Samson 42-34, 42-38 Mounting And Operating Instructions

Self-operated Regulators
Differential Pressure Regulators with Flow Limitation
Type 42-34 · Type 42-38
Mounting and Operating Instructions
EB 3013 EN
Edition July 2009
Contents
Contents Page
1 Design and principle of operation . . . . . . . . . . . . . . . . . . . . . . 4
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Mounting position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Strainer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Shut-off valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.4 Pressure gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.5 Control line, equalizing tank and needle valve . . . . . . . . . . . . . . . . 8
3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.1 Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2 Set point adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2.1 Adjusting the differential pressure . . . . . . . . . . . . . . . . . . . . . . 10
3.2.2 Adjusting the flow restriction . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2.3 Pressure conditions in the plant and regulator . . . . . . . . . . . . . . . . 12
3.3 Decommissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4 Maintenance · Troubleshooting . . . . . . . . . . . . . . . . . . . . . . 18
4.1 Replacing the operating diaphragm . . . . . . . . . . . . . . . . . . . . 19
5 Nameplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6 Dimensions and weights. . . . . . . . . . . . . . . . . . . . . . . . . . 22
7 Customer service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Definitions of the signal words used in these instructions
WARNING!
WARNING indicates a hazardous situation
Note: Supplementary explanations, informa
tion and tips which, if not avoided, could result in death or serious injury.
NOTICE
NOTICE indicates a property damage message.
2 EB 3013 EN
-
Safety instructions
General safety instructions
The regulators must be installed, started up and serviced by fully trained and
4
qualified personnel only, observing the accepted industry codes and practi ces. Make sure employees or third persons are not exposed to any danger.
The regulator complies with the requirements of the European Pressure Equip
4
ment Directive 97/23/EC. The declaration of conformity issued for a valve bearing the CE marking includes information on the applied conformity as sessment procedure. The declaration of conformity can be provided on request.
For appropriate operation, make sure that the regulator is only used in appli
4
cations where the operating pressure and temperatures do not exceed the operating values based on the sizing data submitted in the order.
Note that the manufacturer does not assume any responsibility for damage
4
caused by external forces or any other external factors. Any hazards whichcould be causedin the regulatorby the processmedium or
4
operating pressure are to be prevented by means of appropriate measures. Proper shipping and appropriate storage are assumed.
4
-
-
-
-
Note: Non-electric valve versions which do not have a valve body lined with an insulating coa ting donot have theirown potential ignitionsource according tothe ignition risk assessment sti pulated in EN 13463-1: 2001, section 5.2, even in the rare incident of an operating fault. The refore, they do not fall within the scope of Directive 94/9/EC. For the connection to equipotential bonding, observe section 6.3 in EN 60097-14: 1977 (VDE 0165, Part 1)
EB 3013 EN 3
-
-
-
Design and principle of operation
1 Design and principle of
operation
The differential pressure regulators are used to maintain the differential pressure between the high-pressure and the low-pressure pipe at a set point which is either fixed (Type 42-38) or adjustable (Type 42-34). The re striction built into the valve body allows for limitation of the flow rate. The regulators basically consist of a valve with a seat, plug and restriction as well as a closing actuator with an operating dia phragm. The valve and actuator are deliv ered in separate packaging and need to be connected on siteusing the coupling nut(11).
The process medium flows through the valve in the direction indicated by the arrow. The free areasof flow releasedby the orifice(1.4) and the valve plug (3) determine the flow rate
.
and the differential pressureΔp
V
the plant. Fully balanced valves ensure that the up-
stream and downstream forces acting on the valve plug are eliminated by a balancing bel lows (5) or a balancing diaphragm (5.1). The principle of operation of the regulators with valves balanced by a bellows or by a dia phragm only differ concerning their pressure balancing. Valves balanced by a diaphragm (DN 125 to 250 only) have a balancing dia phragm instead of a balancing bellows (5). The pressure downstream of the orifice (1.4) acts on the outer surface of the metal bellows
plant
across
or balancing diaphragm and the down
stream pressure on the inside of the bellows
or diaphragm. As a result, the forces created
by the upstream and downstream pressures
acting on the valve plug are equally bal
anced.
The regulators in sizes DN 15 to 100 are
-
equipped witha connecting piece(10) forthe
low-pressure control line between the valve
and the actuator.
