Schneider Electric Modbus, Micrologic Data Bulletin

Modbus™ Communications System for Micrologic™ A, P, and H Trip Units
Class 0613
Data Bulletin
0613IB1201 06/2012
Retain for future use.
Table of Contents
List of Tables: ...................................................................................................................... 5
SECTION 1: MICROLOGIC COMMUNICATION SYSTEM ...................................................................................................... 9
Introduction ................................................................................................. 9
List of Abbreviations .................................................................................... 9
Communication System Parameters .......................................................... 9
Communication System Components ....................................................... 10
Micrologic A Trip Units ........................................................................ 10
Micrologic P and H Trip Units .............................................................. 10
Breaker Communication Module (BCM) .............................................. 10
Communication Switches .................................................................... 10
24 Vdc Control Power ......................................................................... 11
Daisy Chain 4-Wire Modbus Network ................................................. 11
Cradle Communication Module (CCM) ............................................... 11
Communicating Shunt Trip and Shunt Close Coils ............................. 11
Ethernet Gateway or Circuit Monitor ................................................... 11
Micrologic Trip Unit, BCM and CCM ................................................... 12
BCM to Daisy Chain ............................................................................ 13
BCM and CCM .................................................................................... 14
Modbus TCP / IP Communication ....................................................... 14
Standard Wiring Practices ........................................................................ 15
Communication System ...................................................................... 15
System Problems ...................................................................................... 16
Troubleshooting ........................................................................................ 16
Addresses, Baud Rate, and Parity Settings .............................................. 17
Micrologic A Trip Unit .......................................................................... 17
Micrologic P and H Trip Unit ................................................................ 18
SECTION 2: COMMUNICATION ARCHITECTURE ............................................................................................................... 19
Introduction ............................................................................................... 19
Module ................................................................................................. 19
Command Interface ............................................................................. 19
Modbus Functions ..................................................................................... 20
Breaker Communication Module: @ Address xx ................................ 20
Communication Profile ........................................................................ 20
Simplified Open/Close Command ....................................................... 20
Cradle Communication Module: @ Address xx + 50 .......................... 21
Metering Module: @ Address xx + 200 ............................................... 21
Protection Module: @ Address xx + 100 ............................................. 23
SECTION 3: COMMAND INTERFACE .................................................................................................................... 24
Operating Principle ................................................................................... 24
Send Commands in Shared Mode ............................................................ 25
Send Commands in Protected Mode ........................................................ 26
Optimize Sending of Commands .............................................................. 28
Remote Configuration ............................................................................... 28
Example of a Remote Parameter-Setting Sequence .......................... 30
SECTION 4: ACCESS TO FILES .................................................................................................................... 31
Introduction ............................................................................................... 31
Event Logs ................................................................................................ 31
Wave Form Capture (WFC) ...................................................................... 32
Event Log of the Breaker Communication Module @ Address xx ............ 32
Event Log of the Protection Module @ Address xx + 100 ...............................34
Event Log of the Metering Module @ Address xx + 200 .......................... 36
© 2012 Schneider Electric All Rights Reserved 3
Modbus® Communications System for Micrologic® A, P, and H Trip Units 0613IB1201 Table of Contents 06/2012
Maintenance Event Logs of the Protection Module
@ Address xx + 100 .................................................................................. 38
Maintenance Event Log of the Metering Module .......................................40
Min-Max Event Log of the Metering Module
@ Address xx + 200 .................................................................................. 42
Wave Form Capture ..................................................................................44
Fault Wave Form Capture ......................................................................... 46
SECTION 5: MODBUS FUNCTIONS .................................................................................................................... 48
Introduction ...............................................................................................48
Modbus / JBus Protocol ............................................................................48
Modbus Exception Responses .................................................................. 48
Standard Modbus Functions ..................................................................... 49
Advanced Modbus Functions .................................................................... 51
APPENDIX A: REGISTERS .................................................................................................................... 52
Formats ..................................................................................................... 52
Table of Registers ..................................................................................... 55
Structure of the Table .......................................................................... 55
Scale Factors .......................................................................................55
Breaker Communication Module @ Address xx .................................. 57
Cradle Communication Module @ Address xx + 50 ............................62
Metering Module @ Address xx + 200 ................................................64
Protection Module @ Address xx + 100 .............................................. 83
Advanced Protection Settings ............................................................. 94
Communication Profile @ Address xx ...............................................112
Activation of the Communication Profile ...................................... 112
I/O Status..................................................................................... 112
Metering....................................................................................... 115
List of Commands ...................................................................................121
Cradle Communication Module Commands @ Address xx + 50 ......121
Breaker Communication Module Commands @ Address xx ............ 122
Metering Module Commands @ Address xx + 200 ........................... 124
Protection Module Commands @ Address xx + 100 ......................... 126
Send Commands in Shared Mode Simplified Open / Close ..............127
Send Commands in Protected Mode .................................................128
Remotely OPEN the Circuit Breaker Commands ..............................129
Remotely CLOSE the Circuit Breaker Commands ............................ 130
Synchronize the Clocks Commands .................................................. 131
Remotely Configure and Set Commands .......................................... 132
Run Remote Resets / Preset Commands ......................................... 134
Manage the Event Logs— Breaker
Communication Module Commands ................................................. 135
Manage the Event Logs—Metering Module Commands ................... 136
Manage the Event Logs— Configure Analog Pre-Defined Alarm n°1:
Over Current Phase A Commands ....................................................137
© 2012 Schneider Electric All Rights Reserved4
List of Tables
Table 1: External 24 Vdc Control Power Supply Characteristics ............................................................. 11
Table 2: Breaker Communication Module Registers ............................................................................... 20
Table 3: Cradle Communication Module Registers ................................................................................. 21
Table 4: Metering Module Registers ........................................................................................................ 22
Table 5: Protection Module Registers...................................................................................................... 23
Table 6: Command Interface Registers................................................................................................... 25
Table 7: Shared Mode Registers in the Command Interface................................................................... 25
Table 8: Protected Mode Registers in the Command Interface............................................................... 26
Table 9: Command Result Codes............................................................................................................ 26
Table 10: Read-Accessed Commands ...................................................................................................... 27
Table 11: Descriptor of the Event Log in the Breaker Communication Module ......................................... 32
Table 12: Format of Records in the Event Log of the Breaker Communication Module............................ 33
Table 13: Events in the Event Log of the Breaker Communication Module............................................... 33
Table 14: Descriptor of the Event Log in the Protection Module................................................................ 34
Table 15: Format of Records in the Event Log of the Protection Module .................................................. 35
Table 16: Events in the Event Log of the Protection Module..................................................................... 35
Table 17: Descriptor of the Event Log in the Metering Module.................................................................. 36
Table 18: Format of Records in the Event Log of the Metering Module .................................................... 37
Table 19: Events in the Event Log of the Metering Module ....................................................................... 37
Table 20: Descriptor of the Maintenance Event Log in the Protection Module .......................................... 38
Table 21: Format of Records in the Maintenance Event Log of the Protection Module............................. 39
Table 22: Descriptor of the Maintenance Event Log in the Metering Module ............................................ 40
