SMA Modbus EDMM-US-10, Modbus EDMM-10 Technical Information

EDMM-10-Modbus-TI-en-11 | Version 1.1ENGLISH
Technical Information
SMA Modbus® Interface
SMA DATA MANAGER M
Legal Provisions
SMA Solar Technology AG
Legal Provisions
The information contained in these documents is property of SMA Solar Technology AG. Any publication, whether in whole or in part, requires prior written approval by SMA Solar Technology AG. Internal reproduction used solely for the purpose of product evaluation or other proper use is allowed and does not require prior approval.
SMA reserves the right to modify the implementation of communication interfaces and protocols at any time without notifying the user. It is the user’s responsibility to determine whether the downloaded content is up to date and to comply with it. SMA shall not be held liable for any damage as well as any assumption of consequential costs for customer systems by SMA that may result from the user’s failure to do so.
Software licenses
You will find the software licenses for the installed software modules on the Internet at www.SMA­Solar.com.
Trademarks
All trademarks are recognized, even if not explicitly identified as such. Missing designations do not mean that a product or brand is not a registered trademark.
SMA Solar Technology AG
Sonnenallee 1 34266 Niestetal Germany Tel. +49 561 9522-0 Fax +49 561 9522-100 www.SMA.de Email: info@SMA.de
Status: 6/5/2018 Copyright © 2018 SMA Solar Technology AG. All rights reserved.
Table of Contents
SMA Solar Technology AG
Technical Information EDMM-10-Modbus-TI-en-11 3
Table of Contents
1 Information on this Document................................................. 4
1.1 Validity........................................................................................................................ 4
1.2 Target Group.............................................................................................................. 4
1.3 Content and Structure of this Document ................................................................... 4
1.4 Levels of warning messages...................................................................................... 4
1.5 Symbols in the Document .......................................................................................... 5
1.6 Typographies in the document.................................................................................. 5
2 Safety ........................................................................................ 6
2.1 Intended Use .............................................................................................................. 6
2.2 Safety Information...................................................................................................... 6
3 Product Overview .................................................................... 8
3.1 Modbus Protocol........................................................................................................ 8
3.2 SMA Modbus Profile ................................................................................................. 8
3.3 System Topology........................................................................................................ 8
3.4 Addressing and Data Transmission........................................................................... 8
3.4.1 Unit IDs.................................................................................................... 8
3.4.2 Register Address, Register Width and Data Block ............................... 8
3.4.3 Data Transmission................................................................................... 9
3.4.4 Reading and Writing of Data................................................................ 9
3.4.5 SMA Data Types and NaN Values ...................................................... 10
3.4.6 SMA Data Formats................................................................................. 10
3.4.7 SMA Firmware Data Formats ................................................................ 11
3.5 Modbus Ports ............................................................................................................. 12
3.6 Data Processing and Time Behavior ......................................................................... 12
3.7 Frequently Used Number Codes .............................................................................. 13
4 Assignment Tables ................................................................... 15
4.1 Information on Assignment Tables ............................................................................ 15
4.2 Unit ID = 1 (Communication Product) ...................................................................... 15
4.3 Unit ID = 2 (System) .................................................................................................. 15
5 Contact ...................................................................................... 19
1 Information on this Document
SMA Solar Technology AG
1 Information on this Document
1.1 Validity
This document is valid for:
• EDMM-10 (SMADataManagerM)
• EDMM-US-10 (SMA Data Manager M)
1.2 Target Group
The tasks described in this document must only be performed by qualified persons. Qualified persons must have the following skills:
• Detailed knowledge of the grid management services
• Knowledge of IP-based network protocols
• Knowledge of the Modbus specifications
• Training in the installation and configuration of IT systems
• Knowledge of and compliance with this document and all safety information
1.3 Content and Structure of this Document
This document does not contain any information on the Modbus registers provided by SMA products. Furthermore, no information on the firmware version to be installed on the respective SMA product is included. Information on firmware versions and device-specific Modbus registers of SMA products can be found on our product pages or Modbus page at www.SMA-Solar.com.
This document does not contain any information on software which can communicate with the Modbus interface (see the software manufacturer's manual).
