Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
available from your local Rockwell Automation sales office or online atwww.rockwellautomation.com/literature) describes some important differences
between solid state equipment and hard-wired electromechanical devices.
Because of this difference, and also because of the wide variety of uses for solid
state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is
acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect
or consequential damages resulting from the use or application of this
equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, Rockwell Automation, Inc. cannot assume responsibility
or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use
of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation, Inc. is prohibited.
http://
Throughout this manual, when necessary we use notes to make you aware of
safety considerations.
WARNING: Identifies information about practices or
circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property
damage, or economic loss.
Important: Identifies information that is critical for successful application and
understanding of the product.
ATTENTION: Identifies information about practices or
circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard,
avoid a hazard, and recognize the consequences.
Shock Hazard labels may be located on or inside the equipment
(e.g., drive or motor) to alert people that dangerous voltage may be
present.
Burn Hazard labels may be located on or inside the equipment
(e.g., drive or motor) to alert people that surfaces may be at
dangerous temperatures.
Allen-Bradley and PowerFlex are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
PowerFlex SCR Bus Supply User Manual
Summary of Changes
The information below summarizes the changes made to this manual since
its last release (March 2011):
Description of ChangesPage
In Chapter 1 in the “1000A SCR Bus Supply Flexibility” section:
• Added information and a table at the beginning to show which conversions are possible
and which are not possible.
• In the “Converting Master Unit to Slave Unit” subsection, added new steps 3 and 4.
• Deleted subsection “Converting Slave Unit to Master Unit” subsection.
In Appendix A in the “Accessories” section:
• Changed Table A.A cat. numbers for rows 256…509, and added new row for 939…1K0.
• Changed Table A.B cat. numbers for rows 256…509, and added new row for 939…1K0.
• Changed Table A.C cat. numbers for rows 256…509, and added new row for 939…1K0.
• Changed Table A.D cat. numbers for rows 256…509, and added new row for 939…1K0.
In Appendix A in the “HF Filter” section:
• Added new HF Filter Wiring Diagram Figure A.5.
• Added new subsection “Solid Ground Systems.”
• Added new subsection “Non-Solid Ground Systems.”
In Appendix A in the “Spare Parts” section:
• Added Important statement above Figure A.8.
• Added new “Availability” column to Table A.E
• Added Important statement above Figure A.9.
• Added new “Availability” column to Table A.F
• Added Important statement above Figure A.10.
• Added new “Availability” column and new footnote 1 to Table A.G
• Added new Figure A.11 to show locations of precharge and gate drive boards for 1000A
unit.
In Appendix A, revised Input Ratings “Operational AC Input Voltage Range” for catalog
number 20SF1K0… from “269…759V” to “528…759V.”
The purpose of this manual is to provide you with the basic information
needed to install, start up, and troubleshoot the PowerFlex SCR Bus Supply.
TopicPage
Who Should Use this Manual?
Reference DocumentationP-1
Rockwell Automation SupportP-2
Conventions Used in This ManualP-2
General PrecautionsP-3
Catalog Number ExplanationP-4
Descriptions and Schematic DiagramsP-5
P-1
Who Should Use this
Manual?
Reference Documentation
This manual is intended for personnel that are qualified to install, program,
and operate adjustable frequency drives and their use in common DC bus
systems.
General Drive Information
TitlePublication
Wiring and Grounding Guidelines for PWM AC DrivesDRIVES-IN001
AC Drives in Common Bus ConfigurationsDRIVES-AT002
Preventive Maintenance of Industrial Control and Drive System EquipmentDRIVES-TD001
Safety Guidelines for the Application, Installation and Maintenance of Solid State ControlSGI-1.1
A Global Reference Guide for Reading Schematic Diagrams0100-2.10
Guarding Against Electrostatic Damage8000-4.5.2
1321 Power Conditioning Products Technical Data1321-TD001
Specific Drive Information
For detailed drive information, including specifications, refer to the
following PowerFlex 70, PowerFlex 700, PowerFlex 700H, PowerFlex
700S, and PowerFlex 750-Series drive publications.
For:Refer to:Publication
PowerFlex
PowerFlex
PowerFlex
®
70/70EC DrivePowerFlex 70 User Manual
PowerFlex 70/700 Reference Manual
®
700/700VC Series A Drive
®
700VC Series B Drive
PowerFlex 70EC/700VC Reference Manual
PowerFlex 700 Series A User Manual
PowerFlex 700 Series B User Manual
PowerFlex 70/700 Reference Manual
PowerFlex 70EC/700VC Reference Manual
PowerFlex® 700S DrivePowerFlex 700S with Phase I Control Installation Manual (Frames 1…6)
PowerFlex
®
750-Series AC DrivePowerFlex 750-Series Drive Installation Instructions
PowerFlex 700S with Phase I Control Installation Manual (Frames 9 and 10)
PowerFlex 700S with Phase I Control User Manual (All Frame Sizes)
PowerFlex 700S with Phase I Control Reference Manual
PowerFlex 700S with Phase II Control Installation Manual (Frames 1…6)
PowerFlex 700S with Phase II Control Installation Manual (Frames 9…14)
PowerFlex 700S with Phase II Control Programming Manual (All Frame Sizes)
PowerFlex 700S with Phase II Control Reference Manual
• In this manual we may refer to the PowerFlex SCR Bus Supply as SCR
Bus Supply or Bus Supply.
• The firmware release is displayed as FRN X.xxx. The “FRN” signifies
Firmware Release Number. The “X” is the major release number. The
“xxx” is the minor update number.
• The following words may be used throughout the manual to describe an
action:
WordMeani ng
CanPossible, able to do something
CannotNot possible, not able to do something
MayPermitted, allowed
MustUnavoidable, you must do this
ShallRequired and necessary
ShouldRecommended
Should NotNot Recommended
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
OverviewP-3
!
!
!
!
!
!
!
