Schneider Electric TK-1xxx Series, TK-5xxx Series Catalog Page

TK-1xxx Series, TK-5xxx Series
Single Setpoint Room Thermostats
For proportional temperature control of pneumatic valves and damper actuators to maintain room air temperatures in heating, ventilating, and air conditioning systems.
• Branch-line to sensing-element pneumatic feedback for linear, stable operation.
• Plastic cover supplied with exposed setpoint and thermometer.
• Cover inserts included for:
- Exposed setpoint only.
- Blank face plate with logo.
90 80 70 60 50
TK-1xx1
TK-1xxx-600
Aspirated Thermostat
(Shown in aspirated box without cover)
Model Chart
Model No.
Dial Markings
a
TK-1001 55 to 85°F
TK-1001-116 13 to 29°C
TK-1001-600 55 to 85°F
TK-1101 55 to 85°F
TK-1101-600 55 to 85°F
TK-1201 55 to 85°F
TK-1281 55 to 85°F
TK-1301
c
55 to 85°F
TK-1301-116 13 to 29°C
TK-1381 55 to 85°F
TK-1601
cd
55 to 85°F
TK-5001 55 to 85°F
TK-5001-116 13 to 29°C
TK-5101 55 to 85°F
TK-5101-116 13 to 29°C
a
Dial stop pins included to limit dual range on all units.
b
Direct Acting (D.A.) increases output pressure on temperature rise. Reverse Acting (R.A.) decreases output pressure on temperature rise.
c
A manual lever is provided to change the thermostat to “Day” when the system is on “Night” . The lever can be used to return to “Night” or the next cycle will return the thermostat to normal operation.
d
Has second white plastic tube to pass full line pressure (20 psi) at night and 0 psi at da y. Used to actuate items such as pressure electric switches.
Control Actionb
Supply Pressure
Direct Acting
Reverse ActingTK-1101-116 13 to 29°C
15 psig Reverse Acting
20 psig Direct Acting
20 psig ReverseActing
15 psig Direct Acting
Direct Acting
15 psig day 20 psig night
Reverse Acting
15 psig day 20 psig night
Direct Acting
15 psig day 20 psig night
Direct Acting
Reverse Acting
Type Thermostat
Two pipe
Two pipe with manual override
Three pipe with manual override
Single Pipe
F-27383-2 © Copyright 2008 TAC. All Rights Reserved. 93
TK-1xxx Series, TK-5xxx Series
InsertTK-xxxx Insert
Figure 1 Cover.
Aspirated model with #6 spanner head screws (requires AT-509) Note: Not available on TK-13xx, 16xx and 5xxx models.
-600
Figure 2 Aspirated Thermostat Cover.
Specifications
Thermostat Proportional type.
Sensing element Bimetal.
Night setback To 20°F (11°C) below day setpoint for Day/Night heating models.
Night setup To 20°F (11°C) above day setpoint for Day/Night cooling models.
Control dial range Refer to Model Chart.
Throttling Range Adjustable 2 to 10°F/10 psi, factory set at 4°F/10 psi.
Output air signal 0.5 psig to supply air pressure -0.5 psig.
Action Refer to Model Chart.
Ambient limits
Shipping -40 to 150°F (-40 to 65°C). 0 to 98% RH, non-condensing.
Operating 40 to 150°F (4 to 65°C). 10 to 98% RH, non-condensing.
Supply air pressure Clean, oil free, dry air required (refer to EN-123).
Nominal Refer to Model Chart.
Maximum 30 psig (207 kPa).
Air connections
Main (black) 5/32 in. dia. spring reinforced plastic tubing.
Branch (white) 5/32 in. dia. spring reinforced plastic tubing.
Air consumption for sizing air compressor
TK-1001, 1101, 12x1, 13x1 13.8 scim (3.8 mL/s).
Air capacity for sizing air mains
TK-1001, 1101, 12x1, 13x1, 16 scim (4.4 mL/s).
TK-16x1 32 scim (8.8 mL/s).
Cover Beige plastic.
Mounting Upright position on wall.
Dimensions 4-3/8 H x 2-3/4 W x 1-5/8 D in. (111 x 70 x 43 mm).
94
© Copyright 2008 TAC. All Rights Reserved. F-27383-2
Loading...
+ 1 hidden pages