Toshiba RBC-RD2-PE Owner Manual

Refrigerant Detection System
Installation Instructions
Détecteur de Réfrigérant
Instructions d’Installation
Kältemitteldetektor
Installationsanleitung
Detector de Refrigerante
Rivelatore del frigorigeno
Istruzioni per l’installazione
Koelmiddeldetector
Installatievoorschriften
RBC-RD1-PE RBC-RD2-PE
1402110301
HFC R407C
33
Contents
Sommaire
Inhalt
Contenido
Indice
Inhoud
GB
F
D
E
I
NL
Caution and Components List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Model Differentiation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Unit Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-10
Electrical Wiring – RD1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-12
Electrical Wiring – RD2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13-14
It is important to read this manual carefully before starting the installation.
Avertissement et Liste des Composants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Spécifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Différenciation des Modèles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Réglage de l’Unité . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17-18
Vue d’ensemble du Système . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19-21
Câblage Electrique – RD1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22-23
Câblage Electrique – RD2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24-25
Il est important de lire ce manuel attentivement avant de procéder à l’installation.
Warnhinweise und Bauteileliste . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Technische Daten . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Modellunterscheidung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Gerätekonfiguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28-29
Systemübersicht . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30-32
Verdrahtung – RD1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33-34
Verdrahtung – RD2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35-36
Bitte diese Anleitung vor Beginn der Installation aufmerksam durchlesen.
Aviso y Lista de Componentes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Especificaciones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Diferenciación de Modelos . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Configuración de la Unidad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39-40
Resumen del Sistema . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41-43
Cableado Eléctrico – RD1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44-45
Cableado Eléctrico – RD2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46-47
Es importante leer atentamente este manual antes de realizar la instalación.
Avvertenze ed Elenco dei componenti . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Caratteristiche tecniche . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Differenziazione dei modelli . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Predisposizione dell’apparecchio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50-51
Panoramica del sistema . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52-54
Circuito elettrico – RD1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55-56
Circuito elettrico – RD2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57-58
È importante leggere attentamente questo manuale prima di iniziare l’installazione.
Waarschuwings- en Onderdelenlijst . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Specificaties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Modeldifferentiatie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Setup van de Installatie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61-62
Systeemoverzicht . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63-65
Elektrische Bedrading – RD1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66-67
Elektrische Bedrading – RD2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68-69
Het is belangrijk om deze handleiding aandachtig te lezen alvorens de installatie aan te vangen.
4
Caution
4
GB
This equipment should only be installed by suitably trained operatives.
Incorrect installation by unqualified personnel may result in the refrigerant detector units not operating correctly, electric shock or fire.
In all cases ensure safe working practices are followed. Observe precautions for persons in the vicinity of the works.
Ensure that all local, national and international regulations are satisfied.
Before commencing the installation, ensure all relevant electrical supplies are isolated.
Carefully unpack the equipment and check for damage or shortages. Please report any damage or shortages immediately.
If solenoid valves are to be used, ensure they are designed to be used with high/low temperatures and pressures of the refrigerant and they are capable of bi-directional flow.
The refrigerant detector units comply with the following EC Directives: 73/23/EEC – Low Voltage Directive 89/336/EEC – Electro Magnetic Compatibility
Accordingly the refrigerant detector units are designated for use in commercial and industrial environments.
Components List
This manual contains the installation instructions for the Refrigerant Leak
detector units RBC-RD1-PE and RBC-RD2-PE. Please read these instructions
thoroughly before starting the installation work.