This document provides a general description of the Modbus interface integrated in SMA products.
1.4 Levels of warning messages
The following levels of warning messages may occur when handling the product.
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates a situation which, if not avoided, can result in property damage.
1 Information on this Document
SMA Solar Technology AG
Technical Information EDMM-10-Modbus-TI-en-11 5
1.5 Symbols in the Document
Symbol Explanation
Information that is important for a specific topic or goal, but is not safety-relevant
Indicates a requirement for meeting a specific goal
Desired result
A problem that might occur
1.6 Typographies in the document
Typography Use Example
bold
• Messages
• Terminals
• Elements on a user interface
• Elements to be selected
• Elements to be entered
• Connect the insulated conductors to the terminals X703:1 to X703:6.
• Enter 10 in the field
Minutes.
>
• Connects several elements to be selected
• Select Settings > Date.
[Button] [Key]
• Button or key to be selected or pressed
• Select [Enter].
2 Safety
SMA Solar Technology AG
2 Safety
2.1 Intended Use
The Modbus interface of the supported SMA products is designed for industrial use and has the following tasks:
• Remote control of the grid management services of a PV system
• Remote-controlled querying of the measured values of a PV system
• Remote-controlled changing of the parameters of a PV system
• Interface for direct marketing The Modbus interface can be used via the protocol Modbus TCP. All components must remain within their permitted operating ranges and their installation
requirements at all times. Use this product only in accordance with the information provided in the enclosed documentation
and with the locally applicable standards and directives. Any other application may cause personal injury or property damage.
Alterations to the product, e.g. changes or modifications, are only permitted with the express written permission of SMA Solar Technology AG. Unauthorized alterations will void guarantee and warranty claims and in most cases terminate the operating license. SMA Solar Technology AG shall not be held liable for any damage caused by such changes.
Any use of the product other than that described in the Intended Use section does not qualify as the intended use.
The enclosed documentation is an integral part of this product. Keep the documentation in a convenient place for future reference and observe all instructions contained therein.
2.2 Safety Information
This section contains safety information that must be observed at all times when working on or with the product.
To prevent personal injury and property damage and to ensure long-term operation of the product, read this section carefully and observe all safety information at all times.
NOTICE
Damage of SMA products due to cyclical changing of parameters
The parameters of SMA products that can be changed with writable Modbus registers (RW) are intended for long-term storage of device settings. Cyclical changing of these parameters leads to destruction of the flash memory of the SMA products.
Parameters for grid management services to control and limit the nominal PV system power are an exception. Such parameters can be changed cyclically.
• Do not change device parameters cyclically.
• Use the parameters for grid management services for the automated remote control of the PV system.
2 Safety
SMA Solar Technology AG
Technical Information EDMM-10-Modbus-TI-en-11 7
NOTICE
Manipulation of PV system data in Ethernet networks
You can connect the supported SMA products to the Internet. When connected to the Internet, there is a risk that unauthorized users can access and manipulate the data of your PV system.
• Set up a firewall.
• Close unnecessary network ports.
• If absolutely necessary, only enable remote access via a virtual private network (VPN).
• Do not set up port forwarding at the used Modbus ports.
Access to data points after activating the Modbus interface
The reading and writing access to data points is possible after activating the Modbus interface. All parameter changes are shown on the user interface of the SMA product.
• Ensure that the Modbus interface is still active after resetting the SMA product to default settings.
3 Product Overview
SMA Solar Technology AG
3 Product Overview
3.1 Modbus Protocol
The Modbus Application Protocol is an industrial communication protocol that is currently used in the solar sector mainly for PV system communication. The Modbus protocol has been developed for reading data from or writing data to clearly defined data areas. The Modbus specification does not prescribe what data is within which data area. The data areas must be defined device-specifically in Modbus profiles. With knowledge of the device-specific Modbus profile, a Modbus client (e.g. a SCADA system) can access the data of a Modbus server (e.g. SMA product with Modbus interface).
The SMAModbus profile and SunSpecModbus profile are used for SMA products.
3.2 SMAModbus Profile
The SMA Modbus profile contains definitions for SMA products. All available data on SMA products was assigned to the corresponding Modbus registers for the definition. Not all SMA products support all Modbus registers of the SMAModbus profile.