General Precautions
ATTENTION: This Bus Supply contains ESD (Electrostatic
Discharge) sensitive parts and assemblies. Static control
precautions are required when installing, testing, servicing or
repairing this assembly. Component damage may result if ESD
control procedures are not followed. If you are not familiar with
static control procedures, refer to Allen-Bradley publication
8000-4.5.2, “Guarding Against Electrostatic Damage” or any other
applicable ESD protection handbook.
ATTENTION: An incorrectly applied or installed Bus Supply
can result in component damage or a reduction in product life.
Wiring or application errors, such as incorrect or inadequate AC
supply, or excessive ambient temperatures may result in
malfunction of the system.
ATTENTION: Only qualified personnel familiar with adjustable
frequency AC drives and associated machinery should plan or
implement the installation, start-up and subsequent maintenance of
the system. Failure to comply may result in personal injury and/or
equipment damage.
ATTENTION: Connect products with or without precharge
circuitry to the SCR Bus Supply common bus output terminals
within the minimum and maximum capacitance and load rating
guidelines.
ATTENTION: To avoid an electric shock hazard, verify that the
voltage on the DC bus terminals (which are connected to the DC
bus capacitors of the Inverter) has discharged before performing
any work on the Bus Supply. Measure the DC bus voltage at the
+DC and -DC output terminals. The voltage must be zero.
ATTENTION: A second source of power for the cooling blower
is present. To avoid an electric shock hazard or moving blades,
verify that the AC power supply has been removed prior to
performing any maintenance or repairs.
ATTENTION: National Codes and standards (NEC, VDE, BSI,
etc.) and local codes outline provisions for safely installing
electrical equipment. Installation must comply with specifications
regarding wire types, conductor sizes, branch circuit protection,
and disconnect devices. Failure to do so may result in personal
injury and/or equipment damage.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
P-4Overview
Catalog Number
Explanation
Position Number
1-345-78910
20SD400NEN
abcdef
a
Product
CodeType
20SPowerFlex SCR Bus Supply
b
Voltage Rating
CodeInput VoltagePhaseDC Output
D400/480V AC3540 - 650V DC
F600/690V AC3675 - 930V DC
Important:PowerFlex SCR Bus Supply 1000A units with Master or Slave
configuration are available for 400/480 and 600/690 Volts.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
OverviewP-5
>°C
V1V3
V4V2V6
F6-F8
G4
K4
G1
K1
K3
G3
K6
G6
G2
K2
G5
K5
F1
F2
F3
V5
4
5
6
7
5
4
6
PE
L1
L2
L3
GND
K1
A2
A1
1
X1
3
X3
X2
L1 L2 L3
1
1
8
7
5
4
2
5
4
3
2
6
M
N
GND
L1
X1
12
115
0
1
4
2
5
6
8
7
9
10
11
F12
K1
22
43213313
443414
F5
F4
➋
➌
➊
➑
➏
➍
➎
Precharge
Board
+DC
-DC
Descriptions and Schematic
Diagrams
The SCR Bus Supply is a single-direction power converter for the front end
of common DC bus drive systems. It converts the incoming 3-phase AC line
voltage to a common DC bus voltage.
Figure P.1 400A and 600A SCR Bus Supply Schematic Diagram
The primary electrical components for the 400A and 600A SCR Bus Supply
are:
Item Description
➊
➋
➌
➍
➎
➏
➑
Six-Pulse, Full-Wave, 3-Phase SCR Bridge Rectifier Unit connected to the line input and DC
Bus output terminals through semi-conductor protection fuses with trip indicator switches.
Bus Supply Overtemperature Sensor located on the heat sink for thermal protection of the
SCR bridge rectifier.
RC snubber circuit routed to the three input phases through semi-conductor protection
fuses with trip indicator switches.
MOV snubber circuit routed to the three input phases.
Precharge Board
Enable Contactor (K1) for the precharge board.
Cooling Blower connected to a customer-supplied 115V AC Power Supply. The customer’s
controls must, at a minimum, command the blower to run whenever contactor K1 is enabled.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
P-6Overview
PE
Figure P.2 1000A SCR Bus Supply Single Unit Schematic Diagram
➌
F7 - 11
L1L4L5L3L2
2
V1
F1
3
2
V3
5
4
3
2
V5
5
4
5
4
3
+ DC
12
11
10
9
8
7
6
5
4
2
1
0
115
X1
L1
L2
L3
GND
➍
>°C
F12
➏
GND
N
L1
➑
➋
F4
F3
F6
F5
F2
2
V4
45
22
443414
K1
43213313
➎
X1
1
3
X3
1
2
4
5
7
8
1
2
3
4
5
6
X2
L1 L2L3
A2
K1
A1
Precharge
Board
M
3
G4
C4
➊
2
V6
3
G6
2
V2
45
C6
45
3
G1
C1
G3
G2
C2
- DC
C3
G5
C5
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
The primary electrical components for the 1000A SCR Bus Supply Single
Unit are:
Item Description
Six-Pulse, Full-Wave, 3-Phase SCR Bridge Rectifier Unit connected to the line input and DC
➊
Bus output terminals through semi-conductor protection fuses with trip indicator switches.
Bus Supply Overtemperature Sensor located on the heat sink for thermal protection of the
➋
SCR bridge rectifier.
RC snubber circuit routed to the three input phases through semi-conductor protection
➌
fuses with trip indicator switches.
MOV snubber circuit routed to the three input phases.
➍
Precharge Board
➎
Enable Contactor (K1) for the precharge board.
➏
Cooling Blower connected to a customer-supplied 115V AC Power Supply. The customer’s
➑
controls must, at a minimum, command the blower to run whenever contactor K1 is enabled.
NOTE: There is no DC output fuse protection in the 1000A SCR unit.
