Schneider Electric DI-16 Data Sheet

[SmartX Controller]
II//OO MMoodduullee DDII--1166
SmartStruxure solution
1
Patented two-piece design
Each module can be separated from its terminal base to allow the site to be wired prior to the installation of the electronics. The patented locking mechanism serves as handles for removing the module from its base. All critical components have a protective cover that permits convection cooling to occur.
Introduction
The DI-16 is a digital input, 16 channel I/O module.
The digital inputs can be used for cost effective sensing of multiple dry contact digital inputs in applications, such as equipment status monitoring or alarm point monitoring. As counter inputs, digital inputs are commonly used in energy metering applications.
Function
Modular and scalable system
The modules are part of a modular system that delivers power and communications on a common bus. Connecting modules is a one-step process: just slide the modules together using the built-in connectors.
Figure: Two-piece design
Hot-connect and Hot-swap
Because critical applications require 24-hour operation, Schneider Electric designed the I/O modules for hot-connection of terminal bases and hot-swapping of the modules to their bases. This design ensures continuous power and communication during service operations.
Auto-addressing
The auto-addressing feature eliminates the need for setting DIP switches or pressing commission buttons. Each module automatically knows its order in the chain and assigns itself accordingly – significantly reducing engineering and maintenance time.
Simple DIN-rail installation
Fasteners easily snap into a locked position for panel installation. The fastener has a quick-release feature for easy DIN-rail removal.
Schneider Electric | Building Business
Trademarks and registered trademarks are the property of their respective owners. 03-16003-02-en June 2016
© 2016 Schneider Electric. All rights reserved.
[SmartX Controller]
SmartStruxure solution
2
Efficient terminal management
The I/O module terminals are clearly labeled and protected by transparent covers. The input and
LED status indicators
The I/O module has a status indicator that denotes
the health and status of the module. output terminals are at the top and bottom of each module and are accessible for maintenance without removing the module. The StruxureWare Building Operation WorkStation software can generate
Each input channel has a dedicated two color
status LED. The LED can be configured to display
either red or green for each input state. custom as-built labels for each module. Pre­perforated letter and A4 size label sheets are available as an accessory.
Accommodates multiple row panel installations
Protection
Protection components on the inputs protect
against high-voltage short-duration transient
events. The SmartStruxure devices use built-in connectors for single row connectivity, side by side. If a panel size requires multiple rows, extension cords are available.
Specifications
Input channels .........................................................................................................................................16
DC input supply power .......................................................................................................................1.6 W
DC input supply voltage...................................................................................................................24 VDC
Environment
Ambient temperature, operating.............................................................................0 to 50 °C (32 to 122 °F)
Ambient temperature, storage.........................................................................-20 to +70 °C (-4 to +158 °F)
Maximum humidity...............................................................................................95 % RH non-condensing
Material
Plastic rating................................................................................................................................UL94-5VB
Enclosure .......................................................................................................................................PC/ABS
Enclosure rating...................................................................................................................................IP 20
Mechanical
Dimensions including terminal base ..............................90 W x 114 H x 64 D mm (3.6 W x 4.5 H x 2.5 D in.)
Weight including terminal base..........................................................................................0.255 kg (0.56 lb)
Weight excluding terminal base.........................................................................................0.131 kg (0.29 lb)
Terminal base ..............................................................................................................................TB-IO-W1
Schneider Electric | Building Business
Trademarks and registered trademarks are the property of their respective owners. 03-16003-02-en
© 2016 Schneider Electric. All rights reserved.
June 2016
[SmartX Controller]
SmartStruxure solution
Agency compliances
Emission ................................................................RCM; EN 61000-6-3; FCC Part 15, Sub-part B, Class B
Immunity ...............................................................................................................................EN 61000-6-2
Safety.................................................................................................EN 61010-1; UL 916 C-UL US Listed
Product ....................................................................................................................................EN 61326-1
Smoke control product safety...........................................................................................................UL 864
Part numbers
DI-16, I/O module
16 digital inputs ..............................................................................................................SXWDI16XX10001
TB-IO-W1, terminal base for I/O module
(Required for each I/O module)......................................................................................SXWTBIOW110001
Accessory part numbers
DIN-RAIL-CLIP, DIN-rail end clip
package of 25 pieces ....................................................................................................SXWDINEND10001
PRINTOUT-A4-W1, printout sheets for terminal labels
A4 sheet size, 100 sheets, 18 labels per sheet...............................................................SXWTERLBL10011
PRINTOUT-LTR-W1, printout sheets for terminal labels
Letter sheet size, 100 sheets, 16 labels per sheet ..........................................................SXWTERLBL10012
S-CABLE-L, S-cable extension cord for the I/O bus, L shaped connectors
1.5 m............................................................................................................................SXWSCABLE10002
S-CABLE-L, S-cable extension cord for the I/O bus, L shaped connectors
0.75 m..........................................................................................................................SXWSCABLE10003
Digital inputs
3
Range .........................................Dry contact switch closure or open collector/open drain, 24 VDC, 2.4 mA
Absolute maximum ratings .................................................................................................-0.5 to +24 VDC
LED polarity ...................................Software selectable, if the LED is activated when the input is high or low
LED color.................................................................................................Red or green, software selectable
Digital
Minimum pulse width .......................................................................................................................120 ms
Counter
Minimum pulse width .........................................................................................................................20 ms
Maximum frequency ...........................................................................................................................25 Hz
Schneider Electric | Building Business
Trademarks and registered trademarks are the property of their respective owners. 03-16003-02-en
© 2016 Schneider Electric. All rights reserved.
June 2016
[SmartX Controller]
SmartStruxure solution
4
For protection from excess current that could be produced by field wiring, follow these instructions:
• Connect one RET terminal on each of the I/O modules to a common chassis/power ground rail in the control panel using a size 16 AWG,
1.3 mm, or larger wire.
Regulatory Notices
Federal Communications Commission
FCC Rules and Regulations CFR 47, Part 15, Class B This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation.
Industry Canada
This Class B digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
Regulatory Compliance Mark (RCM) - Australian Communications and Media
Authority (ACMA)
This equipment complies with the requirements of the relevant ACMA standards made under the Radiocommunications Act 1992 and the Telecommunications Act 1997. These standards are referenced in notices made under section 182 of the Radiocommunications Act and 407 of the Telecommunications Act.
• For more information on wiring, see Hardware Reference Guide.
CE - Compliance to European Union (EU)
2014/30/EU Electromagnetic Compatibility Directive 2011/65/EU Restriction of Hazardous Substances (RoHS) Directive This equipment complies with the rules, of the Official Journal of the European Union, for governing the Self Declaration of the CE Marking for the European Union as specified in the above directive(s) per the provisions of the following standards: EN 61326-1 Product Standard, EN 61010-1 Safety Standard.
WEEE - Directive of the European Union (EU)
This equipment and its packaging carry the waste of electrical and electronic equipment (WEEE) label, in compliance with European Union (EU) Directive 2012/19/EU, governing the disposal and recycling of electrical and electronic equipment in the European community.
UL 916 Listed products for the United States and Canada, Open Class Energy
Management Equipment. UL file E80146.
UL 864 Listed products for the United States. 10thEdition Smoke Control
System. UL file S5527.
Schneider Electric | Building Business
Trademarks and registered trademarks are the property of their respective owners. 03-16003-02-en
© 2016 Schneider Electric. All rights reserved.
June 2016