ARGUS smoke detector© Merten2005V5485-561-0003/08
1.
2. ...max. 25
L1
L2
L3
N
1
GB
ARGUS smoke detector
Operating instructions
ARGUS smoke detector 230 V
Art. no. MTN5475..
ARGUS smoke detector Connect
230 V
Art. no. MTN5485..
Accessories
– Sealing pin for ARGUS smoke detector
(Art. no. MTN547000)
You can use sealing pins to see whether the smoke detector is manipulated.
– System relay flush-mounted for ARGUS smoke detec-
tor (Art. no. MTN548001)
The system relay flush-mounted controls external alarm
devices.
For your safety
DANG ER
¼
Risk of fatal injury from electrical current
The device may only be installed and connected
by skilled electricians. Observe the regulations
valid in the country of use.
CAUTION
½
• Do not paint the smoke detector!
• The loud warning tone can damage your hearing (protect your ears when performing the
functional test).
•Smoke detectors do not extinguish a fire!
• Smoke detectors detect smoke, but no flames
or, heat!
• The power must be supplied to the smoke detector via mains voltage (230 V). The battery
supplies the smoke detector in case of temporary mains voltage failure.
• The smoke detector only works with a functioning, correctly connected and inserted battery.
Functioning without battery is not possible!
• Do not use rechargeable batteries or power
packs!
around where it has been installed and not necessarily other rooms or other floors!
• The smoke detector monitors a specific area
DANGER
½
Smoke fumes are poisonous and can quickly lead
to a loss of consciousness. In the event of fire, inform everyone in the household (smoke will not
wake people up, children tend to hide when in a
panic) and leave the building immediately. If there
is a lot of smoke, crawl along the floor. Do not expose yourself to unnecessary danger. Inform the
fire brigade (WHO, WHERE, WHAT)! - Your local
fire brigade is happy to advise you.
Think about how you can prevent fires and what
|
to do in case of a fire (escape plan, assembly
point, location of fire extinguishers, etc.).
Getting to know the smoke detector
The ARGUS smoke detector 230 V/Connect 230 V (referred to below as the smoke detector) is a mains-powered smoke detector with backup battery for early
detection of smouldering fires and open fires with smoke
building-up indoor.
The green LED of a functional smoke detector glows
green, and the red LED flashes every 40 seconds.
The green LED shows that the 230 V power supply has
been applied. If the 230 V supply fails, the green LED
goes out and the battery takes over supplying the smoke
detector.
If the battery is not supplying enough power, a tone will
sound every 40 seconds to supplement the flashing red
LED. The smoke detector will continue to function for another 30 days.
CAUTION
½
If you are away for longer than 30 days, you will
not hear the warning tone. Therefore, perform a
functional test directly after you return.
If the alarm persists for more than five seconds, the radio
module will activate all other smoke detectors equipped
with a radio module in the range and they will also sound
the alarm.
The detector which detected the smoke will transmit the
alarm signal for at least 60 seconds and until it no longer
detects smoke. A receiving detector will check for an
alarm signal every 50 seconds. If no alarm signal comes
from the transmitting detector, the receiving detector will
also stop the alar.
When you combine a radio smoke detector net-
|
work with a wire smoke alarm network, there may
only be one smoke detector with active radio operation in the wire smoke detector network!
Smoke detector signals
Make sure that everyone in the building is familiar
|
with the signals of the smoke detector!
The following LED and tone signals show the dependend status of the smoke detector:
Smoke alarm
Normal operation
40 s
40 s
~ 230 V
Battery empty
40 s 40 s
Defect of the smoke detector
...........
...........
...........
...........
...........
Connections, displays and operating
elements
A
Battery (9 V monobloc Battery)
B
Battery connection
C
Test button and LEDs (red/green)
D
Smoke detector
E
Switch for radio networking
F
Connecting pins for 230 V
G
Cover cable connection230 V
H
Network terminal 230 V
I
Base
Selecting the installation site
CAUTION
½
The smoke detector monitors a specific area
around where it has been installed and not necessarily other rooms or other floors!
Watch out the following criterias for installing a smoke
detector:
max. 8 m
min. 0,5 m
max. 6 m
min. 0,3 m
max. 60 m²
Do not install the smoke detector
• in areas where there is a draught (next to windows,
doors, etc.)
• in areas where there is steam/exhaust fumes/dust,
etc.
• next to lighting fixtures and ballasts (at least 1 m distance )
min. 0,5 m
The next examples show you how many smoke detector
are necessary for the minimal und optimal protection
rate:
Minimal
Optimal
How to mount the smoke detector
1
1 Mount the base with 2 srews.
2 Connect a 9 V battery and put it into the smoke de-
tector.
3 Open the cover of the cable connection.
– For flush-mounting installation there is a special
base inside the box.
4 Put away the cable connection terminal.
5 Connect the 230 V cables to the terminal.
4
6 Press the smoke detector from below to the base
and turn it anti-clockwise.
Watch out the correct position of the connecting
|
pins for 230 V!
2
How to network the smoke detector
When using several smoke detectors it can make sense
to network the detectors with each other. When one detector is triggered, this triggers the rest of the detectors
in the network.
ARGUS smoke detectors 230 V/Connect 230 V an be
connected via the network terminal by wire or by integrated radio. Wired networking is carried out via a separate
free core of the 230 V cable.
A maximum of 25 detectors can be connected via wire.
Between two detectors the network cable may not be
longer than 25 m.
CAUTION
¼
Wire networking is allowed with ARGUS smoke
detectors Connect 230V/ARGUS smoke
detectors 230 V only.
