
SIEMENS
MAMMOMAT
MAMMOMAT
MAMMOMAT
K
3
3-Stereo
C3
[X
Generator
Setting
Register
RXB7-211.032.01.03.02
Replaces:RXB7-211.032.01.02.02
Weitergabe
Mitteitung
zugestanden.
Rechte
sowie
ihres
Zuwiderhandlungen
får
den
Fall
Vervielfaltigung
Inhalts
der
Instructions
4
dieser
gestattet,
verptkchten
oder
Unterlage,
sowerl
GM-£intragung
nicht
Patenterteilung
Verwertung
nicht
zu
Schadenersst2.
und — Proprieiry
ausdrücklich
Alle
vorbehalten
data,
Contié à uitre
Contiado
como
de
company,
secret
secreto
confidential.
d'entreprise.
industrial.
Nos
AH
rights
Tous
droits
reservamos
englisch
reserved.
resérvês
todos
los
03.93
derechos

2
Setting
Instructions
Cover
sheet
Contents,
1
2
Prerequisites
Line
revision
Meters
Tools
Notes
Important
Checking
X-ray
Checking
Protetive
required
on
decree
connection
Checks
Line
voltage
Measuring
Checking
Checking
level
and
aids
these
notes
and
and
measures
before
the
the
the
required
instructions
on
start-up
recording
recording
and
powering
and
line
frequency
line
internal
line
voltage
supply
voltages
for
the
for
the
power
up
the
resistance
in
the
area
of
DHHS
supply
generator
generator
application
area
of
application
of
the
Contents,
Page
1
2
1-1
1-1
1-1
1-1
1-1
1-2
1-2
1-3
2-1
2-1
2-1
2-1
2-2
2-2
Rev.
Rev.
03
03
03
03
3
Siemens
Medizinische
Inspection
AG
and
Checks
Checking
Checks
Preparations
Checks:
mAs
Technik
without
the
with
radiographic
values
testing
high
rotating
high
voltage
voltage
anode
voltage,
tube
current
and
3-1
3-1
3-1
3-2
3-2
3-3
RXB7-21
1.032.01.03.02
03
Rev.
03

Prerequisites
1-1
Meters
-
Line
resistance
-
Oscilloscope
-
Digital
-
Densitometer
-
Service
cable
-
Normi 7 test
or
SIB
Note:
Tools
Usual
Notes
required
assembly
and
aids
required
meter
e.g.
TEKTRONIX
multimeter
PC
e.g.
e.g.
(e.g.
Siemens - Nixdorf
(PC-Generator)
body
phantom
For
under
Type
safety
no
reasons,
circumstances
oscilloscope.
For
those
falsify
measurement).
measurements
the
measuring
tools.
on
these
instructions
44
15
FLUKE
PDA
81
part
no.
(provided
42
001
the
733
RV090
314
8000 A MAS
PCD
96
60
978
by
the
customer)
(PTW
or
existing
be
disconnected
in
which
result,
use
3NSX/20
RE999
INAK)
PE
conductor
any
the
differential
or
similar)
when
resulting
in
the
operating
ground
amplifier
with
power
loops
(difference
connecting
cord
must
the
may
-
Checks
marked
- — If
brackets
numbers
wiring
diagram
important
The
MAMMOMAT
only
the
function
When
these
changed
The
in
The
-
the
instructions,
and
measured
the
test
Service
Section.8
and/or
with
adjustments
the
radiation
appear
in
the
brackets
containing
notes
2
is
tests
measurements
these
the
equipment
values
certificate
PC
is
required
Start-up
Programming
Setting
Setting
techniques)
in
the
text
indicate
on
start-up
adjusted,
to
be
performed.
to
be
indicate
is
marked
provided.
only
and
functional
the
the
"Sensitivity"
the
"Sensitivity
which
warning
must
symbol 4 .
after a switching
the
page
the
switching
programmed
made
(kV,
that
the
settings
fully
serviceable.
with > shall
for
programming
test
of
"Correction
(film
correction“
be
made
element,
and
element.
and
más,
etc.)
be
entered
the
lontomat
curve"
density)
(adaptation
with
X-rays
circuit
tested
made
are
path
in
within
in
in
according
PM
switched
e.g.
(G2162-6/1A),
number
the
factory,
the
the
factory
the
“Start-up”
to:
to
different
on
of
the
leaving
tolerances
have
not
column
exposure
are
the
in
Siemens
Medizinische
AG
Technik
RXB7-211.032.01.03.02
Rev.
03

