Choice of Language - Selección de idioma - Choix de la langue - Sprachauswahl
Page5
Página40
Page78
Seite116
English UK
Español
Français
Deutsch
L00410644-01_2q / Rev. date: 2014-06-021
IMPORTANT SAFETY INSTRUCTIO...
IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS
Safety Message Types
The following symbols are used in this document:
DANGER
Indicates a potentially hazardous situation which will
result in death or serious injury.
WARNING
Indicates a potentially hazardous situation which could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which could
result in minor or moderate injury. It may also be used
to alert against unsafe practices.
NOTICE
Indicates important information, including situations
which may result in damage to equipment or property.
General Safety
CAUTION
This manual contains important instructions that shall be
followed during installation and maintenance of the MLX
inverter.
NOTICE
BEFORE INSTALLATION
Check for damage to equipment and packaging. If in
doubt, contact the supplier before commencing installation.
WARNING
INSTALLATION
For optimum safety, follow the steps described in this
document. Keep in mind that the inverter has 2 voltagecarrying sides; the PV input and the AC grid.
DANGER
DISCONNECTING THE INVERTER
Before starting work on the inverter, switch off AC at the
mains switch and PV using the PV load switch. Ensure
that the inverter cannot be unintentionally reconnected.
Use a voltage tester to ensure that the unit is disconnected and voltage free. The inverter can still be charged
with very high voltage at hazardous levels even when it
is disconnected from AC grid and solar modules. Wait at
least 5 minutes following disconnection from grid and
PV panels before proceeding.
L00410644-01_2q / Rev. date: 2014-06-02
IMPORTANT SAFETY INSTRUCTIO...
WARNING
RISK OF ELECTRIC SHOCK
These servicing instructions are for use by qualified
personnel only. To reduce the risk of electric shock, do
not perform any servicing other than that specified in
the operating instructions unless you are qualified to do
so.
WARNING
The inverter is not equipped with an isolation
transformer and is intended to be installed according to
NFPA 70, 690.35 with an ungrounded (floating) PV array.
WARNING
Input and output circuits are isolated from the enclosure.
System grounding, when required by the Canadian
Electrical Code, Part I, is the responsibility of the
installer.
1PV load switch (optional)
Illustration 1.1
NOTICE
The PV load switch can be secured in the ‘Off’ position
using a padlock.
CAUTION
DC voltages up to 1000 V are present in a PV system
even when the inverter is disconnected from the AC grid.
Faults or inappropriate use may lead to electric arcing.
CAUTION
MAINTENANCE AND MODIFICATION
Only authorised personnel are permitted to modify the
inverter. To ensure personal safety, use only original
spare parts available from the supplier. If non-original
spare parts are used, compliance with CE/UL guidelines
in respect of electrical safety, EMC, and machine safety is
not guaranteed.
WARNING
INSTALLER
Observe the National Electric Code, ANSI/NFPA 70.
Input and output circuits are isolated from the enclosure.
System grounding is the responsibility of the installer.
CAUTION
All persons installing and servicing inverters must be:
Trained and authorised in general safety rules
•
for work on electrical equipment.
Familiar with local requirements, rules, and
•
regulations for the installation.
CAUTION
The inverter does not provide overcurrent protection.
This must be provided by the installer. See Table 5.8.
CAUTION
The temperature of the cooling racks and components
inside the inverter can exceed 70 °C/158 °F. Observe the
danger of burn injury.
The inverter is to be installed so that it is not expected
to be contacted by persons.
CAUTION
To reduce the risk of fire, connect only to a circuit
provided with 125 A maximum branch-circuit
overcurrent protection in accordance with the National
Electrical Code, ANSI/NFPA 70.
NOTICE
Use 75 °C or 90 °C wire, either AWG copper or AWG
aluminium. See 2.7 Cable Entry.
L00410644-01_2q / Rev. date: 2014-06-02
IMPORTANT SAFETY INSTRUCTIO...
NOTICE
The symbol for protective earth used in this manual is
identified in Illustration 2.18.
The on/off symbol is identified in 3.2.2 Turn PV Load
Switch On.
NOTICE
For information about ambient temperature rating, see
5.4 Installation Conditions.
NOTICE
This manual contains information about field wiring
connections and torque specifications. See 5.5 Torque
Specifications.
NOTICE
This equipment has been tested and found to comply
with the limits for a Class B digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful
interference in a residential installation. This equipment
generates, uses and can radiate radio frequency energy
and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio
communications. However, there is no guarantee that
interference will not occur in a particular installation. If
this equipment does cause harmful interference to radio
or television reception, which can be determined by
turning the equipment off and on, the user is
encouraged to try to correct the interference by 1 or
more of the following measures:
Reorient or relocate the receiving antenna.