In differential pressure control, the high pres
sure (flow) of the plant is transmitted to the
­bottom diaphragm chamber of the actuator
­over the high-pressure control line. The pres
sure downstream of the orifice (1.4) acts on the top diaphragm chamber over the hollow plug stem and the connected low-pressure control line. The differential pressure is con­verted into a positioning force at the dia­phragm (13) and is used to change the posi­tion ofthe valve plug according to theforce of the set point springs (16). Depending on the version of the actuator, the set point springs are installed in the actuator to provide a fixed set point (Type 42-38), or they are located
­outside to allow the set point tobe adjusted as
required (Type 42-34).
-
The restriction (1.1) is used to adjust the flow limitation.
The force limiter (20) as well as the internal
­excess pressure limiter (21) are designed to
protect the seat (2) and plug (3) against over load in caseof extreme operating conditions.
-
-
-
-
-
Table 1 · Regulator configuration
Controller = Valve + Actuator Type 42-34 with connecting piece (
Type 42-38 with connecting piece Type 2423 Balanced Type 2428 Fixed set point
for DN 15 to 100) Type 2423 Balanced Type 2424 Adjustable set point
4 EB 3013 EN
Design and principle of operation
Type 42-34
Type 42-34, Type 42-38 · Balanced by a bellows
DN 15 to 250
Type 2423 Valve balanced by a bellows
Type 2424
Type 2428 Actuator
Actuator
1 Valve body
1.1 Restriction (for flow rate set point adjustment)
1.2 Lock nut
1.3 Cap
1.4 Orifice
2 Seat 3 Plug 4 Plug stem 5 Balancing bellows 7 Spring 8 Venting
(DN 125 and larger)
Fig. 1 · Schematic diagrams of regulator with valve balanced by a bellows
Type 42-38
DN 15 to 100
9 Low-pressure control line
(up to DN 100)
9.1 Low-pressure control line connection (DN 125 and larger)
10 Connecting piece (up to DN 100) 11 Coupling nut 12 Diaphragm stem 13 Operating diaphragm 14 Actuator housing 15 Screws 16 Set point springs 17 Set point adjustment (screw) 18 Nut 19 Diaphragm plate 20 Force limiter 21 Internal excess pressure limiter
EB 3013 EN 5
Installation
Type 2423 Valve balanced by a diaphragm
Type 42-34 · Balanced by a diaphragm · DN 125 to 250
Type 2424 Actuator
1 Valve body
1.1 Restriction (for flow rate set point adjustment)
1.2 Lock nut
1.3 Cap
1.4 Orifice
Fig. 2 · Schematic diagrams of regulator with valve balanced by a diaphragm
2 Installation
See Figs. 1 and 2
The regulator must be installed in the return flow pipe as shown in the installation sche matic in Fig. 5.
When choosing the place of installation, en sure the regulator can be easily accessed af
2 Seat 3 Plug 4 Plug stem
5.1 Balancing diaphragm 11 Coupling nut 12 Diaphragm stem
-
-
-
NOTICE
The regulator mustbe installed freeof stress. If necessary, support the piping near the con nections. However, do not attach supports to the valve or actuator.
ter completion of the plant.
6 EB 3013 EN
-
Installation
Note: Install a strainer (e.g. SAMSON Type 2 N/2 NI) upstream of the regulator to prevent sealing particles, welding spatter or other impurities carried along by the process medium from impairing the proper function ing of the valve, especially tight shut-off.
2.1 Mounting position
See Fig. 3 for permissible mounting positions. Standard installation · Install the valve with
out the actuator in a horizontal pipeline with the connection for the actuator facing down­wards. Make sure the medium flows through the valve in the direction indicated by the ar­row. Then connect the actuator (and the con­necting piece (10) for versions in sizes DN 15 to 100) to the valve using the coupling nut (11).
Standard mountingposition
– all versions –
All versions up to max. 80 °C
NOTICE
Protect the regulator when it is used to control freezing process media. On shutting down the plant in areas not free from frost, depressurize and empty the regu
­lator and remove it from the pipeline.
2.2 Strainer
A strainer installed in the flow pipe (Fig. 5) prevents foreign matter and dirt particles in
­the medium from entering the regulator. The
SAMSON product range includes the Type 2 N/2 NI Strainer (refer to Data Sheet T 1010 EN).
Install the strainer upstream of the regulator. Make sure the direction of medium flow cor­responds with the direction indicated by the arrow on the strainer. The filter element must be suspended downwards. Remember to leave enough space to remove it.