For supported Modbus register (see Section4, page15).
3.3 System Topology
An SMA product with Modbus interface is connected with the SCADA system of the electric utility company or the grid operator via Ethernet. The Modbus interface also enables communication via the Modbus protocol. From the perspective of the Modbus protocol, an SMA product with Modbus interface constitutes a Modbus server that supports the SMA Modbus profile.
3.4 Addressing and Data Transmission
3.4.1 Unit IDs
The UnitID is a superordinate addressing type in the Modbus protocol. The following tables shows the Unit IDs supported by this SMA product.
Unit ID Explanation
1 This Unit ID is reserved for information on the SMA product. 2 This unit ID is reserved for the system parameters and measured val-
ues.
3.4.2 Register Address, Register Width and Data Block
A Modbus register is 16 bits wide. For wider data items, connected Modbus registers are used and considered as data blocks. The address of the first Modbus register in a data block is the start address of the data block.
3 Product Overview
SMA Solar Technology AG
Technical Information EDMM-10-Modbus-TI-en-11 9
3.4.3 Data Transmission
In accordance with the Modbus specification, only a specific volume of data can be transported in a single data transmission in a simple protocol data unit (PDU). The data also contains function­dependent parameters such as the function code, start address or number of Modbus registers to be transmitted. The amount of data depends on the Modbus command used and has to be taken into account during data transmission (see Section3.4.4, page9).
With data storage in the Motorola format "Big Endian", data transmission begins with the high byte and then the low byte of the Modbus register.
3.4.4 Reading and Writing of Data
The Modbus interface can be used via the protocol Modbus TCP. Using Modbus TCP enables read- and write access to the Modbus register. SMA products with Modbus interface use the Modbus TCP as standard.
Access type Explanation
RO (Read-Only) Read only RW (Read-Write) Read and write WO (Write-Only) Write only
The following Modbus commands are supported by the implemented Modbus interface:
Modbus command Hexadecimal value Data volume (number of
registers)*
Read Holding Registers 0x03 1 to 125 Read Input Registers 0x04 1 to 125 Write Single Register 0x06 1 Write Multiple Registers 0x10 1 to 123 Read Write Multiple Registers 0x17 Read: 1 to 125, Write: 1 to
121
* Number of Modbus registers transferable as a data block per command (16 bit)
Error messages on reading or writing individual Modbus registers
If a Modbus register is accessed, which is not contained in a Modbus profile, or if a Modbus command is incorrect, a Modbus exception is generated. Modbus exceptions are also generated when write access occurs on a read-only Modbus register or read access occurs on a write-only Modbus register.
Reading or writing of data blocks
To prevent inconsistencies, data blocks of associated Modbus registers or Modbus register ranges must be read or written consecutively. The 4 bytes of a 64-bit Modbus register must, for example, be read with an operation in a 64-bit SMA data type.
3 Product Overview
SMA Solar Technology AG
Technical InformationEDMM-10-Modbus-TI-en-1110
Reading multiple Modbus registers as a data block
If a data block is read and if at least one register defined in the Modbus profile can be determined in its data range, an answer is returned. If this data block also contains Modbus registers that are not defined in the Modbus profile, NaN is used for the query values in each case. If none of the Modbus registers are defined in the data range of a data block in the Modbus profile, the query is invalid and a Modbus exception is generated.
Error message on writing multiple Modbus registers as a data block
If multiple registers are written in the data block (Modbus command 0x10 and 0x17) and an error occurs when writing, the process continues with the next register in the data block. If some data is dependent on other data, or if some data is mutually exclusive, the data is only processed if the entire data block is valid. Otherwise the entire data block is discarded. In the event of an error, a Modbus exception will be generated.
Modbus exceptions
For Modbus exceptions, see "Modbus Application Protocol Specification" at http:// www.modbus.org/specs.php.