•
Increase the distance between the equipment
•
and receiver.
Connect the equipment into an outlet on a
•
circuit different from that to which the receiver
is connected.
Consult the dealer or an experienced radio/TV
•
technician for help.
Conformity
Go to the download area at www.sma.de for information.
See also 5 Technical Data.
L00410644-01_2q / Rev. date: 2014-06-02
Contents
Contents
1 Introduction
1.1 Purpose of the Manual
1.2 Unpacking
1.3 Identification of Inverter
1.4 Installation Sequence
1.5 Overview of Installation Area
2 Installation
2.1 Environment and Clearances
2.2 Mounting the Mounting Plate
2.3 Mounting the Inverter
2.4 Removing the Inverter
2.5 Access to the Installation Area
2.6 AC Grid Connection
2.7 Cable Entry
2.8 Ethernet Connections
2.9 PV Connection
2.9.1 External String Combiners18
7
8
10
10
10
11
12
12
13
14
15
15
16
17
17
18
2.10 Closure
3 Initial Setup and Start
3.1 User Interface
3.1.1 Operation Modes20
3.2 Display
3.2.1 Initial Setup via LCS Tool21
3.2.2 Turn PV Load Switch On21
3.2.3 Start-up
3.3 LCS Tool
3.3.1 Getting Started22
4 Service
4.1 Troubleshooting
4.2 Maintenance
5 Technical Data
5.1 Specifications
5.2 Trip Settings
19
20
20
20
21
22
28
28
30
31
31
32
5.3 Conformity
5.4 Installation Conditions
5.5 Torque Specifications
L00410644-01_2q / Rev. date: 2014-06-025
33
34
34
Contents
5.6 Mains Circuit Specifications
5.7 Auxiliary Interface Specifications
5.8 Ethernet Connections
35
35
36
6L00410644-01_2q / Rev. date: 2014-06-02
Introduction
1Introduction
The MLX inverters are designed to act exclusively as gridtied inverters for photovoltaic (PV) systems. The inverter
converts DC voltage generated by a solar array into
electrical AC power. The unit must be tied to the utility
grid and a photovoltaic system in order to operate
properly. It is not suitable for any other applications (such
as a battery back-up or wind-powered systems).
The MLX system consists of 4 main components (see also
Illustration 1.1):
MLX inverter.
•
DC combiner.
•
The DC combiner makes it possible to combine
the needed number of PV strings for the MLX
inverter. A DC combiner is needed for each MLX
inverter.
MLX Inverter Manager.
•
The MLX Inverter Manager is required for
operating the MLX inverters. Each Inverter
Manager can handle up to 42 inverters. The
Inverter Manager handles all communication to
the inverters. It forms a single point of interface
for data accusation systems, upload to cloud
services and power-plant control.
LCS Tool.
•
The LCS Tool is required for commissioning and
servicing MLX inverters, via the Inverter Manager.
The LCS Tool acts as the primary user interface
for the MLX system.
11
L00410644-01_2q / Rev. date: 2014-06-027
1
Introduction
Illustration 1.1 System Overview
1PV array
2DC combiner
3MLX inverter
4MLX Inverter Manager
5LCS Tool
6CLX portal or third party
7Utility control
8SCADA system
9Transformer
Table 1.1 System Overview
1.1 Purpose of the Manual
The Installation Guide provides information required to
install and commission the MLX series inverter.
Additional resources available:
Inverter Manager Installation Poster, for
•
information required to commission the MLX
inverter as well as setup of inverter communication (EU).
Inverter Manager Assembly Installation Guide, for
•
information required to commission the MLX
inverter as well as setup of inverter communication (US).
Design Guide, for information required for detailed
•
inverter layout planning in a diversity of solar
energy applications.
Fan Installation Instruction, for information
•
required to replace a fan.
SPD Installation Instruction, for information
•
required to replace surge protection devices.
These documents are available from the download area at
www.sma.de, or from the supplier of the solar inverter.
8L00410644-01_2q / Rev. date: 2014-06-02
Introduction
Illustration 1.2 MLX Inverter
AbbreviationDescription
ANSIAmerican National Standards Institute
AWGAmerican Wire Gauge
cat5eCategory 5 twisted pair cable (enhanced)
DHCPDynamic Host Configuration Protocol
DNODistribution Network Operator
DSLDigital Subscriber Line
EMC (Directive) Electromagnetic Compatibility Directive
ESDElectrostatic Discharge
FCCFederal Communications Commission
FRTFault Ride Through
GSMGlobal System for Mobile Communications
HDDHard Disk Drive
IECInternational Electrotechnical Commission
ITIsolated Terra
LCSLocal Commissioning and Service
LEDLight-Emitting Diode
LVD (Directive) Low Voltage Directive
MCBMiniature Circuit Breaker
MPPMaximum Power Point
MPPTMaximum Power Point Tracking
NFPANational Fire Protection Association
PP is the symbol for active power and is
measured in Watts (W).
