Schneider Electric E4800 user guide

Page 1
PowerLogic
Multi-Circuit Meters
Installation Guide
TM
Series EM4800
Page 2
PowerLogic
DANGER
WARNING
TM
EM4800 Series 930-110-01-B.00
Hazard Categories and Special Symbols
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates an imminently hazardous situation which, if not avoid­ed, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoid­ed, can result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoid­ed, can result in minor or moderate injury.
CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can result in property damage.
NOTE: Provides additional information to clarify or simplify a procedure.
PLEASE NOTE Electrical equipment should be installed, operated, serviced, and maintained
only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
FCC NOTICE This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. This Class B digital apparatus complies with Canadian ICES-003.
© 201 Schneider Electric All Rights Reserved
Page 3
930-110-01-B.00 PowerLogic 04/2011
TM
EM4800 Series
INDUSTRY CANADA CLASS B EMISSION COMPLIANCE STATEMENT
This equipment does not exceed the Class B limits for radio noise emissions from digital apparatus as set out in the radio interference regulations of the Canadian ICES-003.
Avis de conformité aux normes d'Industrie Canada. Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
UL UL (Underwriters Laboratories) are listed by the American Federal
Occupational Safety and Health Administration (OSHA) under NRTL (Nationally Recognized Testing Laboratory) program. They are also accredited by Standards Council of Canada. This equipment complies with UL 61010-1 Second Edition and CSA C22.2 No. 61010-1-04.
© 201
Schneider Electric All Rights Reserved
Page 4
PowerLogic
TM
EM4800 Series 930-110-01-B.00
©  Schneider Electric All Rights Reserved
Page 5
930-110-01-B.00 PowerLogic 04/2011 Table of Contents
TM
EM4800 Series
Table of Contents
INTRODUCTION .........................................................................................1
System Description .....................................................................................1
PowerLogic EM4800 series System Specifications .............................. 1
SAFETY PRECAUTIONS....................................... ... ..................................6
Electrical Standards Compliance ..........................................................6
INSTALLATION........................................................................................... 7
Pre-Installation ............................................................................................ 7
Receiving ............................................................................................... 7
Pre-Installation Checklist .......................................................................7
Site Planning .........................................................................................8
Installation Procedures ...............................................................................8
Mounting the PowerLogic EM4800 meter ............................................. 9
Installing Potential Transformers for Three-Phase Service Greater Than
277V .................................................................................................... 11
Installing the Sense Voltage and Control Voltage Cables in Wye and Del-
ta Services ............................ ............................................. ... ............... 13
Installing the Current Transformers .....................................................21
Connecting the Communications ........................................................30
Start-Up Sequence ..............................................................................30
Pulse Inputs ......................................................................................... 31
Display Navigation ...............................................................................31
Remote Display ...................................................................................32
Recording the Meter Map .................................................................... 32
MAINTENANCE ........................................................................................34
Fuse Replacement ....................................................................................34
REGULATORY COMPLIANCE.................................................................35
Equipment servicing and access .........................................................35
USER NOTES................................................................................ ... ......... 39
© 201
Schneider Electric All Rights Reserved
i
Page 6
PowerLogic
TM
EM4800 Series 930-110-01-B.00
© 201 Schneider Electric All Rights Reservedii
Page 7
930-110-01-B.00 PowerLogic 04/2011 Introduction
TM
EM4800 Series

INTRODUCTION This document describes the PowerLogic EM4833, EM4880 and EM4805

meters, including procedures to install and start up the unit, and complete the initial configuration:
“System Description” on page 1
“Pre-Installation” on page 7
“Installation Procedures” on page 8
“Start-Up Sequence” on page 30
“Fuse Replacement” on page 34 This documentation is intended for those responsible for installing and
configuring the PowerLogic EM4833, EM4880 and EM4805 meters. Installers must be qualified electricians with knowledge of local and national code requirements. See “Safety Precautions” on page 6.

System Description The PowerLogic EM4833, EM4880 and EM4805 meters support:

single-phase, 2-wire
single-phase, 3-wire (network)
three-phase wye and Delta services Depending on how the meters are installed and configured, they can meter
8, 12, or 24 individual meter points. The PowerLogic EM4833, EM4880 and EM4805 meters are designed for residential, commercial, and industrial use and display the power and consumption readings for each measurement point.