Figure P.3 1000A SCR Bus Supply Master Unit Schematic Diagram
>°C
F12
K1
A2
A1
F6
F2
F1
F4
F5
F3
F7-11
L1L4L5L3L2
K1
22
43213313
443414
X1
GND
12
115
0
1
4
2
5
6
8
7
9
10
11
3
2
V3
45
3
2
V5
45
3
2
V1
45
3
2
V4
45
3
2
V6
45
3
2
V2
45
L1
L2
L3
PE
+
-
+
+
-
X3
X4
X6
2
1
X1
3
X3
X2
L1 L2 L3
1
1
8
7
5
4
2
X5
5
4
3
2
6
1
3
4
5
6
7
9
12
11
10
8
127854126543X2
7
8
9
10
11
12
1
2
3
4
5
6
1
5
M
N
GND
L1
Precharge
Board
Gate Driver Board
➋
➌
➊
➑
➐
➏
➍
➎
+DC
-DC
To Gate
Driver X4
on the Slave
(Figure P.4)
OverviewP-7
The primary electrical components for the 1000A SCR Bus Supply Master
Unit are:
Item Description
➊
➋
➌
➍
➎
➏
➐
➑
NOTE: There is no DC output fuse protection in the 1000A SCR unit.
Six-Pulse, Full-Wave, 3-Phase SCR Bridge Rectifier Unit connected to the line input and DC
Bus output terminals through semi-conductor protection fuses with trip indicator switches.
Bus Supply Overtemperature Sensor located on the heat sink for thermal protection of the
SCR bridge rectifier.
RC snubber circuit routed to the three input phases through semi-conductor protection
fuses with trip indicator switches.
MOV snubber circuit routed to the three input phases.
Precharge Board
Enable Contactor (K1) for the precharge board.
Gate Driver Board. The DC power supply is connected to a customer-supplied 115V AC Power
Supply.
Cooling Blower connected to a customer-supplied 115V AC Power Supply. The customer’s
controls must, at a minimum, command the blower to run whenever contactor K1 is enabled.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
P-8Overview
>°C
F12
F6
F2
F1
F4
F5
F3
F7-11
L1L4L5L3L2
X1
GND
12
0
1
4
115
2
5
6
8
7
9
10
11
3
2
V3
45
3
2
V5
45
3
2
V1
45
3
2
V4
45
3
2
V6
45
3
2
V2
45
L1
L2
L3
PE
+
-
+
+
-
X3
X4
X6
2
X6
1
1
8
7
5
4
2
X5
5
4
3
2
6
1
3
4
5
6
7
9
12
11
10
8
1
2
7854126543X2
7
8
9
10
11
12
1
2
3
4
5
6
1
5
M
N
GND
L1
+DC
-DC
Gate Driver Board
From Gate
Driver X6
on the Master
(Figure P.3 or
previous Slave)
➋
➌
➊
➑
➐
➒
➍
To Gate
Driver X4
on the next
Slave
Figure P.4 1000A SCR Bus Supply Slave Unit Schematic Diagram
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
The primary electrical components for the 1000A SCR Bus Supply Slave
Unit are:
Item Description
➊
➋
➌
➍
➐
➑
➒
NOTE: There is no DC output fuse protection in the 1000A SCR Unit.
Six-Pulse, Full-Wave, 3-Phase SCR Bridge Rectifier Unit connected to the line input and DC
Bus output terminals through semi-conductor protection fuses with trip indicator switches.
Bus Supply Overtemperature Sensor located on the heat sink for thermal protection of the
SCR bridge rectifier.
RC snubber circuit routed to the three input phases through semi-conductor protection
fuses with trip indicator switches.
MOV snubber circuit routed to the three input phases.
Gate Driver Board. The DC power supply is connected to the customer-supplied 115V AC
Power Supply.
Cooling Blower connected to a customer-supplied 115V AC Power Supply. The customer’s
controls must, at a minimum, command the blower to run whenever contactor K1 is enabled.
Connection Cable (1 m) connects the gate firing pulses from the Master to the first Slave or
between any two Slaves (maximum 4).
!
Chapter 1
Installation/Wiring
This chapter provides information on the installation and wiring of the
PowerFlex SCR Bus Supply.
TopicPage
Opening the Cover
Minimum Mounting Clearances1-3
AC Supply Source Considerations1-4
General Grounding Requirements1-5
Minimum Capacitance1-6
Maximum Loading1-6
Fusing1-7
Power Wiring1-7
Control Wiring1-11
Jumper Settings1-12
Disconnecting MOVs1-14
Parallel Connection of Slave Units1-15
1000A SCR Bus Supply Flexibility1-16
1000A SCR Bus Supply Redundancy1-17
SCR Bus Supply 12-Pulse Configuration1-18
CE Conformity1-19
1-2
Most start-up difficulties are the result of incorrect wiring. Every precaution
must be taken to assure that the wiring is done as instructed. All items must
be read and understood before the actual installation begins.
ATTENTION: The following information is merely a guide for
proper installation. Rockwell Automation, Inc. cannot assume
responsibility for the compliance or the noncompliance to any
code, national, local or otherwise for the proper installation of this
product or associated equipment. A hazard of personal injury and/
or equipment damage exists if codes are ignored during
installation.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
1-2Installation/Wiring
Opening the Cover
1. Remove the four fastening screws. (The steel sheet cover will stay in
place, even in the vertical position.)
2. Hold the cover with both hands at the bottom, and lift it upward about 2
cm (0.8 in.) and away from the enclosure (Figure 1.1
Figure 1.1Opening the Cover
).
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Installation/Wiring1-3
Refer to Appendix A for detailed dimension information.
below fan
Minimum Mounting
Clearances
The cabinet air inlet and outlet areas for each SCR Bus Supply must be a
minimum of 200 cm
4:1.
Figure 1.2Mounting Clearances
Air Outlet
PowerFlex
Bus Supply
120 mm
(4.7 in.)
SCR
2
(31 in.2). The length-to-width ratio must not exceed
Air Outlet
PowerFlex
SCR
Bus Supply
150 mm
(6 in.)
Air FlowAir FlowAir Flow
300 mm
(12 in.)
Air InletAir Inlet
120 mm
(4.7 in.)
Ambient Operating Temperatures
The PowerFlex SCR Bus Supply is designed to operate at 0…40 °C
(32…104 °F) ambient without derating. For operation in ambients above
40 °C up to 50 °C (104 °F up to 122 °F), the PowerFlex SCR Bus Supply
output Amps must be derated by 1.2% per 1 °C for 400A unit, and by 1.0%
per 1 °C for 600A and 1000A units.
Ensure that proper cooling is provided to the SCR Bus Supply to maintain
the 40 °C rated specification. If the ambient temperature is exceeded, apply
the proper derate factors. Add exhaust fans to the front or top of the
enclosure bay and provide a filtered opening at the bottom of the cabinet
bay.
The SCR Bus Supply watt losses (from specification section) are 1200W at
400A, 1600W at 600A, 2700W at 480V 1000A, and 2800W at 690V
1000A. The three-phase AC line reactor watt losses are listed in the 1321
Power Conditioning Products Technical Data (publication 1321-TD001).
Because of the internal design of the SCR Bus Supply, it is NOT
recommended to rely on an air dam surrounding the SCR Bus Supply.
It is recommended that the system integrator completes a thermal evaluation
to ensure adequate cooling to maintain proper operating conditions for each
cabinet or bay. A minimum air exchange of 725 CFM per SCR Bus Supply
is recommended.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
1-4Installation/Wiring
!
AC Supply Source
Considerations
The PowerFlex SCR Bus Supply is suitable for use on a circuit capable of
delivering a short circuit rating up to a maximum of 85,000 rms
symmetrical amperes.
If a Residual Current Detector (RCD) is used as a system ground fault
monitor, only Type B (adjustable) devices should be used to avoid nuisance
tripping.
Line Reactors
A minimum 3% rated three-phase AC line reactor must be installed for
minimum voltage drop unless the closest supply transformer is matched to
the kVA rating of the PowerFlex SCR Bus Supply. For recommended line
reactors, see Line Reactors
Install one three-phase AC line reactor for each
is recommended to maintain cable length symmetry between the
three-phase AC line reactors and the SCR Bus Supply connections. One
method is to mount the three-phase AC line reactors on the cabinet floor
under the SCR Bus Supply.
Important:It is recommended to keep all wired or bus bar connections
identical in size and length. This includes the AC line
connection to the three-phase AC line reactors and from the
three-phase AC line reactors to the SCR Bus Supply.
on page A-7.
SCR Bus Supply module. It
Unbalanced or Non-Solid Grounded Distribution Systems
Where the potential exists for abnormally high phase-to-ground voltages (in
excess of 125% of nominal), or the supply system is non-solid grounded,
refer to the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives (publication DRIVES-IN001).
ATTENTION: The PowerFlex SCR Bus Supply contains
protective MOVs that are referenced to ground. The MOVs should
be disconnected from ground if the SCR Bus Supply is installed on
any non-solid grounded power distribution system (IT-network).
For jumper location, see Figure 1.7 on page 1-11
.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Installation/Wiring1-5
Ground Grid, Girder or Ground
Rod (Building Ground Potential)
General Grounding
Requirements
The Safety Ground terminal(PE) must be connected to the building
grounding scheme. Ground impedance must conform to the requirements
of national and local industrial safety regulations and/or electrical codes.
The integrity of all ground connections should be periodically checked.
For installations within a cabinet, a single safety ground point or ground bus
bar connected directly to building steel should be used. All circuits
including the AC input ground conductor should be grounded
independently and directly to this point/bar.
Figure 1.3Typical Grounding
R (L1)
S (L2)
T (L3)
SCR
Bus Supply
PE
+DC
- DC
Safety Ground Terminal - PE
The Bus Supply safety ground (PE) must be connected to the customer
grounding scheme or earth ground. This is the safety ground for the Bus
Supply that is required by code. This point must be connected to adjacent
building steel (girder, joist), a floor ground rod, bus bar or building ground
grid. Grounding points must comply with national and local industrial
safety regulations and/or electrical codes.
RFI Filter Grounding
Using an external RFI filter may result in relatively high ground leakage
currents. Therefore, the filter must only be used in installations with
grounded AC supply systems and be permanently installed and solidly
grounded (bonded) to the building power distribution ground. Ensure that
the incoming supply neutral is solidly connected (bonded) to the same
building power distribution ground. Grounding must not rely on flexible
cables and should not include any form of plug or socket that would permit
inadvertent disconnection. Some local codes may require redundant ground
connections. The integrity of all connections should be periodically
checked. Refer to the instructions supplied with the filter.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
1-6Installation/Wiring
Minimum Capacitance
Maximum Loading
In order to commission and test the SCR Bus Supply, a minimum
capacitance is required. The design of the final installation must assure that
the minimum capacitance is connected whenever the bus supply is to be
enabled. If this minimum capacitance is not present, the bus supply internal
fault detection circuit will interpret the condition as a DC bus short and stop
pulse firing. The minimum capacitance (110 µF per SCR bus supply) may
be provided by an external capacitor bank (recommended) or a drive (as
long as the drive remains connected to the DC bus). NOTE: A capacitance
of 110 µF is typical of a 5 HP or 3.7 kW drive. To find DC bus capacitances
for specific PowerFlex drives, refer to Appendix A tables in the Powe rF lex AC Drives in Common Bus Configurations Application Guidelines
(publication DRIVES-AT002).
To avoid overloading the Bus Supply, the following requirement applies:
The DC Input current sum (Normal Duty rating at 40 °C/104 °F) of the
connected drive(s) must not exceed the Bus Supply continuous DC Bus
output current rating.
For the DC Input Current values of the drives, see tables in the respective
drive documentation.
Table 1.A
SCR Bus Supply. No overload capability is built into the tables.
Important:See“Output Ratings
When an overload is being utilized in connected drives or products, that
overload current must be accounted for in the calculation to properly size
the SCR Bus Supply.
Drive RatingDrive Output CurrentDrive DC Input CurrentSCR Bus Supply
DC
Volt ag e
540V3 x 110 kW
650V3 x 60 HP
(1)
Drive RatingDrive Output CurrentDrive DC Input CurrentSCR Bus Supply
DC
Volt ag e
540V3 x 90 kW3 x 170 = 510A 510A3 x 192.3 = 577A 577A600A400V
ND
Power
1 x 45 kW
1 x 30 HP
No overload capability.