2.3 Shut-off valve
We recommend installing a hand-operated shut-off valve (Fig. 5) both upstream of the strainer and at the outlet of the return flow pipe to be able to shut down the plant for cleaning and maintenance, and when the plant is not used for longer periods of time.
-
Only versions with fixed plug guide and up to max. 80 °C
Fig. 3 · Permissible mounting positions
2.4 Pressure gauge
To monitor the pressures in the plant, install a pressure gauge both upstream and down stream of the regulator (Fig. 5).
EB 3013 EN 7
-
Installation
2.5 Control line, equalizing tank and needle valve
Control lines · After mounting the actuator,
fasten the supplied high-pressure control line to the regulator (standard: 8 mm pipe diame ter) routing it from the bottom diaphragm chamber to the high-pressure line (flow pipe) of the plant. Attach the low-pressure control line to the regulator as shown in Figs. 1 and
2.
The controlline to be installed on site for pres sure tapping at the pipeline must be at least three times the nominal size (DN) away from pipe fittings or instruments thatcause flow tur bulence (e.g. pipe bends, manifolds,pressure measuring points or other valves) (see Fig.
4.1). How the lines are routed generally de-
pends on the installation location. Preferably connect the control line at the side of the main pipeline (Fig. 4.4).
Do not change the pipe diameter of the main pipeline so that it is off-center!
Control line kit · A control line kit for tapping pressure directly at the valve body is avail able as an accessory from SAMSON. Refer to Data Sheet T 3095 EN.
Equalizing tank · An equalizing tank is re quired for liquids above 150 °C. Install an equalizing tank in the control line directly downstream of the pressure tapping point. The mounting position of the equalizing tank is indicated by an adhesive label on the tank itself as well as by an arrow and the word "top" stamped onto the top of the tank. Ad here to the mounting position and distances prescribed, otherwise the safe functioning of the regulator cannot be guaranteed.
Correct!
-
4.4 · Connection at the side – correct
Incorrect!
-
4.3 · Connection at the top – incorrect
-
Incorrect!
4.2 · Connection at the bottom – incorrect
-
-
-
DN = Nominal size
4.1 · Control line connection, depending on how the pipeline is routed
Fig. 4 · Control line connection
8 EB 3013 EN
Operation
Needle valve · If the regulator tends to hunt, we recommend installing a SAMSON needle valve in the control line installed on site at the actuator connection.
Note: Needle valves, equalizing tanks and compression-type screw fittings can be sup plied as required. These accessories are listed in the Data Sheet T 3095 EN.
1 Shut-off valve 2 Strainer 3 Differential pressure regulator 4 Equalizing tank (optional) 5 Pressure gauge 6 Needle valve (optional) 7 Motorized valve
Fig. 5 · Typical installation, Type 42-34/42-38
installed in the return flow pipe
3 Operation
See Figs. 1 and 2.
3.1 Start-up
CAUTION!
­First start up the regulator after mounting all
the components, e.g. valve, actuator andcon trol line. Make sure the control line (and needle valve) is open and correctly connected before start-up. For media temperatures above 150 °C, fill the equalizing tank with the process medium (water) before start-up.
Note: On filling the plant, make sure the orifice (1.4) is open byunscrewing the restric­tion (1.1) counterclockwiseas far asit will go.
Open all the valves on the consumer side.
4
Slowly open the shut-off valves starting on the return flow pipe first. In case of valves balanced by a bellows in DN 125 or larger, vent the bellows housing at the stopper (8) located at the side of the bel lows housing.
Rinsing the plant · After filling the plant, first completely open the consumers. At the regu lator, openthe restriction counterclockwise as far as it will go and adjust the maximum dif ferential pressure by tensioning the set point springs to the maximum. Rinse out the pipe line at full flow ratefor several minutes. Check the installed strainer (e.g. by measuring the pressure drop) afterwards. Clean the strainer, if necessary.
-
-
-
-
-
EB 3013 EN 9
Operation · Set point adjustment
NOTICE
When testing the pressure of the plant when the regulatoris already installed, the pressure must not exceed the nominal pressure of the valve by 1.5times nor themaximum permissi ble differential pressure in the actuator (final value of set point range by 1.5 times). If higher test pressures are used, unscrew the control lines connected to the actuator and seal openings atthe actuator andcontrol lines with stoppers.
