SMA Modbus EDMM-US-10, Modbus EDMM-10 Technical Information

EDMM-10-Modbus-TI-en-11 | Version 1.1ENGLISH
Technical Information
SMA Modbus® Interface
SMA DATA MANAGER M
Legal Provisions
SMA Solar Technology AG
Legal Provisions
The information contained in these documents is property of SMA Solar Technology AG. Any publication, whether in whole or in part, requires prior written approval by SMA Solar Technology AG. Internal reproduction used solely for the purpose of product evaluation or other proper use is allowed and does not require prior approval.
SMA reserves the right to modify the implementation of communication interfaces and protocols at any time without notifying the user. It is the user’s responsibility to determine whether the downloaded content is up to date and to comply with it. SMA shall not be held liable for any damage as well as any assumption of consequential costs for customer systems by SMA that may result from the user’s failure to do so.
Software licenses
You will find the software licenses for the installed software modules on the Internet at www.SMA­Solar.com.
Trademarks
All trademarks are recognized, even if not explicitly identified as such. Missing designations do not mean that a product or brand is not a registered trademark.
SMA Solar Technology AG
Sonnenallee 1 34266 Niestetal Germany Tel. +49 561 9522-0 Fax +49 561 9522-100 www.SMA.de Email: info@SMA.de
Status: 6/5/2018 Copyright © 2018 SMA Solar Technology AG. All rights reserved.
Table of Contents
SMA Solar Technology AG
Technical Information EDMM-10-Modbus-TI-en-11 3
Table of Contents
1 Information on this Document................................................. 4
1.1 Validity........................................................................................................................ 4
1.2 Target Group.............................................................................................................. 4
1.3 Content and Structure of this Document ................................................................... 4
1.4 Levels of warning messages...................................................................................... 4
1.5 Symbols in the Document .......................................................................................... 5
1.6 Typographies in the document.................................................................................. 5
2 Safety ........................................................................................ 6
2.1 Intended Use .............................................................................................................. 6
2.2 Safety Information...................................................................................................... 6
3 Product Overview .................................................................... 8
3.1 Modbus Protocol........................................................................................................ 8
3.2 SMA Modbus Profile ................................................................................................. 8
3.3 System Topology........................................................................................................ 8
3.4 Addressing and Data Transmission........................................................................... 8
3.4.1 Unit IDs.................................................................................................... 8
3.4.2 Register Address, Register Width and Data Block ............................... 8
3.4.3 Data Transmission................................................................................... 9
3.4.4 Reading and Writing of Data................................................................ 9
3.4.5 SMA Data Types and NaN Values ...................................................... 10
3.4.6 SMA Data Formats................................................................................. 10
3.4.7 SMA Firmware Data Formats ................................................................ 11
3.5 Modbus Ports ............................................................................................................. 12
3.6 Data Processing and Time Behavior ......................................................................... 12
3.7 Frequently Used Number Codes .............................................................................. 13
4 Assignment Tables ................................................................... 15
4.1 Information on Assignment Tables ............................................................................ 15
4.2 Unit ID = 1 (Communication Product) ...................................................................... 15
4.3 Unit ID = 2 (System) .................................................................................................. 15
5 Contact ...................................................................................... 19
1 Information on this Document
SMA Solar Technology AG
1 Information on this Document
1.1 Validity
This document is valid for:
• EDMM-10 (SMADataManagerM)
• EDMM-US-10 (SMA Data Manager M)
1.2 Target Group
The tasks described in this document must only be performed by qualified persons. Qualified persons must have the following skills:
• Detailed knowledge of the grid management services
• Knowledge of IP-based network protocols
• Knowledge of the Modbus specifications
• Training in the installation and configuration of IT systems
• Knowledge of and compliance with this document and all safety information
1.3 Content and Structure of this Document
This document does not contain any information on the Modbus registers provided by SMA products. Furthermore, no information on the firmware version to be installed on the respective SMA product is included. Information on firmware versions and device-specific Modbus registers of SMA products can be found on our product pages or Modbus page at www.SMA-Solar.com.
This document does not contain any information on software which can communicate with the Modbus interface (see the software manufacturer's manual).
This document provides a general description of the Modbus interface integrated in SMA products.
1.4 Levels of warning messages
The following levels of warning messages may occur when handling the product.
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates a situation which, if not avoided, can result in property damage.
1 Information on this Document
SMA Solar Technology AG
Technical Information EDMM-10-Modbus-TI-en-11 5
1.5 Symbols in the Document
Symbol Explanation
Information that is important for a specific topic or goal, but is not safety-relevant
Indicates a requirement for meeting a specific goal
Desired result
A problem that might occur
1.6 Typographies in the document
Typography Use Example
bold
• Messages
• Terminals
• Elements on a user interface
• Elements to be selected
• Elements to be entered
• Connect the insulated conductors to the terminals X703:1 to X703:6.
• Enter 10 in the field
Minutes.
>
• Connects several elements to be selected
• Select Settings > Date.
[Button] [Key]
• Button or key to be selected or pressed
• Select [Enter].
2 Safety
SMA Solar Technology AG
2 Safety
2.1 Intended Use
The Modbus interface of the supported SMA products is designed for industrial use and has the following tasks:
• Remote control of the grid management services of a PV system
• Remote-controlled querying of the measured values of a PV system
• Remote-controlled changing of the parameters of a PV system
• Interface for direct marketing The Modbus interface can be used via the protocol Modbus TCP. All components must remain within their permitted operating ranges and their installation
requirements at all times. Use this product only in accordance with the information provided in the enclosed documentation
and with the locally applicable standards and directives. Any other application may cause personal injury or property damage.
Alterations to the product, e.g. changes or modifications, are only permitted with the express written permission of SMA Solar Technology AG. Unauthorized alterations will void guarantee and warranty claims and in most cases terminate the operating license. SMA Solar Technology AG shall not be held liable for any damage caused by such changes.
Any use of the product other than that described in the Intended Use section does not qualify as the intended use.
The enclosed documentation is an integral part of this product. Keep the documentation in a convenient place for future reference and observe all instructions contained therein.
2.2 Safety Information
This section contains safety information that must be observed at all times when working on or with the product.
To prevent personal injury and property damage and to ensure long-term operation of the product, read this section carefully and observe all safety information at all times.
NOTICE
Damage of SMA products due to cyclical changing of parameters
The parameters of SMA products that can be changed with writable Modbus registers (RW) are intended for long-term storage of device settings. Cyclical changing of these parameters leads to destruction of the flash memory of the SMA products.
Parameters for grid management services to control and limit the nominal PV system power are an exception. Such parameters can be changed cyclically.
• Do not change device parameters cyclically.
• Use the parameters for grid management services for the automated remote control of the PV system.
2 Safety
SMA Solar Technology AG
Technical Information EDMM-10-Modbus-TI-en-11 7
NOTICE
Manipulation of PV system data in Ethernet networks
You can connect the supported SMA products to the Internet. When connected to the Internet, there is a risk that unauthorized users can access and manipulate the data of your PV system.
• Set up a firewall.
• Close unnecessary network ports.
• If absolutely necessary, only enable remote access via a virtual private network (VPN).
• Do not set up port forwarding at the used Modbus ports.
Access to data points after activating the Modbus interface
The reading and writing access to data points is possible after activating the Modbus interface. All parameter changes are shown on the user interface of the SMA product.
• Ensure that the Modbus interface is still active after resetting the SMA product to default settings.