Table 1.B Heavy Duty HD (150%, 1 minute; 200%, 3 seconds)
HD
Power
and Table 1.B provide guidance on the nominal operation of the
”in Appendix A for overload capability.
ND Output
Currents
3 x 205 = 615A
1 x 85 = 85A
3 x 77 = 231A
1 x 40 = 40A
HD Output
Currents
ND Output
Current Sum
700A3 x 226 = 678A
271A3 x 84.5 = 253.5A
HD Output
Current Sum
ND DC Input
Currents
1 x 95 = 95A
1 x 42.9 = 42.9A
HD DC Input
Currents
ND DC Input
Current Sum
773A1000A400V
297A400A 480V
HD DC Input
Current Sum
Maximum DC
Output Amps
Maximum DC
Output Amps
(1)
AC Input
Vol ta ge
(1)
AC Input
Vol ta ge
(1)
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
No overload capability.
Installation/Wiring1-7
!
!
Fusing
Power Wiring
The 400A and 600A PowerFlex SCR Bus Supplies have built-in AC line
and DC bus fuses. The 1000A unit has six in-path fuses which
simultaneously protect AC and DC paths. All units are equipped with fuse
trip indicator switches. For a list of recommended replacement fuses, refer
to these pages.
SCR Bus SupplySee Page…
400AA-15
600AA-17
1000AA-19
ATTENTION: National Codes and standards (NEC, VDE, BSI,
etc.) and local codes outline provisions for safely installing
electrical equipment. Installation must comply with specifications
regarding wire types, conductor sizes, and disconnect devices.
Failure to do so may result in personal injury and/or equipment
damage.
To maintain balanced impedance, and thus balance current in the SCR Bus
Supply, it is recommended to keep all wired or bus bar connections identical
in size and length. This includes the AC line connection to three-phase AC
line reactors and from the three-phase AC line reactors to the SCR Bus
Supply.
EMC Compliance
Refer to CE Conformity on page 1-19 for details.
Cable Trays and Conduit
If cable trays or large conduits are to be used, refer to guidelines in the
Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC
Drives (publication DRIVES-IN001).
ATTENTION: To avoid a possible shock hazard caused by
induced voltages, unused wires in the conduit must be grounded at
both ends. For the same reason, if a drive sharing a conduit is being
serviced or installed, all drives using this conduit should be
disabled. This will help minimize the possible shock hazard from
“cross coupled” motor leads.
DC Bus Wiring Guidelines
For DC Bus wiring guidelines, refer to AC Drives in Common Bus
Configurations (publication DRIVES-AT002).
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
1-8Installation/Wiring
Power Connection Bus Bars and Terminals
Figure 1.4400A Unit Bus Bar and Terminal Locations for Customer Wiring
➋
DC-
DC+
L1
➍
Table 1.C 400A Unit Power Connection Specifications
Item DescriptionCopper Bus Bars
AC Line Input
➊
L1, L2, L3
DC Bus
➋
DC+, DC-
Protective Earth PEM8 x 25 mm (0.98 in.) stud;
➌
Control Terminal BlockSee Tabl e 1. F
➍
(1)
Input/output power bus bar connections require the use of either lug type connectors to terminate field-installed
conductors or bus bars.
L2
L3
40 x 5 mm (1.57 x 0.2 in.) with
single 14 mm (0.55 in.) diameter
hole for customer terminal
40 x 5 mm (1.57 x 0.2 in.) with
single 14 mm (0.55 in.) diameter
hole for customer terminal
torque to 6 N•m (54 lb•in)
➊
➌
Recommended Minimum Size
(1)
Bus BarWire
40 x 5 mm120 mm
(or 2 x 50 mm
40 x 5 mm150 mm2
(or 2 x 70 mm
Size per NEC or local code
2
2
)
2
)
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Installation/Wiring1-9
DC+
DC-
➋
L1
L2
L3
➊
➍
➌
Figure 1.5600A Unit Bus Bar and Terminal Locations for Customer Wiring
Table 1.D 600A Unit Power Connection Specifications
Recommended Minimum Size
Item DescriptionCopper Bus Bars
AC Line Input
➊
L1, L2, L3
DC Bus
➋
DC+, DC-
Protective Earth PEM12 x 25 mm (0.98 in.) stud;
➌
Control Terminal BlockSee Table 1.F
➍
50 x 5 mm (1.97 x 0.2 in.) with
two 14 mm (0.55 in.) diameter
holes for customer terminal
50 x 5 mm (1.97 x 0.2 in.) with
two 14 mm (0.55 in.) diameter
holes for customer terminal
torque to 15 N•m (133 lb•in)
(1)
Bus BarWire
50 x 5 mm240 mm
(or 2 x 95 mm
60 x 5 mm300 mm2
(or 2 x 120 mm
Size per NEC or local code
2
2
)
2
)
(1)
Input/output power bus bar connections require the use of either lug type connectors to terminate field-installed
conductors or bus bars.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
1-10Installation/Wiring
DC+
DC-
L1
L2
L3
➋
➊
➍
➌
Figure 1.61000A Unit Bus Bar and Terminal Locations for Customer Wiring
Table 1.E 1000A Unit Power Connection Specifications
Recommended Minimum Size
Item DescriptionCopper Bus Bars
AC Line Input
➊
L1, L2, L3
DC Bus
➋
DC+, DC-
Protective Earth PEM12 x 25 mm (0.98 in.) stud;
➌
Control Terminal BlockSee Ta b l e 1 . F
➍
(1)
Input/output power bus bar connections require the use of either lug type connectors to terminate field-installed
conductors or bus bars.
50 x 10 mm (1.97 x 0.39 in.) with
two 14 mm (0.55 in.) diameter
holes for customer terminal
60 x 10 mm (2.36 x 0.39 in.) with
two 14 mm (0.55 in.) diameter
holes for customer terminal
torque to 15 N•m (133 lb•in)
(1)
Bus BarWire
50 x 10 mm
(or 80 x 5 mm)
60 x 10 mm
(or 100 x 5 mm)
Size per NEC or local code
2 x 240 mm2
2 x 300 mm2
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Installation/Wiring1-11
12
11
10
9
8
7
6
5
4
2
1
0
115
GND
12
11
10
9
8
7
6
5
4
2
1
0
115
GND
Control Wiring
Important points to remember about control wiring:
• Use Copper wire only. Wire gauge requirements and recommendations
are based on 75 °C (168 °F). Do not reduce wire gauge when using
higher temperature wire.
• Wire with an insulation rating of 600V or greater is recommended.
• Control wires outside the cabinetshould be separated from power wires
by at least 0.3 meters (1 foot).
Table 1.F Control Terminal Specifications
Wire Size Range
Item Name
Control Terminals2.5 mm2
➍
(1)
Maximum/minimum sizes that the terminals will accept - these are not
recommendations.
Figure 1.7Control Terminal Arrangement
(14 AWG)
(1)
0.25 mm2
(22 AWG)
TorqueMaximumMinimum
0.8 N•m
(7 lb•in)
TerminalBus SupplyDescriptionNotes
115 and 0All units115V AC
Supply Input
1 and 2
4 and 5
6 and 7400A and 600A
8 and 9400A and 600A
10 and 11All unitsNC Contact
12 and GND All unitsJumper MOVs
(1)
(1)
units
1000A unitsOpens if any of the snubber circuit fuses or DC
units
1000A unitsOpens if any of the line input branch circuit fuses
Contactor Coil
115V AC
NC Contact
(2)
Output
NC Contact
(2)
Output
NC Contact
(2)
Output
(2)
Output
to Ground
For cooling blower (and power supply on the
Gate Driver Board - on Master and Slave Units)
Contactor must be energized to enable the
controller
Opens if the Enable Contactor is energized
Opens if any of the snubber circuit fuses
(F6…F8) trip
bus feedback fuses (F7…F11) trip
Opens if any of the line input or DC bus branch
circuit fuses (F1…F5) trip
(F1…F6) trip
Opens at power stack heat sink overtemperature
Disconnects MOVs from ground by removing this
jumper. (See Disconnecting MOVs
for details.)
on page 1-14
(1)
Not used on Slave Units.
(2)
Refer to Appendix A for contact rating.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
1-12Installation/Wiring
NOTE: Optional HF Filter
(seepage A-11
)
Drive Run Interlock
To protect the Bus Supply from overtemperature, the normally closed
contacts (Bus Supply Overtemperature - terminals 10 and 11) should be
wired to either the AC line input contactor for the Bus Supply or the Run
interlock circuit (enable input) of each connected drive. This ensures that
the drives are stopped in case of Bus Supply Overtemperature.
Control Wiring Example
Figure 1.8Example of SCR Bus Supply, 1000A Single with Multiple Drives Using
Drive Run Interlocks, Running Simultaneous
115 VAC
K1M
K1M
Stop
Run
K1M
115
1
4
5
6
7
8
9
10
11
K1 *
F7-11
Precharge
*
M
0
AC Drive
110 kW
205A
-
M
3
Board
f
F1-6
>°C
2
K1MK1MK1MK1M
RC
F7-F9
f
AC Drive
110 kW
205A
-
M
3
L1
PowerFlex
SCR Bus
Supply
F1-F6
DC Bus
f
* The customer’s controls
must, at a minimum,
command the blower
to run whenever contactor
K1 is enabled.
AC Drive
110 kW
205A
-
M
3
f
AC Drive
45 kW
85A
-
3
f
M
Jumper Settings
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
The PowerFlex SCR Bus Supply precharge board has three jumpers. See
Figure 1.9 on page 1-13
for jumper locations and positions.
• LINE TYPE Jumper: Always set to the “3-ph” default right-side position
(towards the board edge).
• SPARE 1 Jumper: For board firmware version 1.21 (or earlier), this
jumper is non-functional. For firmware version 1.22 (or later), the SCR
Bus Supply is shipped with this jumper in the right (default) inactive
state position. When the jumper is placed in the left (RGU/AFE) or
active position, the firmware is active for SCR and RGU/AFEparallel
operation on common bus systems, where the SCR is in parallel with an
Installation/Wiring1-13
active front end that is used only as a regenerative brake unit. The
PowerFlex SCR Bus Supply will then deliver the required motoring
power and the RGU/AFE will provide the possibility to feed the
regenerative energy back to the AC power line.The auto-voltage
limitation (allowing the SCRs to phase back) associated with high AC
line will be disabled. The left (RGU/AFE) jumper position provides the
best protection for parellel SCR and RGU/AFE operation.
• SPARE 2 Jumper: For board firmware version 1.21 (or earlier), this
jumper is non-functional. For firmware version 1.22 (or later), this
jumper is used for slow ramp-up, which slows the DC bus voltage charge
up time (from 0.2 to 1.3 seconds). Slow ramp-up should be used when
the connected DC bus capacitance is greater
following table.
than the values shown in the
Max. Bus Capacitance
SCR Bus Supply
400A40,000 µF200,000 µF
600A60,000 µF300,000 µF
1000A @ 480V100,000 µF500,000 µF
1000A @ 690V50,000 µF250,000 µF
(1)
It is recommended to derate the capacitance value by 20% in master/slave configurations.
To operate the SCR Bus Supply with a slow ramp-up, set the SPARE 2
jumper to the left (SLOW) position.
For standard applications where only the PowerFlex SCR Bus Supply
provides the required common DC power, make sure the SPARE 1 and
SPARE 2 jumpers are in their default settings (right side—towards the
board edge) shown in Figure 1.9
Figure 1.9Location of LED Indicators and Jumpers on the Precharge Board
Precharge Board
Firmware Version Label
with Normal Ramp
.