Table 23: Format of Records in the Maintenance Event Log of the Metering Module............................... 41
Table 24: Descriptor of the Min-Max Event Log in the Metering Module ................................................... 42
Table 25: Format of Records in the Min-Max Even Log of the Metering Module....................................... 43
Table 26: Descriptor of the Wave Form Capture in the Metering Module.................................................. 44
Table 27: Format of Records in the Wave Form Capture of the Metering Module .................................... 45
Table 28: Descriptor of the Fault Wave Form Capture in the Protection Module ...................................... 46
Table 29: Format of Records in the Fault Wave Form Capture of the Protection Module ......................... 47
Table 30: Read Functions.......................................................................................................................... 49
Table 31: Write Functions.......................................................................................................................... 49
Table 32: Diagnostic Functions.................................................................................................................. 49
Table 33: Example of an Advanced Modbus Function .............................................................................. 51
Table 34: Trip Record Fields...................................................................................................................... 53
Table 35: Alarm Record Fields .................................................................................................................. 53
Table 36: Basic Protections ....................................................................................................................... 54
Table 37: Advanced Protections................................................................................................................ 54
© 2012 Schneider Electric All Rights Reserved 5
Modbus™ Communications System for Micrologic™ A, P, and H Trip Units 0613IB1201 List of Tables 06/2012
Table 38: Digital Alarms.............................................................................................................................54
Table 39: Scale Factors ............................................................................................................................. 55
Table 40: Configuration.............................................................................................................................. 57
Table 41: Identification............................................................................................................................... 57
Table 42: Diagnostics Counters and Password ......................................................................................... 58
Table 43: Metering / Protection Module Event Notification ........................................................................58
Table 44: Cause of Tripping....................................................................................................................... 59
Table 45: Circuit Breaker Status, Auto / Manu ...........................................................................................60
Table 46: List of Possible Values for Register 661 (Circuit Breaker
Status) in the Breaker Communication Module .......................................................................... 61
Table 47: Time Stamping...........................................................................................................................61
Table 48: Configuration.............................................................................................................................. 62
Table 49: Identification............................................................................................................................... 62
Table 50: Diagnostics Counters and Password ......................................................................................... 62
Table 51: Cradle Status ............................................................................................................................. 63
Table 52: Time Stamping...........................................................................................................................63
Table 53: Voltages ..................................................................................................................................... 64
Table 54: Currents ..................................................................................................................................... 65
Table 55: Power.........................................................................................................................................65
Table 56: Power Factor.............................................................................................................................. 66
Table 57: Frequency .................................................................................................................................. 66
Table 58: Fundamental .............................................................................................................................. 67
Table 59: Total Harmonic Distortion........................................................................................................... 68
Table 60: Energy........................................................................................................................................70
Table 61: Demand Current.........................................................................................................................70
Table 62: K-Factor Demand....................................................................................................................... 71
Table 63: Demand Power .......................................................................................................................... 71
Table 64: Time Stamping...........................................................................................................................72
Table 65: Configuration.............................................................................................................................. 73
Table 66: Spectral Components (Odd Rank) ............................................................................................. 75
Table 67: Spectral Components (Even Rank)............................................................................................77
Table 68: Analog Pre-Defined Alarms........................................................................................................ 79
Table 69: Characteristics of the Protection Module ...................................................................................83
Table 70: Basic Protections Settings (Long-Time Protection-Alarm N° 1000 Ir)........................................ 84
Table 71: Basic Protections Settings (Short-Time Protection-Alarm N° 1001 Isd)..................................... 85
Table 72: Basic Protections Settings (Instantaneous Protection-Alarm N° 1002 Ii)................................... 86
Table 73: Basic Protections Settings (Ground-Fault Protection-Alarm N° 1003 Ig) ................................... 87
Table 74: Basic Protections Settings (Earth-Leakage Protection Alarm N° 1004 Idelta n) ........................ 88
© 2012 Schneider Electric All Rights Reserved6
Table 75: Protection Module Measurements ............................................................................................. 89
Table 76: Status of the Protection Module................................................................................................. 90
Table 77: Time Stamping and Trip / Alarm History .................................................................................... 91
Table 78: Trip History................................................................................................................................. 91
Table 79: Alarm History ............................................................................................................................. 92
Table 80: Micrologic Configuration ............................................................................................................ 93
Table 81: Ground-Fault Alarm—Alarm N°1014 (I
Protection) .................................................................. 94
g
Table 82: Earth-Leakage Alarm—Alarm N°1015 (IΔn Protection) ............................................................. 95
Table 83: Current Unbalance—Alarm N°1016 (I
Table 84: Maximum Current—Alarm N°1017 (I
Table 85: Maximum Current—Alarm N°1018 (I
Table 86: Maximum Current—Alarm N°1019 (I
Table 87: Maximum Current—Alarm N°1020 (I
Table 88: Minimum Voltage—Alarm N°1021 (V
Table 89: Maximum Voltage—Alarm N°1022 (V
Table 90: Voltage Unbalance—Alarm N°1023 (V
Table 91: Reverse Power—Alarm N°1025 (rP
Table 92: Minimum Frequency—Alarm N°1026 (F
Table 93: Maximum Frequency—Alarm N°1027 (F
Protection) .............................................................. 96
unbal
Protection)............................................................... 97
A max
Protection)............................................................... 98
B max
Protection) .............................................................. 99
C max
Protection) ............................................................ 100
N max
Protection) ............................................................... 101
min
Protection).............................................................. 102
max
Protection) .......................................................... 103
unbal
Protection)................................................................. 104
max
Protection)........................................................... 105
min
Protection) ......................................................... 106
max
Table 94: Phase Rotation Alarm—Alarm N° 1028................................................................................... 107
Table 95: Load Shedding and Reconnection Based on Current—Alarm N°1029 ................................... 108
Table 96: Load Shedding and Reconnection Based on Power—Alarm N°1030 ..................................... 109
Table 97: Relay Configuration M2C/M6C ................................................................................................ 110
Table 98: Circuit Breaker ......................................................................................................................... 112
Table 99: Input......................................................................................................................................... 113
Table 100: Tripping Cause......................................................................................................................... 113
Table 101: Alarm Setpoint ......................................................................................................................... 114
Table 102: Currents ................................................................................................................................... 115
Table 103: Maximum Values of Currents................................................................................................... 115
Table 104: Voltages................................................................................................................................... 115
Table 105: Frequency................................................................................................................................ 116
Table 106: Power....................................................................................................................................... 116
Table 107: Energy ..................................................................................................................................... 117
Table 108: Current Demand .......................................................................................................
Table 109: Power Demand ........................................................................................................................ 117
Table 110: Maximum Values of Voltages .................................................................................................. 118
Table 111: Power Factor............................................................................................................................ 118
Table 112: Total Harmonic Distortion ........................................................................................................ 119
© 2012 Schneider Electric All Rights Reserved
............... 117
7
Modbus™ Communications System for Micrologic™ A, P, and H Trip Units 0613IB1201 List of Tables 06/2012
Table 113: Available and Reserved Registers ........................................................................................... 119
Table 114: Basic Protection Settings ......................................................................................................... 119
Table 115: Circuit Breaker ID..................................................................................................................... 120
Table 116: Miscellaneous .......................................................................................................................... 120
Table 117: Cradle Communication Module Commands ............................................................................ 121
Table 118: Breaker Communication Module Commands ..........................................................................122
Table 119: Metering Module Commands................................................................................................... 124
Table 120: Protection Module Commands ................................................................................................. 126
© 2012 Schneider Electric All Rights Reserved8
Section 1—Micrologic Communication System
Introduction The Modbus communication option makes it possible to remotely use all the
functions of a MasterPact™, PowerPact™, or Compact™ circuit breaker, its Micrologic trip unit, and all its options.
Remote operations are based on a secure communication architecture. The Modbus communication system may be used to interconnect the control units (A, P, or H) and a supervisor, and a PLC or Modbus master. The connection uses an RS485 physical link and the Modbus-RTU protocol.
List of Abbreviations BCM – Breaker Communication Module
CCM – Cradle Communication Module
HMI – Human Machine Interface (Control Pad)
LED – Light Emitting Diode
MM – Trip Unit Metering Module
PIF – Product Interface Module
PLC – Programmable Logic Controller
PM – Trip Unit Protection Module
RS485 – Specific Type of Communication System
RTU – Remote Terminal Unit
SMS – System Management Software
TCP / IP – Transmission Control Protocol / Internet Protocol
Communication System Parameters
Micrologic trip units use a system consisting of:
4-wire Modbus,
RTU, RS485 network,
master / slave (Micrologic trip units are always slaves),
any Modbus software (not proprietary),
daisy chain using Belden
recommended).
®
shielded / twisted cable (8723
© 2012 Schneider Electric All Rights Reserved
9
Modbus™ Communications System for Micrologic™ A, P, and H Trip Units 0613IB1201 Section 1—Micrologic Communication System 06/2012
Communication System Components
Circuit breakers that have Micrologic trip units are Powerpact, Compact, and Masterpact.
The communication system consists of:
Micrologic trip units (A, P, or H models are capable of communication),
Breaker Communication Module (BCM),
communication switches that report circuit breaker status (open, closed,
tripped, ready to close) into the BCM,
24 Vdc control power,
daisy chain 4-wire Modbus network,
drawout circuit breakers also have cradle communication module
(CCM),
communicating shunt trip and shunt close coils,
ethernet gateway or circuit monitor to allow Modbus TCP / IP
communication.
Micrologic A Trip Units Trip units require 50 mA at 24 Vdc control power. Control power source
to the trip unit must be isolated from the 24 Vdc control power to the BCM. The positive or negative output of the power supply must not be earth grounded. The DC output of the 24 Vdc power supply must also be isolated from its input. See External 24 Vdc Control Power Supply Characteristics on 11.
Micrologic A trip units control power connections to F1 (-) and F2 (+).
See the trip unit manual and the Masterpact NT/NW Universal Power
Circuit Breakers catalog for specific information about the trip unit and other components.
Micrologic P and H Trip Units Micrologic P or H trip units require 100 mA at 24 Vdc control power.
Control power source to the trip unit must be isolated from the 24 Vdc control power to the BCM. The positive or negative output of the power supply must not be earth grounded. The DC output of the 24 Vdc power supply must also be isolated from its input. See External 24 Vdc Control Power Supply Characteristics on 11.
P and H trip units control power connections to F1 (-) and F2 (+).
See the trip unit manual and the Masterpact NT/NW Universal Power
Circuit Breakers catalog for specific information about the trip unit and other components.
Breaker Communication Module (BCM) The BCM requires 50 mA at 24 Vdc control power. Control power source
to the trip unit must be isolated from the 24 Vdc control power to the BCM. The positive or negative output of the power supply must not be earth grounded. The DC output of the 24 Vdc power supply must also be isolated from its input. See External 24 Vdc Control Power Supply Characteristics on 11.
The BCM control power connections to E1 (+) and E2 (-).
Communication Switches Report circuit breaker status into BCM. Switches are actuated by the
circuit breaker mechanism to indicate open, closed, tripped, and ready to close status.
Switches are installed in the circuit breaker mechanism and connected
by wiring and connector into the BCM.
See BCM instructions for each circuit breaker type for instructions and
mounting information.
© 2012 Schneider Electric All Rights Reserved10
24 Vdc Control Power The 24 Vdc (E1, E2) power supply for the BCM must be separate from
the 24 Vdc power supply module for the Micrologic trip units (F1-, F2+).
The separate power supplies provide isolation between the trip unit and
the communication system. The positive or negative output of the power
supply must not be earth grounded. The DC output of the 24 Vdc power
supply must also be isolated from its input. Specifications are in the table
below:
Table 1: External 24 Vdc Control Power Supply Characteristics
Rated Output Current 1 A
Rated Voltage 24 Vdc
Overall Accuracy ± 5% Vn
Ripple 200 mV peak to peak
Noise 200 mV peak to peak
Voltage Output Variation Limit 21.6 V < V
Capacitive Load 500 µF
Input / Output Capacitive Load 150 pF max
< 26.3 V
out
Daisy Chain 4-Wire Modbus Network Use 22 AWG Belden
®
shielded / twisted cable (8723).
Ground shield at one end of the chain only.
Respect Standard Wiring Practices as explained on page15.
Cradle Communication Module (CCM) Used with drawout construction.
CCM requires 50 mA at 24 Vdc control power. Control power source can
be the same as the one powering the BCM. Control power source must
be isolated and ungrounded. See External 24 Vdc Control Power Supply
Characteristics on 11.
Provides connections for daisy chain communication wires.
Provides connections for 24 Vdc control power.
Can be connected to cradle position switches to report circuit breaker
position (connected, test, disconnected) in the cradle.
Maintains communication parameters (address, baud rate, parity) for the
cradle so when a spare circuit breaker is racked in, the communication
parameters are automatically transferred.
Communicating Shunt Trip and Shunt Close Coils
Allows opening and closing the circuit breaker through communication
network.
Connected to BCM.
Special three-wire shunt trip and close coils are required.
Ethernet Gateway or Circuit Monitor Modbus TCP / IP Communication
System Wide Communication
Web Pages
Communication from any Browser
© 2012 Schneider Electric All Rights Reserved
11
Modbus™ Communications System for Micrologic™ A, P, and H Trip Units 0613IB1201 Section 1—Micrologic Communication System 06/2012
System Diagrams
Micrologic Trip Unit, BCM and CCM Drawout circuit breakers have four modules:
BCM (Breaker Communication Module)
Trip Unit PM (Protection Module)
Trip Unit MM (Metering Module)
CCM (Cradle Communication Module)
Figure 1:
Daisy Chain Connected Deviecs
Address
(51)
(1)
(101)
(201)
Circuit Breaker
Cradle
CCM
BCM
PM
MM
Trip Unt
Circuit
Breaker
© 2012 Schneider Electric All Rights Reserved12
1
3
2
Communicating System
Connection to the Bus
Connection Between Modules
Fixed Unit
Drawout Unit
Connection to the Bus
Communicating System Using the Modbus Protocol
10
0
%
E1
E2
E3
E4
E5
E6
4
E1
E2
E3
E4
E5
E6
Plug-In COM Connector
Prefabricated Connector
Wires
To Cradle Module
Connector
Drawout Circuit Breaker Connections
06/2012 Section 1—Micrologic Communication System
BCM to Daisy Chain 1. Trip Unit
2. BCM
3. CCM
4. Communicating Shunt Trip or Shunt Close Coil
© 2012 Schneider Electric All Rights Reserved
13
Modbus™ Communications System for Micrologic™ A, P, and H Trip Units 0613IB1201
Modbus
CCM
6
5
4
3
2
1
1
2
3
4
5
6
1
2
3
4
Green
White
Red
Black
E1
E2
E3
E4
E5
E6
Com
Secondary Connections
Black
Green
+24VDC
Gnd
Red
White
Modbus
BCM
O / F
PF
SDE
DLO / Tumbler
Gnd
OFO
E1
E2
E3
E4
E5
E6
BreakerCradle
1
2
3
4
5
6
7
8
CT +
CT -
CD +
CD -
CE +
CE -
1
2
3
4
5
Green
White
Red
Black
Shield
Green
White
Red
Black
Shield
12
11
10
9
Gnd
+24VDC
Gnd
+24VDC
+24VDC
Gnd
Cradle Position Switches
Daisy Chain
T
Section 1—Micrologic Communication System 06/2012
BCM and CCM
Modbus TCP / IP Communication
Powerlogic Network Server
SMS
Powerlogic
CM4000 with ECC
Or
EGX Ethernet
Gateway
Ethernet
Circuit Breaker
Browser
RS-485 Mixed Mode
Circuit Monitors or Power Meters
Web
© 2012 Schneider Electric All Rights Reserved14
Standard Wiring Practices
Communication System Belden
22 AWG shielded, twisted with bare drain wire from shield
Standard Colors:
— Rx+ = Green
— Rx- = White
— Tx+ = Red
— Tx- = Black
— shield – bare
Up to 32 devices on a single daisy chain.
Devices include:
— Circuit Monitors
— Power Meters
—PIF-3’s
—PIF-85’s
— Powerlink™ Panels
— Digital Relays
— Digitrip™ 810D’s
— Micrologic Trip Units
— Model 98 Temperature Controllers
—PLCs
Requires unique addresses for each device on the daisy chain.
Daisy chain wiring lengths:
®
8723
Baud Rate 1–16 Devices 17–32 Devices
1200 10,000 ft. (3,050 m) 10,000 ft. (3,050 m)
2400 10,000 ft. (3,050 m) 5,000 ft. (1,525 m)
4800 10,000 ft. (3,050 m) 5,000 ft. (1,525 m)
9600 10,000 ft. (3,050 m) 4,000 ft. (1,220 m)
19200 10,000 ft. (3,050 m) 2,500 ft. (762.5 m)
Requires resistor / capacitor terminator at the end of each daisy chain.
Catalog number: 3090MCTAS485
Belden
®
cable shield must be connected to ground at only one point. We
recommend that this be done at the master device.
Maintain color code throughout system.
Ensure connections are on proper stripped and connection is on wire not
on insulation.
Do not strip wires more than necessary or they may short together or to
ground and disrupt communication.
Maintain baud rate and parity throughout the daisy chain.
Do not use “T” connections except from CCM to BCM, when less than
1 M of cable is needed.
© 2012 Schneider Electric All Rights Reserved
15
Modbus™ Communications System for Micrologic™ A, P, and H Trip Units 0613IB1201 Section 1—Micrologic Communication System 06/2012
System Problems Most Modbus system problems are related to wiring and addressing.
Never
Connect 24 Vdc to communication terminals—it will damage the BCM.
Allow the shield to touch ground at more than one point—it can cause
communication errors due to circulating currents in shield.
Change cable type—it can cause communication errors.
Use Modbus address 16 in a mixed-mode daisy chain (mixed mode
means that there are more than one type of communication on the daisy chain). Address 16 can be used by other components in the system leading to communication errors.
Use SY / MAX address 01 in a mixed-mode daisy chain. Address 01 can be
used by other components in the system leading to communication errors.
Mix 2-wire and 4-wire devices on the same daisy chain (2-wire Modbus
is not recommended for Micrologic trip unit communication systems)—it can cause additional load on the communication network and slow down or stop communication.
Troubleshooting General
Ensure all shipping splits and other connections are made.
Confirm 24 Vdc control power exists at the CCM and E1 / E2 at proper
polarities.
Confirm circuit breaker is in Test or Connected positions.
Confirm trip unit is powered (display should be active).
Check communication parameters and press “address sync” on CCM.
Check wiring color codes.
CCM LED Indicators
No LEDs:
24 Vdc control power present.
One LED solid Green:
24 Vdc control power; no network traffic.
One LED solid Red:
CCM is defective.
One LED solid Green with short voids:
seeing good Modbus packets on the wire.
One LED solid Green with short Red flashes:
indicates the CCM is seeing Modbus packets with errors,
or
indicates the CCM is connected to a “mixed-mode” daisy chain.
Pressing “Address Sync” push-button on CCM:
— three (3) flashes of Red followed by three (3) flashes of Green:
information successfully transferred from BCM to CCM,
— three (3) flashes of Red followed by solid Green:
error transferring information from BCM to CCM.
Racking circuit breaker into Test position:
— three (3) flashes of Red followed by three (3) flashes of Green:
information successfully transferred from CCM to BCM,
— three (3) flashes of Red followed by solid Green:
error transferring information from CCM to BCM.
© 2012 Schneider Electric All Rights Reserved16
Micrologic 3.0 A
menu
long time
alarm
instantaneous
.4
.5
.6
.7.8.9
.95 .98
1
Ir
x In
.5
1
2
4
8
12
16 20
tr
(s)
@ 6 Ir
24
3
6
8
setting
Ii
1.5
2
4
5
10
12
x In
A
Max
Ir=
tr=
Isd=
s
tsd=
Im=
Ig
=
tg=
Digital Display
Change to XX
Press Simultaneously for 3 seconds
Navigation Buttons
47
(by default)
Ad47
2
. . .
3
1
46
06/2012 Section 1—Micrologic Communication System
Wiring Checks with Multi-Meter
Continuity:
— disconnect master device,
— check continuity between each wire,
— twist each pair together and check for continuity,
— ensure no continuity between wires and ground.
DC Voltage:
— with system fully connected, but NO communication activity,
— measure between Rx+ / Rx- (green / white) on each slave device:
should measure approximately 4 Vdc,
— measure between Tx+ / Tx- (red / black) on each slave device:
should measure approximately 0.8 Vdc.
Addresses, Baud Rate, and Parity Settings
Micrologic communication system uses four addresses: BCM, CCM, trip unit protection module, and trip unit metering module.
Addresses, baud rate, and parity are set through the HMI for the A, P, or H Micrologic trip units. The HMI address setting actually addresses the BCM from 1 to 47 (47 is the default). The other three addresses are set automatically: CCM = BCM + 50 (97 is default), trip unit protection module = BCM + 100 (147 is the default), and trip unit metering module = BCM + 200 (247 is the default).
Micrologic A Trip Unit
Enter configuration mode: Press both buttons and
hold for 3-seconds.
Menus to change: Address
Baud Rate
Parity
Language
To step between parameters: Press and hold the arrow
button. Display will “flash” twice when value is saved.
NOTE: You cannot “go back”.
You will have to start over if you need to make changes.
© 2012 Schneider Electric All Rights Reserved
17
Modbus™ Communications System for Micrologic™ A, P, and H Trip Units 0613IB1201 Section 1—Micrologic Communication System 06/2012
Micrologic P and H Trip Unit
© 2012 Schneider Electric All Rights Reserved18
ModuleModule
ModuleModule
B Communications
Modbus RS 485
06/2012 Section 2—Communication Architecture
Section 2—Communication Architecture
Introduction
Module A module contains:
a table of registers that may be read-accessed only,
files such as the event log,
commands for functions such as writing in the registers, turn the circuit
breaker ON or OFF, reset counters, etc.,
Modbus functions used to remotely access the registers and the manger
files.
NOTE: The commands for the metering and protection modules are
controlled by the breaker communication module.
Command Interface A command interface in the breaker communication module and cradle
communication module is used to control the applications. This interface monitors execution of the command and issues a report.
© 2012 Schneider Electric All Rights Reserved
19
Modbus™ Communications System for Micrologic™ A, P, and H Trip Units 0613IB1201 Section 2—Communication Architecture 06/2012
Modbus Functions The device and cradle Modbus options operate in slave mode and enable a
Modbus master to access all the registers, files and applications contained in the modules.
Breaker Communication Module: @ Address xx
The breaker communication module may be used to remotely monitor circuit breaker status:
open (OFF),
closed (ON),
tripped (SDE),
ready to close (PF), and so on.
It is also possible to remotely open or close the circuit breaker if the MX and / or XF communicating coils are installed.
Remote control may be disabled by locally setting the Micrologic control unit to manual (“Manu”) mode. “Auto” mode enables remote control of the circuit breaker.
Table 2: Breaker Communication Module Registers
Register Range Description
515–543 Modbus Configuration and Identification
544–577 Diagnostics Counters and Modbus Password
603–624 Metering / Protection Module Event Notification
650–670 Tripping Cause and Circuit Breaker Status
671–715 Time-Stamping of Last Status Changes
718–740
800 Communication Profile Activation
12000–12215 Communication Profile
Event Log in the Breaker Communication Module (see “Access to Files” on page 31).
NOTE: More detailed information on these registers is presented in the
Appendix, Table of Registers, “Breaker Communication Module @ Address xx” on page 57.
Communication Profile In order to optimize the number of Modbus request, a communication profile
has been implemented. The communication profile is located in the breaker communication module @address xx. This communication profile contains information coming from the breaker communication module, the metering module and the protection module. The communication profile is defined in the register range: 12000–12215.
Simplified Open/Close Command In order to simplify the application software to remotely open or close the circuit
breaker, a simplified Open/Close command has been implemented. The simplified Open/Close command is located in the breaker communication module @ address xx. With the simplified Open/Close command, it is not necessary to request the flag, neither to enter in configuration mode, neither to read the control word. It is still necessary to be in Auto mode (see register 670). Furthermore, this simplified Open/Close command is password protected (default value = 0000). In order to change the password, it is mandatory to use the « magic box » and the associated Micrologic utility RSU (please consult us).
The simplified Open/Close command is a share command (command code = 57400).
© 2012 Schneider Electric All Rights Reserved20
NOTE: More detailed information on this command is presented in the
Appendix, List of Command, “Breaker Communication Module Commands @ Address xx” on page 122.
NOTE: Communication profile and simplified Open/Close command are
available only with a Breaker Communication Module firmware version greater or equal to V2.0 (register 577 must be greater or equal to 02000).
Cradle Communication Module: @ Address xx + 50
The cradle communication module indicates the position of the device on the cradle:
“connected” position,
“test” position,
“disconnected” position.
Table 3: Cradle Communication Module Registers
Register Range Description
515–543 Modbus Configuration and Identification
544–577 Diagnostics Counters and Modbus Password
661–664 Cradle Status
679–715 Time-Stamping of Last Status Changes
NOTE: More detailed information on these registers is presented in the
Appendix, Table of Registers, “Cradle Communication Module @ Address xx + 50” on page 62.
Metering Module: @ Address xx + 200 The metering module prepares the electrical values used to manage the
low-voltage distribution system.
Every second, the metering module refreshes the “real-time” RMS measurements. Using this data, it then calculates the demand and energy values, and stores the minimum / maximum values recorded since the last reset.
Metering-module operation depends on the Micrologic settings:
type of neutral (internal, external, none),
the normal direction for the flow of active power
(this setting determines the sign of the measured power),
voltage-transformation ratio,
rated frequency.
The metering module must be set independently of the protection module to determine:
the calculation mode for the power (type of distribution system),
the calculation mode for the power factor (IEEE
®
, IEEE alt., IEC).
© 2012 Schneider Electric All Rights Reserved
21
Modbus™ Communications System for Micrologic™ A, P, and H Trip Units 0613IB1201 Section 2—Communication Architecture 06/2012
Table 4: Metering Module Registers
Register Range
1000–1299 Real-Time Measurements The metering module refreshes the real-time measurements every second.
1300–1599
1600–1899
2000–2199 Energy Measurements
2200–2299 Demand Values
3000–3299 Time-Stamping
3300–3999 Configuration of the Metering Module
4000–4099 Reserved
4100–5699 Spectral Components
5700–6899 Analog Pre-Defined Alarm (1 to 53)
7100–7499
Description Details
The minimum values for real-time measurements may be accessed at the registers of the real-time values + 300.
All the minimum values are stored in memory and may be reset to zero, group by group according to the list below, by the command interface:
• RMS current,
• current unbalance,
• RMS voltage,
• voltage unbalance,
Minimum Values for the Real-Time Measurements from 1000 to 1299
Maximum Values for the Real-Time Measurements from 1000 to 1299
File Header / Status (See “Access to Files” on page 31)
• frequency,
•power,
• power factor,
• fundamental,
• total harmonic distortion,
• voltage crest factor,
• current crest factor.
NOTE:
The minimum and maximum values of the real-time measurements are stored in the memory. They may be reset to zero. The maximum values of the demand measurements are time stamped and stored in memory. They may be reset to zero.
The maximum values for the real-time measurements may be accessed at the registers of the real-time values + 600.
All the maximum values are stored in memory and may be reset to zero, group by group according to the list below, by the command interface:
• RMS current,
• current unbalance,
• RMS voltage,
• voltage unbalance,
• frequency,
•power,
• power factor,
• fundamental,
• total harmonic distortion,
• voltage crest factor,
• current crest factor.
The energy counters may be:
• reset to zero,
• preloaded with an initial value,
using the reset applications via the command interface.
The demand values are refreshed every 15 seconds for sliding windows or at the end of the time interval for block windows. When block windows are used, an estimation of the value at the end of the time interval is calculated every 15 seconds.
The time-stamping function becomes useful once the time and date have been set on the Micrologic control unit, either locally or via the communication network.
If power to the Micrologic control unit is cut, the time and date must be set again. With firmware release “logic 2002 AA” and above, the clock is powered by the battery. So, it is no more necessary to set time and date after power comes off on the Micrologic control unit.
If power to the communication option is cut, the time and date must be set again. The maximum drift of the Micrologic clock is approximately 0,36 seconds per day. To avoid any significant drift, the clocks must be periodically synchronized via the communication network.
The configuration registers may be read at all times. The registers may be modified via the command interface in configuration mode.
• RMS / phase of voltage harmonic,
• RMS / phase of current harmonic.
The alarms registers may be read at all times. The registers may be modified via the command interface in configuration mode. These alarms (available with Micrologic H only) can be used to trigger wave form capture.
Event log configuration / characteristics and format of records for:
Wave Form Capture (file n° 5)
Event Log of the Metering Module (file n° 10)
Min-Max Event Log (file n° 11)
Maintenance Event Log of the Metering Module (file n° 12)
© 2012 Schneider Electric All Rights Reserved22
NOTE: More detailed information on these registers is presented in the
Appendix, Table of Registers, “Metering Module @ Address xx + 200” on page 64.
Protection Module: @ Address xx + 100 The protection module ensures the critical circuit breaker functions. The
Micrologic control unit was designed to make this module completely independent to minimize any issues with the protection functions of the trip units.
It does not use the measurements generated by the metering module, but rather calculates the protection-function inputs and outputs itself. This ensures extremely fast reaction times.
The protection module manages:
the basic protection: the long-time (LT), short-time (ST), instantaneous
and ground-fault current protection functions,
the advanced protection: currents I
V
unbal
, frequency F
max
and F
min
, I
max
, voltages V
unbal
max
, maximum reverse power Rp
, V
max
and
min
, phase
rotation .
The protection module controls:
the automatic load shedding and reconnection functions, depending on
current and power,
the optional M2C and M6C contacts.
Remote access to the protection module depends on the parameters set locally on the Micrologic control unit and on the position of the protective cover for the settings.
A local operator may disable all remote access to the protection module. It is also possible to limit access to certain users by setting up a password on the Micrologic control unit.
A protection function intended to trip the circuit breaker cannot be modified if the protective cover is closed, with or without the password.
© 2012 Schneider Electric All Rights Reserved
Table 5: Protection Module Registers
Register Range Description
8750–8753 Characteristics of the Protection Module
8754–8803
8833–8842 Measurements Carried Out by the Protection Module
8843–8865 Status of the Protection Module
9000–9599 Time-Stamping and Trip / Alarm History
9600–9628 Micrologic Configuration
9629–9799 Advanced Protection Settings
9800–9899 Relay Configuration (M2C / M6C)
9900–9924
9932–9956
9964–9989
Fine Settings for the Long-Time, Short-Time, Instantaneous, Ground­Fault and Earth-Leakage Protection Functions
Event Log (See Section: “Access to Files” on page 31)
File N° 20
Maintenance Event Log (See Section: “Access to Files” on page 31)
File N° 12
Fault Wave Form Capture (See Section: “Access to Files” on page 31)
File N° 22
NOTE: More detailed information on these registers is presented in the
Appendix, Table of Registers, “Protection Module @ Address xx + 100” on page 83.
23
Modbus™ Communications System for Micrologic™ A, P, and H Trip Units 0613IB1201 Section 3—Command Interface 06/2012
Section 3—Command Interface
Operating Principle Write-access to Micrologic data and control-unit options is monitored to
inhibit accidental operation and operation by unauthorized persons.