3.4.5 SMA Data Types and NaN Values
The following table shows the data types used in the SMA Modbus profile and compares these to possible NaN values. The SMA data types are listed in the assignment tables in the Type column. The SMA data types describe the data widths of the assigned values:
Type Explanation NaN value
S16 A signed word (16-bit). 0x8000 S32 A signed double word (32-bit). 0x8000 0000 STR32 32byte data field, in UTF8 format. ZERO U16 A word (16-bit). 0xFFFF U32 A double word (32-bit). 0xFFFF FFFF U32 For status values, only the lower 24 bits of a double word
(32-bit) are used.
0xFFFF FD
U64 A quadruple word (64-bit). 0xFFFF FFFF FFFF
FFFF
3.4.6 SMA Data Formats
The following SMA data formats describe how SMA data is to be interpreted. The data formats are used, for example, for the display of data or for its further processing. The SMA data formats are listed in the Format column of the assignment tables.
Format Explanation
Duration Time in seconds, in minutes or in hours, depending on the Modbus
register
3 Product Overview
SMA Solar Technology AG
Technical Information EDMM-10-Modbus-TI-en-11 11
Format Explanation
ENUM or TAGLIST
Coded numerical values. The breakdown of the possible codes can be found directly under the designation of the Modbus register in the assignment tables.
FIX0 Decimal number, commercially rounded, without decimal place. FIX1 Decimal number, commercially rounded, one decimal place. FIX2 Decimal number, commercially rounded, two decimal places. FIX3 Decimal number, commercially rounded, three decimal places. FIX4 Decimal number, commercially rounded, four decimal places. FUNCTION_SEC The date saved in the Modbus register will be transmitted in the
event of a change to a function and starts this. After execution of the function, no status value is set. A security question must be executed
in the client software prior to execution of the function. FW Firmware version HW Hardware version (e.g. 24) IP4 4-byte IP address (IPv4) of the form XXX.XXX.XXX.XXX. RAW Text or number. A RAW number has no decimal places and no thou-
sand or other separation indicators. Outline Purchase Agreement Revision number of the form 2.3.4.5. TEMP Temperature values are stored in special Modbus registers in de-
grees Celsius (°C), in degrees Fahrenheit (°F), or in Kelvin K. The
values are commercially rounded, with one decimal place. TM UTC time, in seconds UTF8 Data in UTF8 format. DT Date/time (Transmission in seconds since 1970-01-01)
3.4.7 SMA Firmware Data Formats
Four values are extracted from the delivered double word (DWORD) within the corresponding Modbus register. The values "Major" and "Minor" are contained BCD-coded in bytes 1 and 2. Byte 3 contains the "Build" value (not BCD-coded). Byte 4 contains the "Release Type" value according to the following table:
Release type Release-type coding Explanation
0 N No revision number 1 E Experimental release 2 A Alpha release 3 B Beta release
3 Product Overview
SMA Solar Technology AG
Technical InformationEDMM-10-Modbus-TI-en-1112
Release type Release-type coding Explanation
4 R Release 5 S Special release > 5 As number No special interpretation
Example:
Product firmware version: 1.05.10.R Values from double word (DWORD): Major: 1, Minor: 05, Build: 10, Release type: 4 (Hex: 0x1
0x5 0xA 0x4)
3.5 Modbus Ports
The following table shows the default setting of the supported network protocols:
Network protocol Modbus port
TCP 502
Using free ports
Only use free ports when using another port than 502. The following range is generally available: 49152 to 65535.
You can find more information on occupied ports in the database "Service Name and Transport Protocol Port Number Registry" at http://www.iana.org/assignments/service-names­port-numbers/service-names-port-numbers.xml.
Changing the Modbus port
If you change one of the communication ports, you must also change the corresponding Modbus port of a connected Modbus/client system. Otherwise the SMA product can no longer be accessed via the Modbus protocol.
3.6 Data Processing and Time Behavior
In this Section, you can find typical data-processing and reaction times of the Speedwire Modbus interface and time details for saving parameters in SMA products.
NOTICE
Damage of SMA products due to cyclical changing of parameters
The parameters of SMA products that can be changed with writable Modbus registers (RW) are intended for long-term storage of device settings. Cyclical changing of these parameters leads to destruction of the flash memory of the SMA products.
Parameters for grid management services to control and limit the nominal PV system power are an exception. Such parameters can be changed cyclically.