(1)
Max. Bus Capacitance
with Slow Ramp
(Ramp-Up)
(SCR and
RGU/AFE
Paralleling)
SPARE
SPARE
LINE
TYPE
(1)
2
Slow Norm
1
Yes No
1-ph 3-ph
POWER
OK
ALARMLEDs
FAULT
default positions
Jumpers shown in
TIP: To identify the firmware version, remove the SCR Bus Supply cover
and check the firmware version label on the Precharge Board (Figure 1.9
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
).
1-14Installation/Wiring
!
Disconnecting MOVs
The PowerFlex SCR Bus Supply contains protective MOVs that are
referenced to ground. To prevent damage, the MOVs should be
disconnected from ground if the Bus Supply is installed on any
non-solid grounded distribution system where the line-to-ground voltages
on any phase could exceed 125% of the nominal line-to-line voltage. To
disconnect the MOVs from ground, remove the jumper (12-GND) on the
control terminal block shown in Figure 1.7 on page 1-11
non-solid grounded systems are defined in Table 1.G
Table 1.G Recommended MOV Configurations
MOV/Input Filter
Capacitors
Connected• UL compliance
Disconnected• Helps avoid severe equipment
(2)
Power Source Type
Solid Grounded
• AC fed, solidly grounded
• DC fed from passive rectifier which
has an AC source and solid ground
Non-Solid Grounded
• AC fed ungrounded
• Impedance grounded
• High resistive ground
• B phase ground
• Regenerative unit (common DC bus
supply and brake)
• DC fed from an active converter
(1)
It is highly recommended to accurately determine the power source type and then configure appropriately.
(2)
When MOVs are disconnected, the power system must have its own transient protection to ensure known and
controlled voltages.
(1)
Benefits of Correct Power Source
Type Configuration
• Reduced electrical noise
• Most stable operation
• EMC compliance
• Reduced voltage stress on
components and motor bearings
damage when ground fault occurs
. Solid and
.
For more information on non-solid grounded system installation, see Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives
(publication DRIVES-UM001).
ATTENTION: To avoid an electric shock hazard, verify that the
voltage on the bus capacitors has discharged before removing the
jumper. Measure the DC bus voltage at the +DC and –DC output
terminals. The voltage must be zero.
Table 1.H Jumper Removal
Item Jumper Jumper LocationRemoves…
12 and GNDControl Terminals
➍
(1)
For control terminal location, see Figure 1.4, Figure 1.5 or Figure 1.6.
(1)
MOVs from Ground
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Installation/Wiring1-15
DC Bus
Power
Input
Master UnitSlave Unit #1Slave Unit #n
Precharge
Board
Enable
Contactor
Gate
Driver
Gate
Driver
Gate
Driver
CableCable
Main Switch or
Main Input Contactor
Up to 5 Units Maximum
(4750A Maximum DC Bus Current
without altitude or ambient derating)
Aux. Supply
115 VAC
Parallel Connection of Slave
Units
Up to four 1000A PowerFlex SCR Bus Supply Slave units may be
connected in parallel with one 1000A Master. The derate for each additional
slave is 5% plus 5% for the master. Thus, the maximum possible output
rating without altitude or ambient derating is 4750 Amps (0.95 x 5 x 1000
amps) at 40 °C.
Figure 1.10 Example for Master-Slave Configuration
(shown without circuit protection for clarity)
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
1-16Installation/Wiring
1000A SCR Bus Supply
Flexibility
The 1000A SCR Bus Supply can be converted in the following ways.
1000A SCR Bus Supply
Convert from: Standalone
MasterYes
SlaveNoNo
Because of numerous internal changes (components, cables, and hardware)
the following conversions are not allowed:
• Standalone to master
• Standalone to slave
• Slave to standalone
• Slave to master
NOTE: See Figure A.11 on page A-19
Converting Master Unit to Standalone Unit
No changes are required to run a master (without slave units) as a
standalone SCR Bus Supply.
Convert to…
StandaloneMasterSlave
NoNo
Ye s
for circuit board location.
Converting Master Unit to Slave Unit
It is possible to reconfigure a master SCR Bus Supply to run as a slave SCR
Bus Supply. To convert a master unit to a slave, perform these steps.
1. Remove the cables between the precharge board connectors (X2 and
X3) and the gate driver printed circuit board connector X4 (see
Figure P.3 on page P-7
2. Connect a cable from the gate driver printed circuit board connector
(X4) to the new master SCR Bus Supply or another slave SCR Bus
Supply gate connector (X6, see Figure P.4 on page P-8
precharge board does not need to be removed from the converted SCR
Bus Supply.
3. Ensure that the precharge relay is not energized (terminal
block…terminal 1 and 2, see page 1-11
4. Place a label near the data nameplate stating that the SCR bus supply
has been converted to catalog # 20Sx1K0NES, where x is the voltage
class of the unit.
).
). Note that the
).
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Installation/Wiring1-17
1000A SCR Bus Supply
Redundancy
It is not recommended to install parallel master SCR Bus Supplies. The
reason is that there is nothing to synchronize the SCR gate firing between
the precharge printed circuit boards in separate SCR Bus Supplies. Each
precharge board has circuitry designed to energize the DC bus, which has
little to no impedance to limit the inrush current. This DC bus charging
synchronization could lead to power device failure.
If redundancy of the SCR Bus Supply master is required by the application,
there are two options.
• A microcontroller or other electronically or manually-controlled switch
or contact network can be used to reconfigure the wire harnesses
between the redundant master SCR Bus Supplies. Basically, one SCR
Bus Supply becomes the master and the other becomes the slave by the
logic selection of the controlling or steering network. One example of
numerous possible configurations is shown in Figure 1.11
Figure 1.11 Basic Master/Slave Redundancy System Configuration
Enable
Control Logic
* Only one Master enabled.
.
Master
Precharge
PCB
Gate
PCB
• Although not recommended, synchronization differences might be
minimized by using the slower ramp time available in precharge printed
circuit boards with firmware version 1.22 (or later). The standard ramp
time is for the rise of DC bus to phase full on in approximately 0.2
seconds, while the slower ramp time will take approximately 1.3
seconds. This will help to limit the inrush current in the system.