PCBPrinted Circuit Board
PCCPoint of Common Coupling
The point on the public electricity network to
which other customers are, or could be,
connected.
PEProtective Earth
PELVProtected Extra-Low Voltage
PLAPower Level Adjustment
P
NOM
POCPoint of Connection
P
STC
PVPhotovoltaic, photovoltaic cells
RCDResidual-Current Device
RCMUResidual Current Monitoring Unit
R
ISO
ROCOFRate Of Change Of Frequency
QQ is the symbol for reactive power and is
SS is the symbol for apparent power and is
STCStandard Test Conditions
SWSoftware
THDTotal Harmonic Distortion
TN-STerra Neutral - Separate. AC Network
TN-CTerra Neutral - Combined. AC Network
TN-C-STerra Neutral - Combined - Separate. AC
TTTerra Terra. AC Network
Power, Nominal conditions
The point at which the PV system is connected
to the public electricity grid.
Power, Standard Test Conditions
Insulation Resistance
measured in reactive volt-amperes (VAr).
measured in volt-amperes (VA).
Network
11
Table 1.2 Abbreviations
L00410644-01_2q / Rev. date: 2014-06-029
Introduction
1
1.2 Unpacking
Contents:
Inverter
•
Mounting plate
•
Accessories bag, containing:
•
6 wall plugs 8 x 50 mm
•
6 mounting screws 6 x 60 mm
•
1 M25 cable gland with sealing
•
grummet for Ethernet cables
2 x conduit bracket (2 in)
•
1 equipment grounding bolt M6 x 12
•
mm
Installation guide, booklet format
•
Quick guide, poster format
•
1.3 Identification of Inverter
1.4 Installation Sequence
1.Pay special attention to the important safety
instructions at the beginning of this manual.
2.Install the inverter according to 2.1 Environmentand Clearances, 2.2 Mounting the Mounting Plate,
and 2.3 Mounting the Inverter.
3.Open the inverter according to 2.5 Access to theInstallation Area.
4.Install AC according to 2.6 AC Grid Connection.
5.Install Ethernet according to 2.8.1 EthernetConnections.
6.Install PV according to 2.9 PV Connection.
7.Close the inverter according to 2.5 Access to theInstallation Area.
8.Turn on AC.
9.Finalise commissioning by using the Local
Commissioning and Service Tool (LCS Tool). The
tool is available from the download area at
www.sma.de. The hardware requirements for the
LCS Tool are:
PC running WindowsTM 7 and onwards
•
150 Mb HDD
•
2 Gb RAM
•
For setup via the LCS Tool, refer to 3.3 LCS Tool.
10.Turn on PV by turning on the PV load switch.
Refer to 2.9.2 Connection of PV.
11.Verify the installation by:
Inverter display: LED ‘On’ is solid green.
•
LCS Tool: In inverter view status is ‘On
•
grid’.
12.The inverter is now in operation.
Illustration 1.3 Product Label, Example
The product label on the side of the inverter shows:
Inverter type.
•
Important specifications.
•
Serial number, located under the bar code, for
•
inverter identification.
10L00410644-01_2q / Rev. date: 2014-06-02
Introduction
1.5 Overview of Installation Area
11
Illustration 1.4 Overview of Installation Area
PELV (Safe to touch)
2Equipment grounding
7Ethernet interface x 2
8RS-485 interface (not in use)
Live Part
1AC connection terminals
5PV connection terminals
Other
3Surge Protection AC
4Surge Protection DC
6PV load switch (optional)
Table 1.3 Overview of Installation Area
L00410644-01_2q / Rev. date: 2014-06-0211
2
Installation
2 Installation
2.1 Environment and Clearances
Illustration 2.6 Mount Upright on Vertical Surface. Backwards
tilt of up to 10 degrees is permitted
Illustration 2.1 Avoid Constant Stream of Water
Illustration 2.2 Avoid Direct Sunlight
Illustration 2.3 Ensure Adequate Air Flow
Illustration 2.4 Ensure Adequate Air Flow
Illustration 2.7 Prevent Dust and Ammonia Gases
NOTICE
When planning the installation site, ensure that the
inverter product label and warning labels remain visible.
For details, refer to 5 Technical Data.
Illustration 2.5 Mount on Non-flammable Surface
12L00410644-01_2q / Rev. date: 2014-06-02
Installation
2
2.2 Mounting the Mounting Plate
2
Illustration 2.8 Safe Clearances
NOTICE
Ensure 620 mm / 24 in base clearance for adequate
airflow.
