be the header unit.
EN
Wiring
TO DISCONNECT THE APPLIANCE FROM MAIN POWER SUPPLY.
This appliance must be connected to the main supply by means of a switch with a contact separation of at least 3 mm.
The remote controller cannot be connected to all the three indoor units (header and follower units). Connect it only to the indoor unit that will become the header indoor unit (Unit A). Connecting the remote controller to the follower indoor unit will cause malfunction.
Refrigerant Piping (Branch piping system is used for refrigerant piping)
Compared with R22, pressure of R410A is about 1.6 times. Unless the piping is installed correctly, gas leak may be caused during operation such as pressure boosting. Conduct a leak test of the pipe connecting parts correctly.
In case the actual length of the piping exceeds the standard piping length, accurately add the refrigerant referring to Additional Refrigerant Amount.
Heat insulation materials for the branch pipes are not supplied as accessories. Provide heat insulation correctly using fitting covers or other materials sold on the market. For further information, read Refrigerant Piping and Piping heat Insulation on this manual. Improper heat insulation work will result in a failure and a claim.
4
EN
Branch Kit 1:3
2 COMPONENT
The following parts are supplied as accessories of the branch pipes. Check them when opening the carton box.
Distributor Part name Quantity
Liquid side Gas side Different-size joint
Ø9.5
Ø9.5
Ø9.5
Ø12.7
QTY:1
Ø15.9
Ø15.9
Ø15.9
Ø25.4
QTY:1
Liquid pipe
Gas pipe
Branch pipe heat insulator 2 Installation Manual 1
Ø12.7 Ø9.5 1 Ø9.5 Ø6.4 3 Ø25.4 Ø28.6 1 Ø25.4 Ø15.9 1 Ø15.9 Ø12.7 3
5EN
Branch Kit 1:3
3 REFRIGERANT PIPING
Tolerance of pipe length and Height difference
<RAV-SM1603AT(Z)(ZG)-E>
Indoor unit A
Branch pipeBranch pipe
a
Indoor unit C
Indoor unit B
Branch pipe
b
c
H
Distributor
L
Main pipe
Total length (L + a, L + b, L + c) 50 m
Pipe length
(one way)
Refrigerant
pipe
specifications
Height
difference
Number of bent portions 10 or less
Between indoor
unit and outdoor
Branch pipe length (a, b, c) 15 m
Maximum difference between indoor units
unit
(|a - b|, |b - c|, |c - a|)
Between indoor units (Δh) 0.5 m
When outdoor unit is higher (H) 30 m
When outdoor unit is lower (H) 30 m
10 m
EN
6
EN
Branch Kit 1:3
<RAV-SM2244AT, SM2804AT series>
Indoor unit A
Branch pipeBranch pipe
a
Indoor unit C
Indoor unit B
Branch pipe
b
c
H
Distributor
L
Main pipe
Total length (L + a, L + b, L + c) 70 m
Pipe length
(one way)
Refrigerant
pipe
specifications
Height
difference
Number of bent portions 10 or less
Between indoor
unit and outdoor
Branch pipe length (a, b, c) 20 m
Maximum difference between indoor units
unit
(|a - b|, |b - c|, |c - a|)
Between indoor units (Δh) 0.5 m
When outdoor unit is higher (H) 30 m
When outdoor unit is lower (H) 30 m
10 m
CAUTION
When planning a layout for Units A, B and C, comply with the following:
1. The lengths after branching (“a” and “b”, “b” and “c”, “a” and “c”) should be equal if feasible. Install Units A, B and C so that the difference of the branching lengths becomes less than 10 m if the lengths cannot be equal due to the branch pipe position.
2. Install Units A, B and C on the same level. If Units A, B and C cannot be installed on the same level, the difference in level should be limited to 0.5 m or less.
7EN