RBC-RD1-PE: Control box & screw caps
Remote sensor/audible alarm assembly FCU interface cable Installation instructions Owners manual
RBC-RD2-PE: Control box with integral sensor & screw caps
CDU interface cable Installation instructions Owners manual Mounting bracket Screws x 4
Refrigerant Detector Components:
5
GB
Specifications
ppm ppm ppm
Fault Code
Low
High
Flood
Years
Model RBC-RD1-PE RBC-RD2-PE
Description Remote Sensor & Sounder
Indoor refrigerant detector
Standard
Single
220 - 240
50
300
HFC 407C
Grey
80 (102)
160
55
All RAV AI "4" Series &
MMS indoor units
Refrigerant Type Colour Height (inc glands) Width Depth Compatibility
Phase
Volts
Hz
mA
mm mm mm
Power
Supply
Features RBC-RD1-PE RBC-RD2-PE
N/A 1000 2200
1 type: >4hrs
04
N/A
04 04
Volt free NC relay O/P
240V~ 5A
5 – 7
No
Outdoor refrigerant detector
N/A
Single
220 - 240
50
300
HFC 407C
Grey
80 (102)
160
55
MMS Outdoor units only
250 1000 2200
2 types: < 4hrs & > 4hrs
B6 B5 B6 B6
Volt free NC relay O/P
240V~ 5A
5 - 7
Yes (>80dBA)
Low Level Alarm High Level Alarm Flood Alarm Sensor Failure
Fault Codes
Valve Shutoff (optional) Output Relays Rating Sensor Life Audible Alarm
6
GB
Model Differentiation
There are two models available, the first is RBC-RD1-PE. The RD1 is designed to be installed next to the indoor unit, with the remote sensor and audible alarm located at a low level and preferably under the indoor unit.
The RD1 is designed for use with MMS indoor units and RAV ‘4’ Series AI indoor units only.
The second model is the RBC-RD2-PE. The (RD2) is designed for use in the modular multi outdoor unit. The unit will be located within the compressor housing, and it has an internal sensor.
The RD2 can only be fitted to the MMS outdoor unit.
The functionality of both systems will be covered in indoor & outdoor operation section of this manual.
There are two control PCB’s inside the refrigerant detector, each with jumpers which enable specific functions to be enabled/disabled. The diagrams below show the locations of these jumpers.
Unit Setup
control board
N L
ALARM
BJP
AJP
AI+ sig – mute + buzzer
ABC
JP
Sub PCB
7
GB
Unit Setup
The function of the jumpers are listed below:
From the above the only jumpers which are user selectable are "JP" and "AJP".
JP: If this jumper is removed the indoor unit or outdoor system will not shutdown (hence B6 – indoor, and 04 – outdoor fault codes would not be generated). Removing this jumper is not recommended unless it is critical that the system must remain operating.
AJP: If this jumper is fitted, then the Alarm (Solenoid valve relay) contacts are closed. This is not depended on the unit being powered. The primary reason for this jumper is during commissioning. If valves are fitted, then the air conditioning system can run, even when the detector is not commissioned or powered.
All other jumpers must be fitted as shown in the table for correct system operation.
Jumper RBC-RD1-PE RBC-RD2-PE
A B C
JP AJP BJP
Not Used
Not Present
Not Used
Disable unit shutdown
Close Alarm contacts
Present
Not Used
Present
Not Used
Disable unit shutdown
Close Alarm contacts
Not Present
8
GB
System Overview
A typical RBC-RD1-PE installation would be in a hotel room or office.
The remote sensor assembly should be located low down in the room, for example, the same height as power sockets etc. Also the position of the sensor is important. The recommended position is below the indoor unit or below the refrigerant pipe work to the indoor unit.
To ensure correct operation, the points (listed below) must be followed during installation:
o The maximum height of the sensor from the floor should be 300mm.
o Adequate ventilation must be maintained around the sensor assembly.
o The recommended minimum distance between the sensor assembly and other
objects in the room is 500mm.
o The detector must be mounted where air streams cannot influence the operation of
the detector.
9
System Overview
9
GB
The sensor assembly has been designed to be fitted into any standard flush or surface mount back box. The remote sensor assembly has been built into a standard electrical grid-plate, maximising the number of cover-plates available to the installer.
The main control unit is designed to be located just below the ceiling, beside the indoor unit.
If solenoid valves (optional: to be supplied by the installer) are to be installed, then it is recommended that the valves are located on the outside of the area which the detector is protecting.
Below is a diagram of a typical installation for the RD1.
Isolating solenoid valves positioned in the gas and liquid lines (optional – supplied by installer)
Hotel room
FCU
FCU Interface Cable
Control Unit
Power source 230V~50Hz (from FCU)
Remote sensor/audible alarm interconnecting cable
Metal oxide refrigerant detector.