L00410644-01_2q / Rev. date: 2014-06-0213
2
Installation
Illustration 2.10 Mounting the Mounting Plate
Illustration 2.9 Mounting Plate
NOTICE
Use of the mounting plate delivered with the inverter is
mandatory. If the inverter is mounted without the
mounting plate, the guarantee becomes void.
It is highly recommended to use all 6 mounting holes.
Mount the mounting plate:
Install in the defined environment.
•
Use screws and wall plugs that can safely carry
•
the weight of the inverter.
Ensure that the mounting plate is correctly
•
aligned.
Observe safe clearances when installing 1 or
•
more inverters, to ensure adequate airflow.
Clearances are specified in Illustration 2.8 and on
the mounting plate label.
Mounting multiple inverters in a single row is
•
recommended. Contact the supplier for
guidelines when mounting inverters in more than
1 row.
Ensure adequate clearance at the front, for safe
•
installation and service access to the inverter.
.
2.3 Mounting the Inverter
CAUTION
Refer to local health and safety regulations when
handling the inverter.
Procedure:
1.Lift the inverter. Locate the slots on the side of
the mounting plate. Use M12 or ½ in lifting bolts
and matching nuts (not part of delivery).
Illustration 2.11 Position the inverter
14L00410644-01_2q / Rev. date: 2014-06-02
Installation
2
Illustration 2.12 Lifting Bolts
2.On the inverter, position the side screws against
the mounting plate slots.
3.Push the inverter as shown so the side screws
slide into the 2 lower slots and the 2 upper slots.
See Illustration 2.13 and Illustration 2.14.
2.4 Removing the Inverter
Procedure:
1.Perform removal in the reverse order of
mounting.
2.Lift the inverter.
3.Lift and slide the inverter out of the mounting
plate slots.
4.Lift the inverter free of the mounting plate.
2.5 Access to the Installation Area
DANGER
Before starting work on the inverter, switch off AC at the
mains switch and PV using the PV load switch. Ensure
that the inverter cannot be unintentionally reconnected.
Use a voltage tester to ensure that the unit is disconnected and voltage free. The inverter can still be charged
with very high voltage at hazardous levels even when it
is disconnected from AC grid and solar modules. Wait at
least 5 minutes following disconnection from grid and
PV panels before proceeding.
2
Illustration 2.13 Slide into Slots
CAUTION
Observe ESD safety regulations. Discharge any electrostatic charge by touching the grounded enclosure,
before handling any electronic component.
Procedure:
1.To open the cover, loosen the 3 lower front
screws using a TX 30 screwdriver. The screws are
captive screws and cannot fall out.
2.
Lift the cover 180°. A magnet holds the cover
open.
3.To close the cover, lower it into place and fasten
the 3 front screws.
Illustration 2.14 Detail of Sliding into Slot
4.Check that the 4 side screws sit securely in the
mounting plate slots.
5.Release the inverter.
L00410644-01_2q / Rev. date: 2014-06-0215
2
Installation
Insulation Resistance Detection
The inverter has a built-in Insulation Resistance Detection /
ISO circuit, which is certified according to the UL 1741 for
Non-Isolated EPS Interactive PV Inverters. The Insulation
Resistance Detector performs a measurement of the
connected PV system resistance to ground before the
inverter connects to the grid. If the resistance is below the
grid code set value, the inverter will wait and re-measure
the resistance after a short while. When the resistance is
above the grid code set value, the inverter performs a selftest and connects to the grid.
Illustration 2.15 Loosen Front Screws and Lift Cover
2.6 AC Grid Connection
DANGER
These instructions for AC grid connection are for
qualified personnel only. To reduce the risk of electric
shock, do not perform any servicing other than that
specified in the operating instructions unless you are
qualified to do so.
CAUTION
For fuse and RCD information, refer to 5 Technical Data.
AC fuse rating must not exceed the ampacity of the
conductors used.
NOTICE
Wiring methods used shall be in accordance with the
National Electric Code, ANSI/NFPA 70, and the Canadian
Electrical Code, Part I.
Always observe local regulations.
All installers must observe the relevant wiring methods.
IMI Detection
The inverter has built-in IMI/RCMU (Insulation Monitoring
Interrupter / Residual Current Monitoring Unit). Certification is according to the UL 1741 for Non-Isolated EPS
Interactive PV Inverters. The IMI/RCMU circuit is 100%
single fault immune. It acts on a continuous ground fault
current and a sudden change in the ground fault current.
This functionality is running during normal operation.
Illustration 2.16 Installation Area
Illustration 2.17 AC Cable Wire Strip
The MLX inverter must only be connected to a 3-phase
grid.