PowerLogic EM4800 series System Specifications

The PowerLogic EM4800 series system architecture includes:
single-phase, 2-wire; single-phase, 3-wire (network); and three-phase compatibility
120/208V, 120/240V and 277/480V configurations, and 347/600V with external potential transformers
up to 8, 12, or 24 individual meter points
local Ethernet configuration interface via PC and web browser
on-board modem and Ethernet ports for remote reporting
serial port for remote display
2 pulse inputs to connect metering devices
Table 1 lists the system specifications of the PowerLogic EM4833, EM4880 and EM4805 meters.
© 201
Schneider Electric All Rights Reserved
1
Page 8
PowerLogic
TM
EM4800 Series 930-110-01-B.00
Table 1: PowerLogic EM4800 series meter specifications
Specification PowerLogic EM4833 meter PowerLogic EM4880 meter PowerLogic EM4805 meter
Dimensions Height: 13.125 in. (33.5 cm)
Weight 8.77 lb (3.98 kg) 8.77 lb (3.98 kg) 11.9 lb (5.4 kg) Sense voltage 100V to 300V 50/60Hz
Control voltage and current North America: 120V 125 mA 60 Hz
Current transformers Measurement Category III
Measurement accuracy (Accuracy compliant when
used with 0.3% CTs)
Pulse inputs 1 and 2 Dry form A and solid-state form A
Non-volatile memory storage 120 days in 15-minute intervals 120 days in 15-minute intervals 120 days in 15-minute intervals
Width: 12 in. (30.5 cm) Depth: 2.125 in. (5.5 cm)
2W+N+Protective Earth Wye 3W+N+Protective Earth Wye 3W+Protective Earth Delta
International: 230-240V 63 mA 50/60 Hz
0.333 V secondary CT Note: All CTs used with the product
must be UL recognized/listed.
ANSI C12.20 Class 0.5 IEC 62053-22 Class 0.5S
compatible Maximum frequency 10 Hz Minimum pulse width 20 ms
Height: 13.125 in. (33.5 cm) Width: 12 in. (30.5 cm) Depth: 2.125 in. (5.5 cm)
100V to 300V 50/60Hz 2W+N+Protective Earth Wye 3W+N+Protective Earth Wye 3W+Protective Earth Delta
North America: 120V 125 mA 60 Hz International: 230-240V 63 mA
50/60 Hz 80 mA secondary CT
200 A primary CT Meter burden: 4.04 ohms CT burden: 20 ohms Part number: METSECT80200 Note: All CTs used with the product
must be UL recognized/listed. ANSI C12.20 Class 0.5
IEC 62053-22 Class 0.5S Measurement Canada Approved
EG07 compliant Dry form A and solid-state form A
compatible Maximum frequency 10 Hz Minimum pulse width 20 ms
Height: 13.125 in. (33.5 cm) Width: 17 in. (44 cm) Depth: 2.125 in. (5.5 cm)
100V to 300V 50/60Hz 2W+N+Protective Earth Wye 3W+N+Protective Earth Wye 3W+Protective Earth Delta
North America: 120V 125 mA 60 Hz International: 230-240V 63 mA
50/60 Hz 5 A secondary CT
Note: All CTs used with the product must be UL recognized/listed.
ANSI C12.20 Class 0.5 IEC 62053-22 Class 0.5S Measurement Canada Approved
EG07 compliant Dry form A and solid-state form A
compatible Maximum frequency 10 Hz Minimum pulse width 20 ms
Onboard modem V.90 V.90 V.90 Onboard Ethernet port 10/100 Mb/s 10/100 Mb/s 10/100 Mb/s Serial port 115 kb/s 115 kb/s 115 kb/s Fuse rating (F1) North America:120V: T125 mA, 250V
International 230V: T63 mA, 250V
North America:120V: T125 mA, 250V International 230V: T63 mA, 250V
North America:120V: T125 mA, 250V International 230V: T63 mA, 250V
Environmental
Operating temperature -40 to 70oC -40 to 70oC -40 to 70oC Operating humidity 5% to 90% non-condensing 5% to 90% non-condensing 5% to 90% non-condensing Usage environment Indoor or enclosed outdoor
Maximum altitude 9843 ft (3000 m) 9843 ft (30 00 m) 9843 ft (3000 m) Pollution degree 2 2 2
environment
Indoor or enclosed outdoor environment
Indoor or enclosed outdoor environment
© 201 Schneider Electric All Rights Reserved2
Page 9
930-110-01-B.00 PowerLogic 04/2011 Introduction
TM
EM4800 Series
Front Panel Display
The PowerLogic EM4833, EM4880 and EM4805 meters have the following front panel features (Figure 1 shows the PowerLogic EM4880 front panel):
LCD — displays 2 rows of 16 characters for each of the meter points (8, 12, or 24)
Display button — cycles through the available information for each of the meter points
Left and right arrow buttons — selects which of the meter points is on the display
Figure 1: PowerLogic EM4880 front panel
Display
Select
PowerLogic
EM4800
© 201
Schneider Electric All Rights Reserved
3
Page 10
PowerLogic
1
4
1
6
7
8
10
11
12
13
5
1
1
2
9
15
14
17
16
3
Legend: 1 Cover screw location 2 Meter point input connector 3 Cable connector 4 Mounting keyhole 5 Ingress punch-outs 6 Earth stud 6 Sense voltage terminal block 8 Control voltage terminal block 9 Fuse 10 Control voltage jumper 11 Modem port 12 Display 13 Remote display connector 14 Serial RS232 15 Ethernet port 16 Pulse in terminal blocks 17 Pulse out connector
TM
EM4800 Series 930-110-01-B.00
Figure 2 shows the internal view of thePowerLogic EM4833 and PowerLogic EM4880. See Figure 3 for the internal view of the PowerLogic EM4805.
Figure 2: PowerLogic EM4833 and PowerLogic EM4880 internal view
© 201 Schneider Electric All Rights Reserved4
Page 11
930-110-01-B.00 PowerLogic 04/2011 Introduction
Figure 3: PowerLogic EM4805 internal view
TM
EM4800 Series
76
8
9
10
11
1
1
5
12
13
4
14
3
15
16
2
17
1
1
Legend: 1 Cover screw location 2 Meter point input (JM8) 3 Meter point input (JM1) 4 Mounting keyhole 5 Ingress punch-outs 6 Earth stud 7 Sense voltage terminal block 8 Control voltage terminal block 9 Fuse 10 Control voltage jumper 11 Modem port 12 Display 13 Remote display connector 14 Serial RS232 15 Ethernet port 16 Pulse in terminal blocks 17 Pulse out connector
© 201
Schneider Electric All Rights Reserved
5
Page 12
PowerLogic
DANGER
TM
EM4800 Series 930-110-01-B.00
SAFETY PRECAUTIONS Carefully observe these safety instructions.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
Only qualified electrical workers should install this equipment. Such work should be performed only after reading this entire set of instructions.
The equipment must be accessible to authorized personnel only. Equipment must be installed in areas where access can be restricted.
NEVER work alone.
Before performing visual inspections, tests, or maintenance of this equipment, disconnect all sources of electric power. Assume that all circuits are live until they have been completely de-energized, tested, and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including the possibility of backfeeding.
Turn off all power supplying the meter and the equipment in which it is installed before working on it.
Always use a properly rated voltage sensing device to confirm that all power is off.
Before closing all covers and doors, carefully inspect the work area for tools and objects that may have been left inside the equipment.
Successful equipment operation requires proper handling, installation, and operation. Neglecting fundamental installation requirements can lead to personal injury as well as damage to electrical equipment or other property.
NEVER bypass external fusing.
NEVER short the secondary of a Potential Transformer (PT).
Always short the secondary of a current transformer prior to disconnecting current input loads.
Failure to follow these instructions will result in death or serious injury.

Electrical Standards Compliance Use the unit only in accordance with the electrical power rating

The unit is only to be installed by a qualified electrician
Initial installation of the unit must be inspected by the local electrical Inspection Authority
Install the unit in compliance with the following local and national electrical codes:
Canada: Canadian Electrical Code, Part I, CSA C22.1
United States: National Fire Protection Association (NFPA) 70; US
National Electrical Code
Elsewhere: International Electrotechnical Commission (IEC) 364,
Part 1-7
Ensure that the unit is properly earthed
If the equipment is installed or used in a manner other than that specified in this document, it may void your warranty or impair the protection of the equipment.
© 201 Schneider Electric All Rights Reserved6
Page 13
930-110-01-B.00 PowerLogic 04/2011 Installation
TM
EM4800 Series

INSTALLATION This section contains the following installation topics:

“Pre-Installation” on page 7
“Installation Procedures” on page 8
“Start-Up Sequence” on page 30

Pre-Installation The pre-installation checklist and site planning must be performed before

installing the equipment at the site.

Receiving The equipment required for each PowerLogic EM4800 meter installation

includes:
high-density meter (PowerLogic EM4833, PowerLogic EM4880 or PowerLogic EM4805)
For the PowerLogic EM4833 and PowerLogic EM4880, one 12-ft (4-m) AMP cable with one 50-pin connector supplied with each unit
TM
For the PowerLogic EM4805, two Mate-n-Lok supplied with each unit in 8-, 12-, or 24-connector variants
CD and meter configuration software, this installation manual and an installation record form
When you receive your order, verify that the items listed above are included with the shipment, and visually inspect them for damage. If any parts are missing or damaged, contact your Schneider Electric representative.
wiring harnesses

Pre-Installation Checklist The installer must provide the following information, tools, and equipment

before proceeding with the installation:
certified current transformers for metering (not supplied)
an appropriate 15-Amp maximum circuit breaker or a fused disconnect switch for the type of panel
current/voltage meter to test the phasing of panels
RJ45 Ethernet patch cable
2
4-wire 14 AWG (1.63 mm circuits, or 3-wire 14 AWG (1.63 mm
) cable for three-phase wye connected
2
) cable for a single-phase wye
connected circuits
small flat-head screwdriver
#2 Phillips screwdriver
crimping tool
18 AWG butt splice connector
wire strippers
four 1-inch (25 mm) #8 mounting screws suitable for selected mounting surface
© 201
Schneider Electric All Rights Reserved
7
Page 14
PowerLogic Installation 04/2011
TM
EM4800 Series 930-110-01-B.00
If using a modem, these items are also required:
phone or butt set to test the phone line
RJ11 junction box
RJ11 splitter to tap into the existing junction box
RJ11 patch cable
xDSL filter if required (many businesses have their internet access on the same line as the fax)

