Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local
Rockwell Automation sales office or online at
literature) describes some important differences between solid state equipment and
hard-wired electromechanical devices. Because of this difference, and also because of
the wide variety of uses for solid state equipment, all persons responsible for applying
this equipment must satisfy themselves that each intended application of this
equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written
permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety
considerations.
http://www.rockwellautomation.com/
WARNING: Identifies information about practices or
circumstances that can cause an explosion in a hazardous
!
environment, which may lead to personal injury or death, property
damage, or economic loss.
Important: Identifies information that is critical for successful application and
understanding of the product.
ATTENTION: Identifies information about practices or
circumstances that can lead to personal injury or death, property
!
damage, or economic loss. Attentions help you identify a hazard,
avoid a hazard, and recognize the consequences.
Shock Hazard labels may be located on or inside the equipment
(e.g., drive or motor) to alert people that dangerous voltage may be
present.
Burn Hazard labels may be located on or inside the equipment
(e.g., drive or motor) to alert people that surfaces may be at
dangerous temperatures.
Allen-Bradley, PowerFlex, DriveExplorer, DriveExecutive, and DPI are either registered trademarks or trademarks of Rockwell Automation, Inc.
PowerFlex 700L Active Converter Power Module User Manual
Summary of Changes
The information below summarizes the changes resulting from the firmware
v3.001 upgrade to this manual since its last release (June, 2006):
Description of New or Updated InformationPage(s)
To all pages, added a new footer containing:
• Publication description (1st line).
• Publication number hyperlink underlined in blue (2nd line) linking to the date of the
publication on the back cover.
The back cover publication date line hyperlinks to the newest version of the publication
on Rockwell Automation’s Literature Library web site.
Added new information about the Active Converter operating as a Coupled unit (DPI
SLAVE) or as a Stand Alone unit (DPI MASTER).
Changed the following for Parameter 051 - [Option Select]:
• Bit 6 changed from “Reserved” to “VC Inverter.”
• Bit 7 changed from “Reserved” to “Prechg Cntrl.”
• The default changed from “xxxx xxxx xx00 0001” to “xxxx xxxx 0000 0001.”
Added new Parameter 105 - [Regen I Lmt].3-9
Changed Parameter 153 - [CML Bandwidth] maximum value from “3000 Rad/sec” to
“4000 Rad/sec.”
Changed the description for Parameter 157 - [PF Bandwidth] to include that it should be
used only when unbalanced voltage compensation is enabled in Parameter 051 [Option Select].
Changed Parameter 162 - [Capacitance] maximum value from “32767 µF” to “65535 µF.” 3-12
Added new Parameter 170 - [Bus Capacitance].3-12
Added new Bit 11 (High DC Link) to Parameter 214 - [Start Inhibit].3-14
Changed Parameter 238 - [Fault Config] default from “xxxx xxx1 1110 1100” to
“xxxx xxx1 0110 1100.”
Added two new parameter groups which are only displayed and available in the
Communication File when the Converter is operated as a Stand Alone unit:
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Preface
Overview
The purpose of this manual is to provide you with the basic information
needed to wire and operate the PowerFlex 700 Active Converter Power
Module.
For information on ...See page ...
Who Should Use this Manual?
What Is Not in this ManualP-1
Reference MaterialsP-2
Manual ConventionsP-2
General PrecautionsP-3
P-1
Who Should Use this
Manual?
What Is Not in this Manual
This manual is intended for qualified personnel. You must be able to wire
and operate Adjustable Frequency AC Drive devices. In addition, you must
have an understanding of the parameter settings and functions.
This manual is designed to provide only basic active converter I/O wiring,
start-up, programming, and other related information.
LPM20 Liquid-Cooled AC Drive Installation
For information on installing LPM20 Liquid-Cooled AC drives, please refer
to LPM20 Liquid-Cooled Adjustable Frequency AC Drive Installation Manual — (Publication No. 20N-IN001…).