3.2 Set point adjustment
3.2.1 Adjusting the differential pressure
Type 42-34 only · Set the required differen-
tial pressure by turning the set point screw (17) when the plant is almost closed and the orifice (1.4) is completely open. Then adjust the value for the flow restriction.
Turn clockwise= Tensioning thesprings To increase the set point
Turn counterclockwise = Relieving the springs of tension→To reduce the set point.
How to proceed
Close motorized valve!
4
Unscrew cap (1.3) and undo lock nut
4
(1.2). Turn the restriction (1.1) counterclockwise
4
as far as it will go (completely opening it) to deactivate the flow restriction.
Relieve the set point springs (16) of ten
4
sion. Open motorized valve slightly (approx.
4
10 % travel).
-
Adjust the differential pressure by
4
tensioning the set point springs at the set point screw (17).
3.2.2 Adjusting the flow restriction
Open control and shut-off valvesas well as all the consumers (minimum plant resistance) to achieve the maximum flow rate.
Close the bypass, if applicable. Adjust the desired flow limitation by turning
the restriction (1.1),monitoring the flow meter in the heat meter (see Table 2 · Flow rate set points for water).
Note: Always start the set point adjustment based on a closed restriction.
Turn clockwise to close the restriction Reduces the flow rate.
Turn counterclockwise to open the restric tion→Increases the flow rate.
How to proceed
Completely close the restriction (1.1) to
4
block the flow rate Completely open motorized valve.
4
Open restriction (1.1), turning it counter
4
clockwise, until the desired flow rate is reached.
Initially open the restriction by one turn at
4
a time, while monitoring the flow rate at
-
-
-
10 EB 3013 EN
Operation · Set point restriction
the flow meter in the heat meter. Then ad just it in small steps until the required flow rate is constant (generally,±2 % devia tions are acceptable).
If therequired flow rate is not reached,the
4
differential pressure set point must be in creased (see section 3.2.1).
When the required flow rate is reached,
4
secure the setting of the restriction (1.1) with the lock nut (1.2). Screw back on cap (1.3).
Lead-seal the set point setting at the set
4
point adjuster (17) and cap (1.3).
If the pressure drop in the plant is known, the adjustment diagrams for water in Figs. 7 to 10 (pages 14 to 17) can also be used.
Example: Adjusting the flow restriction
Determining the adjustment values using the adjustment diagram in Fig. 7.
A Type 42-34 Regulator, DN 25, set point range 0.25 to 3.5 m³/h, is to be used in a plant to limit the flow rate to 3.0 m³/h.
The pressure dropacross the plant is0.4 bar. To which value do you have to adjust the dif
ferential pressure set point and how many turns of the set point screw at the restriction will be required?
Solution:
-
Follow the sequence from A to E in the dia
­gram in Fig. 7.
The pressure dropΔp across the plant serves as a basis. This value must be known!
­AssumingΔp = 0.4 bar, this value corre
sponds to point A in the diagram. Add the upper differential pressure across the restric tionΔp
A horizontal line corresponding to this value is drawn from A to the right-hand side, result ing in point B. Point B is located on the straight line associated with the differential pressureΔp to be adjusted =0.6 bar (see sec­tion 3.2.1).
From point B, the line is further drawn verti­cally downward to the desired limiting curve for the flow rate (3.0 m³/h), resulting in point C. Then, plot the line from point C straight to the curve associated with the nominal size and you will reach point D.
The vertical line above point D which meets point E shows the required number of turns of the set point screw.
Result: approx. 1.9 times Based on a closed restriction, the set point
-
screw must be turned counterclockwise approx. 1.9 times.
, assumed to be 0.2 bar.
restriction
-
-
-
-
EB 3013 EN 11
Operation
3.2.3 Pressure conditions in the plant and regulator
When selecting the differential pressure set point or set point range, it is important to observe that the differential pressure set pointΔp across the completely open plantΔp tion)Δp
restriction
.
plant
Table 2 list the flow rates with the known upper differential pressure value at the restriction for Type 2423 Valves balanced by a bellows and balanced by a diaphragm.
set point
=Δp
p
Δ
The minimum required differential pressureΔp is calculated as follows:
=Δp
p
Δ
min
Fig. 6 shows a schematic diagram of the plant’s pressure conditions.