Low level position
10
GB
System Overview
A standard RBC-RD2-PE installation would be in the compressor housing of the MMS (Modular Multi System) outdoor unit.
As the MMS is designed for up to five outdoor units, it would mean up to five detectors would be required per system.
All the detectors will be connected together in series and connected to the Inverter unit electrical box.
The refrigerant sensor forms an integral part of the control box. Therefore control box must be located within 200mm (maximum height) from the compressor housing base.
If solenoid valves (optional: to be supplied by the installer) are to be installed, then it is recommended that the valves are located on the outside of the outdoor unit, but before the pipe work joins the common refrigeration circuit.
Below is a diagram showing where to locate the control unit in the MMS outdoor.
Using the supplied bracket, unscrew the right hand screw form the compressor mounting base, locate bracket and replace screw into the compressor base. Ensuring the screw is fully tightened.
Fuse
CDU Interface cable (only on inverter)
To solenoid
valves
L1
N
Control Unit
PCB
PCB
11
GB
+
Sig
Buzz
Electrical Wiring – RD1
There are various options when installing a RD1 unit, firstly it can be installed as a stand alone unit. Secondly it can be installed with any AI indoor unit (‘4’ Series and MMS indoors), this will enable fault codes to be generated and the indoor unit can be shut down. Thirdly solenoid valves can also be installed as an optional extra.
Ensure that the control unit is protected with a 1A 240VAC fuse.
The maximum rating of the solenoid relay is 240V~ 5A.
It must be noted that any solenoids valves selected for this application must be capable of operating at a pressure of 33bar and with the flow being bi-directional.
If rear entry is required, Ø16mm holes can be made in the rear of the control box. Centre marks for the holes are provided.
Remote Sensor
Assembly
TOP TOP
PCB
COM
MAKE
Indoor Unit
RAV = CN17 MM = CN21
2 Core
Cable
(Supplied)
Solenoid Valves
(Optional)
Volt Free Relay
Contacts
Max Rating
240V~5A
230V 50Hz 1A Supply
N
ALARM
L
AI+ sig – mute + buzzer
12
GB
Electrical Wiring – RD1
Mount the control box (mounting dimensions on rear of control box) near to the indoor unit. Mount the remote sensor assembly to a standard flush or surface mount pattress low down in the room.
From the remote sensor assembly connect a 6-core cable to the control unit, as shown in the above wiring diagram.
Connect the control unit to a fused (1A 240VAC) power supply using a 3-core cable, the power can be derived from the indoor unit if desired. Please refer to the above wiring diagram.
If the refrigerant detector is to be integrated with either a AI ‘4’ series RAV system or MM system. Then the FCU interface cable (supplied) is required to be connected to the indoor PCB. Please refer to the above wiring diagram.
o If the detector is to be connected to a RAV AI system, then connect the FCU
interface cable to CN17 on the indoor PCB.
o If the detector is to be connected to a MM system, then connect the FCU interface
cable to CN21 on the indoor PCB.
If solenoid valves are to be used, then an additional 2-core cable will be required to connect to the volt free NC relay contacts. The maximum rating of the contacts are 240V @ 5A, if this is not sufficient then an additional power relay or contactor must be used. Please refer to the above wiring diagram.
13
GB
Electrical Wiring – RD2
Mount the RD2 inside the compressor housing as shown in the System Overview section of this manual.
Connect a 3-core supply cable from the control unit to the electrical box on the outdoor unit, please refer to the wiring diagram below. Ensure a 1A fuse is fitted, to protect the control unit.
If only one CDU is used then connect the CDU interface cable from the control unit to the electrical box on the outdoor unit.
o Firstly locate the three ceramic fuses at the top of the electrical box.
o From the top fuse (red cables) remove the thin (AWG20) red cable from the right
side of the fuse, and in its place fit the CDU interface cable with the ring crimp terminal on the end.
o From the thin (AWG20) cable just removed from the fuse, cut off the ring terminal
and strip 5mm of insulation. Place into the crimp butt joint, and crimp firmly.