Site Planning 1. Determine the number of PowerLogic EM4800 series meters to be

installed and ensure adequate space. For clearances, see Figure 4 on page 10.
2. Determine the number of analog phone lines or Ethernet drops required, and ensure they are installed before installing the PowerLogic EM4833, EM4880 and EM4805 meters. The recommended maximum number of PowerLogic meters per phone line is 50.
3. Determine the number and types of meters or monitors required (single-phase, network, or three-phase).
4. Determine the model number and correct sense voltage based on the voltage label on the top right side of the unit.
Access to Power and Lighting
The installation site must be supplied with access to the main electrical panel and any sub-panels. Portable or permanent lighting must be available to provide the installers with a clear view of the equipment and of the installation environment. Each installation may vary depending on physical site restrictions.

Installation Procedures This section provides information about activities that must be performed to

install the PowerLogic EM4833, EM4880 and EM4805 meters in a single-phase 2-wire, single-phase 3-wire (network), or three-phase 4-wire application. The installation procedures must be performed in the following order:
1. “Mounting the PowerLogic EM4800 meter” on page 9
2. “Installing Potential Transformers for Three-Phase Service Greater Than 277V” on page 11
3. “Installing the Sense Voltage and Control Voltage Cables in Wye and Delta Services” on page 13
4. “Installing the Current Transformers” on page 21
5. “Connecting the Communications” on page 30 a. “Connecting the Phone Line” on page 30 b. “Connecting the Ethernet Cable” on page 30 c. “Manually Testing Communications” on page 30
6. “Start-Up Sequence” on page 30
7. “Recording the Meter Map” on page 32
© 201 Schneider Electric All Rights Reserved8
Page 15
930-110-01-B.00 PowerLogic 04/2011 Installation
TM
EM4800 Series

Mounting the PowerLogic EM4800 meter Figure 4 shows the general mounting layout for metering 120V/208V wye

services, and Figure 5 shows the general mounting layout for metering 347V/600V wye services.
1. Remove the front cover from the meter by removing the four screws with a #2 Phillips screwdriver. Retain the cover and screws for later re-installation.
2. Mount the PowerLogic meter on the wall and secure it by inserting a screw in each mounting keyhole and tightening the screws.
3. Mount the shorting block enclosure on the wall as shown in Figures 4 and 5. Secure it by inserting a screw in each mounting keyhole and tightening the screws.
4. Install the conduit for voltage and current connections.
In Figure 4, the meter is powered and takes its sense voltage directly from a breaker within the panel.
© 201
Schneider Electric All Rights Reserved
9
Page 16
PowerLogic
6.0 in
15.2cm
11.0 in
27.9 cm (6312)
10.67 in
27.1cm
4.0 in
10.2 cm
1
2
2
1
2
2
1
1
3
4
4
6
5
7
8
9
8
Legend:
1. Mounting keyhole
2. Cover screw location
3. Electrical distribution panel
4. CT conduit
5. Voltage conduit
6. Shorting block enclosure
7. Shorting jumper
8. Shorting block
9. DIN rail
TM
EM4800 Series 930-110-01-B.00
Figure 4: 120V Mounting Layout, Dimensions and Clearances
© 201 Schneider Electric All Rights Reserved10
Page 17
930-110-01-B.00 PowerLogic 04/2011 Installation
TM
EM4800 Series

Installing Potential Transformers for Three-Phase Service Greater Than 277V

Potential transformers are required when metering services greater than the rated voltage input of the meter. Potential transformers are used to reduce the line-to-neutral voltage of the service to 120V. The accuracy class should be 0.3% or better, with a burden rating of 30VA.
For applications in Canada, Measurement Canada approved potential transformers are required. Measurement Canada requires an accuracy class of 0.3% or better, with a 150VA rating.
NOTE: Potential transformer burden depends on the control voltage source. If control voltage is provided separately (not derived from the metered voltage), then lower transformer burden may be acceptable. Contact your local Schneider Electric representative for details.
Mount the potential transformer enclosure between the supply voltage and the PowerLogic meters as shown in Figure 5. Transformer configuration must be Y||Y (wye-wye).
In Figure 5, the meter is powered from the potential transformers that are fed from a breaker within the 600Y/347V panel. The CT cable is connected to the shorting enclosure before connecting to the CTs in the panel.
© 201
Schneider Electric All Rights Reserved
11
Page 18
PowerLogic
H1
X1
H2 X2
H1
X1
H2 X2
H1
X1
H2 X2
C
B
A
N
C
B A
N
1
2
3
4
11
Z
5
6
7
8
13
11
12
Shorting block detail
10
9
Legend: 1 Shorting block enclosure 2 Shorting block 3 Distribution panel 4 Current transformer 5 Load breaker 6 Meter breaker 7 Transformer enclosure 8 PowerLogic meter 9 Load 10 Current input cable 11 Shorting jumper 12 Shorting block 13 DIN rail
TM
EM4800 Series 930-110-01-B.00
Figure 5: Typical three-phase 347V installation
© 201 Schneider Electric All Rights Reserved12
Page 19
930-110-01-B.00 PowerLogic 04/2011 Installation
TM
EM4800 Series

Installing the Sense Voltage and Control Voltage Cables in Wye and Delta Services