Δp
is calculated from the known pressure drop
set point
and the pressure drop directly at the orifice (restric
+Δp
set point
Δp
Δp
set point
plant
plant
min
min
restriction
between the flow pipe and return flow pipe
2
&
V
+
K
VS
Δp
restriction
-
p
1
p
Δ
p
Δ
p
Δ
Fig. 6 · Pressure conditions in the plant
Minimum differential pressure between
min
flow and return flow pipes in bar Pressure drop at restriction in bar
restriction
Differential pressure set point adjusted
set point
at the regulator in bar
12 EB 3013 EN
p
2
Type 42-34
or
Type 42-38
p
Δ
&
V K
VS
Differential pressure (pressure drop) across
plant
a completely open plant in bar Flow rate adjusted in m³/h Valve flow coefficient in m³/h
Operation
Table 2 · Flow rate set points for water in m³
/h
Type 2423 Valve balanced by a bellows
p
p
p
Δ
Δ
set p.
plant
0.2
0.1
bar
bar
0.5
0.3
bar
bar
1.0
0.5
bar
bar
Max. perm. diff. pressureΔp
DN ... 15 20 25 32 40 50 65 80 100 125 150 200 250
Δ
restr.
.
0.05 0.15 0.25 0.4 0.6 0.9 2 3.5 6.5 11 18 20 26
min
0.1
V
bar
0.2 bar
0.5 bar
V
V
1.4 2.1 2.4 4.9 7.7 11.2 19 28 44 56 84 126 154
max
.
2 3 3.5 7 11 16 28 40 63 80 120 180 220
max
.
3 4.5 5.3 9.5 16 24 40 58 90 120 180 260 300
max
25 bar 20 bar 16 bar 12bar 10 bar
Type 2423 Valve balanced by a diaphragm
Nominal size DN 125 150 200 250
Flow rate set points in m³/h with
Δ
Max. perm. diff. pressureΔp
p
restriction
= 0.2 bar
11 to 120 18 to 180 20 to 320 26 to 350
12 bar 10 bar
3.3 Decommissioning
Preferably close the shut-off valves starting from the flow pipe side and then return flow pipe side.
EB 3013 EN 13
Operation
p (bar)
Δ
Pressure drop across the plant
Differential pressure set point (fixed for Type 42-38, adjustable Type 42-34)
1.6
1.4
Turns of the set point adjuster
3
2
E
DN 15
DN 20
DN 25
DC
1.2
1.0
1.2
0.8
1.0
0.6
0.4
A
0.2
1
0.1
0.2
0.8
B
0.6
0.4
1.6
1.4
1.8
0.6
1.2
1.8
2.4
3.0
3.6
4.2
4.8
5.4
˚
V
max
3
m
/h
Adjustment diagram based on water!
Fig. 7 · Adjustment diagram DN 15 to 25
14 EB 3013 EN
0.2 0.4
0.5
Upper diff. pressureΔp
p (bar)
Δ
Pressure drop across the plant
Differential pressure set point (fixed for Type 42-38, adjustable Type 42-34)
1.6
1.4
Operation
Turns of the set point adjuster
6
4
DN 40
DN 50
DN 32
1.2
1.0
1.2
0.8
1.0
0.6
0.4
0.2
0.2
2
0.1
0.8
0.6
0.4
1.6
1.4
1.8
˚
V
3
m
3.0
6.0
9.0
12.0
15.0
18.0
21.0
24.0
27.0
max
/h
Adjustment diagram based on water!
Fig. 8 · Adjustment diagram DN 32 to 50
0.2 0.4
0.5
Upper diff. pressureΔp
EB 3013 EN 15
Operation
p (bar)
Δ
Pressure drop across the plant
Turns of the set point adjuster
8765 32110 9
DN 65
DN 80
4
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
0.1
0.2
Differential pressure set point (fixed for Type 42-38, adjustable Type 42-34)
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
˚
V
max
3
m
/h
8
16 24
32
40 48 56 64
72 80 90
Adjustment diagram based on water!
DN 100
Fig. 9 · Adjustment diagram DN 65, DN 80 and DN 100
16 EB 3013 EN
0.2 0.4
0.5
Upper diff. pressureΔp
p (bar)
Δ
Pressure drop across the plant
Operation
Differential pressure set point (fixed for Type 42-38, adjustable Type 42-34)
1.6
1.4
Turns of the set point adjuster
12
8
DN 125
DN 150
1.2
1.0
1.2
0.8
1.0
0.6
0.4
0.2
0.2
4
0.1
0.8
0.6
0.4
1.6
1.4
1.8
˚
V
m
20
40 60
80
100 120 140 160
180 200
max
3
/h
Adjustment diagram based on water!