Fuse
PCB
PCB
L1
N
CDU Interface cable (only on inverter) 2-Core cable (Supplied)
Solenoid Valves
Volt free relay
contacts,
Max rating
240V~5A
No connection
required, as unit uses
internal sensor
CDU Connection Detail
Crimp
(red)
LN
ALARMAI
+ sig – mute + buzzer
14
GB
Electrical Wiring – RD2
If more than one CDU is installed (max 5 – 46HP), then each refrigerant detector must be connected in series to the unit in the inverter CDU. The CDU interface cable is only required in the inverter CDU.
Connect each refrigerant detector using 3-core cable to the L1, N and earth terminals in each CDU. Each detector unit must be protected by a 1A 240VAC fuse.
Connect the AI control cable as shown below:
Then to complete the loop connect the cables to the inverter electrical box, as described on the previous page.
If solenoid valves are to be used, then an additional 2-core cable will be required to connect to the volt free NC relay contacts. The maximum rating of the contacts are 240V @ 5A, if this is not sufficient then an additional power relay or contactor must be used. Please refer to the above wiring diagram.
It must be noted that any solenoids valves selected for this application must be capable of operating at a pressure of 33bar and with the flow being bi-directional.
Connect to Inverter
Electrical Box
CDU #5
(Fix)
CDU #4
(Fix)
CDU #3
(Fix)
CDU #2
(Fix)
CDU #1
(Inv)
AI AI
AI AI AI
15
Avertissement
15
F
Cet équipement doit être installé par des personnes adéquatement formées.
Un
e installation erronée par du personnel non qualifié peut entraîner un mauvais
fonctionnement des détecteurs de réfrigérant, des électrocutions ou des incendies.
En toutes circonstances, s’assurer que les pratiques de travail sûres sont respectées. Suivre les précautions d’usage concernant les personnes situées à proximité des travaux.
S’assurer que toutes les réglementations locales, nationales et internationales sont respectées.
Avant de procéder à l’installation, s’assurer que toutes les alimentations électriques appropriées sont mises hors circuit.
Déballer soigneusement l’équipement et vérifier qu’il n’est pas endommagé et qu’aucune pièce ne manque. Prière de signaler immédiatement tout dommage éventuel ou toute pièce manquante.
Si des électrovannes sont utilisées, s’assurer qu’elles sont conçues pour résister à des températures hautes/basses ainsi qu’aux pressions du réfrigérant et qu’elles peuvent fonctionner en écoulement bidirectionnel.
Les
détecteurs de réfrigérant sont conformes aux Directives CE : 73/23/EEC – Directive Basse Tension 89/336/EEC – Compatibilité Electromagnétique
Par conséquent, les détecteurs de réfrigérant sont désignés pour un usage en milieux commercial et industriel.
Liste des Composants
Ce manuel contient les instructions d’installation pour les Détecteurs de Fuites de
Réfrigérant RBC-RD1-PE et RBC-RD2-PE. Prière de lire ces instructions
attentivement avant de procéder au travail d’installation.
RBC-RD1-PE: Boîte de commande & capuchons de vis
Ensemble de sonde à distance /d’alarme sonore Câble d’interface de FCU Instructions d’installation Mode d’emploi
RBC-RD2-PE: Boîte de commande avec sonde intégrée & capuchons de vis
Câble d’interface de CDU Instructions d’installation Mode d’emploi Support de montage Vis x4
Composants des Détecteurs de Réfrigérant :
16
F
Spécifications
ppm ppm ppm
Bas
Haut
Inondation
Années
Modèle RBC-RD1-PE RBC-RD2-PE
Description
Sonde à distance & Avertisseur sonore
Détecteur de réfrigérant
intérieur
Standard
Mono
220 - 240
50
300
HFC 407C
Gris
80 (102)
160
55
Toutes les Séries RAV AI
"4" & les unités
intérieures MMS
Type de Réfrigérant Couleur Hauteur
(avec presse-étoupe) Largeur
Profondeur Compatibilité
Phase
Volts
Hz
mA
mm
mm mm
Alimentation
Caractéristiques RBC-RD1-PE RBC-RD2-PE
Pas applicable
1000 2200
1 type: >4 h.
