Field Devices Europe
FLOW CAPACITIES AND CLOSE OFF PRESSURE RATINGS
Two-way valves, VZ22
Valve Close Off Pressure (kPa)
DN k
VS
TAC Part no.
15 0.16 721-0702 1600
15
15
15
15
15
20
20
0.25 721-0706 1600
0.40 721-0710 1600
0.63 721-0714 1600
1.00 721-0718 1200
1.60 721-0722 1200
2.50 721-0726 400
4.00 721-0730 400
Three-way valves, VZ32
with Actuators MZ18A,
MZ18B, MZ18L
04
(180 N)
Valve Close Off Pressure (kPa)
DN k
VS
A AB
B AB TAC Part no.
with Actuators MZ18A,
15 0.25 0.16 731-0706 800
15
15
15
15
20
20
0.40 0.25 731-0710 800
0.63 0.40 731-0714 800
1.00 0.63 731-0718 250
1.60 1.00 731-0722 250
2.50 1.60 731-0726 240
4.00 2.50 731-0730 240
Three-way valves, VZ42
Valve Close Off Pressure (kPa)
DN k
VS
A AB
B AB TAC Part no.
with Actuators MZ18A,
15 0.40 0.25 741-0710 800
15
15
15
20
20
0.63 0.40 741-0714 800
1.00 0.63 741-0718 250
1.60 1.00 741-0722 250
2.50 1.60 741-0726 240
4.00 2.50 741-0730 240
MZ18B, MZ18L
(180 N)
MZ18B, MZ18L
(180 N)
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes.