Technical Specifications 
CU1
FAILSAFE TIMER UNIT
TERMINAL CONNECTIONS
120
35mm DIN rail 
mounting
45
73
To gain access 
to switches & fuse 
flip off lid with 
a small screwdriver.
Access to replaceable fuse
Isolate power 
before opening.
Power supply: 
Relay outputs:
Maximum switched 
current/voltage/load:
Internal fuse:
Mounting:
Enclosure protection:
Terminal Isolation:
Ambient temperature:
Internal switches:
LED indication:
Conformity:
110/230V AC (Switch selectable) 
24V AC/DC. 
2 N/O + 1 N/C. (TUV approved)
4A / 250V AC / 1000VA 
2A / 30V DC / 60W 
500mAT (Replaceable). 
35mm DIN-rail. 
IP 40 DIN 0470. 
IP 20 DIN 0470.
-10°C to +55°C. 
110/230V AC selector 
A, B, C, D Timing range selector. 
Red = Power 0n, 
Red/Green LED: Red = Timing, Green = Output. 
Remote indication connection terminals provided. 
EN 60204, EN 292 pts 1& 2.
SUPPLY
110/230
V AC
SELECTABLE
13
23
3114
24
32A1 X1
X2
A2
R2 R1 R3
SUPPLY
24V AC/DC
TEST REMOTE INDICATIONS SAFETY
1
SAFETY
2
AUXILIARY
1  2
1  2
1  2
1  2
< 1 second to 10 seconds.
A
 1 second to 39 seconds.  6 second to 5 mins 10 seconds.  48 second to 41 mins 
BCD
TIMER RANGE INTERNAL SWITCH SETTING
 Fully CCW 
Maximum
 Fully CW 
Minimum
RED GREEN
+
_
The CU1 Failsafe Timer is designed to integrate in the safety control system 
of automated machinery. Upon energisation the unit powers up (Red LED) 
and the timer commences operation. Upon the selected time delay being 
completed the Signal LED turns Green indicating that the safety outputs are 
made and the auxiliary output is now "OFF". 
The outputs and timer circuit are failsafe and cross monitored making the 
CU1 ideal for the safe control of safety critical parts - typically guard 
interlocking switches with guard locking. In this way the machine is given 
time to stop before access is possible. 
Time delay selection is a simple matter for a qualified person to set the DIP 
switches and fine tune accordingly. In addition a replaceable plug in 500mAT 
fuse is accessible behind the removable panel (isolate the power before 
opening) preventing short circuits or overloads from damaging the unit.
CU1 TIMER UNIT
500mA
1 Select general range
Check time delay is set correctly
3 
2 Fine tune
A2  -- X2  R2 R3 14 24 32
POWER
OUTPUT
A1  + X1  R1 O 13  23 31
MADE IN THE EC
240/
110
24V
AC/DC
240/ 
110
24V
AC/DC
Sicherheitstechnik
CU 1
Failsafe Timer
EN60204 
BS EN 292
A Remote Indicator Box is also available which gives 
visual status indication at the point of access.
R1R2R3
To CU1
REMOTE 
INDICATOR BOX 
38
36
69
Max (3 core) 
cable size 6mm dia.
Sicherheitstechnik
CU1
REMOTE INDICATION
RED 
ROT 
ROUGE
GREEN
GRUN
VERT