The sense voltage (A, B, C, N) provides phase voltages for metering. The configuration depends on the type of service being metered:
see “For a single-phase panel with the 120V variant of the meter:” on page 15
see “For a 208Y/120V three-phase wye panel with the 120V variant of the meter:” on page 16
see “For a 416Y/240V (or 380Y/220V) three-phase wye panel with the 230/240V variant of the meter:” on page 17
see “For a 480Y/277V three-phase wye panel with the 120V variant of the meter:” on page 18
see “For a 600Y/347V or higher three-phase wye panel with potential transformers with the 120V variant of the meter:” on page 19
see “For a three-phase Delta panel with the 120V variant of the meter:” on page 20
The PowerLogic EM4833, EM4880 and EM4805 meters are shipped from the factory with a control voltage jumper that can be used to to connect the control voltage input and the sense voltage inputs to provide control voltage to the unit. The following procedures explain how to connect the sense voltage inputs for each of the service types.
For a single-phase panel, use a 3-wire (red, black, white), 14 AWG (1.63 mm black, blue, white), 14 AWG (1.63 mm2), 90°C (194°F) cable. For a Delta service, use a 3-wire (red, black, blue), 14 AWG (1.63 mm
2
), 90°C (194°F) cable. For a three-phase panel, use a 4-wire (red,
2
), 90°C (194°F) cable. Metallic, flexible armored cable (BX cable) is recommended for commercial installations as shown in Figure 6 on page 15.
The PowerLogic meters must be connected to the sense voltage and control voltage through a properly rated disconnect that disconnects all line and neutral wires, so it can be powered down. The disconnect must be located within easy reach of the meter operator, and must be labeled as such. Opening the disconnect or breaker is the disconnect device. For multiple PowerLogic meter installations, the same disconnect can be used to power all meters, and must be labeled for all meters it supplies power to. The disconnect device must meet IEC 60947-1, IEC 60947-3 and/or comply with the local electrical code.
© 201
Schneider Electric All Rights Reserved
13
Page 20
PowerLogic
DANGER
TM
EM4800 Series 930-110-01-B.00
To install the control voltage cable in a 208Y/120V or 120/240V application:
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
This equipment must only be installed and serviced by qualified electrical personnel.
Turn off all power supplying this equipment before working on or inside equipment.
Always use a properly rated voltage sensing device to confirm power is off.
Replace all devices, doors and covers before turning on power to this equipment.
The meters must be connected to the sense voltage and control voltage through a properly rated voltage disconnect (not shown in the wiring diagrams).
Failure to follow these instructions will result in death or serious injury.
NOTE: If the circuit breaker panel does not designate phase A, phase B and phase C feeds, make your own designation and use it for the rest of the installation.
1. Before connecting the sense voltages, turn off the power to the circuit being connected.
2. Always use a properly rated voltage sensing device to confirm power is off.
3. Connect the sense voltages phase A, B, C, and N leads from the voltage disconnect to the meter as described in Figure 6 on page 15 and Figure 7 on page 16.
NOTE: The phase wiring sequence A, B, C between the PowerLogic EM4800 meter and the panel must match or the measurement readings will be wrong.
4. If more than one meter is being installed, repeat this procedure for each additional meter.
© 201 Schneider Electric All Rights Reserved14
Page 21
930-110-01-B.00 PowerLogic 04/2011 Installation
For a single-phase panel with the 120V variant of the meter:
Connect meter terminal A to the voltage disconnect phase A (red wire)
Connect meter terminal B to the voltage disconnect phase B (black wire)
Connect meter neutral terminal to neutral bar in the voltage disconnect panel (white wire)
Connect earth wire to earth post using lug provided
Meter terminal C is not connected
Install power supply shorting jumpers (see Figure 6)
The PowerLogic EM4833, EM4880 and EM4805 meters are rated for direct input of 120V to 277V 60Hz phase potential. When metering services greater than 120V, the meter is powered from a separate 120V instrument transformer. Figure 9 shows the wiring of the control voltage transformer for a service between 240V and 277V.
Figure 6: PowerLogic EM4800 meter in a 120/240V single-phase connection
TM
EM4800 Series
2
1
8
3
7
6
5
4
Legend: 1 BX cable 2 Earth 3 Phase B (black) 4 Shorting jumper 5 Sense voltage terminal block (J3) 6 Neutral (white) 7 Phase A (red) 8 0.75-inch (1.9-cm) strain relief
© 201
Schneider Electric All Rights Reserved
15
Page 22
PowerLogic
Legend: 1 BX cable 2 Earth 3 Phase C (blue) 4 Phase B (black) 5 Shorting jumper 6 Sense voltage terminal block (J3) 7 Neutral (white) 8 Phase A (red) 9 0.75-inch (1.9-cm) strain relief
8
4
7
5
6
2
1
3
9
TM
EM4800 Series 930-110-01-B.00
For a 208Y/120V three-phase wye panel with the 120V variant of the meter:
Connect meter terminal A to the voltage disconnect phase A (red wire)
Connect meter terminal B to the voltage disconnect phase B (black wire)
Connect meter terminal C to the voltage disconnect phase C (blue wire)
Connect meter neutral terminal to neutral bar in the voltage disconnect panel (white wire)
Connect earth wire to earth post using lug provided
Install power supply shorting jumpers (see Figure 7)
Figure 7: PowerLogic EM4800 meter 208Y/120V three-phase wye service connection
© 201 Schneider Electric All Rights Reserved16
Page 23
930-110-01-B.00 PowerLogic 04/2011 Installation
For a 416Y/240V (or 380Y/220V) three-phase wye panel with the 230/240V variant of the meter:
Connect meter terminal A to the voltage disconnect phase A (red wire)
Connect meter terminal B to the voltage disconnect phase B (black wire)
Connect meter terminal C to the voltage disconnect phase C (blue wire)
Connect meter neutral terminal to neutral bar in the voltage disconnect panel (white wire)
Connect earth wire to earth post using lug provided
Install power supply shorting jumpers (see Figure 8)
Figure 8: PowerLogic EM4800 meter 416Y/240V three-phase wye service connection
TM
EM4800 Series
2
1
9
3
8
4
7
6
5
Legend: 1 BX cable 2 Earth 3 Phase C (blue) 4 Phase B (black) 5 Shorting jumper 6 Sense voltage terminal block (J3) 7 Neutral (white) 8 Phase A (red) 9 0.75-inch (1.9-cm) strain relief
© 201
Schneider Electric All Rights Reserved
17
Page 24
PowerLogic
8
5
7
6
10
2
1
4
3
9
Legend: 1 BX cable 2 Earth 3 AuxA (red) 4 AuxN (white) 5 Phase C (blue) 6 Sense voltage terminal block (J3) 7 Neutral (white) 8 Phase A (red) 9 Phase B (black) 10 0.75-inch (1.9-cm) strain relief
TM
EM4800 Series 930-110-01-B.00
For a 480Y/277V three-phase wye panel with the 120V variant of the meter:
Connect meter terminal A to the voltage disconnect phase A (red wire)
Connect meter terminal B to the voltage disconnect phase B (black wire)
Connect meter terminal C to the voltage disconnect phase C (blue wire)
Connect meter neutral terminal to neutral bar in the voltage disconnect panel (white wire)
Connect earth wire to earth post using lug provided
From the auxiliary power transformer, connect 120V auxiliary power to AUXA and AUXN on the meter (see Figure 9)
Figure 9: PowerLogic EM4800 meter 480Y/277V three-phase wye service connection
© 201 Schneider Electric All Rights Reserved18
Page 25
930-110-01-B.00 PowerLogic 04/2011 Installation
For a 600Y/347V or higher three-phase wye panel with potential transformers with the 120V variant of the meter:
Connect meter terminal A to the voltage disconnect phase A (red wire)
Connect meter terminal B to the voltage disconnect phase B (black wire)
Connect meter terminal C to the voltage disconnect phase C (blue wire)
Connect meter neutral terminal to neutral bar in the voltage disconnect panel (white wire)
Connect earth wire to earth post using lug provided
Install power supply shorting jumpers (see Figure 10)
NOTE: For the wiring of the potential transformers, see Figure 5.
Figure 10: PowerLogic EM4800 meter 600Y/347V or higher three-phase wye service with potential transformers connection
TM
EM4800 Series
2
1
9
3
8
4
7
6
5
Legend: 1 BX cable 2 Earth 3 Phase C (blue) 4 Phase B (black) 5 Shorting jumper 6 Sense voltage terminal block (J3) 7 Neutral (white) 8 Phase A (red) 9 0.75-inch (1.9-cm) strain relief
© 201
Schneider Electric All Rights Reserved
19
Page 26
PowerLogic
8
4
5
6
9
2
1
3
7
Legend: 1 BX cable 2 Earth 3 Phase C (blue) 4 Phase B (black) 5 Shorting jumper 6 Sense voltage terminal block (J3) 7 J3-B to J3-N shorting wire 8 Phase A (red) 9 0.75-inch (1.9-cm) strain relief
TM
EM4800 Series 930-110-01-B.00
Delta service metering
To use the PowerLogic EM4800 meter in a Delta service, the line-to-line voltage from the Delta service must be reduced to 120V line-to-line using appropriate potential transformers. Metering a Delta service requires only two potential transformers, and only two CTs for phase A and C. Using the phase B CT is optional.
For a three-phase Delta panel with the 120V variant of the meter:
Connect meter terminal A to the voltage disconnect phase A (red wire)
Connect meter terminal C to the voltage disconnect phase C (blue wire)
Connect meter neutral terminal to meter terminal B (black wire)
Connect earth wire to earth post using lug provided (see Figure 11)
Figure 11: PowerLogic EM4800 meter three-phase Delta service connection
© 201 Schneider Electric All Rights Reserved20
Page 27
930-110-01-B.00 PowerLogic
3
1
2
T
H
IS SID
E T
OWARDSS
O
UR
C
E
4
5
Legend: 1 Source 2 Energy ow 3 Load 4 X1 5 X2
DANGER
2011
04/2011 Installation
TM
EM4800 Series