16L00410644-01_2q / Rev. date: 2014-06-02
Installation
2
On the AC cable, strip insulation on all 4 wires. The
protective earth wire (PE) must be longer than the mains
wires. See Illustration 2.17.
1.Verify that the inverter rating matches the grid.
2.Ensure that main circuit breaker is released, and
take precautions to prevent connection.
3.Open the front cover.
4.Insert the cable through the AC gland to the
terminal blocks.
5.Connect the 3 mains wires (L1, L2, L3) and the PE
wire to the terminal block with the respective
markings. The PE wire is marked with the symbol
shown in Illustration 2.18.
6.Optional: Make an extra PE connection at the
secondary PE earthing points using the external
equipment grounding bolt delivered with the
inverter. See Illustration 5.2.
7.All wires must be properly fastened with the
correct torque. See 5.5 Torque Specifications.
2.7 Cable Entry
Options for cable entry
Cable glands (premounted), or
•
2-inch conduit adapters (supplied in accessories
•
bag)
If changing to the 2-inch conduit adapters, ensure to
tighten the screws in the order shown in Illustration 2.19
and Illustration 2.20. First tighten all screws with 0.75 Nm
(6.5 in-lbf) and then 1.5 Nm (13 in-lbf).
Illustration 2.19 AC Mounting Bracket
2
Illustration 2.18 Protective Earth Symbol
Terminal
AC
PV
Table 2.1 Acceptable Conductor Sizes
1)
Always observe current capacity of cables used.
1)
Range
16-95 mm
6-4/0 AWG
16-95 mm
6-4/0 AWG
Max. conductor temperature ratingConductor material Cable jacket diameter with supplied cable gland
2
90 ºCAl/Cu37-44 mm
2
90 ºCAl/Cu14-21 mm
2.8 Ethernet Connections
Before connecting Ethernet cables, refer to the
requirements in 5.8 Ethernet Connections.
Illustration 2.20 DC Mounting Bracket
Procedure:
1.Do not remove the RJ-45 connector on the
Ethernet cable.
2.Run the cables through the base of the inverter
via cable glands. See Illustration 2.21.
3.Cut slice in rubber grummet. Place the grummet
in the gland to ensure proper seal.
4.Plug into the Ethernet connector.
L00410644-01_2q / Rev. date: 2014-06-0217
Installation
2
5.Fasten cables with cable ties to ensure a durable
connection over time. See Illustration 2.22.
Illustration 2.21 Run Cables Through Cable Glands
CAUTION
PV array is floating, with both the (+) and (-) conductors
connected to the inverters' PV inputs. Neither conductor
is to be connected to earth.
A DC load switch on either the DC combiner or inverter
(optional) for safe disconnect of DC power to inverter is
required.
CAUTION
Do NOT connect PV to earth!
Illustration 2.22 Fasten with Cable Ties
2.9 PV Connection
2.9.1 External String Combiners
PV strings must be connected to the DC input via an
external string combiner. The purpose of the string
combiner is to combine the PV strings from the PV array
and secure the individual strings against overcurrent.
NOTICE
It is essential that all PV strings connected to the DC
combiner are even in number and type of modules and
tilt and orientation.
NOTICE
Observe correct fuse rating. Consult module manufacturers' manuals for information on correct string fuse
rating.
Use a suitable voltmeter that can measure up to 1000 V
DC. Verify the polarity and maximum voltage of the PV
arrays by measuring the PV open-circuit voltage. The
inverter is protected against reversed polarity and will not
generate power until the polarity is correct.
Illustration 2.23 Do Not Connect PV to Earth
The combined output from the DC combiner must be
connected to the DC input of the MLX inverter.
18L00410644-01_2q / Rev. date: 2014-06-02
Installation
2
2
Illustration 2.26 DC Label
2.10 Closure
Illustration 2.24 DC Connection Area
1.On the inverter or string combiner turn the PV
load switch into off position.
2.Connect the PV cables from the external string
combiner to the inverter. Ensure correct polarity,
see Illustration 2.25.
3.All wires must be properly fastened with the
correct torque. See 5.5 Torque Specifications.
Illustration 2.25 Connect to PV Input
1.Close the cover of the inverter installation area.
Fasten the 3 front screws. See 5.5 Torque Specifi-cations.
2.Turn on AC power.
L00410644-01_2q / Rev. date: 2014-06-0219
Initial Setup and Start
3 Initial Setup and Start
3
3.1 User Interface
The user interface comprises:
Local display, for all inverter variants. The local
•
display enables read-only status information of
the inverter. It is not possible to configure or set
up the MLX inverter via the display. The ‘#’ in the
display explains the operation modes.
Local Commissioning and Service Tool (LCS Tool).