PowerFlex 700L Liquid-Cooled AC Drive Information
For information on installing PowerFlex 700L Liquid-Cooled AC drives,
please refer to PowerFlex 700L Liquid-Cooled Adjustable Frequency AC Drive User Manual — (Publication No. 20L-UM001…).
PowerFlex 700 Vector Control Information (standard)
For PowerFlex Liquid-Cooled AC drives equipped with standard PowerFlex
700 Vector Control, please refer to the PowerFlex 700 Adjustable Frequency AC Drive User Manual — Series B (Publication No. 20B-UM002…) which
provides I/O wiring, start-up, programming, and vector control encoder
information.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
P-2Overview
PowerFlex 700S Phase II Control Information (optional)
For PowerFlex Liquid-Cooled AC drives equipped with optional PowerFlex
700S Phase II Control, please refer to the PowerFlex 700S High Performance AC Drive — Phase II Control User Manual (Publication No.
20D-UM006…) which provides I/O wiring, start-up, programming, and
other related information.
Reference Materials
Manual Conventions
Publications
Publications can be obtained online at
http://www.rockwellautomation.com/literature
The following manuals are recommended for general drive information:
TitlePublication
Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC DrivesDRIVES-IN001…
Preventive Maintenance of Industrial Control and Drive System EquipmentDRIVES-TD001…
Safety Guidelines for the Application, Installation, and Maintenance of Solid State
Control
A Global Reference Guide for Reading Schematic Diagrams0100-2.10
Guarding Against Electrostatic Damage8000-4.5.2
Allen-Bradley Drives Technical Support
Online: www.ab.com/support/abdrives
• In this manual we refer also to the PowerFlex 700 Active Converter
Power Module as Active Converter, converter or PowerFlex 700AC.
• To help differentiate parameter names and LCD display text from other
text, the following conventions will be used:
.
SGI-1.1
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
– Parameter Names will appear in [brackets].
For example: [DC Bus Voltage].
– Display Text will appear in “quotes.” For example: “Enabled.”
• The following words are used throughout the manual to describe an action:
WordMe aning
CanPossible, able to do something
CannotNot possible, not able to do something
MayPermitted, allowed
MustUnavoidable, you must do this
ShallRequired and necessary
ShouldRecommended
Should NotNot recommended
OverviewP-3
General Precautions
ATTENTION: This drive contains ESD (Electrostatic Discharge)
sensitive parts and assemblies. Static control precautions are
!
required when installing, testing, servicing or repairing this
assembly. Component damage may result if ESD control
procedures are not followed. If you are not familiar with static
control procedures, refer to Allen-Bradley publication 8000-4.5.2,
“Guarding Against Electrostatic Damage” or any other applicable
ESD protection handbook.
ATTENTION: An incorrectly applied or installed drive can
result in component damage or a reduction in product life. Wiring
!
or application errors, such as, undersizing the motor, incorrect or
inadequate AC supply, or excessive ambient temperatures may
result in malfunction of the system.
ATTENTION: Only qualified personnel familiar with adjustable
frequency AC drives and associated machinery should plan or
!
implement the installation, start-up, and subsequent maintenance
of the system. Failure to comply may result in personal injury and/
or equipment damage.
ATTENTION: To avoid an electric shock hazard, verify that the
voltage on the bus capacitors has discharged before performing
!
any work on the drive. After removing power to the drive, wait 5
minutes for the bus capacitors to discharge. Refer to the:
• LPM20 Liquid-Cooled Adjustable Frequency AC Drive
Installation Manual (Publication No. 20N-IN001…),
Figure 4.2, and measure the DC bus voltage at the locations
shown. The voltage must be zero.
• PowerFlex 700L Liquid-Cooled Adjustable Frequency AC
Drive User Manual (Publication No. 20L-UM001…), and
measure the DC bus voltage at the DC POSITIVE and DC
NEGATIVE test point sockets located on the front of the power
module. The voltage must be zero.
ATTENTION: Risk of injury or equipment damage exists. DPI
host products must not be directly connected together via 1202
!
cables. Unpredictable behavior can result if two or more devices
are connected in this manner.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
P-4Overview
Notes:
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Chapter 1
Installation/Wiring
This chapter provides information on installing and wiring the PowerFlex
700 Active Converter Power Module.
For information on…See page…
Removing the Active Converter Power Module Covers
Removing the Active Converter Control Cassette1-2
Wiring the Active Converter Control Cassette I/O Terminals1-4
Most start-up difficulties are the result of incorrect wiring. Every precaution
must be taken to assure that the wiring is done as instructed. All items must
be read and understood before the actual installation begins.
1-2
ATTENTION: The following information is merely a guide for
proper installation. Rockwell Automation, Inc. cannot assume
!
responsibility for the compliance or the noncompliance to any
code, national, local or otherwise for the proper installation of
this drive or associated equipment. A hazard of personal injury
and/or equipment damage exists if codes are ignored during
installation.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
1-2Installation/Wiring
Removing the Active
Converter Power Module
Covers
All converter covers, regardless of drive frame size, are similarly removed
by unfastening the screws. A Frame 3B converter is shown as an example.
PORT
MOD
NET A
NET B
(4 Screws)
PowerFlex 700L
Liquid-Cooled AC Drive
Frame 3B Converter shown
Removing the Active
Converter Control Cassette
Regenerative PowerFlex 700L Liquid-Cooled AC drives use an Active
Converter Power Module equipped with a converter control cassette.
Frame 2 and 3A Drives
PowerFlex 700L Liquid-Cooled Frame 2 and 3A drives combine the Active
Converter and Inverter into a single Power Module. Figure 1.1
location and removal of the Active Converter control cassette to access its
terminal blocks for control wiring. (The Inverter control cassette is located
just above the Active Converter control cassette.)
shows the
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Installation/Wiring1-3
Figure 1.1 Removing the Frame 2 and 3A Active Converter Control Cassette
Synchronization Cable
(For use with 700S Phase II Control only)
Internal DPI Cable
Synchronization Cable
(For use with 700 Vector Control only)
Frame 3B Drives
Pin 1
40-Pin
Ribbon Cable
SHLD
SHLD
Communications
Adapter Option
Detail
P1
P2
Figure 1.2 shows the location and removal of the Active Converter control
cassette to access its terminal blocks for control wiring. Frame 3B drives
have separate Converter Power Modules and Inverter Power Modules.
Figure 1.2 Removing the Frame 3B Active Converter Control Cassette
Synchronization Cable
(For use with coupled Inverter Power
Modules with 700S Phase II Control only)
Internal DPI Cable
Synchronization Cable
(For use with coupled Inverter Power
Modules with 700 Vector Control only)
40-Pin
Ribbon Cable
Pin 1
P2
P1
Detail
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
1-4Installation/Wiring
Wiring the Active Converter
Control Cassette I/O
Terminals
All wiring should be installed in conformance with the applicable local,
national, and international codes (e.g., NEC/CEC). Signal wiring, control
wiring, and power wiring must be routed in separate conduits to prevent
interference with drive operation. Use grommets, when hubs are not
provided, to guard against wire chafing.
ATTENTION: Do not route signal and control wiring with
!
Important points to remember about I/O wiring:
• Use Copper wire only. Wire gauge requirements and recommendations
are based on 75 degrees C. Do not reduce wire gauge when using higher
temperature wire.
• Wire with an insulation rating of 600V or greater is recommended.
• Control and signal wires should be separated from power wires by at
least 0.3 meters (1 foot).
Important:I/O terminals labeled “(–)” or “Common” are
power wiring in the same conduit. This can cause interference
with drive operation. Failure to observe this precaution could
result in damage to, or destruction of, the equipment.
not referenced to
earth ground and are designed to greatly reduce common mode
interference. Grounding these terminals can cause signal noise.
Terminal blocks P1 and P2, shown in Figure 1.1
connection points for all inputs, outputs, and power connections to the
Active Converter control cassette.
1. Remove the terminal block plug from the socket, and make connections.
2. Reinstall the terminal block plug when wiring is complete. The terminal
blocks have keys, which make it difficult to insert a terminal block plug
into the wrong socket.
and Figure 1.3, contain
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
J1 40-Pin
Ribbon Cable
Header
Installation/Wiring1-5
Figure 1.3 Active Converter Control Cassette I/O Terminal, Cable Connection, and
DPI SLAVE/MASTER Switch SW1 Locations
Active Converter
Control PCB Assembly
J2 30-Pin
Ribbon Cable
Header
J9 Synchronization
Cable Header
(700S Ph. II Control only)
J4 Internal DPI
Cable Header
P1 I/O Terminals
(see Table 1.B for
terminal descriptions)
P1-7 and P1-8
Synchronization
Cable Connection
(700 Vector Control only)
P1-13 and P1-14
Factory-Installed
Gate Kill Jumper
SW1
DPI SLAVE = OFF
ON
DPI MASTER = ON
ON
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
7
6
5
4
3
2
1
SW1
P2 I/O Terminals
(see Table 1.C for
terminal descriptions)
I/O Terminal Blocks
Table 1.A Active Converter Control Board I/O Terminal Block Specifications
NameDescription
I/O BlocksSignal and power
(1)
Voltage Feedback
Resistor PCB Assembly
Wire Size Range
MaximumMinimum MaximumRecommended
2
connections
Maximum/minimum that the terminal block will accept - these are not recommendations.
1.5 mm
(16 AWG)
(1)
2
0.14 mm
(28 AWG)
PowerFlex 700L Active Converter Power Module User Manual
0.25 N-m
(2.2 lb.-in.)
Publication PFLEX-UM002D-EN-P
Torque
0.22 N-m
(1.9 lb.-in.)
1-6Installation/Wiring
Table 1.B Active Converter Control PCB Assembly P1 Terminal Descriptions
PinDescription
1Comm Out +
2Comm Out 3SOC Out +
4SOC Out 5Comm In +
6Comm In 7SOC In +
8SOC In 9Aux Out N.O.
10Aux Out Common
11Analog In Signal
12Analog In Common
13Gate Enable
1424 Vdc
15Aux Input
Table 1.C Voltage Feedback Resistor PCB Assembly P2 Terminal Descriptions
PinDescription
7L3
4L2
1L1
Specific pins on P1 and P2 terminals require control wiring connections to
the Input Filter Bay. For wiring information, please refer to the PowerF lex
700L Liquid-Cooled Adjustable Frequency AC Drive User Manual
(Publication No. 20L-UM001…).
Using the Active Converter as a Coupled Unit vs. Standalone Unit
Frame 3B converter power structures may be ordered as a unit Coupled to
an inverter (DPI SLAVE), or as a Stand Alone unit (DPI MASTER). Frame
2 and Frame 3A power structures are always wired for the converter to be a
Coupled unit.
Coupled
Figure 1.4
(DPI SLAVE). In this configuration, the Converter is connected to a
PowerFlex 700L Inverter through DPI Port 6. When configured for "Run On
Start," the Converter is able to start and stop automatically as the Inverter is
started and stopped.
shows the Active Converter wired to operate as a Coupled unit
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Installation/Wiring1-7
Figure 1.4 Active Converter Operating as a Coupled Unit (DPI SLAVE)
Frame 3A with Converter as a
Coupled Unit (DPI SLAVE)
I
n
HIMHIM
v
e
r
t
e
r
C
o
n
v
e
r
t
e
r
1203-USB or 1203-SSS
Serial Converter
Personal
Computer
Stand Alone
Figure 1.5
unit (DPI MASTER). In this configuration, the Converter may have a HIM
or any PowerFlex 7-Class network communication adapter (20-COMM-x)
connected. This may be preferred when the converter is to supply the DC
bus for a set of common bus inverters. When configured for "Run On Start,"
the precharge bypass contactor may be configured to close when the power
is turned on and the DC Bus voltage is stable (see Parameter 51 - [Option
Select]). The Converter starts and stops with commands from the HIM, the
1203-USB or 1203-SSS serial converter, or a 20-COMM-x network
communication adapter.
