Schneider Electric VBB Series, VBS Series Selection Guide

Selection Guide
VBB/VBS Series Ball Valve Assemblies
Application
The VBB and VBS Series valves with SmartX Actuators are 2-Way or 3-Way, 1/2” or 3/4”, characterized ball valves. The M3 and M2 SmartX Actuators are direct coupled to the VBB/VBS Series valves and accept two-position, floating or proportional control signals from a DDC system, controller, or thermostat for control of hot or chilled water, or solutions of up to 60% glycol. Typical applications include VAV reheat, fan coil units, hot and chilled water coils in air handling units, heat pumps and unit ventilators.
Features
• Easy product selection — all actuators fit all valve bodies.
• Fast, easy actuator installation — no linkage or tools required.
• Flow characterizing insert provides equal percentage flow characteristic for stable, accurate floating and proportional control.
• ANSI IV seat leakage (0.01%) for both 2-Way and 3-Way valves (A and B port).
• Brass and stainless steel trim models.
• Cvs from 0.3…10.
• Normally open, normally closed, and non-spring return assemblies available.
• Two-position, Floating or Proportional (0…5 Vdc, 0…10 Vdc, 5…10 Vdc, or 4…20 mA dc).
• Proportional actuator is direct or reverse acting.
• RoHS Compliant (VBS Assemblies).
• Reach Compliant.
Applicable Literature
• VBB and VBS Series Two-position Spring-Return Ball Valves Installation Instructions, F-27392.
• VBB and VBS Series Floating Spring Return and Non-spring Return Ball Valves Installation Instructions, F-27393.
• VBB and VBS Series Proportional Spring Return and Non­spring Return Ball Valves Installation Instructions, F-27394.
• VBB and VBS Series Brochure, F-27681.
• EN-205 Water System Guidelines, F-26080.
• EN-206 Guidelines for Powering Multiple Actuators, F-26363.
© 2019 Schneider Ele ctric . All rig hts res erve d. All tradema rks are o wned by S chneid er Elect ric Industries SAS o r its af filia ted comp anies. August , 2019 tc Docume nt Number: F-273 95-15
Selection Guide
Specications
ctuator
A
Voltage 24 Vac for oating and proportional
100…277 Vac for two position multi-voltage
types
Power Requirements
Control Signal 2-Position, Floating, or Proportional; half wave
Timing, Full Open to Full Close
Manual Operating Lever / Position Indicator
Auxiliary End Switch (optional)
Materials Thermoplastic base and cover.
Shipping & Storage Temperature Limit
Operating Temperature Limit
Proportional 32…140 °F (0…60 °C)
Two-Position 32…169 °F (0…76 °C)
at max uid temp.
Locations NEMA 2, IEC IP31. Indoor Use Only.
Valve
a
Service
System Static Pressure Limit
Fluid Temperature Limit 20…250°F (-7…121°C).
Cv (Kv) See Tables 4 through 7.
Close-o󰀨 Pressure
Di󰀨erential Pressure 30 psi normal operation
Seat Material PTFE
Characterized Insert Glass-lled PEEK
Seat Leakage ANSI class IV (0.01%) at both A and B
End Connections NPT threaded (VBxxNxx)
Rangeability Greater than 300:1.
Body Material Forged brass.
Stem Material Stainless steel anti-blow out stem with
Ball Material Chrome plated brass (VBB series)
a. Not rated for steam service.
b. Close-o󰀨 is dened as the maximum allowable pressure drop to which a valve
may be subjected while fully closed.
b
See Table-1, Table-2, and Table-3.
rectied power supply
See Table-1, Table-2 and Table-3.
Standard on all models.
SPST 24 Vac/Vdc, 101 mA…5 A max.
Approved for use in air plenums.
-40…169 °F (-40…76°C).
Floating 32…140 °F (0…60 °C)
Humidity 5…95% relative humidity,
non-condensing.
Hot and chilled water, up…60% glycol.
600 psi (4137 kPa).
130 psi 2-Way; 70 psi 3-Way
20 psi quiet operation.
ports with pressure at inlet.
dual Viton™ o-rings.
or stainless steel (VBS series).
Agency Listings
M2 SmartX actuators
M3 SmartX actuators:
UL 60730-1 & -2-14 and CSA E60730-1 & -2-14.
FCC part15 classB & ICES-003 classB emissions
European Union: LVD 2014/35/EU and EMC
2014/30/EU directives, per EN 60730-1 & -2-14.
EN 61000-6-2 immunity & EN 61000-6-3 emissions
Australia This product meets requirements to bear the RCM
Plenum Rating Actuators with terminal block or plenum cable leads
CRN Number CRN OC0970.9012345678NTY.
RoHS Compliant
VBS valves and M3/M2 actuators comply with
European Directive RoHS 2 Directive 2011/65/EU.
Please consult factory for part number specic
REACh Compliant
Compliant as dened in Article 33 of the REACh
North America: c-UL-us LISTED per
UL 873 and C22.2 No.24.
European Union: LVD 2006/95/EC and
EMC 2004/108/EC directives compliant.
North America: c-UL-us LISTED per
compliant.
compliant.
Mark.
are plenum rated.
compliance.
Regulation (EC)1907/2006.
Application Schematics
Typical applications
For simplicity, balancing valves and control devices are not shown.
Mixing applications
Typical Three-Way Fan Coil Application
Supply
Return
Bypass
B
AB A
AAB
Typical Two-Way Fan Coil Application
Return
Supply
August , 2019 tc © 2019 Schneider Ele ctric . All rig hts res erve d. All tradema rks are o wned by S chneid er Elect ric Industries SAS o r its af filia ted comp anies.
Document Number: F-27395-15
Loading...