04
N/A
04 04
Sortie de relais N.F. à tension
nulle
240V~ 5Amp
5 – 7
Non
Détecteur de réfrigérant
extérieur
Pas applicable
Mono
220 - 240
50
300
HFC 407C
Gris
80 (102)
160
55
Uniquement les unités
extérieures MMS
250 1000 2200
2 types: < 4 h. & > 4 h.
B6 B5 B6 B6
Sortie de relais N.F. à tension
nulle
240V~ 5Amp
5 - 7
Oui (>80dBA)
Alarme de Bas Niveau Alarme de Haut Niveau Alarme d’inondation Panne de Sonde
Codes de Faute
Fermeture de Vanne (en option) Puissance de Sortie des Relais Longévité de la Sonde
Alarme Sonore
Code de Faute
17
F
Différentiation des Modèles
Deux modèles sont disponibles, le premier étant le RBC-RD1-PE. Le RD1 est conçu pour une installation à côté de l’unité intérieure, avec la sonde à distance et l’alarme sonore situées à bas niveau et de préférence sous l’unité intérieure.
Le RD1 est conçu uniquement pour une utilisation avec les unités intérieures MMS et les unités intérieures AI de la Série RAV ‘4’.
Le second modèle est le RBC-RD2-PE. Ce modèle (RD2) est conçu pour une utilisation avec l’unité extérieure Modular Multi. L’unité devra être placée à l’intérieur du carter de compresseur et comprend une sonde interne.
Le RD2 ne peut être monté que sur l’unité extérieure MMS.
La fonctionnalité des deux systèmes sera décrite dans la section sur le fonctionnement intérieur et extérieur de ce manuel.
Il y a deux cartes de circuit imprimé de commande à l’intérieur du détecteur de réfrigérant, chacune avec des cavaliers permettant la mise en/hors service de fonctions spécifiques. Les diagrammes ci-dessous montrent la position de ces cavaliers.
Réglage de l’Unité
carte de commande
N L
ALARM
BJP
AJP
AI+ sig – mute + buzzer
ABC
JP
Carte de Circuit Imprimé Secondaire
18
F
Réglage de l’Unité
La fonction des cavaliers est listée ci-dessous :
Parmi les cavaliers ci-dessus, seuls les "JP" et "AJP" sont utilisables.
JP : Si ce cavalier est retiré, l’unité intérieure ou le système extérieur ne s’arrêtera pas (les codes de faute B6 – intérieur, et 04 – extérieur ne seront donc pas produits). Il n’est pas recommandé de retirer ce cavalier à moins qu’il soit impératif que le système continue à fonctionner.
AJP : Si ce cavalier est en place, les contacts de l’Alarme (relais d’électrovanne) sont fermés. Ceci ne dépend pas du fait que l’unité est sous tension ou non. Le rôle principal de ce cavalier est pour la mise en service. Si des vannes sont en place, le système de climatisation peut fonctionner, même si le détecteur n’est pas en service ou sous tension.
Tous les autres cavaliers doivent être mis en place comme indiqué dans le tableau pour assurer le fonctionnement du système.
Cavalier RBC-RD1-PE RBC-RD2-PE
A B C
JP AJP BJP
Pas Utilisé
Pas Présent
Pas Utilisé
Désactive l’arrêt d’unité
Ferme les contacts d’Alarme
Présent
Pas Utilisé
Présent
Pas Utilisé
Désactive l’arrêt d’unité
Ferme les contacts d’Alarme
Pas Présent
19
F
Vue d’ensemble du Système
Une installation typique du RBC-RD1-PE serait dans une chambre d’hôtel ou dans un bureau.
L’ensemble de la sonde à distance doit être placé en position basse dans la pièce, par exemple à la même hauteur que les prises de courant, etc. La position de la sonde est également importante. La position recommandée est sous l’unité intérieure ou sous la tuyauterie de réfrigérant de l’unité intérieure.
Pour assurer un bon fonctionnement, les points (listés ci-dessous) doivent être suivis durant l’installation:
o La hauteur maximale de la sonde au-dessus du sol doit être de 300 mm.
o Une ventilation adéquate doit être maintenue près de l’ensemble de sonde.
o La distance minimale recommandée entre l’ensemble de sonde et d’autres objets
dans la pièce est de 500 mm.
o
Le détecteur doit être monté à un endroit où les courants d’air ne peuvent pas influencer son fonctionnement.