Installing the Current Transformers The three models of PowerLogic EM4800 meter use current transformers

(CTs) with different secondary outputs. The PowerLogic EM4833 meter uses split-core 0.333V CTs (see Figure 12), and the PowerLogic EM4880 meter uses 80mA CTs only (see Figure 13) and is typically used where accuracy is important and long secondary CT wiring is required (up to 300 feet [91.44 meters]). The PowerLogic EM4880 meter can also use a 5A CT if a 5A converter has first been installed.
For instructions, see “Installing the CTs on the PowerLogic EM4833 and PowerLogic EM4880” on page 22, and “Installing 5A Converters and CTs on the PowerLogic EM4880” on page 23.
The PowerLogic EM4805 uses 5A secondary CTs. For instructions, see “Installing the 5A CTs on the PowerLogic EM4805” on page 27.
Current transformers connect to the PowerLogic EM4833 and PowerLogic EM4880 meters through the 50-conductor CT cable provided with the meter. Table 2 describes the CT wire pairs and the cable color scheme for each meter point. You can also find this information on the inside of the meter’s outer cover.
Each CT has an X1 (positive) and X2 (neutral) wire pair and uses butt-splice connectors to attach the CT to a specific meter wire pair. The direction of the energy flow is indicated on the CT.
Figure 12: PowerLogic EM4833 split-core 0.333V current transformer
© 2010 Schneider Electric All Rights Reserved
21
Page 28
PowerLogic
2
3
1
5
4
H1
Legend: 1 Source 2 Energy ow 3 Load 4 X1 5 X2
DANGER
DANGER
TM
EM4800 Series 930-110-01-B.00
Figure 13: PowerLogic EM4880 mA current transformer
Installing the CTs on the PowerLogic EM4833 and PowerLogic EM4880
Do not apply power until you have made these connections and followed all of the instructions below:
Connect all CTs to the appropriate circuits
Connect the CTs to the cables
Connect the cables to the PowerLogic EM4800 meter
To install the mA current transformers on the PowerLogic EM4880 or the
0.333V current transformers on the PowerLogic EM4833, follow these steps:
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on or inside the equipment.
Always use a properly rated voltage sensing device to confirm the power is off.
NEVER open circuit a CT; use the shorting block to short circuit the leads of the CT before removing the connection from the meter.
Do not crimp the insulation when making the wire connections.
Failure to follow these instructions will result in death or serious injury.
© 201 Schneider Electric All Rights Reserved22
Page 29
930-110-01-B.00 PowerLogic 04/2011 Installation
TM
EM4800 Series
1. Connect the 50-pin connector to the PowerLogic connector located at the bottom side of the unit, and secure it in place with the retaining clips.
2. Feed the free end of the cable through the bottom left of the meter enclosure.
This cable is made up of twisted-pair wires for connecting the individual CTs to the metered points. The color codes for the X1 (positive) and X2 (neutral) connections for each CT are listed in Table 2 on page 26.
NOTE: The direction of the energy flow is indicated on the CT.
3. Turn off the power feed to the panel where the CTs are being installed. Always use a properly rated voltage sensing device to confirm power is
off.
4. Feed the CT cable into the panel through an appropriate punch-out with an approved strain relief.
5. Strip the plastic sheaths on the cable to an appropriate length to expose the wire pairs. Cut and strip the CT leads and wire pair leads to an appropriate length. Crimp the CT leads to the wire pairs for each meter point.
6. Connect the X1 lead of the CT to the X1 lead of the cable, then connect the X2 lead of the CT to the X2 lead of the cable (see Table 2).
7. When using solid-core CTs, remove the feed wire from the circuit breaker, place the CT over the wire, and reconnect to the circuit breaker. Ensure that the arrow on the CT label is pointing in the direction of the energy flow (toward the load).
8. When using split-core CTs, separate the halves of the CT and place the CT over the wire to the circuit breaker. Ensure that the CT is facing the source as shown on the label. Install cable ties to ensure that the CT halves are held together securely.
9. Repeat steps 5 to 8 for the remaining CTs.
Installing 5A Converters and CTs on the PowerLogic EM4880
When both low-current (200A and 400A) and high-current (600A or higher) circuits need to be measured with the same PowerLogic meter, converters are available to allow the use of Measurement Canada approved 5A CTs with the appropriate current rating. 5A CT converters transform the 5A maximum output from a standard CT to the 80mA maximum of the PowerLogic meter.
The 5A side of the converter is the black and red wire pair, and the 80mA side of the converter is the black and white wire pair.
NOTE: It is recommended that 5A converters and shorting devices be installed in a sealable metal enclosure.
© 201
Schneider Electric All Rights Reserved
23
Page 30
PowerLogic
DANGER
TM
EM4800 Series 930-110-01-B.00
To connect the 5A CT to the converter on the PowerLogic EM4880, follow these steps:
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on or inside the equipment.
Always use a properly rated voltage sensing device to confirm the power is off.
NEVER open circuit a CT; use the shorting block to short circuit the leads of the CT before removing the connection from the meter.
Do not crimp the insulation when making the wire connections.
Failure to follow these instructions will result in death or serious injury.
1. Connect the X1 lead of the 5A CT to the shorting device.
2. Connect the X2 lead of the 5A CT to the shorting device.
3. Connect the X1 lead (red) from the 5A side of the converter to the CT X1 lead on the shorting device.
4. Connect the X2 lead (black) from the 5A side of the converter to the CT X2 lead on the shorting device.
5. Connect the X1 lead (white) from the 80mA side of the converter to the X1 lead within the 25 pair cable for the selected meter point ID listed in Table 2.
6. Connect the X2 lead (black) from the 80mA side of the converter to the X2 lead within the 25 pair cable for the selected meter point ID listed in Table 2
Figure 14 shows a 5A CT connected to the converter.
© 201 Schneider Electric All Rights Reserved24
Page 31
930-110-01-B.00 PowerLogic 04/2011 Installation
Figure 14: PowerLogic EM4880 5A CT connection to converter
TM
EM4800 Series
4
6
5
3
2
7
8
9
1
12
11
10
Legend: 1 Shorting block 2 X2 3 Energy ow 4 5A CT 5 X1 6 Red (X1) 7 5A Converter 8 X1 to 25-pair cable 9 X2 to 25-pair cable 10 Enclosure 11 Black (X2) 12 Shorting bar
© 201
Schneider Electric All Rights Reserved
25
Page 32
PowerLogic
TM
EM4800 Series 930-110-01-B.00
