3 Operation
Proceed as follows:
Unscrew the ller plug on the chamber
and undo the vent screw on the dia­phragm actuator.
For applications with steam: use the sup- plied plastic funnel or a watering can to ll the chamber with water until it over­ows at the vent hole on the actuator.
For applications with other liquids, ll the compensation chamber with the process me­dium.
Screw the ller plug back on the cham- ber and tighten.
1 Application
A compensation chamber is installed in the control line together with the listed regulators and actuators. The liquid lled in the cham­ber (water for steam control) acts as a buffer for process medium temperatures above 150°C and for steam. It prevents any hot process medium coming into direct contact with the actuator diaphragm and damaging it.
2 Installation
Install the compensation chamber at the highest point of the control line. Make sure that the control line between the diaphragm chamber and compensation chamber as well as between the pipeline and the compensa­tion chamber inclines downwards at a ratio of at least 1:10.
Connect the control line at the side of the pipeline transporting the process medium or the manifold.
The mounting position of the chamber is in­dicated on the chamber by an adhesive la­bel with an arrow as well as by the word oben (top) impressed on the chamber. It is imperative that the mounting position of the chamber is observed to guarantee the safe functioning of the regulator.
Weld the control line coming from the pres­sure tapping point to the R
3
/
8
socket of the
chamber.