Prerequisites
-
Section.9
-
Section.10
Further
Final
Recording
Setting
Reading
the
programming
procedures
the
programmed
real-time
the
exposure
clock
counter
values
and
deleting
the
error
memory
Note:
Checking
X-ray
In
certificate
Only:
must
acceptance
Furthermore,
completed
the
decree
area
-
cut-off
-
resolution
-
output
be
determined
Checking
In
the
area
checks
Schedule
supplements
must
If
the
generator
approximately 5 seconds
and
recording
of
application
is
supplied,
dose
of
values
test
certificate.
the
front
with
the
operator's
and
recording
of
application
be
made
and
User’s
to
the
operating
is
of
most
the
film/screen
of
ihe
by
the
page
of
according
Spot
switched
for
the
German
of
which
constancy
owner
of
the
data.
for
DHHS
Checks"
instructions"
off
with
before
the
is
systems
of
the
acceptance
the
regulations,
to
the
switching
area
X-ray
completed
used
test
eguipment
DHHS
instructions
RB7-211.101...
RB7-211.203...).
the
Service
it
of
application
decree,
in
the
and
test
certificate
area
additional
"DHHS
(included
PC
connected,
on
again.
an
acceptance
factory.
recorded
must
of
application
measurements
Maintenance
in
in
the
of
the
also
"DHHS
wait
the
test
be
and
Siemens
Medizinische
AG
Sec.
Sec.
Sec.
Sec.
Sec.
Sec.
Sec.
Sec.
The
Some
Technik
Required
Radiation-on
Manual
Check
labels
termination
the
Reproducibility
kVp-accuracy
mAs-accuracy
Automatic
results
of
the
must
values
indicators
maximum
exposure
be
recorded
to
be
of
exposure
adjustable
control
in
"Test
determined
mAs
with
certificate"
can
be
taken
the
following
RB7-211.037....
from
the
kV-values
test
certificate.
RXB7-211.032.01.03.02
Rev.
03

Prerequisites
1-3
Protective
-
Prior
with
Note:
-
To
prevent
S2
(SS)
SS
relay).
Note:
Note:
measures
to
any
intervention
the
main
switch.
が
the
system
voltage
Z1,
as
sheet X 2117-15-).
on
After
380 V d.c.
be
voltage
minutes;
-
-
will
transformer
the
line
connection
accidental
p.c.
board
shut-down
present
indicated
will
the
The
p.c.
requiring
contact
Before
equipment.
removing
in
the
is
only
still
be
present
T1,
triggering
D702
of
by
LÉD
drop
to
LED
extinguishes
boards
particular
and
place
equipment,
switched
transformer
terminal
to
“OFF”
the
on
the
V24
less
contain
care
only
or
inserting a p.c.
off
at
the
of
high
system,
intermediate
on
p.c.
than
electrostatic
in
on a conductive
disconnect
at
the
deck
generator
T10
and
of
the
stand
voltage
(position
there
board
30 V within
at
their
2)
may
about
handling
board,
and
circuit.
D710.
30
it
from
the
or
with
S2/D711,
line
connection,
also
p.c.
board
(see
wiring
radiation,
(no
activation
still
be
This
This
about
V.
highly-sensitive
(ground
support;
switch
set
about
will
3
before
see
off
power
D711
diagram
the
of
the
components
TI
219).
the
supply
line
line
filter
as
switch
making
well
Siemens
Medizinische
AG
Technik
RXB7-21
1.032.01.03.02
Rev.
03