Table 2: PowerLogic EM4833 and PowerLogic EM4880 CT color pair identification
1-phase, 24 meter points Network- or 1-phase, 12 meter points 3-phase, 8 meter points Meter point ID
(meter point #­probe #)
1-1 Black Green 1-1 Black Green 1-1 Black Green 2-1 Black White 1-2 Black White 1-2 Black White 3-1 Black Red 2-1 Black Red 1-3 Black Red 4-1 Red Green 2-2 Red Green 2-1 Red Green 5-1 Red White 3-1 Red White 2-2 Red White 6-1 Black Orange 3-2 Black Orange 2-3 Black Orange 7-1 Black Brown 4-1 Black Brown 3-1 Black Brown 8-1 Black Yellow 4-2 Black Yellow 3-2 Black Yellow 9-1 Black Blue 5-1 Black Blue 3-3 Black Blue 10-1 Green Yellow 5-2 Green Yellow 4-1 Green Yellow 11-1 Green Blue 6-1 Green Blue 4-2 Green Blue 12-1 Green White 6-2 Green White 4-3 Green White 13-1 Blue White 7-1 Blue White 5-1 Blue White 14-1 Green Orange 7-2 Green Orange 5-2 Green Orange 15-1 Green Brown 8-1 Green Brown 5-3 Green Brown 16-1 Blue Yellow 8-2 Blue Yellow 6-1 Blue Yellow 17-1 Brown White 9-1 Brown White 6-2 Brown White
Connect X1 CT lead to:
Connect X2 CT lead to:
Meter point ID (meter point #­probe #)
Connect X1 CT lead to:
Connect X2 CT lead to:
Meter point ID (meter point #­probe #)
Connect X1 CT lead to:
Connect X2 CT lead to:
18-1 Orange White 9-2 Orange White 6-3 Orange White 19-1 Red Orange 10-1 Red Orange 7-1 Red Orange 20-1 Red Yellow 10-2 Red Yellow 7-2 Red Yellow 21-1 Red Brown 11-1 Red Brown 7-3 Red Brown 22-1 Blue Orange 11-2 Blue Orange 8-1 Blue Orange 23-1 Yellow White 12-1 Yellow White 8-2 Yellow White 24-1 Blue Brown 12-2 Blue Brown 8-3 Blue Brown
© 201 Schneider Electric All Rights Reserved26
Page 33
930-110-01-B.00 PowerLogic 04/2011 Installation
TM
EM4800 Series
Installing the 5A CTs on the PowerLogic EM4805
Use the two 12-pair wiring harnesses provided with the meter to connect the 5A CTs to the PowerLogic EM4805.
For wire color coding, see Table 3 or the label inside the outer cover of the meter. Follow these instructions to install the 5A CTs on the PowerLogic EM4805.
Do not apply power until you have made these connections and followed all instructions below:
Connect all CTs to shorting blocks to the appropriate circuits
Connect the shorting blocks to the cables
Connect the cables to the PowerLogic EM4805
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on or inside the equipment.
Always use a properly rated voltage sensing device to confirm the power is off.
NEVER open circuit a CT; use the shorting block to short circuit the leads of the CT before removing the connection from the meter.
Do not crimp the insulation when making the wire connections.
Failure to follow these instructions will result in death or serious injury.
1. Connect the two wiring harnesses to the PowerLogic EM4805. The connectors are labeled Plug 1/Plug 5 to Plug 4/Plug 8 on the cable.
This is also labeled on the meter. Ensure the connectors are inserted in the proper order and that the connectors are securely locked in place.
TM
a. Connect the first wiring harness to the Mate-n-Lok
connectors 1 to 4, and secure the cables to the PowerLogic EM4805 chassis with cable ties.
TM
b. Connect the second wiring harness to the Mate-n-Lok
connectors 5 to 8, and secure the cables to the PowerLogic EM4805 chassis with cable ties.
2. Turn off the power feed to the panel where the CTs are being installed. Always use a properly rated voltage sensing device to confirm the power is off.
3. Route the free end of the cable out of the meter enclosure through the slot in the base of the chassis.
4. Strip the plastic sheaths to an appropriate length to expose the wire pairs. Cut and strip the wire pair leads to an appropriate length.
5. Connect the wire pair leads from the meter to the CT shorting block. See Table 3 for the color pair assignment of each meter point. Ensure that the CT shorting block is in the shorted position.
6. Connect the CT wire pair leads to the input of the CT shorting block. See Table 3 for the color pair assignment of each meter point.
7. Remove the feed wire from the circuit breaker, place the CT over the wire, and reconnect to the circuit breaker. Ensure that the arrow on the CT label is pointing in the direction of the energy flow (toward the load).
© 201
Schneider Electric All Rights Reserved
NOTE: The direction of the energy flow is indicated on the CT.
27
Page 34
PowerLogic
P8
P7
P5
P3
P2
P1
1
2
3
3
1
Legend: 1 Cable tie-down point 2 10/100 BaseTX Ethernet port 3 Pulse in terminal block P1 Meter point 1 connector plug P2 Meter point 2 connector plug P3 Meter point 3 connector plug P4 Meter point 4 connector plug P5 Meter point 5 connector plug P6 Meter point 6 connector plug P7 Meter point 7 connector plug P8 Meter point 8 connector plug
_
TM
EM4800 Series 930-110-01-B.00
8. Repeat steps 5 to 7 for remaining CTs.
9. Remove the shorting block jumper. Figure 15 shows the 5A CT wiring harness connected to the PowerLogic
EM4805.
Figure 15: Connecting the 5A CT wiring harness
© 201 Schneider Electric All Rights Reserved28
Page 35
930-110-01-B.00 PowerLogic
TM
EM4800 Series
04/2011 Installation
Table 3: PowerLogic EM4805 CT color pair identification
1-phase, 12 or 24 meter points Network- or 1-phase, 12 meter points 3-phase, 8 meter points Meter point ID
(meter point #­probe #)
Cable 1 Cable 1 Cable 1
1-1 Black Red 1-1 Black Red 1-1 Black Red 2-1 Black White 1-2 Black White 1-2 Black White 3-1 Black Green 2-1 Black Green 1-3 Black Green 4-1 Black Blue 2-2 Black Blue 2-1 Black Blue 5-1 Black Yellow 3-1 Black Yellow 2-2 Black Yellow 6-1 Black Brown 3-2 Black Brown 2-3 Black Brown 7-1 Black Orange 4-1 Black Orange 3-1 Black Orange 8-1 Red White 4-2 Red White 3-2 Red White 9-1 Red Green 5-1 Red Green 3-3 Red Green 10-1 Red Blue 5-2 Red Blue 4-1 Red Blue 11-1 Red Yellow 6-1 Red Yellow 4-2 Red Yellow 12-1 Red Brown 6-2 Red Brown 4-3 Red Brown
Cable 2 Cable 2 Cable 2
13-1 Black Red 7-1 Black Red 5-1 Black Red 14-1 Black White 7-2 Black White 5-2 Black White 15-1 Black Green 8-1 Black Green 5-3 Black Green
Connect X1 CT lead to:
Connect X2 CT lead to:
Meter point ID (meter point #­probe #)
Connect X1 CT lead to:
Connect X2 CT lead to:
Meter point ID (meter point #­probe #)
Connect X1 CT lead to:
Connect X2 CT lead to:
16-1 Black Blue 8-2 Black Blue 6-1 Black Blue 17-1 Black Yellow 9-1 Black Yellow 6-2 Black Yellow 18-1 Black Brown 9-2 Black Brown 6-3 Black Brown 19-1 Black Orange 10-1 Black Orange 7-1 Black Orange 20-1 Red White 10-2 Red White 7-2 Red White 21-1 Red Green 11-1 Red Green 7-3 Red Green 22-1 Red Blue 11-2 Red Blue 8-1 Red Blue 23-1 Red Yellow 12-1 Red Yellow 8-2 Red Yellow 24-1 Red Brown 12-2 Red Brown 8-3 Red Brown 1-1 Black Red 1-1 Black Red 1-1 Black Red
© 201
Schneider Electric All Rights Reserved
29
Page 36
PowerLogic Installation 04/2011
TM
EM4800 Series 930-110-01-B.00