•
The LCS Tool enables configuration of 1 or
multiple MLX inverters.
3.1.1 Operation Modes
The inverter has 5 operation modes, indicated by LEDs.
StatusLEDs
Green
Off grid
Connecting
On grid
Internal inverter event
Fail safe
- - - - - - - - - - - - - - - - -
Red
- - - - - - - - - - - - - - - - -
Green
▬██▬██▬██▬██▬██▬
Red
- - - - - - - - - - - - - - - - -
Green
Red
Green
Red
Green
Red
██████████████████
▬
- - - - - - - - - - - - - - - - -
▬██▬██▬██▬██▬██▬
- - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - -
▬██▬██▬██▬██▬██▬
▬
On grid (Green LED on)
#60.
The inverter is connected to the grid and energises the
grid. The inverter disconnects when:
it detects abnormal grid conditions (dependent
•
on grid code), or
an internal event occurs, or
•
PV power is insufficient (no power is supplied to
•
the grid for 10 minutes).
The inverter then enters connecting mode or off grid
mode.
Internal Inverter Event (Green LED flashing)
#54.
The inverter is waiting for an internal condition to be
within limits (for example a too high temperature) before
it will go back on grid.
Fail Safe (Red LED flashing)
#70.
If the inverter detects an error in its circuits during the selftest (in connecting mode) or during operation, the inverter
goes into fail safe mode, disconnecting from grid. The
inverter will remain in fail safe mode until power has been
absent for a minimum of 10 minutes, or the inverter has
been shut down completely (AC+PV).
3.2 Display
Table 3.1 Operation Modes
Off grid (standby) (LEDs off)
#0-51.
When no power has been delivered to the AC grid for
more than 10 minutes, the inverter disconnects from the
grid and shuts down. User and communication interfaces
remain powered for communication purposes.
Connecting (Green LED flashing)
#52-53.
The inverter starts up when the PV input voltage reaches
the minimum DC feed-in voltage. The inverter performs a
series of internal self-tests, including measurement of the
resistance between the PV arrays and earth. Meanwhile, it
also monitors the grid parameters. When the grid
parameters have been within the specifications for the
required amount of time (depends on grid code), the
inverter starts to energise the grid.
NOTICE
It can take up to 10 sec. until the display activates, after
power up.
The integrated display on the inverter front gives the user
access to information about the PV system and the
inverter.
20L00410644-01_2q / Rev. date: 2014-06-02
Initial Setup and Start
3
Illustration 3.1 Overview of Display Buttons and Functionality
KeyFunction
Adjust contrast level of display. Use
F1
F2
F3
F4
Home
OK
Arrow Up
Arrow Down
Arrow Right
Arrow Left
Back
On - Green LED
Alarm - Red LED
arrow up/down button while holding
down the F1 button.
Not in use
Return to main screen
Not in use
A step up
A step down
Toggles screen right
Toggles screen left
Return to main screen
IP address
•
Inverter Manager MAC address
•
Inverter software version
•
3.
Actual values. This section contains:
PV voltage and current
•
Phase-to-phase voltages
•
Phase currents
•
Grid frequency
•
3.2.1 Initial Setup via LCS Tool
The LCS Tool makes it possible to chose from a list of
predefined settings for different grids. All grid-specific
limits must be configured using the LCS Tool.
After installation, check all cables and close the inverter.
Turn on AC power.
WARNING
Correct selection of grid code is essential to comply with
local and national standards.
3.2.2 Turn PV Load Switch On
3
Table 3.2 Overview of Display Buttons and Functionality
The screen structure is divided into 3 sections:
1.
Main screen. Current and daily production. This
section contains:
Actual power output (kW)
•
Energy counter current day (kWh)
•
Total energy counter (kWh)
•
Current date
•
Current time
•
Operation mode (#)
•
2.
Inverter information. This section contains:
Inverter type
•
Inverter name
•
Serial no.
•
L00410644-01_2q / Rev. date: 2014-06-0221
Illustration 3.2 PV Load Switch
Turn PV load switch on, either via inverter or string
combiner.
3.2.3 Start-up
The inverter starts automatically if sufficient solar
irradiation is available. The start-up takes a few minutes.
During this period, the inverter performs a self-test
procedure.
NOTICE
The inverter is protected against reversed polarity. The
inverter does not generate power until any reversed
polarity is corrected.
3
Initial Setup and Start
3.3 LCS Tool
The MLX inverters and Inverter Managers must be commissioned via the Local Commissioning and Service Tool (LCS
Tool). Commissioning is required before the MLX inverters
can connect to the AC grid and start to convert power.
The LCS Tool is available from the download area at
www.sma.de.
