MAx-305 & MAx-318 Series
MAx-405 Through MAx-419
Series
Two-Position Actuators
General Instructions
For two-position operation of dampers, valves, and other equipment which require the return to normal position upon power interruption.
Hazardous location models offer a sturdy cast aluminum case with bolted cover. They have two 3/4" pipe tapped openings for joints with rigid metal conduit. All wiring is brought out to separate terminals for ease of installation. These factory enclosure and actuator assemblies are Underwriters Laboratories listed.
MA-3xx, MA5-318,
MA-4xx, MA5-419
(Standard)
•Compatible with most SPST control devices
•Spring return
•24, 120, 208, and 240 Vac models
•Actuators with part number suffix "-500" are equipped with SPDT auxiliary switch
•Actuator has a rugged die cast aluminum housing with two 1/2” conduit openings
•Hazardous location actuator housing has two 3/4" pipe taped openings for rigid metal conduit connection
•Oil immersed motor and gear train
MA6-3xx, MA6-4xx, MA7-4xx,
MA8-3xx, MA8-4xx
(Hazardous Locations)
•Electric/Electronic Products Catalog, F-27382
•Valve Products Catalog, F-27384
•Cross-Reference Guide, F-26789
•AV-29x Valve Linkage for Hazardous Location Gear Train Actuators General Instructions, F-27441.
•Apparatus for Hazardous Locations EN-56-2,
F-18451.
•AV-390 Series, Valve Linkage for Gear Train Actuators General Instructions, F-24376.
•Material Safety Data Sheet (MSDS) for BCS-51-168 Oil (Until Feb. 1989)
•Material Safety Data Sheet (MSDS) for BCS-51-185 Oil (Until March 2002) (MAx-3xx-x-x-3 and MAx-4xx-x-x-3)
•Material Safety Data Sheet (MSDS) for BCS-51-185-1 Oil (Current) (MAx-3xx-x-x-4 and MAx-4xx-x-x-4)
•High Temperature Exposure Performance (UL 555S) MAx-31x-x-x-4, MAx-41x-x-x-4 Series Actuators Engineering Information EN-216, F-27068
Printed in U.S.A. 6/12 |
© Copyright 2012 Schneider Electric All Rights Reserved. |
F-06491-32 |
Actuator Inputs
Connections: Coded screw terminals.
Control Circuit: Two-wire.
Power Input: See Table-1.
Actuator Outputs
Torque: See Table-1.
Shaft Rotation:
MA-305, MA-405, MA6-305, MA6-405, CW 180° when power is applied. MA-318, MA-41x, MAx-318, MAx-41x, CW 180° when power is applied.
Spring Return: CCW to the original position when the actuator is de-energized.
Auxiliary Switch (-500 Models): SPDT makes (or breaks) the circuit at the powered end of stroke.
Environment
Ambient Temperature Limits:
Shipping & Storage, -40 to 136 °F (-40 to 58 °C). Operating, -40 to 136 °F (-40 to 58 °C). Humidity: 5 to 95% RH, non-condensing.
Location: NEMA Type 4 when used with the gasket (provided) and water-tight conduit connectors (not provided), optional hazardous location models.
Agency Listings:
US Standard UL 873, Underwriters Laboratories (File #E9429 XAPX, Temperature Indicating and Regulating Equipment).
Candadian Standard C22.2 No. 24: Underwriters Laboratories (File #E429 Category XAPX7, Temperature Indicating and Regulating Equipment).
Hazardous Location Models, UL file #E29291. Designed for use in hazardous locations N.E.C., Class 1, Groups C and D, and Class 2, Groups E, F, and G. Temperature code T6 for hazardous housing.
Table-1 Model Chart.
|
Power |
|
|
VA |
|
Rated |
No Load |
|
|
||
Part Number |
Supply |
Auxiliary |
Input |
|
Timing in |
Mounting |
Application |
||||
|
|
|
Torque |
||||||||
|
|
Switcha |
Watts |
|
|
|
Seconds at |
||||
|
Vac |
Hz |
Running |
|
Holding |
lb-in. (N-m) |
|
|
|||
|
|
|
|
75 °F (24 °C)b |
|
|
|||||
MA-305 |
24 |
|
No |
|
56 |
|
56 |
|
|
Any Position |
|
|
|
|
|
|
|
|
(Horizontal |
|
|||
MA-305-500 |
|
Yes |
25 |
|
16 (1.8) |
|
Damper |
||||
|
|
|
|
|
|
||||||
|
|
|
|
|
|
Output Shaft |
|||||
MA-405 |
|
|
No |
|
|
|
|
Actuators |
|||
120 |
60 |
|
48 |
|
48 |
|
|
Position |
|||
|
|
|
|
|
|
|
|||||
MA-405-500 |
Yes |
|
|
|
|
Preferred) |
|
||||
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
MA-318 |
24 |
|
No |
|
92 |
|
32 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
MA-318-500 |
|
Yes |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
MA-416 |
208 |
|
No |
|
104 |
|
38 |
|
20 |
|
|
|
|
|
|
|
|
|
|
||||
MA-416-500 |
|
Yes |
70 |
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
Running |
|
|
|
|
|
Output Shaft |
Damper |
MA-418 |
|
|
No |
|
|
|
|
|
|||
120 |
60 |
|
108 |
|
42 |
60 (6.8) |
|
Must Be |
and Valve |
||
|
|
|
|
|
|||||||
MA-418-500 |
Yes |
25 |
|
|
|||||||
|
|
|
|
|
|
|
Horizontal |
Actuators |
|||
|
|
|
|
|
|
|
|
|
|||
MA-419 |
|
|
No |
Holding |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MA-419-500 |
240 |
|
Yes |
|
120 |
|
39 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
MA5-419 |
50 |
No |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
MA5-419-500 |
|
Yes |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
a4.4 FLA, 26.4 LRA @ 24 or 120 Vac; 2.4 FLA, 13.2 LRA @ 240 Vac.
bSpring return timing with full load opposing spring is approximately 60 sec.
