INSTALLATION AND MAINTENANCE INSTRUCTIONS
REVISED
by the Graphic Development Department
Please review all content carefully.
HFS-MM Miniature Monitor Module
SPECIFICATIONS
Nominal Operating Voltage: 15-32 VDC
Average Operating Current: 375µA maximum (group poll); 350 µA (direct poll); 600 µA Max. (Communicating, IDC Shorted)
EOL resistance: 47K Ohms
Maximum SLC Wiring Resistance: 40 Ohms
Maximum IDC Wiring Resistance: 1,500 Ohms
Maximum IDC Voltage: 11 Volts
Maximum IDC Current: 450µA
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% Non-condensing
Dimensions: 1.3˝ H x 2.75˝ W x 0.5˝ D
Wire Length: 6˝ minimum
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The HFS-MM minitature monitor module can be installed in a single gang
junction box directly behind the monitored unit. Its small size and light weight
allow it to be installed without rigid mounting (see Figure 1). The HFS-MM is
intended for use in intelligent, two-wire systems where the individual address
of each module is selected using rotary switches. It provides a two-wire initiating device circuit for normally open contact fire alarm and security devices.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to listed-compatible control panels only.
FIGURE 1:
MOUNTING AND WIRING
NOTE: This module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances and regulations.
1. Connect the red (+) and black (–) wires to the positive and negative loop
power leads of the signaling line circuit (SLC).
2. Connect the violet (+) and yellow (–) wires to a two-wire, normally open
initiating loop.
3. Install the specified EOL resistor value to terminate the initiating loop.
4. Reference the control panel device address map to determine appropriate
addressing.
5. Set the address on the module per job drawings.
6. Install the module in the desired mounting location.
FIGURE 2. TYPICAL 2-WIRE STYLE B INITIATING DEVICE CIRCUIT
CONFIGURATION:
UL LISTED
COMPATIBLE
CONTROL
PANEL
(+)
SIGNAL LINE CIRCUIT (SLC)
(–)
Northford, CT 06472-1653
I56-3487-000
12 Clintonville Road
Phone: 203.484.7161
TO
NEXT
DEVICE
0
ALL WIRING
SHOWN IS
SUPERVISED AND
POWER LIMITED
15
14
13
12
11
10
9
TENS
YELLOW
VIOLET
0
1
2
3
4
5
6
7
8
(–)
1
2
3
4
5
9
6
8
7
ONES
(+)
(+)
(–)
BLACK
RED
47k EOL
INCLUDED
C0614-02
C1063-00
HW-460-016 1 I56-3487-000
©2009 Honeywell International, Inc.