The hardware requirements for the LCS Tool are:
PC running WindowsTM 7 and onwards
•
150 Mb HDD
•
2 Gb RAM
•
The LCS Tool must be installed on a local PC drive. The PC
must be connected to the Inverter Manager’s LAN 1 port
via Ethernet.
NOTICE
The Inverter Manager must have an IP address assigned
by a DHCP server on the LAN 1 port.
It is important that the PC running the LCS Tool is
connected to the same IP subnet as the Inverter
Manager.
Port LAN 2 is intended for MLX inverters exclusively.
Illustration 3.3 Commissioning of Inverters Using LCS Tool
1.Start up the LCS Tool. The tool displays a list of
all identified Inverter Managers. It can take
several minutes before the LCS Tool has
identified all Inverter Managers.
2.The screen now shows a list of all Inverter
Managers (see Illustration 3.4). To start the wizard,
click the Inverter Manager to be configured. By
clicking the Inverter Manager, the inverter(s)
discovered by the Inverter Manager are displayed.
Uncommissioned inverters (no grid code
assigned) are presented with a blue square
together with their software version.
22L00410644-01_2q / Rev. date: 2014-06-02
Initial Setup and Start
3
3
Illustration 3.4 LCS Tool - Initial Screen
3.Verify that date and time are correct. If not, set
date and time and continue. See Illustration 3.5.
Illustration 3.5 LCS Tool - Verify Date and Time
4.A list of inverters identified by the selected
Inverter Manager is shown. See Illustration 3.6.
Verify that the list of inverters is complete.
Verify that all inverters are present. It is possible
to continue the configuration of the listed
L00410644-01_2q / Rev. date: 2014-06-0223
inverters even if not all inverters are discovered.
The undiscovered inverters can always be
configured later.
3
Initial Setup and Start
Illustration 3.6 LCS Tool - List of Connected Inverters
5.Select the desired country from the list of options
available for the inverters in the network. See
Illustration 3.7.
6.Select the desired grid code from the list of
options available for the selected country. If
needed, load a custom grid code by clicking the
‘Load’ button. See Illustration 3.7. The ‘Create’
button is inactive and cannot be used.
Illustration 3.7 LCS Tool - Select Country and Grid Code
7.The LCS Tool prompts for a confirmation of the
selected country and grid code. See
24L00410644-01_2q / Rev. date: 2014-06-02
Illustration 3.8. Incorrect configuration can be
changed using the ‘Back’ button and changing
the settings in the previous windows.
Initial Setup and Start
3
3
Illustration 3.8 LCS Tool - Verification of Country and Grid Code
8.The system now applies the selected grid code to
the Inverter Manager and the discovered
inverters. Any inverter added at a later stage
automatically inherits the same grid code. Only 1
grid code per Inverter Manager is possible.
NOTICE
It is essential to choose the correct grid code. The grid
code cannot be changed afterwards without contacting
SMA.
9.A green square identifies the commissioned
inverters. However, the inverters do not connect
to grid before a ‘Start’ command is issued from
the bar below the top menu. See Illustration 3.9.
L00410644-01_2q / Rev. date: 2014-06-0225
3
Initial Setup and Start
Illustration 3.9 LCS Tool - List of all Inverters Connected to the Inverter Manager
10.If sufficient PV power is present and the grid
code conditions are met, the inverters connect to
the grid.
11.Upon commissioning, it is possible to download a
commissioning report under the menu ‘Reports’.
The report contains all information about inverter
settings, including actual disconnect values for
each inverter. See Illustration 3.10.
Illustration 3.10 LCS Tool - Commissioning Report
26L00410644-01_2q / Rev. date: 2014-06-02
Initial Setup and Start
3
NOTICE
If the desired grid code is not available, or if the LCS
Tool warns about incompatible software versions, the
grid code and software library must be updated on the
LCS Tool.
For utility-interactive inverters, field adjustable trip limits
and trip times can be altered from default settings. See
5.2 Trip Settings. After user registration and authorisation,
authorised service personnel can generate new grid code
settings at www.sma.de. The new grid code settings can be
downloaded as a file and applied to the MLX inverters via
the LCS Tool. These grid code files are encoded and can
only be used for the particular installation.
3
L00410644-01_2q / Rev. date: 2014-06-0227
Service
4Service
4.1 Troubleshooting
The information is organised in tables showing messages
appearing in the LCS Tool, known as events. The tables
contain descriptions of events as well as explanations of
which actions to take when an event occurs.
4
Event Type
ID
Display
Description
Action
DNO
Hotline
PV
Indicates whether the event relates to grid, PV, internal or fail safe issues.
The specific event ID.
Text shown in display.
Description of the event.
Description of which action to take prior to contacting any other parties.
If the prescribed action has not identified the malfunction, contact the DNO for further assistance.
