Toshiba RBC-FDP2-F-PE User Manual

RBC-FDP2-F-PE Interface
A/B connect to the Toshiba TCC-NET. TCC-NET installation should follow
Toshiba Remote Controller
R
G
modes.
with or without a standard remote controller and detects any faults that can
Installation and Operating Instructions
13.00
20.00
26.00
ALL DIMENSIONS IN MM NOT TO SCALE
FDP2 Description
The FDP2-F is a monitoring and control interface for the Toshiba Digital Inverter, SHRM and SMMS range of air-conditioners.
Fault Reporting
The FDP2-F Interface detects all indoor and outdoor faults occurring in TCC-NET compatible Toshiba air-conditioners and reports them by closing relay contacts R1-R2. The FDP2-F is connected on the TCC-NET network
be displayed on the controller for up to 8 units. Red and Green LEDs Indicate Fault/No Fault state.
Control Functions
GROUP CONTROL. Multiple FDP2 Interfaces can be connected to form large groups of units controlled from a single remote controller.
OPERATION PRESETS. Remote controller operation can be locked and various different preset run conditions can be sent from the FDP2.
DUTY/STANDBY. Pairs of FDPs can operate duty/standby control with 24 hour alternating duty, and changeover on fault.
HARDWIRED CONTROL. In conjuntion with an FDP2-BMS unit control can be achieved through potentiometer and volt-free contact inputs as well as via BMS integration.
CUSTOM CONTROL. FDP2 interfaces can be supplied in custom configurations to suit specific applications.
Warnings and Cautions
Do not exceed the specified fault relay ratings
Fault
No Fault
FDP2-F
Fault Interface
TCC-NET D-BUS RELAY
ABD1D2R1
ON
SW1 SW7
ON
RealTime Control Systems Ltd FDP2 Model 9410-2-A6
63.00
87.00
Ø 4.00
72.00
R2C
Ø 9.00
18.60
Mounting
The FDP2 should be mounted using the keyhole mounting points as indicated in the adjacent diagram.
75.00
Ø 4.00
Ø 9.00
Basic Cable Installation
Cabling should be a minimum 0.75mm2 throughout. Terminals TCC-NET Toshiba installation specifications. Terminals R1-R2 connect to fault
monitoring or indication equipment according to the specified rating of the relay. The FDP2 is powered from the TCC-NET and requires no extra power supply.
Indoor Unit
TCC-NET D-BUS RELAY
ABD1D2R1
R2C
A
B
LED Functionality
Normal Operation
R G
R G
R G
Error Conditions
R G
R G
R G
TCC-NET
Key:
Power-Up sequence Factory Configuration
Power-Up sequence Custom Configuration
TCC-NET Holdoff. After power-up and during unit configuration
Device configuration error
No unit master found on TCC-Net
D-BUS Communications timeout
Duplicate D-BUS Address detected
To fault monitoring
FLASHINGOFF ON
R
No Fault State
G
R
Unit Fault
G
Standard Operation
The FDP2 has a number of standard configurations that can be set using
ON
SW1 SW7
FDP2 Configuration Switches
ON
switches SW1 to SW7 shown above. Factory configuration is configured with all switches OFF. In this mode the FDP2 operates as a standard fault monitoring device. Additional preset modes are available using SW1 and SW2 to operate the system in preset Heat, Cool and Auto modes*.
Fault Monitoring
8 Units max
Fault Monitoring + Locked Cooling Preset
18
8 Units max
Fault Monitoring + Locked Heating Preset
23
8 Units max
Fault Monitoring + Locked Auto Preset
21
8 Units max
*Units that do not support specific modes such as cooling-only units will operate in fan-only in unsupported
9570-0 FDP2-F Installation & Operating Instructions issue 1.14.02 Copyright © RealTime Control Systems Limited. 2005
FDP2 Advanced Operation
ADDRESSING The FDP2 has the facility to create control groups using multiple FDP2s connected together on the D-Bus network. In standard configuration up to 16 FDP2 devices can be connected together. Each FDP2 is assigned a D-Bus address using the configuration switches SW4 to SW7. Unit addresses are shown below.