Wired networking with ARGUS Connect smoke
detectors is not allowed.
With a radio network, it is possible to assign different ID
numbers to ensure that other smoke detectors in the
neighbourhood (where the recept ion ranges overlap) are
not triggered, for example.
There are group and device IDs.
• Group ID: for establishing a smoke detector group
• Device ID: for establishing an individual device address (for later use)
These group IDs are set using the 4 switches of the
switch bank located directly next to the network terminal.
When one smoke detector is triggered, the warning
tones of the other smoke detectors in the transmission
radius with the same group ID are triggered (the LED
only glows on the smoke detector triggered initially).
These smoke detectors are no longer able to transmit
the signal by radio, as they can only be receivers or
transmitters!
V5485-561-00 03/08
Radio operation is switched off when the ID has
1.3
1.21.4
1.1
= max. 40
1.x
1.x
max. 10
2
3
5
4
1
10
7
8
9
6
∅ 30 m
Σ = max. 10
|
been set to 0.0 (all switches to "0"). This is useful
if the smoke detector is only networked by cable.
For all other switch settings, radio operation is always switched on!
1
0
=0
1 2 3 4
1 2 3 4
1
0
=0
=
Network a maximum of 40 smoke detectors
As a rule, several smoke detectors are combined to form
a system. More than 40 smoke detectors should never
be networked, regardless of whether the connections
are wireless or wired. If more than 40 radio detectors are
networked, then the time required until the last detector
has reacted will be too long to guarantee a reliable fire
alarm.
Maximum of 10 radio-networked smoke detectors
in one radio cell
The maximum radio module range of 30 m means that
devices are surrounded by a radio cell with a diameter of
30 m. Within such a radio cell, 10 Connect smoke detectors may be radio-networked together.
In reality, the size of a radio cell is reduced by many factors. Structural conditions are just as much a factor as
with all other radio components. Walls and furniture, etc.
also cause attenuation, which must be taken into account. This is why a functional test is obligatory before final installation!
Maximum of 2 radio-networked smoke detectors in
one wired line
1.3
1.2
1.1
2.1
2.2
3.2
3.3
1.4
1.5
2.3
2.4
3.1
When Connect smoke detectors are wired to one another, they form a wired line. Within a line like this, a maximum of 2 radio-networked smoke alarms is allowed.
Each of these smoke alarms must always be assigned to
a different group ID. This type of network is conceivable
in a multiple family house, where two flats are connected
to each other. Radio operation for all other smoke detectors in this wired line must be switched off (ID = 0.0).
If 2 radio-networked smoke alarms already exist in the
wired line, then no additional wired lines may be connected to this system via radio.
Again, the reason is the running time for the signals,
which would be too long in such a system. The time between triggering the first detector and the reaction of the
last one would be too long to guarantee a reliable fire
alarm.
If there is only one radio-networked smoke alarm in wi red
lines, then up to 10 wired lines may be networked via radio. The radio-networked smoke alarms of these wired
lines must all be in the same radio cell.
How to operate the smoke detector
Conduct a functional test
• After installation
• Every time you change the battery
• After a long absence (more than 30 days)
• At least once a year
1 Press the test button for at least 1 second.
As lon g as th e te st b utt on i s pressed, a pulsating warning
tone sounds and the red LED flashes.
If not, check the battery/battery connection or replace
the smoke detector.
The smoke detector transmits a test alarm for 60 seconds. All other networked Connect smoke detectors will
detect this within 50 seconds and sound the alarm as
well.
We recommend that you replace your smoke detector after about ten years.
How to change the battery
CAUTION
½
• There is a risk of explosion if the battery is not
replaced in the correctly. Do not damage, crush
or short circuit the battery. Do not use pointed
or sharp tools when replacing the battery. Only
use batteries of the same type when replacing
used batteries.
• Dispose used batteries according to the relevant regulations and without harming the environment.
1 Turn the smoke detector clockwise and pull it down-
wards away from the base.
2 Change the battery.
3 Mount the smoke detector again.
Maintenance and care
Wipe the smoke detector clean (using a moist cloth only), carefully remove dust using a brush.
Carry out a functional test afterwards.
Technical data
Battery: 9 V, monobloc battery,
Battery life
With 230 V supply: approx. 4-5 years, depen-
With Battery supply only: approx. 2,5 years
Supply voltage: AC 230 V -15%/+10%
Battery failure signal: every 30 sec., 30 days
Optical display: red LED (Operation)
Sensitivity: EN 14604:2005
Volume of the signal
transmitter: approx. 85 dB(A) at a
Network: up to 40 smoke alarms
Network cable: E. g. with additional free
Cable length: between two smoke detec-
Radio frequency: 868 MHz
Transmission range
Indoor/outdoor up to 30 m/up to 100 m
Operating temperature
range: 0°C to +60°C
Type of protection IP 42
Dimensions: 112x44 mm (ø x H)
VdS approval: G207119
Accordring to: EN 14604
IEC 6LR61 (alkaline)
dent of the self discharge of
the battery
50 Hz
green LED (Network)
distance of 3 m
(of these, up 25 via wire)
core in 230 V network
(1 x 1,5 mm2)
tors up to 25 m
(up to 500 m total)
112x59 mm (ø x H)
(surface mounting base)
Schneider Electric Industries SAS
If you have technical questions, please contact the
Customer Care Center in your country.
www.schneider-electric.com
This product must be installed, connected and used in
compliance with prevailing standards and/or installation
regulations. As standards, specifications and designs
develop from time to time, always ask for confirmation of
the information given in this publication.
V5485-561-00 03/08