Fig. 10 · Adjustment diagram DN 125 and DN 150
0.2 0.4
0.5
Upper diff. pressureΔp
EB 3013 EN 17
Maintenance · Troubleshooting
4 Maintenance ·
Troubleshooting
The regulators are maintenance free. Never theless, they are subject to natural wear, par ticularly at the seat, plug and operating dia phragm.
Depending on the operating conditions, the regulator needs to be checked at regular in tervals to avoid possible malfunctions.
CAUTION!
On performing any work on the regulator, make sure the relevant section of the pipeline
-
is depressurized and, depending on the pro
-
cess medium, drained as well.
-
For high temperatures, allow the regulator to cool down to ambient temperature before starting any work on it.
-
Interrupt or shut off the control line to avoid any hazards which could be caused by mov ing parts. As valves are not free of cavities, remember that residual process medium might still be contained in the valve. We recommend to remove the valve from the pipeline after it has been depressurized and drained. Make sure that all the plant sections connected to the control line are also depressurized. If this is not the case, shut off the control line.
Details on malfunctions and the recom­mended action can be found in the Ta- ble 3 · Troubleshooting.
Proceed as described in section 4.1 if the op erating diaphragm is defective.
-
-
-
18 EB 3013 EN
Maintenance · Troubleshooting
Table 3 · Troubleshooting
Malfunction Possible reasons Recommended action
Remove valve from pipeline. Clean seat and plug.
Flow rate or differential pressure exceeds the flow
.
or
rate
V differential pressure set point.
Flow rate or differential pressure does not reach the flow rate
.
or
V differential pressure set point.
Control loop hunts
Seat and plug leak
Operating diaphragm defective
Control line blocked
Valve too large to regulate the flow rate or too small to regulate the differential pressure
Wrong set point range selected
Safety equipment, e.g. pressure limiter, has been triggered
Insufficient pressure drop across the plantΔp
Strainer blocked Drain and clean filter of the strainer. Direction of flow, valve incorrect-
ly installed
Valve too large for control task
Restriction (or needle valve) is missing in a control line to dam pen pulsation
Replace plug, if necessary. Otherwise send the regulator to SAMSON for repair.
Replace diaphragm (see section 4.1) or send the regulator to SAMSON for repair.
Remove control line and clean it. Check and clean the screw joint with orifice plate.
Recalculate K for further action.
coefficient and contact SAMSON
VS
Check set point range and contact SAMSON for further action.
Check plant and unlock safety equipment.
Compare existing differential pressure across the plant with the plant’s drag: Min. differential pressure across the plant
p
=Δp
Δ
min
restriction
+ (
.
VK
/
2
+Δp
)
VS
Install the valve so that the direction of flow is the same as indicated by the arrow.
Recalculate K for further action.
coefficient and contact SAMSON
VS
Install a needle valve in the control line and start
-
to close it until the control loop becomes stable. NOTICE Do not completely close needle valve.
Contact SAMSON if the malfunction cannot be remedied using the above table.
plant.
4.1 Replacing the operating diaphragm
See Figs. 1 and 2.
If just the operating diaphragm is defective, it can bereplaced without having to remove the valve from the pipeline. Relieve the relevant
section of the pipeline of pressure and drain it. Unscrew the control lines and separate the actuator from the valve.
EB 3013 EN 19
Maintenance · Troubleshooting
Type 2428 Actuator
1. Place actuator upside down.
2. Undo screws (15) at the actuator. Pull out the top cover (+ chamber) together with diaphragm plate (19) and diaphragm (13) as wellas the diaphragm stem(12).
3. Unscrew nut (18), while holding the dia phragm stem stationary using a suitable tool.
4. Lift off diaphragm plate (19) and pull out diaphragm (13).
5. Check the diaphragm stem (12) for scor ing and replace it with a new one, if nec essary.
NOTICE
The stem surface is roller-burnished. Never regrind the stem!
6. Insert a new diaphragm.
7. Proceed in the reverse order to reassem­ble the actuator. Secure nut (18) from turning with suitable adhesive (e.g. 8121-0230 from SAMSON). Use lubri cant from SAMSON (8150-0111).
8. Check screw fittings for dirt and clean them, if necessary.
Start up as described in section 3.1.
Type 2424 Actuator
1. Place actuator upside down.
2. Relieve set point springs (16) completely of tension byturning the setpoint adjuster (17) counterclockwise.
3. Take off set point springs (16) and set point adjuster (17).
4. Undo screws (15) at the actuator. Re move topcover (+ chamber)and take out inner springs in the + chamber.
5. Lift out diaphragm plate (19) together
-
-
-
with diaphragm (13), diaphragm stem (12) and excess pressure limiter unit . Re move forcelimiter (20) together with stem (12).
6. Check stem (12) for scoring and replace it with a new one, if necessary.
NOTICE
The stem surface is roller-burnished. Never regrind the stem! When exchanging the dia­phragm stem, the nipple (guide bushing) in the actuator cover must also be replaced.
7. Unscrew nuts (18) and pull out dia­phragm stem.
8. Remove diaphragm (13) and insert a new diaphragm.
9. Insert diaphragm stem. Tighten nuts (18)
­to fix diaphragm, diaphragm plate and
washer into place. Secure nut (18) from turning with suitable adhesive (e.g. 8121-0230 from SAMSON).
10. Proceed in the reverse order to reassem ble the actuator. Use lubricant (8150-0111).
11.Check screw fittings for dirt and clean them, if necessary.
Start up as described in section 3.1.
-
-
-
20 EB 3013 EN
5 Nameplates
Nameplates
Valve nameplates
DIN version
ANSI version
Actuator nameplate
Valve
1 Valve type 2 Model number 3 Model number index 4 Order number or order date
coefficient
5K
VS
8 Nominal size 9 Nominal pressure 10 Perm. differential pressure in bar 11 Perm. temperature in °C 12 Body material
ANSI version 5 Nominal size 8 Perm. differential pressure in psi 9 Perm. temperature in °F 10 Body material
V coefficient (K
11 C 12 ANSI Class (pressure rating)
Actuator
1 Model number 2 Model number index 3 Order number or order date 4 Effective diaphragm area 5 Labeling acc. to DIN 6 Labeling acc. to ANSI 7 Max. perm. pressure 8 Nominal size 9 Differential pressure at restriction 10 Set point range 11 Diaphragm material 12 Year of production
VS
x 1.17)
Fig. 11 · Nameplates
EB 3013 EN 21
Dimensions and weights
6 Dimensions and weights
Valve balanced by a bellows
Type 42-38 Valve balanced by a bellows
– see Table 5 on p. 23 –
Fig. 12 · Dimensions, valve balanced by a bellows
Valve balanced by a diaphragm
Type 42-34 · Valve balanced by a bellows
– see Table 5 on p. 23 –
Table 4 · Dimensions in mm and weights
Type 42-34 · Valve balanced by a diaphragm
Nom. size DN 125 150 200 250
Length L
Height H1
Height H2
Weight in kg
1)
With 640 cm² actuator
Fig. 13 · Dimensions, valve balanced by a diaphragm
400 480 600 730
720 745 960
295 325 345 375
95 115
1)
2901)305
22 EB 3013 EN
1)
Type 42-34 · Balanced by a diaphragm
Dimensions and weights
Table 5 · Dimensions in mm and weights · Type 24-34, Type 24-38 · Balanced by a bellows
Nominal size DN 15 20 25 32 40 50 65 80 100 125 150 200 250
Length L
Height H1
Height H2
Other materials
Forged steel
Type 42-34 Differential Pressure Regulator with Flow Limitation · Balanced by a bellows
Set point range
0.1 to
0.6 bar
Height H
Actuator
Weight
1)
Height H
Set point range
0.2 to 1 bar
Set point range
0.5 to
1.5 bar
Actuator
Weight
Height H
Actuator
Weight
1)
1)
Type 42-38 Differential Pressure Regulator with Flow Limitation · Balanced by a bellows
Height H
Set point range
0.2 0.3
0.4 · 0.5 bar
Actuator
Weight
1)
in kg
1)
The weight is based on the version made of EN-JL1040/PN 16 (GG-25). +10 % for other materials
2)
Optionally with 320 cm² actuator
130 150 160 180 200 230 290 310 350 400 480 600 730
285 360 415 460 590 730
115 135 195 220 265 295 400
113 130 155 161 −−−−−−−
670 745 800 990 1120 1260
Ø D = 285 mm
Ø D = 225 mm A = 160 cm²
16 16.5 17.5 24 24.5 27 46 51 65 135 185 425 485
in kg
2)
A = 320 cm²
Ø D = 390 mm
A = 640 cm²
670 745 800 990 1120 1260
Ø D = 225 mm A = 160 cm²
16 16.5 17.5 24 24.5 27 42 47 61 135 185 425 485
in kg
2)
Ø D = 390 mm
A = 640 cm²
670 745 800 880 1040 1210
Ø D = 225 mm A = 160 cm²
16 16.5 17.5 24 24.5 27 42 47 61 125 175 415 475
in kg
2)
Ø D = 285 mm
A = 320 cm²
450 525 585
Ø D = 225 mm A = 160 cm²
Ø D = 285 mm
A = 320 cm²
11.5 12 13 19.5 20 22.5 38 43 57
EB 3013 EN 23
Customer service
7 Customer service
Should any malfunctions or any defect occur, SAMSON's After-Sales Service is prepared to help you on site.