Frame 3B with Converter as a
Coupled Unit (DPI SLAVE)
C
o
n
v
e
r
t
e
r
I
n
v
e
r
t
e
r
1203-USB or 1203-SSS
Serial Converter
Personal
Computer
shows the Active Converter wired to operate as a Stand Alone
Figure 1.5 Active Converter Operating as a Stand Alone Unit (DPI MASTER)
Frame 3B with Converter as a
Stand Alone Unit (DPI MASTER)
C
o
HIM
n
v
e
r
t
e
r
196755-C01
193136
20-COMM-x
181046-C01
I
n
HIM
v
e
r
t
e
r
1203-USB or 1203-SSS
Serial Converter
PowerFlex 700L Active Converter Power Module User Manual
Personal
Computer
Publication PFLEX-UM002D-EN-P
1-8Installation/Wiring
The Frame 3B Active Converter power module is ordered as a Stand Alone
unit (DPI SLAVE) by specifying equipment type P in the catalog number
(refer to the catalog number explanation in the PowerFlex 700L User Manual).
The Stand Alone (DPI SLAVE) Active Converter is supported with Active
Converter firmware revision 3.001 (or higher).
To operate the Frame 3B Active Converter as a Stand Alone unit (DPI
SLAVE) the DPI MASTER/SLAVE switch (SW1) on the Active Converter
control board must be properly set. Refer to Setting the DPI MASTER/
SLAVE Switch (SW1) below for details.
Setting the DPI MASTER/SLAVE Switch (SW1)
Active Converters with version 2.006 (or lower) firmware are always
operated as a peripheral on DPI port 6. In this case, switch SW1 on the
Active Converter control PCB assembly (Figure 1.3
SLAVE). Do not use the ON setting. For Active Converters with version
3.001 (or higher) firmware, switch SW1 is used to select between converter
operation as a Coupled unit (DPI SLAVE position) or as a Stand Alone unit
(DPI MASTER position).
) is set to OFF (DPI
Connecting an Active
Converter Power Module to
an Inverter Power Module
Frame 2 and 3A Drives
Coupling a Frame 2 or 3A Power Module is achieved by using two cables: a
DPI cable and a control synchronization cable. These cables are factory
installed.
Frame 3B Drives
Coupling a Frame 3B Active Converter Power Module to a Frame 3B
Inverter Power Module is achieved by using two cables: a DPI cable and a
control synchronization cable. For the Complete Drive equipment type,
these cables are factory installed. When Power Modules are purchased
separately, these cables are user installed. For information regarding these
cables and their installation, please refer to the PowerFlex 700L Liquid-Cooled Adjustable Frequency AC Drive User Manual (Publication
No. 20L-UM001…), Chapter 3 in the “Synchronization Connections for
Frame B” section.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Chapter 2
Start Up
The start-up procedure built into the HIM addresses only the start up of the
inverter. This chapter describes how to start up the PowerFlex 700 Active
Converter Power Module.
For information on…See page…
Establishing Communication as a Coupled Unit
Establishing Communication as a Stand Alone Unit 2-8
Converter Sequencing2-12
Control Setup2-14
Converter Faults2-17
2-1
Establishing
Communication as a
Coupled Unit
When the Converter is set to operate as a Coupled unit (DPI SLAVE), the
first step after turning on power is to verify that you are able to
communicate with the unit and that it properly displays selected data.
Data is exchanged between the Inverter Power Module and Active
Converter Power Module to pass control and status information.
