TK-17xx Series
Dual Setpoint, Single Output Room Thermostats
For proportional control of pneumatic-actuated
valves and damper actuators to maintain room air
temperatures in heating, ventilating, and air
conditioning systems.
Features:
• Branch-line to sensing-element pneumatic feedback for
linear, stable operation.
• Plastic cover supplied with exposed setpoint and
thermometer.
• Cover insert included with a blank face plate with logo.
Model Chart
Model No.
Dial Range
TK-1717
TK-1727 Reverse Reverse
TK-1731 Reverse Direct
TK-1741 Direct Reverse
TK-1711
TK-1751
e
55 to 85°F
TK-1721
TK-1761
a
22 psi required if setpoints are more than 20°F apart.
b
Control dial is marked in °F on one side a nd °C on the other side. Units have built-in stops that can limit high and/or low setting of each dial.
c
Direct Acting (D.A.) ⎯ Increase output pressure on temperature rise.
Reverse Acting (R.A.) ⎯ Decrease output pressure on temperature rise.
d
For additional options or to reverse heat/cool legend, order cover replacement kit AT-46-500 Heat/Cool, Cool/Heat or Day/Night.
e
Units include a manual override lever for overriding 22 psig (152 kPa) operation and placing control into 15 psig (103 kPa) control mode when unit is
supplied with 22 psig (152 kPa). Lever automatically resets when supply pressure is reduced to 15 psig (103 kPa).
15 psig Supply Pressure
b
Control Action
c
Direct
Direct
Reverse Reverse
Cover Legend
Heat
Day
d
Dial Range
55 to 85°F
90
80
70
60
50
Day
Ngh
t
TK-17xx
20 psig Supply Pressure
b
Control Action
Direct
Direct
a
c
Cover Legend
Cool
Night
96
with
Insert
Figure 1 Covers.
© Copyright 2008 TAC. All Rights Reserved. F-27383-2