Connecting the Communications Connections for communications using the modem or Ethernet are described

in this section.
Connecting the Phone Line
If the modem reporting option is being used, an analog telephone patch cable and a splitter may be required to connect the customer phone line to the PowerLogic EM4800 meter.
1. Connect the patch cable between the termination block of the phone line and the PowerLogic EM4800 meter.
2. Route the cable through the slot in the PowerLogic EM4800 meter enclosure.
3. See the PowerLogic EM4800 meter Configuration Guide for instructions on how to program the meter for dial-out operation before performing a manual configuration test.
Connecting the Ethernet Cable
If the Ethernet port is used to report data, an RJ45 patch cable is required to connect the Ethernet port to the local Ethernet network.
1. Route the cable through the slot in the PowerLogic EM4800 meter enclosure.
2. If the local network automatically assigns IP addresses through a DHCP server, the PowerLogic EM4800 meter will be able to report using its factory default IP settings. If the local network is configured for static IP addresses, refer to the PowerLogic EM4800 meter Configuration Guide for instructions on how to configure default static IP addresses.

Start-Up Sequence Use the following procedure to start up the PowerLogic EM4800 meter.

1. Ensure that all CT and sense voltage wiring is securely installed.
2. Remove all tools from the work area.
3. Re-install all cover plates and equipment covers.
4. Power up the meter. The LCD on the front panel of the meter indicates the operating status of the unit as follows:
a. Initial power up message “PowerLogic EM48xx” b. After the internal configuration is complete, the display shows
default information for the first meter.
Manually Testing Communications
This procedure clears the meter memory, manually tests the communications from the PowerLogic EM4800 meter, and updates the meter clock. To force the meter to send data, follow these steps:
1. Press and hold the Display button for 5 to 7 seconds until the diagnostics mode is displayed, then release.
2. If communicating via Ethernet, press the Display button until "Local IP Address" appears on the display.
a. If the IP address is 169.254.0.10, the meter has not found a
DHCP server. As a result, the meter will use its default IP configuration and may not be able to report. See the PowerLogic EM4800 meter Configuration Guide for instructions on how to program default IP addresses.
© 201 Schneider Electric All Rights Reserved30
Page 37
930-110-01-B.00 PowerLogic 04/2011 Installation
TM
EM4800 Series
b. If the IP address is not 169.254.0.10, the meter has acquired an
IP address from the local network, and will be able to report data and synchronize time.
3. Press the Display button until the “Send” command appears on the display.
4. Press the left or right arrow button to manually force the PowerLogic EM4800 meter to report metering data using the Ethernet or modem connection. This clears data from the PowerLogic EM4800 meter memory, and ensures the time is set correctl y.

Pulse Inputs There are two pulse in terminal blocks in the PowerLogic meter, as shown in

Figure 15. Each terminal block has a negative terminal pin on the right and a positive terminal pin on the left. The pulse inputs are compatible with both dry and solid-state form A contacts, 10 Hz (maximum), 20 ms pulse width (minimum). The inputs are not polarity-sensitive to dry relay contacts. When the pulsing device provides solid-state form A outputs, the negative terminal from the source device must be connected to the negative terminal of the PowerLogic meter pulse in terminal block.

Display Navigation The PowerLogic EM4800 meter has three buttons to control the information

presented on the LCD. The display has a normal and a diagnostics mode. The PowerLogic EM4800 meter starts in normal mode, and enters diagnostics mode when the Display button is pressed and held for 5 seconds. To adjust the contrast, hold down the Display button, and use the right and left arrow buttons to increase and decrease the contrast respectively.
Normal Mode
In Normal mode, the Display button scrolls through the information for each meter. The left and right arrow buttons select the previous or next meter points respectively. The following information is available:
Real Energy Delivered kWh D
Real Energy Received kWh R
Real Power Watts
Reactive Energy Delivered KVarhD
Reactive Energy Received KVarhR
Reactive Power Var
In Normal mode, the right and left arrow buttons scroll the display from meter points 1 to 8, 1 to 12, or 1 to 24, depending on your configuration.
Diagnostics Mode
Diagnostics mode is accessed by pressing and holding the Display button for 5 seconds. In Diagnostics mode, pressing the Display button will scroll through the following additional information:
Send data command
CT Primary value and Real Power Watts per phase
Voltage per phase
Local IP address
Reset factory default IP address command
Date and time (UTC)
© 201
Schneider Electric All Rights Reserved
31
Page 38
PowerLogic Installation 04/2011
TM
EM4800 Series 930-110-01-B.00
In Diagnostics mode, the right and left arrow buttons scroll the display from meter 1 to 8, 1 to 12, or 1 to 24, depending on your configuration. When the local IP address is shown on the LCD, use the right and left arrow buttons to scroll through the following information:
Remote host server IP address
Time server IP address
Default IP address
Default NetMask
Default gateway
PPP user name
Phone number
AT command string
Alternate phone number
Unit serial number
Firmware build number
Ethernet port MAC address
Firmware revision
Potential transformer ratio

Remote Display For installation and operating instructions for the EM4800 Remote Display

(part number METSxEM48RD), refer to the "PowerLogic Remote Display Kit for EM4800 Meters" technical document.