20
Vue d’ensemble du Système
20
F
Electrovannes d’isolement situées dans les lignes de gaz et liquides (en option – fournies par l’installateur)
Chambre d’hôtel
FCU
Câble d’Interface de FCU
Unité de Commande
Source d’alimentation 230V~50Hz (du FCU)
Câble de raccordement de sonde à distance / d’alarme sonore
Détecteur de réfrigérant à oxyde métallique.
Position niveau bas
L’ensemble de sonde a été conçu de façon à pouvoir être installé dans n’importe quel support arrière standard encastré ou monté en surface. L’ensemble de sonde à distance a été fabriqué dans une plaque à grille électrique standard, pour maximiser le nombre de plaques de fermeture disponibles à l’installateur.
L’unité de commande principale est conçue pour être positionnée juste en dessous du plafond, à côté de l’unité intérieure.
Si des électrovannes (en option : à fournir par l’installateur) doivent être installées, il est recommandé de placer celles-ci en dehors de la zone couverte par le détecteur.
Voir diagramme d’une installation typique du RD1 ci-dessous.
21
F
Vue d’ensemble du Système
Une installation standard du RBC-RD2-PE serait à l’intérieur du carter de compresseur de l’unité extérieure du MMS (Système Modular Multi).
Etant donné que le MMS est conçu pour un fonctionnement avec jusqu’à cinq unités extérieures, jusqu’à cinq détecteurs par système peuvent être requis.
Tous les détecteurs seront connectés ensemble en série et raccordés à la boîte électrique de l’unité d’Inverseur.
La sonde de réfrigérant forme une partie intégrante de la boîte de commande. La boîte de commande doit donc être positionnée à moins de 200 mm (hauteur maximale de la base du carter de compresseur.
Si des électrovannes (en option : à fournir par l’installateur) doivent être installées, il est recommandé que celles-ci soient situées à l’extérieur de l’unité extérieure, mais avant le raccordement de la tuyauterie avec le circuit de réfrigération commun.
Voir diagramme ci-dessous illustrant l’emplacement de l’unité de commande dans le MMS extérieur.
En utilisant le support fourni, dévisser la vis avec pas à droite du socle de fixation du compresseur, positionner le support, puis remettre la vis dans le socle du compresseur. S’assurer que la vis est serrée à fond.
Fusible
Cable d’interface de CDU (seulement sur inverseur)
Vers
électrovannes
L1
N
Unité de Commande
Carte de
Circuit
imprimé
Carte de
Circuit
imprimé
22
F
+
Sig
Buzz
Câblage Electrique – RD1
Plusieurs options existent lors de l’installation d’une unité RD1. Premièrement, elle peut être installée comme une unité indépendante. Deuxièmement, elle peut être installée avec toute unité intérieure AI (Série ‘4’ et MMS intérieur), ce qui permet de produire des codes de fautes et d’arrêter l’unité intérieure. Troisièmement, des électrovannes peuvent également être installées en option.
S’assurer que l’unité de commande est protégée avec un fusible de 1 Amp 240VCA.
La puissance nominale maximale du relais de solénoïde est 240V ~ 5 Amp.
Il est à noter que toute électrovanne choisie pour cette application doit être capable de fonctionner sous une pression de 33 bars et avec un écoulement bidirectionnel.
Si une entrée par l’arrière est requise, des trous de Ø16 mm peuvent être faits dans l’arrière de la boîte de commande. Le centre des trous est marqué.
Ensemble de Sonde
à Distance
TOP TOP
Carte de
Circuit imprimé
COM
MAKE
Unité Intérieure
RAV = CN17 MM = CN21
Câble à 2 âmes (Fourni)
Electrovannes
(En option)
Contacts de Relais à
Tension Nulle
Puissance Max. 240V
~ 5 Amp
Alimentation 1 Amp 230V 50Hz
N
ALARM
L
AI+ sig – mute + buzzer
Loading...
+ 50 hidden pages