2 |
© Copyright 2012 Schneider Electric All Rights Reserved. |
F-06491-32 |
Table-2 Actuator Part Numbers for Hazardous Location Applications.
|
Hazardous Location Actuator Assemblies |
||
Standard |
Part Numbersb c d |
||
Part Numbersa |
|
|
|
Damper Actuators |
Valve Actuators |
||
|
|||
|
|
|
|
MA-305 |
MA6-305 |
— |
|
MA-305-500 |
— |
— |
|
MA-405 |
MA6-405 |
— |
|
MA-405-500 |
MA6-405-500 |
— |
|
MA-318 |
MA6-318 |
MA8-318 |
|
MA-318-500 |
MA6-318-500 |
MA8-318-500 |
|
MA-416 |
MA6-416 |
— |
|
MA-416-500 |
MA6-416-500 |
— |
|
MA-418 |
MA6-418 |
MA8-418 |
|
MA-418-500 |
MA6-418-500 |
MA8-418-500 |
|
MA-419 |
MA6-419 |
— |
|
MA-419-500 |
MA6-419-500 |
— |
|
MA5-419 |
MA7-419 |
— |
|
MA5-419-500 |
MA7-419-500 |
— |
aMAx-31x-x-x-4 and MAx-41x-x-x-4 series actuators provide significantly improved high temperature exposure performance for use in smoke or fire dampers, or combination smoke and fire dampers. Refer to Engineering Information EN-216 (UL 555S), F-27068.
bClass 1, Groups C & D, and Class 2, Groups E, F, and G hazardous locations; refer to EN-56-2.
cModels for hazardous locations are only available as factory-built enclosure/actuator assemblies.
dSee standard actuator part number wiring diagrams for wiring terminations.
Damper Only |
|
AM-111 |
Crank arm for 5/16" diameter damper shaft |
AM-112 |
Crank arm for 3/8" diameter damper shaft |
AM-113 |
Crank arm for 1/2" diameter damper shaft |
AM-115 |
Crank arm for 7/16" diameter damper shaft |
AM-122 |
Linkage connector straight type |
AM-123 |
Damper clip |
AM-125 |
5/16" diameter x 20" damper rod |
AM-125-048 |
5/16" diameter x 48" damper rod |
AM-132 |
Ball joint connector |
AM-161 |
Damper linkage kit |
AM-161-1 |
Damper linkage kit |
AM-301 |
90° mounting bracket (not used with MA6-xxx, MA7-xxx, & MA8-xxx) |
Valve Only (To be used with 60 lb-in. (6.8 N-m) actuators only, excluding MA7-xxx & MA8-xxx)
AV-29 & AV-300 Linkage for 2-1/2" & 3" discontinued VB-9323
AV-391 |
Linkage for 1/2" to 2" VB-7xxx and 1/2" to 1-1/4" discontinued VB-9xxx |
AV-392 |
Linkage for 1-1/2" and 2” discontinued VB-9xxx |
AV-395 |
Linkage for 2-1/2" to 4" VB-931x or discontinued VB-92xx |
Valve Only (To be used with 60 lb-in. (6.8 N-m) MA7-xxx & MA8-xxx hazardous location actuators only)
AV-291
AV-295
F-06491-32 |
© Copyright 2012 Schneider Electric All Rights Reserved. |
3 |
|
|
|
MA-305 |
|
|
|
|
Thermostat |
|
MA-405 |
|
|
|
|
1 |
Series Actuator |
|
|
||
L1 or H |
or Switch |
2 |
NC |
|||
|
|
|
|
|
||
|
|
|
Motor |
COM |
|
|
L2 or G |
|
|
Field Coil |
|
|
NO |
|
|
|
|
|
|
1Actuator rotates 180° CW when thermostat or switch contacts are closed. Actuator spring returns when thermostat or switch contacts are open.
2Aux. Switch for -500 Models
Figure-1 Typical Wiring for MA-305 and MA-405 Series.
|
|
|
MA-318, MA-416 |
|
|
|
|
|
|
MA-418, MA-419 |
4 |
NC |
|
|
|
|
Series Actuator |
|||
|
|
|
|
|
||
|
Thermostat |
|
|
|
COM |
|
|
|
NC |
|
|
|
|
|
or Switch |
1 |
|
|
NO |
|
L1 or H |
|
2 |
|
|||
|
|
NO |
|
|
||
|
|
|
|
|
|
|
L2 or G |
|
|
3 |
|
|
|
1Actuator rotates 180° CW when thermostat or switch contacts are closed. Actuator spring returns when thermostat or switch contacts are open.
2High Input (Running)
3Low Input (Holding)
4Aux. Switch for -500 Models
Figure-2 Typical Wiring for MA-318, MA-416, MA-418, and MA-419 Series.
4 |
© Copyright 2012 Schneider Electric All Rights Reserved. |
F-06491-32 |