Commands sent to Micrologic control units are carried out using a command interface.
The command interface manages transmission and execution of the various commands using the registers numbered from 7700 to 7729 that may be accessed by the Modbus read and write functions.
The breaker communication module supports the command interface for the commands intended for the circuit breaker, measurement, and protection modules.
The cradle communication module supports its own command interface.
Slave @ xx [breaker communication module]
Command Interface 7700 to 7729 Command Interface 7700 to 7729
Commands Intended for the
Breaker Communication Module
Commands Intended for the
Protection Module
Commands Intended for the
Metering Module
Slave @ xx+50 [cradle communication module]
Commands Intended for the
Cradle Communication Module Only
The command interface offers two command modes:
Shared Mode:
This mode may be used to send up to 20 commands in series. It returns exclusively the indications on command transmission via the Modbus protocol. This mode does not return the result of command execution.
Protected Mode:
This mode may be used to monitor execution of a command and to manage access by a number of supervisors to a single circuit breaker. This is the case for the Modbus multi-master architectures on Ethernet TCP / IP.
When a command is written, the command interface updates its registers
with information on command execution. It is necessary to wait until the command is terminated before sending the next command.
(Recommended time-out is 500 ms.)
Furthermore, when the command is terminated, it is necessary to respect a delay before sending the next command.
(Recommended delay is 20 ms.)
Access control is achieved by a flag reservation and freeing mechanism. In protected mode, a command may be issued only after receiving a flag.
NOTE: Certain commands may be accessed only in protected mode. See
“List of Commands” on page 121 to determine the possible command­management modes.
© 2012 Schneider Electric All Rights Reserved24
Table 6: Command Interface Registers
Register
7700 10 R / W INT 0..65535 A P / H
7715 5 R INT 0..65535 A P / H
7720 10 R / W INT 0..65535 A P / H
7730 100 R INT 0..65535 A P / H
1
See “Micrologic Command Interface for the Modbus Programmer”.
2
See “List of Commands” on page 121.
Number of Registers
Read /
Scale Unit Format Interval A P / H Description Label
Write
command interface in shared mode— commands
command interface in protected mode— state
command interface in protected mode— commands
command interface in protected mode— return
1, 2
1, 2
1, 2
1, 2
ShCmdIf
PrCmdIfState
PrCmdIf
PrCmdIfBuffer
Send Commands in Shared Mode The shared mode uses the registers numbered 7700 to 7709 in the
command interface:
Table 7: Shared Mode Registers in the Command Interface
Registers Description
7700 Command Number
7701 Parameter P1
7702 Parameter P2
7703 Parameter P3
7704 Parameter P4
7705 Parameter P5
7706 Parameter P6
7707 Parameter P7
7708 Parameter P8
7709 Parameter P9
See the “List of Commands” on page 121 that may be accessed in shared mode and the corresponding parameters in the section with the list of commands for Micrologic control units.
Proceed in the following manner to send a command in shared mode.
1. Parameters
Fill in the command parameters in registers 7701 to 7709.
2. Write Command
Write the command number to register 7700 to initiate execution.
It is possible to optimize data flow on the communication system by using function 16 in the Modbus protocol. In this case, the data may be written to registers 7700 to 7709 in a single step. The circuit breaker communication option will automatically put steps 1 and 2 in the correct order.
© 2012 Schneider Electric All Rights Reserved
25
Modbus™ Communications System for Micrologic™ A, P, and H Trip Units 0613IB1201 Section 3—Command Interface 06/2012
Send Commands in Protected Mode
Registers 7715 to 7719:
May be read-accessed only and provide the indications required to use the protected mode.
Register 7719:
Command result codes table.
The protected mode uses the registers numbered 7715 to 7829 in the command interface.
Table 8: Protected Mode Registers in the Command Interface
Registers Description
7715 Flag query.
7716 Flag active.
7717 Number of the command being executed.
7718 Number of the last command executed.
7719 Result code of the last command executed.
1
Register 7715 must be read-accessed to ensure it is 0, if it is not 0 then another user is in configuration mode and you cannot proceed to the next step, see page 128.
2
The active flag indicates to a supervisor the number of the flag with current access rights to the command interface in protected mode. Only the supervisor that was attributed the given number during a flag query has the right to use the command interface in protected mode. The active flag returns to 0 if no command is sent for two minutes or if the user returns the flag (see the command table for information on return).
3
he number of the command currently being executed remains set to 0 as long as no command is sent to 7720. As soon as a command is sent, register 7717 indicates the number of the command. It returns to 0 when command execution is terminated.
4
When command execution is terminated, register 7718 receives the number of the command and register 7719 indicates the result code. The contents of registers 7718 and 7719 are not modified until the next command has been completely executed
1
2
3
4
4
Table 9: Command Result Codes
Result Codes Description of Register 7719
0 Command successfully executed.
10
11 Command not executed, a local user is using the resources.
12
14
15 Invalid record size.
16 Illegal file command.
17 Insufficient memory.
42 Invalid file number.
81 Command not defined.
82 Command parameters not set or invalid.
107 Invalid record number.
125 Invalid number of records.
200 Protected mode not active.
201 End of time delay. Command not executed.
202 Invalid password. Command not executed.
Command not executed, the necessary resources are not available or the option is not installed or remote access = NO.
Command not executed, the portable test kit is using the local resources.
Command not executed, the resources are being used by a remote user.
© 2012 Schneider Electric All Rights Reserved26
Registers 7720 to 7729:
May be read-accessed. They are used to send parameters and run execution of commands in protected mode.
Table 10: Read-Accessed Commands
Registers Description
7720 Command Number
7721 Parameter P1
7722 Parameter P2
7723 Parameter P3
7724 Parameter P4
7725 Parameter P5
7726 Parameter P6
7727 Parameter P7
7728 Parameter P8
7729 Parameter P9
See the “List of Commands” on page 121 that may be accessed in protected mode and the corresponding parameters in the section with the list of commands for Micrologic control units.
Command interface registers 7730–7829 may be read accessed. They are used as a buffer for the returned data.
Proceed as follows to send a command in protected mode.
1. Request the Flag
Read register 7715 to ensure it is 0, if it is not 0 then another user is in
configuration mode and you cannot proceed to the next step, see
page 128. It is possible, however, that you already took the flag for
another command and did not return it. For example: if you wished to
sequence sending of a series of commands. It is possible to check if you
have the rights by reading the active flag at register 7716. In this case,
even if you did not read 0 at 7715 when you made the request, it is
possible to send the commands.
2. Fill in Parameters
Fill in the command parameters (P1 to P9) in registers 7721 to 7729.