Line
connection
and
power
supply
2-1
Checks
e
On
pic.
Set
-
Set
-
Set
Line
Note:
The
(see
But
done
fuses)
voltage
equipment
test
if,
nevertheless,
at
the
in
Measuring
before
board
switch
switch
switch
powering
0702:
S1
(UZW)
S2
(SS)
S3
to
and
With
single-phase
711)
must
be
(Jumpers
With
fuses!
certificate)
transformer T 10
accordance
in
two-phase
has
already
and
reconnection
the
line
with
to
to
"OFF"
position
line
frequency
supply,
bridged
the
service
supply,
been
adjustment
as
the
internal
up
the
"OFF"
(position
1
the
according
bag)
fuse
set
to
for
well
wiring
diagram X 2117 - 15.
resistance
generator
(position
fuse
to
holders
to
the
required
the
line
the
line
as
p.c.
2)
2)
holders
the
wiring
F20
frequency
voltage
board
F20
and
line
is
necessary,
D711
and
F5
diagram
F5
must
voltage
is
not
(insertion
(on
board
on
page
be
fitted
in
the
needed.
this
or
removal
D
15!
with
factory
must
be
of
Siemens
Medizinische
AG
Remove
Connect
System
Carry
e...
System
To
achieve
values:
if
the
with
Section
Technik
out
above
F10
and
line
resistance
contactor
measurement
contactor
the
full
output,
MAMMOMAT
0.25
Ohm
0.45
Ohm
0.50
Ohm
0.60
Ohm
0.65
Ohm
0.85
Ohm
values
5.
F20.
"ON"
"OFF"
are
meter
to
fuse
the
resistance
3/Stereo
at
110
V
at
208
V
at
230
V
at
240
V
at
277
V
at
400 V (2-phase)
exceeded,
reduce
holders
measured
MAMMOMAT
0.35
0.70
0.80
1.00
1.05
1.40
the
generator
F10
must
Ohm
Ohm
Ohm
Ohm
Ohm
Ohm
and
at
at
at
at
at
at
F20.
not
exceed
C3
110
V
208
V
230
V
240
V
277
V
400
V
power
RXB7-211.032.01.03.02
the
in
accordance
following
Rev.
03

2-2
Fig.1
Line
connection
and
power
supply
Checking
Remove
System
Measure
Check
T10
and
System
Re-insert
System
-
There
and
3
(X
2117
-
There
filter
Z1
Checking
The
correct
en
set
in
e
Switch
-
The
following
the
line
F10
and F20
contactor
voltage
that
the
line
board
contactor
F10 and
contactor
must
be
-15-)
must
be a voltage
(mechanically
the
supply
supply
the
factory.
on
the
generator
diodes
voltage
"ON"
at
voltage
D711
"OFF"
F20
"ON"(Do
230 V (+10%,
F10
in
amd
agrees
not
between
behind
the
generator
F20
with
swiich
-15%)
195 V and
transformer
voltages
voltages + 5V, + 15
Only a visual
must
be
V
39
V38
V
41
V
40
check
"on"
{
(-15V)
(
(
the
generator
at
transformer
V,-15
of
the
on
p.c.
voltage
T1;
function
board D 704:
plugged
on
yet)
T1
264 V at
3/Fig.
Vand
1)
+
is
on
(2/Fig.1),
the
output
(X
2117
24 V have
therefore
transformer
terminals
of
the
line
-21-)
already
needed.
1
be-
Siemens
Medizinische
AG
Technik
RXB7-211.032.01.03.02
Rev.
03

Inspection
For
tungsten
tube
and
testing
P49 W 0.3
For
molybdenum
tube
P49
MO
3-7
0.3
M , 30
40
mm
4
FOOT
TTT
Fig.
9
30
kV
150
mA
100
ms/T
KV,
lontomat
Plexiglas
suli
wha
1V/T
1
WT
(ti = depending
with
grid
(P = 4.5
+
+
E
т I
ahi,
RT
AO
AA
аа
TATA
+ +
>
(1 T = 5 kV)
(1 T =
40
mA)
on
progr.
kW)
ана
ааа
sensitivity)
M
40
p
maquina
30
120
100
,30
KV,
mm
Plexiglas
LL
kV
mA
ms/T
lonto.
w.
grid
+
그
+
nh
1V/T
1V/T
(t = depending
sensitivity)
+
И
+
(1 T 4 5 kV)
(1 T =
(P = 3.6
「
기
ΣΤ
bonnet
kW)
11111
PŘÁT:
40
mA)
on
progr.
Fig.
>
1
10
Siemens
Medizinische
AG
Technik
RXB7-211.032.01.03.02
Rev.
03

Start-up
Checking
9
Use
9
Operation
9
Connect
D
702
9
Generator
and
and
the
must
functional
programming
Service
service
of
be
and
PC
the
Service
PC
set
Service
to
to
check
PC
on
board
position
PC
test
with
and
is
described
D702
1.
"ON"
of
the
program
using
the
IONTOMAT
service
the
IONTOMAT
in
section
connection
PC
11
cable,
PM.
the
PM
switch
S3
on
4-1
board
Display
ci>
a\>
Your
name
Password
Main
menu
Configuration
ΙΟΝΤΟΜΑΤ
Sensitivity
IONTOMAT
Corr.
curve
please
please
ΡΜ
PM
Entry
required
{A:}
{B:} < Enter>
MAMC2 < Enter
BENUTZERNAME
mæt
<|>
<|> <1>
<|>
<i>
< 一 >
1...31.0
<|>
<F2>
0...10
€
<1>
<>
<i>
<e>,
<F
<1>
Enter
2>
>
<Enter>
<Enter>
<Enter>
<Enter>
>
<Enter
<Tab>
>
Remarks
According
disk
drive
see
seclion
Select
Select
"Configuration"
"IONTOMAT
ne
Select
Program
tivity)
system
2
Save
Select
Program
according
stem
Two
"Sensitivity"
according
used,
different
data
“Corr.
used,
different
to
Service
names
7
the
plug
sections
systems
with
curve”
the
correction
to
the
sections
systems
PC
subroutine
PM"
subroutine
positions
to
the
film-screen
8-2
are
possible.
<F2>
subroutine
curve
film-screen
8-2
are
subrouti-
(Sensi
and
8-3.
sy-
and
8-3.
possible.
IONTOMAT
Configuration
Main
Siemens
Medizinische
AG
menu
Technik
PM
<ESC>
<ESC>
<F
10>
Program
exited.
RXB7-211.032.01.03.02
Rev.
03

Start-up
and
functional
test
of
the
IONTOMAT
PM
4-5
Checking
e
Make
used
and
density
e
If
necessary,
Service
the
e
Before
e
Different
exposure
The
following
For
MAMMOMAT
Exposures
Exposures
Magnification
For
MAMMOPMAT
Exposures
Exposures
Magnification
the
film
test
exposures
check
of
1.5
or
correct
PC
triggering
film
density
techniques
corrections
with
without
with
without
density
at
the
film
the
density
the
section
(see
the
test
corrections
with
C3
grid:
grid:
technique:
3
and
grid:
grid:
technique:
30
kV
with
density
in
required
programmed
8-1)
exposures,
can
the
"Sens-cor”
are
possible:
same
same
Select
MAMMOMAT
2
cm
Plexiglas
each
case.
by
the
sensitivity
select
be
programmed
module.
"Sens-cor”
"Sens-cor"
"Sens-cor”
-Stereo
different
"Sens-cor”
system
different
"Sens-cor”
system
different
system
"Sens-cor”
Selection
the
magnification
for
The
films
customer.
values
"Main
menu"
for
for
with
is
made
table.
all
film-screen
must
either
(plug
positions)
for
the
different
all
radiographic
all
radiographic
[fl]
manually
for
each
radiographic
for
each
radiographic
for
each
radiographic
automatically
systems
have
systems
systems
by
attaching
a
using
Siemens
Medizinische
AG
Technik
RXB7-211.032.01.03.02
Rev.
03

Appendix
Working
ょ
ーーー ニ ーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーーー
Description
with
Password
The
In a confidential
were
Regarding
of
<
>
the
Service
protection
Mammomat
informed
the
the
syntax
The
PC
software
circular,
-
-
about
password,
the
used
in
indication
is
protected
the
Technical
Service
password.
please
these
instructions:
of
which
characters.
For
CAPITALS
example:
Capital
For
example:
letters
<Enter>,
indicate
the
name
by a password.
Managers
Managers
ask
your
function
<ESC>
data
which
of a register,
and
manager.
keys
to
etc.
must
files
the
press
be
is
entered
etc.
given
unchanged.
between
mn,
these
Italics
Bold
XX yy
ZZ
ts
Notes!
kk
kk
i
Menu
selection:
italics
For
example:
entered.
Square
nally
entered.
Data
relating
appears
wing
entry
This
character
sed.
Data
can
Curved
the
other,
Important
When
When
they
are
Selection
The
module
represent
For
brackets
to
on
the
be
entered
brackets
one
remarks
the
password
several
shown
is
made
selected
data
in
user
enclose
formats,
monitor
indicates
in
indicate
must
be
are
indicated
is
menus,
in a box
with
which a value
name,
selected.
entered,
programs,
the
is
the
name
additions
user
screen
that
piace
that
(program
keys < f > and < |
highlighted
to
entries
and
at
this
of
"x,
out
of
in a
only
files
window).
commands
etc.
which
point
y,
several
box.
these
in
should
of
the
shown
is
the
2"
(e.g.
characters
etc,
are
the
display.
be
entered.
technician
which
bold
important
space
day's
terms
listed
presented
>.
may
and
for
key
must
date).
are
should
as
the
one
shown..
for
selection,
be
be
optio-
it
follo-
be
pres-
below
Siemens
Medizinische
AG
Technik
RXB7-211.032.01.03.02
Rev.
03