• Do not change device parameters cyclically.
• Use the parameters for grid management services for the automated remote control of the PV system.
3 Product Overview
SMA Solar Technology AG
Technical Information EDMM-10-Modbus-TI-en-11 13
Signal runtime via the SMA product with Modbus interface
The signal runtime of the SMA product with Modbus is usually 100ms. The signal runtime is the time required by the SMA product to process incoming Modbus commands.
Data Transfer Interval via the Modbus protocol
For system stability reasons, the time period between data transfers via the Modbus protocol must be at least ten seconds. No more than five parameters and measured values should be transmitted per SMA inverter.
Data Transfer Interval via the Modbus protocol
The physical reaction time of SMA products is normally approx. one second. The physical reaction time is the time between the changing of setpoints in a SMA product until their physical implementation. Such a change would be, for example, changing cosφ.
Reaction time of the Modbus interface
The reaction time of the Modbus interface is five to ten seconds. The reaction time of the Modbus interface is the time between the arrival of the parameter specifications in the SMA product until the corresponding measured values are provided to the Modbus interface. Due to this reaction time, parameter specifications can only be displayed via a Modbus/client system (e.g. a SCADA system) at a corresponding or larger interval.
3.7 Frequently Used Number Codes
The following table contains number codes which, as function coding in data format ENUM, are frequently used in the SMA Modbus profile.
The event numbers of the SMA products are not decrypted with the number codes in this document.
The event numbers of the SMA products are device-specific and cannot be decrypted with the number codes in this document. To decrypt the event numbers of low or medium-power inverters, you require additional information such as operating parameters and measured values (see Technical Description "Measured Values and Parameters" at www.SMA­Solar.com).
To decrypt the event numbers of central inverters, contact the Service department (see Section5, page19).
Code Explanation Code Explanation
51 Closed 1387 Reactive power Q, setpoint via analog
input 276 Instantaneous value 1388 cos φ, setpoint via analog input 295 MPP 1389 Reactive power / voltage characteris-
tic curve Q(U) with hysteresis and
deadband 303 Off 1390 Active power limitation P via analog
input
3 Product Overview
SMA Solar Technology AG
Technical InformationEDMM-10-Modbus-TI-en-1114
Code Explanation Code Explanation
308 On 1391 Active power limitation P via digital in-
puts 309 Operation 1392 Errors 311 Open 1393 Wait for PV voltage 336 Contact the manufacturer 1394 Wait for valid AC grid 337 Contact the installer 1395 DC area 338 Invalid 1396 AC grid 381 Stop 1455 Emergency stop 455 Warning 1466 Waiting 461 SMA (manufacturer specification) 1467 Starting 1041 leading 1468 MPP search 1042 lagging 1469 Shutdown 1069 Reactive power / voltage characteris-
tic curve Q(V)
1470 Disturbance
1070 Reactive power Q, direct setpoint 1471 Warning/error e-mail OK 1071 Reactive power const. Q (kVAr) 1472 Warning/error e-mail not OK 1072 Q specified by PV system control 1473 System info e-mail OK 1073 Reactive power Q(P) 1474 System info e-mail not OK 1074 cos φ, direct setpoint 1475 Error e-mail OK 1075 cos φ, setpoint via system control 1476 Error e-mail not OK 1076 cos φ(P) characteristic curve 1477 Warning e-mail OK 1077 Active power limitation P (W) 1478 Warning e-mail not OK 1078 Active power limitation P (%) of PMAX 1479 Wait after grid interruption 1079 Active power limitation P via system
control
1480 Wait for electric utility company
4 Assignment Tables
SMA Solar Technology AG
Technical Information EDMM-10-Modbus-TI-en-11 15
4 Assignment Tables
4.1 Information on Assignment Tables
The following subsections are sorted by unit ID. Each contains a table of the Modbus registers which can be accessed using this unit ID. The tables present the following information:
Information Explanation
ADR Decimal Modbus register Description/number codes Short description of the Modbus register and the number codes
used CNT Number of assigned Modbus registers Type Data type Format Data format of the saved value Access Access type
4.2 Unit ID = 1 (Communication Product)
The following table lists the parameters provided by the communication product and measured values that can be accessed at Unit ID = 1:
ADR Description/number codes CNT Type Format Access
30001 Version number of the SMA profile 2 U32 RAW RO 30003 SUSyID (Device ID) 2 U32 RAW RO 30005 Serial number 2 U32 RAW RO 30007 Modbus data change: counter value will in-
crease if data in the Profile has changed (overflow).