3. Write Command
Write the command number to register 7720 to initiate execution.
4. Wait for Command Execution
Wait until the command is fully terminated, by reading registers 7717
and 7718 (recommended time-out = 500 ms).
5. Check Result Code
Check the result code for the command by reading register 7719.
6. Send New Command
Send new commands in protected mode by starting with step 2 or go on
to step 7 (recommended delay between command fully terminated and
new command = 20 ms).
7. Release the Flag
Return the flag to free the protected mode. See the command table for
information on returning the flag.
© 2012 Schneider Electric All Rights Reserved
27
Modbus™ Communications System for Micrologic™ A, P, and H Trip Units 0613IB1201 Section 3—Command Interface 06/2012
Optimize Sending of Commands It is possible to optimize data flow on the communication system by using
function 16 in the Modbus protocol. In this case, the data may be written to registers 7720 to 7729 in a single step. The command interface will automatically put steps 2 and 3 in the correct order.
NOTE: Do not use function 23 to optimize steps 1, 2 and 3, because this
function does not check access rights to protected mode before sending the command. This may cause problems for another supervisor who currently has the access rights.
Most of the commands that may be used to remotely control the circuit breaker implement two steps, namely the request for the flag (step 1) and return of the flag (step 7).
This mechanism makes it possible for a number of supervisors to issue commands, on the condition that the two steps be implemented.
Using this procedure, you take and return the flag for each of the commands to be issued. In this case, the possible degree of parallelism between the various supervisors is increased, but at the cost of more traffic on the communication system.
If you have a number of commands to send, optimize the mechanism by sending all the commands between the two steps; for example, request the flag, send all the commands in one shot and then return the flag. In this case, you occupy the command interface for a longer time, but traffic on the communication system is optimized.
Remote Configuration
NOTE: Detailed information on the registers is
presented in the Appendix containing the “Table of Registers” on page 55.
A number of simple concepts must be clear in order to remotely configure the circuit breaker successfully.
Configuration is carried out via the registers:
The configuration for all the modules (circuit breaker, cradle, measurements, and protection functions) may be read-accessed in the table of registers.
The only way to remotely modify a configuration is to modify the contents of the configuration registers.
The table of registers may be write-accessed in configuration mode only:
To modify the configuration registers, it is necessary to remove the register write-protect function by running the command required to enter configuration mode, via the command interface. Once in configuration mode, it is possible to write access the configuration registers and you may modify one or more registers using the standard Modbus write functions.
Breaker Communication Module Slave @ xx
Regular Range Configuration Registers
534–543
Identification of the Breaker Communication Module
Cradle Communication Module Slave @ xx + 50
Regular Range Configuration Registers
534–543
Identification of the Cradle Communication Module
© 2012 Schneider Electric All Rights Reserved28
Metering Module Slave @ xx + 200
Regular Range Configuration Registers
3303–3355 Configuration of the Metering Module
6000–6011 Configuration of Analog Pre-Defined Alarm 1
6012–6635 Configuration of Analog Pre-Defined Alarm 2 to 53
Protection Module Slave @ xx + 100
Regular Range Configuration Registers
8753–8803 Fine Adjustments for the Basic Protection
9604–9618 Configuration of the Protection Module
Continued on next page
9629–9798 Settings for the Advanced Protections
9800–9846 Configuration of the Output Relays (M2C / M6C)
xx = breaker communication module address.
Specific conditions must be met to enter the configuration mode.
Remote access is not possible if local configuration is underway and visa-versa.
When a user is in the process of locally modifying the configuration of Micrologic or of its options, it is not possible to start a remote-configuration sequence.
Micrologic considers that a local user is in the process of modifying the configuration when a parameter field is highlighted or as soon as the Micrologic plastic cover is opened.
Access to configuration mode is subject to different restrictions depending on the module.
Access to configuration mode for the protection module requires the remote-access code that was programmed on the front panel of the Micrologic control unit.
This code may be obtained only via the setting screen on the Micrologic control unit itself. It is only possible to access the configuration mode for the protection module if the Micrologic control unit has been set to authorize remote access. This setting must be made manually via the front panel of the Micrologic control unit. It is possible to consult the protection module register 9800 to check the status of this parameter.
Access to configuration mode for the breaker communication, cradle communication and metering modules requires a check word that must first be read in the table of registers. This two-step operation is intended to avoid inadvertent access to the configuration mode.
The access commands for configuration mode implement the protected mode and systematically inform on the command result.
New configurations are always checked before being accepted.
When writing in the configuration registers, the Modbus write functions are accepted, even if the written value exceeds the limits presented in the tables of registers that should be consulted first.
To assist in configuring the protection functions, Micrologic provides access to a set of registers that list the minimum and maximum permissible values for the various protection settings.
© 2012 Schneider Electric All Rights Reserved
29
Modbus™ Communications System for Micrologic™ A, P, and H Trip Units 0613IB1201 Section 3—Command Interface 06/2012
All the configuration data entered are checked before they enter into effect. This check is run when you exit configuration mode, using the commands Out_pCfg, Out_mCfg or Out_CommCfg.
If one of the configuration settings is incorrect, all the new configuration data are rejected. The system indicates why the data are rejected via the result returned for the command used to exit the configuration mode. The protection module indicates the first ten faulty configuration registers. See the information on command Out_pCfg for further details.
The new configuration data take effect only on exiting configuration mode.
The new configuration data take effect only on exiting configuration mode so that the data can be checked; for example, it is when the Out_pCfg, Out_mCfg or Out_CommCfg command has been successfully run that the new configuration settings become active.
Example of a Remote Parameter-Setting Sequence
Below are the steps that must be followed to modify the long-time (LT) current setting.
1. Check that remote access is authorized by reading register 9800 at address @+100 [protection module].
2. Make sure you have the remote-access code, noted on the “Local / Remote” screen in the “COM setup” menu of Micrologic.
3. Enter configuration mode for the protection module, using the In_pCfg command. See the Appendix, “Examples of Commands” on page 127.
4. Enter the new setting in registers 8753 to 8803, at the address @+100 [protection module]. Make sure these new settings are below the value set by the rotary switch.
5. Exit configuration mode for the protection module, using the Out_pCfg command, and check first for an error code returned by the command interface, then the parameters returned by Out_pCfg in registers 7730 to 7739 of the circuit breaker command interface.
6. Read the contents of the registers 8756 and 8757. The settings should be those entered, if step 5 did not return an error.
© 2012 Schneider Electric All Rights Reserved30
Loading...
+ 114 hidden pages