An example is given for how to communicate with the Active Converter
Power Module using a CIP message from a ControlLogix controller.
Accessing Active Converter Power Module Parameters
The Active Converter operates as a DPI peripheral on port 6. This section
describes how to access parameters in the Active Converter.
Using the HIM
1. On power up, the HIM displays the main menu and communicates with
the Inverter.
F-> StoppedAuto
0.0RPM
Main Menu:
Diagnostics
Parameter
Device Select
2. As you scroll down to “Device Select,” the HIM shows the following
indication. With “Device Select” highlighted, press the Enter key.
F-> StoppedAuto
0.0RPM
Main Menu:
Parameter
Device Select
Memory Storage
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
2-2Start Up
3. The HIM displays that it is currently communicating with the Inverter on
DPI Port 0.
F-> StoppedAuto
0.0RPM
Device: Port 0
PowerFlex 700S 2
PowerFlex 700 AC
4. Press the Down arrow to scroll to “PowerFlex 700 AC.”
F-> StoppedAuto
0.0RPM
Device: Port 6
PowerFlex 700S 2
PowerFlex 700 AC
5. With “PowerFlex 700 AC” highlighted as shown in Step 4, press the
Enter key to start communicating with the Active Converter on DPI Port
6.
Port 6 Device
PowerFlex 700AC
Main Menu:
Diagnostics
Parameter
Device Select
– To examine the fault queue in the Active Converter, press the Up
Arrow to scroll to “Diagnostics” and press the Enter key.
– To begin examining parameters (with “Parameters” highlighted),
press the Enter key.
– To resume communication with the Inverter, press the Down Arrow to
scroll to “Device Select” and press the Enter key.
6. After accessing the Parameter menu, the display shows the File menu.
Press the Up or Down Arrow to select the desired file and press the Enter
key.
Port 6 Device
PowerFlex 700AC
FGP: File
Monitor
Command
Limit Config
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Start Up2-3
7. The display then shows the groups of parameters in the selected file.
Press the Up or Down Arrow to select the desired group and press the
Enter key.
Port 6 Device
PowerFlex 700AC
FGP: Group
Current
Vol ta ge
Power & Ti me
8. The display then shows the parameters in the selected group. Press the
Up or Down Arrow to select the desired parameter and press the Enter
key.
Port 6 Device
PowerFlex 700AC
FGP: Parameter
Rated Amps
Input Current R
Input Current S
9. The display then shows the value of the selected parameter and allows
for entry of a new value for parameters that are read/write.
Port 6 Device
PowerFlex 700AC
FGP: Par1
Rated Amps
705.0 Amps
[Alt] [View] - > Limits
Using DriveExplorer
When using DriveExplorer, the window shows the files and groups for the
Active Converter (left pane) and the parameters for the selected group (right
pane). Double-click a parameter in the right pane to edit it
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
2-4Start Up
Using DriveExecutive
When using DriveExecutive, the Active Converter parameters are displayed
in a linear list. Uploading reads parameter values from all DPI peripherals
but downloading parameters only write to the Inverter. To download
parameter values to the Active Converter, you must first select the
Converter.
Verifying Feedback Parameters
Using the HIM, DriveExplorer or DriveExecutive, verify that reasonable
values are displayed for the following parameters in the Active Converter
Power Module:
• Line to Line Voltage – Verify converter parameters 11 - [Input Voltage
RS], 12 - [Input Voltage ST], and 13 - [Input Voltage TR] display a
reasonable Line to Line RMS Voltage. Verify the voltage imbalance
displayed in parameter 16 - [V Imbalance] does not exceed 5.0%.
• DC Link Voltage – Verify converter parameter 14 - [DcLink Voltage]
displays a reasonable DC Link Voltage.
• AC Line Frequency – Verify converter parameter 40 - [Line Frequency]
Temp] displays a reasonable ambient temperature. Verify parameter 32 [IGBT Junction Temp] displays the temperature of the liquid being
pumped through the coldplate.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.