2 U32 RAW RO
30051 Device class:
• 8128 = Communication products
2 U32 ENUM RO
30193 UTC system time (s) 2 U32 DT RO
4.3 Unit ID = 2 (System)
In the following table, you can find the PV system parameters that you can access using unit ID = 2. The system parameters represent measured values and parameters of the communication product and also system devices that are connected via the Modbus protocol. Parameters such as time settings are transferred by the communication product to the devices of the system and there, depending on the device type, processed further. Measured values such as energy meter values are queried by the devices and made available as accumulated values:
ADR Description/number codes CNT Type Format Access
30193 UTC system time (s) 2 U32 DT RO
4 Assignment Tables
SMA Solar Technology AG
Technical InformationEDMM-10-Modbus-TI-en-1116
ADR Description/number codes CNT Type Format Access
30513 Total energy fed in on all line conductors
(in Wh)
4 U64 FIX0 RO
30775 Current active power on all line conductors
(W)
2 S32 FIX0 RO
30805 Reactive power on all line conductors (VAr) 2 S32 FIX0 RO 31235 Power limitation via digital input (in %) 2 U32 FIX2 RO 31239 PV power limitation via communication (in%)2 U32 FIX2 RO
31241 PV power limitation via communication for
direct marketing (in %)
2 U32 FIX2 RO
31243 Minimum PV power limitation (in %) 2 U32 FIX2 RO 31249 Active power of system at PCC (in W) 2 S32 FIX0 RO 31251 Reactive power of system at PCC (in VAr) 2 S32 FIX0 RO 34609 Ambient temperature (°C) 2 S32 TEMP RO 34615 Global wind speed (m/s) 2 U32 FIX2 RO 34621 PV module temperature (°C) 2 S32 TEMP RO 34623 Total irradiation on the external irradiation
sensor/pyranometer (W/m²)
2 U32 FIX0 RO
34625 Ambient temperature (°F) 2 S32 TEMP RO 34627 Ambient temperature (K) 2 S32 TEMP RO 34629 PV module temperature (°F) 2 S32 TEMP RO 34631 PV module temperature (K) 2 S32 TEMP RO 34633 Global wind speed (km/h) 2 U32 FIX1 RO 34635 Global wind speed (mph) 2 U32 FIX1 RO
4 Assignment Tables
SMA Solar Technology AG
Technical Information EDMM-10-Modbus-TI-en-11 17
ADR Description/number codes CNT Type Format Access
34653 Digital input group 1, coded as status:
• 311 = Open
• 2055 = DI1
• 2056 = DI1 DI2
• 2057 = DI1 DI2 DI3
• 2058 = DI1 DI2 DI3 DI4
• 2059 = DI1 DI2 DI4
• 2060 = DI1 DI3
• 2061 = DI1 DI3 DI4
• 2062 = DI1 DI4
• 2063 = DI2
• 2064 = DI2 DI3
• 2065 = DI2 DI3 DI4
• 2066 = DI2 DI4
• 2067 = DI3
• 2068 = DI3 DI4
• 2069 = DI4
2 U32 ENUM RO
40015 Reactive power setpoint Q, in% of the
maximum active power (PMAX) of the PV plant.
Value range:
• -100% to -1% = load
• 0% = no reactive power
• 1% to 100% = generator
1 S16 FIX1 WO
40016 Active power setpoint P, in % of the maxi-
mum active power (PMAX) of the PV plant. Value range:
• -100% to -1% = load
• 0% = no active power
• 1% to 100% = generator
1 S16 FIX0 WO
40018 Quick shut-down of the inverters
• 381 = stop (AC side)
• 1467 = start
• 1749 = full stop (AC and DC sides)
2 U32 ENUM WO
4 Assignment Tables
SMA Solar Technology AG
Technical InformationEDMM-10-Modbus-TI-en-1118
ADR Description/number codes CNT Type Format Access
40022 Reactive power setpoint Q, in% of the
maximum active power (PMAX) of the PV plant.