You can also send the defective regulator directly to your local SAMSON representative for re pair. Addresses of SAMSON subsidiaries, agencies and service centers are listed in the prod uct catalogs and in the Internet at www.samson.de.
To allow SAMSON to find the fault and to have an idea of the installation situation, specify the following details (refer to the nameplate):
Type and nominal size of the valve
4
Order number and model number
4
Upstream and downstream pressure
4
Flow rate in m³/h
4
Has a strainer been installed?
4
Sketch of the installation
4
8 Technical data
-
-
Table 6 · Type 42-34, Type 42-38
Valve balanced by a bellows
Type 42-34 42-38
Nominal size Nominal pressure
Valve body
Max. perm. temperature
Pressure at which the internal excess pressure limiter responds, depending on diaphragm area A
Set point ranges
Leakage rate
1)
Higher temperatures on request
Actuator
1)
DN 15 to 250 DN 15 to 100
PN 16, 25 or 40 (acc. to DIN EN 12516-1)
See pressure-temperature diagram in T 3013 EN
With equalizing tank: Liquids up to 220 °C
Without equalizing tank: Liquids up to 150 °C
Air and gases up to 80 °C
160 cm² = 1.2 bar 320 cm² = 0.6 bar 640 cm² = 0.3 bar
0.1 to 0.6 bar 0.2 to 1 bar
0.5 to 1.5 bar
0.05 % of K
160 cm² = 0.6 bar 320 cm² = 0.3 bar
0.2 0.3 0.4 0.5 bar
coefficient
VS
24 EB 3013 EN
Technical data
Valve balanced by a diaphragm
Type 42-34 Nominal size
Nominal pressure
Valve body
Max. perm. temperature
Actuator
1)
Pressure at which the internal excess pressure limiter responds, depending on diaphragm area A
Set point ranges
Leakage rate
1)
Higher temperatures on request
PN 16, 25 or 40 (acc. to DIN EN 12516-1)
See pressure-temperature diagram in T 3013 EN
With equalizing tank: Liquids up to 220 °C
Without equalizing tank: Liquids up to 150 °C
0.1 to 0.6 bar 0.2 to 1 bar · 0.5 to 1.5 bar
DN 125 to 250
Air and gases up to 80 °C
160 cm² = 1.2 bar 320 cm² = 0.6 bar 640 cm² = 0.3 bar
0.05 % of K
coefficient
VS
Table 7 · Data for Type 2423 Valve
Valve balanced by a bellows · KVScoefficients, z values and max. perm. differential pressures
Nominal size DN 15 20 25 32 40 50 65 80 100 125 150 200 250
Travel K
coefficient m³/h
VS
z value Max. perm. diff.
pressureΔp
4 6.3 8 16 20 32 50 80 125 190 280 420 500
0.65 0.6 0.55 0.45 0.4 0.35 0.3
10 mm 16 mm 22 mm
25 bar 20 bar 16 bar 12bar 10 bar
Valve balanced by a diaphragm · KVScoefficients and max. perm. differential pressures
Nominal size DN 125 150 200 250
K
VS
m³/h
coefficient
22 mm travel 35 mm travel
Max. perm. diff. pressureΔp
190 290 550 600 250 380 650 800
12 bar 10 bar
See Table 2 on page 13 for the flow rate set points for both valve versions.
EB 3013 EN 25
SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 Internet: http://www.samson.de
EB 3013 EN
S/Z 2009-09
Loading...