Recording the Meter Map The final step in the installation process is to complete the Installation

Record, and record the mapping of the meters to the wired points. A copy of Figure 16, which is organised to resemble a breaker panel, is provided with each PowerLogic EM4800 meter, and is to be completed and delivered to your system administrator.
© 201 Schneider Electric All Rights Reserved32
Page 39
930-110-01-B.00 PowerLogic
TM
EM4800 Series
04/2011 Installation
Figure 16: Installation Record (sample shown)
© 201
Schneider Electric All Rights Reserved
33
Page 40
PowerLogic
DANGER
2
3
Legend: 1 Fuse holder 2Fuse 3Fusecover
1
TM
EM4800 Series 930-110-01-B.00
MAINTENANCE Do not perform any operation or maintenance procedures that are not
described in this product documentation. Visually inspect the equipment yearly and ensure it is free of dust or other particles. If necessary, wipe with a clean cloth. Individual components are not user-serviceable and must be returned to Schneider Electric for repair.

Fuse Replacement

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
Turn off all power supplying this equipment before working on or inside equipment.
Always use a properly rated voltage sensing device to confirm the power is off.
Replace all devices, doors and covers before turning on power to this equipment.
Failure to follow these instructions will result in death or serious injury.
1. Turn off all sources of power before attempting to replace the fuse. Always use a properly rated voltage sensing device to confirm the power is off.
2. Remove the outer cover from the unit.
3. Locate fuse F1 at the top left corner inside the unit.
4. Remove the fuse cover, then remove the fuse from the holder as shown in Figure 17.
5. Replace fuse F1 with a fuse that meets the specifications listed in Table 1 on page 2.
6. Replace the fuse cover.
7. Re-install the cover and turn on the power source.
Figure 17: Replacing the fuse
© 201 Schneider Electric All Rights Reserved34
Page 41
930-110-01-B.00 PowerLogic 04/2011 Regulatory Compliance
TM
EM4800 Series

REGULATORY COMPLIANCE The PowerLogic EM4800 meter must be installed by a qualified electrician

with knowledge of local installation regulations. Initial installation of the unit, and any subsequent modification to the unit, must be inspected by the local electrical inspection authority.
The PowerLogic EM4800 meter complies with the standards listed in Table 4.
Table 4: Regulatory Compliance
Discipline Regulatory and industry standard
Standards UL certified to IEC/EA/UL/CSA 61010-1 2nd Edition
CSA-C22.2 No. 61010-1-04 Emissions (EMC) FCC Part 15 Class B, ICES-003 EN55022, IEC 6100-4-5 Surge power/telephone lines ANSI/TIA968-A: 2002

Equipment servicing and access The information in this section must be considered as a mandatory

requirement, and must be strictly adhered to when installing and operating PowerLogic EM4833, EM4880 and EM4805 meters.

Access to equipment

The equipment must be accessible to authorized personnel only. Equipment must be installed in areas where access can be restricted.

Servicing the equipment

No preventive maintenance is required on any of the equipment. Visually inspect the equipment yearly and ensure it is free of dust or other particles. If necessary, wipe with a clean cloth.

Component servicing

Individual components are not user-serviceable, and must be returned to Schneider Electric for repair. If an equipment fault occurs, do not attempt to repair the faulty component.
All maintenance activities should be performed by qualified personnel only. Do not perform any operating or maintenance procedures that are not described in the product documentation provided by Schneider Electric.
© 201
Schneider Electric All Rights Reserved
35
Page 42
PowerLogic
TM
EM4800 Series 930-110-01-B.00

Graphical symbols

Table 5 shows the graphical symbols that appear on the equipment.
Table 5: Graphical symbols that appear on equipment
Symbol Description
Indicates the supply wire protective earth, also known as
chassis ground, for the primary ground.
This symbol indicates a replaceable fuse.
© 201 Schneider Electric All Rights Reserved36
Page 43
930-110-01-B.00 PowerLogic 04/2011 Index
TM
EM4800 Series

Index

Numerics
347V installation
typical three-phase configuration
5A converters and current transformers
install 23
5A current transformers
install 27
12
A
audience 1
C
compliance
electrical safety
control voltage and current
meter 2
current transformers
install 22 meter 2
6
D
delta service
install sense voltage and control voltage cables 13
dimensions
meter 2
E
electrical safety compliance 6 equipment
access servicing 35
equipment servicing 35
35
F
fuse rating
meter 2
I
install
5A converters and current transformers 23 5A current transformers 27
potential transformers 11 installation 7 installation procedures
overview 8 Installing 23
M
maximum altitude
meter
2
maximum pulse per second
meter 2 measurement accuracy
2
meter meter
control voltage and current
CT color pair identification 26, 29
current transformers 2
2
dimensions 2 fuse rating 2 installation in a 120/208V three-phase wye panel with
120V variant 16
installation in a 240/416V three-phase wye panel with 230/
240V variant 17
installation in a 277/480V three-phase wye panel with
120V variant
installation in a 347/600V or higher three-phase wye panel
with 120V variant 19 installation in a single-phase panel with 120V variant 15 installation in a three-phase Delta panel with 120V variant
18
20
internal view 4–5 maximum altitude 2 maximum pulse per second 2 measurement accuracy 2 minimum pulse width 2 mounting 9 NVM storage 2 onboard Ethernet port 2 onboard modem 2 operating humidity 2 operating temperature 2 pollution degree 2 pulse inputs 1 and 2 2 sense voltage 2 serial port 2 specifications 2 usage environment 2 weight 2
meter map
recording 32
minimum pulse width
meter 2
mounting
9
meter
N
NVM storage
2
meter
O
onboard Ethernet port
2
meter
onboard modem
meter
2
operating humidity
meter 2
operating temperature
2
meter
P
pollution degree
2
meter
potential transformers
install
11
English
© 201
Schneider Electric All Rights Reserved
37
Page 44
meter
TM
EM4800 Series 930-110-01-B.00
2
PowerLogic Index 04/2011
pre-installation 7
English
pulse inputs 31 pulse inputs 1 and 2
S
sense voltage
2
meter
sense voltage and control voltage cable installation
wye and delta service 13
serial port
meter 2 servicing equipment 35 site planning 8 site preparation
lighting 8
power 8 specifications
meter 2 start-up sequence 30
U
usage environment
2
meter
W
weight
2
meter wye service
install sense voltage and control voltage cables 13
© 201 Schneider Electric All Rights Reserved38
Page 45
930-110-01-B.00 PowerLogic 04/2011 user notes
TM
EM4800 Series

USER NOTES

© 201
Schneider Electric All Rights Reserved
39
Page 46
PowerLogic
TM
EM4800 Series 930-110-01-B.00
© 201 Schneider Electric All Rights Reserved40
Page 47
930-110-01-B.00 PowerLogic
TM
EM4800 Series
04/2011
© 201
Schneider Electric All Rights Reserved
Page 48
PowerLogic
TM
EM4800 Series
Installation Guide
Schneider Electric USA
Power Monitoring and Control 295 Tech Park Drive, Suite 100 Lavergne, TN 37086 USA 1-888-SquareD (1-888-778-2733) www.powerlogic.com
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences ari sing out of the use of this material.
930-110-01-B.00 © 201
Schneider Electric All Rights Reserved
04/
2011
Loading...