Value range:
• -100% to -1% = load
• 0% = no reactive power
• < 0% to 100% = generator
1 S16 FIX2 WO
40023 Active power setpoint P, in % of the maxi-
mum active power (PMAX) of the PV plant. Value range:
• -100% to -1% = load
• 0% = no active power
• < 0% to 100% = generator
1 S16 FIX2 WO
40492 Direct marketer:
Reactive power setpoint Q, in% of the maximum active power (PMAX) of the PV plant.
Value range:
• -100% to -1% = load
• 0% = no reactive power
• < 0% to 100% = generator
1 S16 FIX2 WO
40493 Direct marketer:
Active power setpoint P, in % of the maxi­mum active power (PMAX) of the PV plant.
Value range:
• -100% to -1% = load
• 0% = no active power
• < 0% to 100% = generator
1 S16 FIX2 WO
41167 Manually set active power limit for the en-
tire system (%)
2 U32 FIX2 RO
5 Contact
SMA Solar Technology AG
Technical Information EDMM-10-Modbus-TI-en-11 19
5 Contact
Deutschland Österreich Schweiz
SMA Solar Technology AG Niestetal Sunny Boy, Sunny Mini Central,
SunnyTripower: +495619522‑1499
Monitoring Systems (Kommunikationsprodukte): +495619522‑2499
Fuel Save Controller (PV-Diesel-Hybridsysteme): +495619522-3199
Sunny Island, Sunny Boy Stor­age, Sunny Backup: +495619522-399
Sunny Central, Sunny Central Storage: +495619522-299
SMA Online Service Center: www.SMA-Service.com
Belgien Belgique België Luxemburg Luxembourg Nederland
SMA Benelux BVBA/SPRL Mechelen +3215286 730 SMA Online Service Center:
www.SMA-Service.com
Česko Magyarország Slovensko
SMA Service Partner TERMS a.s.
+4203876 85 111 SMA Online Service Center:
www.SMA-Service.com
Türkiye SMA Service Partner DEKOM
Ltd. Şti. +90 24 22430605 SMA Online Service Center:
www.SMA-Service.com
France SMA France S.A.S.
Lyon +33 472 22 97 00 SMA Online Service Center :
www.SMA-Service.com
Ελλάδα Κύπρος
SMA Service Partner AKTOR FM.
Αθήνα +30 210 8184550 SMA Online Service Center:
www.SMA-Service.com
España Portugal
SMA Ibérica Tecnología Solar, S.L.U.
Barcelona +34935635099 SMA Online Service Center:
www.SMA-Service.com
United King­dom
SMA Solar UK Ltd. Milton Keynes +441908304899 SMA Online Service Center:
www.SMA-Service.com
Italia SMA Italia S.r.l.
Milano +39028934-7299 SMA Online Service Center:
www.SMA-Service.com
Australia SMA Australia Pty Ltd.
Sydney Toll free for Australia:
1800SMAAUS (1800762287)
International: +61294914200
5 Contact
SMA Solar Technology AG
Technical InformationEDMM-10-Modbus-TI-en-1120
United Arab Emirates
SMA Middle East LLC Abu Dhabi +9712234 6177 SMA Online Service Center:
www.SMA-Service.com
India SMA Solar India Pvt. Ltd.
Mumbai +912261713888
ไทย SMA Solar (Thailand) Co., Ltd.
กรุงเทพฯ +6626706999
대한민국 SMA Technology Korea Co.,
Ltd. 서울 +82-2-520-2666
South Africa SMA Solar Technology South
Africa Pty Ltd. Cape Town 08600SUNNY (08600 78669) International: +27 (0)21 826
0699 SMA Online Service Center:
www.SMA-Service.com
Argentina Brasil Chile Perú
SMA South America SPA Santiago de Chile +562 2820 2101
Other coun­tries
International SMA Service Line Niestetal 00800SMASERVICE
(+8007627378423) SMA Online Service Center:
www.SMA-Service.com
www.SMA-Solar.com
Loading...