If the prescribed action has not identified the malfunction, contact the inverter hotline for further assistance.
If the prescribed action has not identified the malfunction, contact the PV supplier for further assistance.
Grid-related Events
IDStatus
DescriptionActionDNO Hotline PV
message
1–6Grid voltage too low.Check voltage and AC installation. If the voltage is
zero, check the fuses.
7–9Grid voltage average over 10 minutes
too high.
10–15 Grid voltage too high.Check voltage and AC installation.x-16–18 The inverter has detected a voltage peak
on the grid.
19, 22 Grid frequency too low or too high.Check grid frequency.x-31–33 DC grid current too high.For repeated daily occurrences, perform onsite grid
34–37 Residual Current Monitoring Unit (RCMU)
has measured an excessive current.
40AC grid notOKThe AC grid has been out of range for
more than 10 minutes (frequency and/or
voltage).
41–43 Fault ride through. The inverter has
detected that grid voltage was below or
above a certain level.
48, 51 Grid frequency too low or too high.Check grid frequency and AC installation.x-54–56 DC grid current too high (stage 2).For repeated daily occurrences, perform onsite grid
61Loss of mains, open phase detected.If the event reoccurs several times each day, contact
62Loss of mains.If the event reoccurs several times each day, contact
Check that the installation is correct according to
the installation guide. If so, increase the mean
voltage limit according to 3.3.1 Getting Started.
Check voltage and AC installation.x--
analysis.
Turn both DC and AC off and wait until the display
turns off. Then turn on DC and AC and observe if
the event reoccurs.
Visual inspection of all PV cables and modules.
Check grid frequency, grid voltage, SW version, and
grid code setting.
If this event is reported several times each day,
perform onsite grid analysis.
analysis.
the DNO.
the DNO.
x--
x--
-x -
-x -
x--
x--
x--
x--
Table 4.1 Grid-related Events
28L00410644-01_2q / Rev. date: 2014-06-02
Service
4
PV-related Events
IDStatus
DescriptionActionDNO Hotline PV
message
103PV current is too
high/waiting
115,
PV ISO too lowThe resistance between ground and PV
260
258PV voltage too
high/waiting
278DC voltage high warning.Check that PV installation and layout correspond
Table 4.2 PV-related Events
Too many PV modules connected in
parallel. Should only appear on newly
installed systems.
is too low for the inverter to start up.
This will force the inverter to make a
new measurement after 10 minutes.
DC voltage is too high.Check that PV installation and layout correspond
Check number of strings in parallel and current
ratings. Has the current limit been exceeded?
Reconnect strings in parallel.
Make a visual inspection of all PV cables and
modules for correct installation according to the
installation guide. The event could indicate that
the PE connection is missing.
to recommendations in the manuals.
to recommendations in the manuals.
-x x
-x x
-x x
-x x
Internal Events
IDStatus
DescriptionActionDNO Hotline PV
message
201–208 The internal temperature of the inverter is
too high.
209, 210 Voltage on DC bus is too high.If event persists, reset the inverter by discon-
211Fan rpm low Fan speed is too low.Check if the inverter fan is blocked.-x213–215 Internal error. Voltage measured before and
after the relay differs too much.
216–218 Current measured on AC side is too high.Call service.-x219–221 Internal error. Voltage measured before and
after the relay differs too much.
225–240,
275
241, 242,
245, 249
248Internal CPU error.Restart the inverter. If event persists, call
252–254 Current measured on AC side is too high.If the event is repeated, call service.-x243, 263 Internal error.Restart the inverter. If event persists, call
279Temperature sensor error.If the event is repeated, call service.-x280Self-test 24-hour timeout. Self-test must run
281Too many RCMU events during the past 24
282Grid code settings invalid.Restart the inverter. If event persists,
283Gatedrive error.Restart the inverter. If event persists, call
Failure in memory/EEPROM.Restart the inverter. If event persists, call
Internal communication error.Restart the inverter. If event persists, call
at least once per 24 hours.
hours.
Only 4 automatic reconnect attempts after
event 34 is allowed during a 24-hour period.
The inverter will automatically try to
reconnect after a certain period.
Check that the inverter is not covered and
that the ventilation duct is not blocked.
necting DC and AC, using the switches. If the
event is repeated, check the maximum PV
voltage using the display to see if it is above
the limits.
Call service.-x-
Call service.-x-
service.
service.
service.
service.
None.---
Wait up to 24 hours. If event 34 also occurs,
follow the action for event 34.
reconfigure the grid code settings.
service.
-x -
-x -
-x -
-x -
-x -
-x -
-x -
-x -
-x -
4
L00410644-01_2q / Rev. date: 2014-06-0229
Loading...
+ 123 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.