ADDRESS 0
ADDRESS 1
ADDRESS 2
ADDRESS 4
ADDRESS 5
ADDRESS 6
ADDRESS 8
ADDRESS 9
ADDRESS 10
ADDRESS 12
ADDRESS 13
ADDRESS 14
FDP2 Group Control
Group control allows up to 16 FDP2s to be connected on a D-Bus local network. Each FDP2 reports faults for the locally attached units. The FDP2 with address 0 is a MASTER and determines the settings for all systems connected to FDP2s addressed as slaves. The operating mode of the master is determined by SW1, SW2 as shown in the Standard Operation configuration instructions overleaf.
LOCAL CONTROL With SW1 OFF and SW2 OFF the MASTER FDP2 system operates under the control of the attached remote controller. SLAVE FDP2 devices will duplicate these settings to allow large groups to be controlled from one remote controller. Remote controllers on the slave FDP2s are locked and can be omitted if desired.
FDP2 Duty/Standby Operation
Duty/Standby will alternately run two systems on 24 hour alternating run/standby. If a fault occurs on either system then both systems are switched on until the fault is cleared.
Duty/Standby is achieved using two FDP2 devices, one with Address 0 and one with Address 1 with a D-BUS connection between the two. SW3 must be switched ON on both devices to enable the operation.
21
SW3 ON for Duty/standby
8 Units max
ADDRESS 3
ADDRESS 7
ADDRESS 11
ADDRESS 15
Address 0 is the FDP2 MASTER address. Address 1 to 15 are FDP2 SLAVE addresses that can be used to create large control groups.
NETWORK INSTALLATION The D-Bus network requires a twisted pair cable connecting terminals D1 and D2 on each FDP2 as shown below. Terminal D1 must be connected to all other D1 terminals. Terminal D2 must be connected to all other D2 terminals. In addition the common terminal C on all devices must be connected together. If a shielded cable is used then the shield can be used for this purpose. The network must be installed as a point to point BUS configuration, Star and Ring connections must NOT be used.
ADDRESS 0
TCC-NET D-BUS RELAY
ABD1D2R1
R2C
D1 D1 D2 D2
C C
ADDRESS 1
TCC-NET D-BUS RELAY
ABD1D2R1
R2C
SPECIFICATION Use solid or stranded 24awg shielded or unshielded twisted pair to Cat3, Cat4 or Cat5 specification. Use a twisted pair for connections D1,D2 and an extra core for connection C.
NETWORK LENGTH Standard installation for total network distances of up to 500m can be achieved following the basic daisy-chaining method showed in the above diagram. Network layout should follow a point-to-point connection, ‘T’ and star connections are not supported,
8 Units max
Address 0 (MASTER)
8 Units max
D-BUS
16 FDP2 max
Address 1 (SLAVE)
PRESET CONTROL If the master is configured for Heat, Cool or Auto preset control then the FDP2 slave units will operate to the same settings as the master. The diagram below shows the system configured for the Cool preset. See overleaf for SW1, SW2 settings for Heat and Auto presets.
D-BUS
16 FDP2 max
18
Address 0 (MASTER)
18
Address 1 (SLAVE)
8 Units max
8 Units max
Address 0 (MASTER)
1 Day 1 Day 1 Day FAULTDUTY/STANDBY
D-BUS
16 FDP2 max
21
Address 1 (SLAVE)
8 Units max
The MASTER FDP2 can be configured using SW1 and SW2 to operate using one of the three preset modes Heat, Cool or Auto. Alternatively the MASTER can be configured for local control, in which case the remote controller attached to the MASTER FDP2 can be used to set the operating settings during master duty.
Advanced control
More sophisticated control con be achieved using the FDP2-BMS interface, this provides a number of inputs that allow external control of unit operation, or connection to Building Management Systems. The FDP2 interfaces can also be customised for specific operating requirements. Contact Toshiba for details.
Functional Specification
Electrical Environmental
18V DC from TCC-NET
Power
Relay
<1VA 1A, 24VAC max
1A, 30VDC max
Mechanical
Dimensions (mm)
Mounting
Casing Weight Connectors
H72 x W87 x D19
Two keyhole mounting flanges
Zinc coated mild steel 80g Rising clamp to 0.75mm
cable
2
TemperatureSupply Storage
Operation
Humidity
Protection
EMC Emissions EMC Immunity
-10oC to 50oC 0oC to 50oC
0-90% RH non-condensing
IP30
EN61000-6-1 EN61000-6-3
Loading...