For additional recommendations about SCR Bus Supply redundancy,
contact Rockwell Automation Technical Support.
SlaveSlave
Gate
PCB
Slave
Gate
PCB
Gate
PCB
Master
Precharge
PCB
Gate
PCB
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
1-18Installation/Wiring
Y
Reactor
Standalone
or
Master
SCR Bus
Supply
Reactor
Fuses*
Gate
Harness
Fuses*
Enable
Slave
Reactor
12-Pulse
Transformer
Slave
Reactor
AC Line
Standalone
or
Master
SCR Bus
Supply
Gate
Harness
Fuses*Fuses*
* Fuses are optional.
DC Bus
SCR Bus Supply 12-Pulse
Configuration
Standalone or master/slave SCR Bus Supplies can be used on applications
that use a 12-pulse transformer to minimize power line harmonics.
Important:Be sure to select the slow ramp time(see Jumper Settings
page 1-12).
Figure 1.12
optional slave SCR Bus Supplies.
Figure 1.12 12-Pulse System Configuration
shows a recommended 12-pulse system configuration with
on
For additional recommendations about SCR Bus Supply 12-pulse
configurations, contact Rockwell Automation Technical Support.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Installation/Wiring1-19
CE Conformity
Conformity with the Low Voltage (LV) Directive and Electromagnetic
Compatibility (EMC) Directive has been demonstrated using harmonized
European Norm (EN) standards published in the Official Journal of the
European Communities. The PowerFlex SCR Bus Supply complies with the
EN standards listed below when installed according to the User Manual.
CE Declarations of Conformity are available online at:
http://www.ab.com/certification/ce/docs
Low Voltage Directive (73/23/EEC)
• EN50178 Electronic equipment for use in power installations
EMC Directive (89/336/EEC)
• EN61800-3 Adjustable speed electrical power drive systems Part 3:
EMC product standard including specific test methods.
Harmonic Emissions
Electronic converters such as the Bus Supply can cause conducted low
frequency disturbances (harmonic emissions) to the supply network. The
mandatory three-phase AC line reactors will substantially reduce harmonic
currents produced by the Bus Supply. However, the magnitude of the
harmonic currents and resulting harmonic voltages depends upon the
network impedance at the point where the unit is connected to the network.
Currently there are no mandatory harmonic emission limits related to CE
compliance for equipment connected to private power networks. Upon
request, Rockwell Automation can provide information regarding harmonic
emissions from the SCR Bus Supply.
General Notes
• The DC bus cable to the inverter(s) should be kept as short as possible to
avoid electromagnetic emission and capacitive currents. Therefore the
inverter(s) should be located in the same cabinet as the Bus Supply or
next to the cabinet with the Bus Supply. If the connection leads between
DC bus and inverter(s) are leaving the cabinet, shielded cables must be
used.
• Use of line filters in non-solid grounded systems is not recommended.
• The PowerFlex SCR Bus Supply with external Line Reactor and HF
filter satisfies CE EMC emission limits for the industrial environment. If
used in a residential or domestic environment itmay cause radio
interference. The user is required to take measures to prevent
interference, in addition to the essential requirements for CE compliance
listed below, if necessary.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
1-20Installation/Wiring
• Conformity of the drive with CE EMC requirements does not guarantee
an entire machine installation complies with CE EMC requirements.
Many factors can influence total machine/installation compliance.
Essential Requirements for CE Compliance
Conditions 1…5 listed below must be satisfied for the PowerFlex SCR Bus
Supply to meet the requirements of EN61800-3.
1. Bus Supply and inverter must be PowerFlex type and CE compatible.
2. Externally mounted Line Reactor and HF filter (specified in
Appendix
Figure 1.8 on page 1-12
3. Review important precaution/attention statements throughout this
document before installing the drive(s).
A) must be connected to the line input as shown in
.
4. Grounding as described in General Grounding Requirements
page 1-5.
5. Control wiring and DC bus wiring leaving the cabinet must be braided,
shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.
For additional conditions, refer to the respective drive Reference Manual.
on
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
!
!
!
Chapter 2
Start Up/Troubleshooting
This chapter provides the necessary information for the start up and
troubleshooting of the PowerFlex SCR Bus Supply.
TopicPage
Start-Up
Precharge Board LED Indicators2-4
Troubleshooting2-6
ATTENTION: Power must be applied to the SCR Bus Supply
and the Inverter to perform the following start-up procedure. Some
of the voltages present are at incoming line potential. To avoid
electric shock hazard or damage to equipment, only qualified
service personnel should perform the following procedure.
Thoroughly read and understand the procedure before beginning.
If an event does not occur while performing this procedure, do not proceed. Remove power including user-supplied control voltages.
User-supplied voltages may exist even when main AC power is not
applied to the Bus Supply. Correct the malfunction before
continuing.
2-2
ATTENTION: When operating the SCR Bus Supply, a minimum
of one 7.5 kW (10 HP) PowerFlex 700/700S Inverter must be
connected to the DC bus—otherwise the internal fault detection
circuit will interpret the condition as an Output Voltage Loss and
stop pulse firing. This is indicated on the Precharge Board by the
Alarm LED (7 flashes) and after 30 seconds by the Fault LED (2
flashes). Refer to Table 2.A
ATTENTION: Second source of power for cooling blower is
present. To avoid an electric shock hazard or moving blades, verify
the AC power supply has been removed prior to performing any
maintenance or repairs.
and Table 2.B.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
2-2Start Up/Troubleshooting
Start-Up
Before Applying Power to the Bus Supply
❏ 1.Verify that the minimum of one Inverter is connected to the DC bus.
❏ 2.Confirm that all inputs are connected to the correct terminals and are
properly torqued.
❏ 3.Using an ohmmeter or other continuity testing device, verify that shorts
do not exist between Source 1 and Source 2:
Source 1Source 2Checkmark Below if No Short Exists
L1L2
L1L3
L2L3
L1PE
L2PE
L3PE
L1DC+ Bus
L2DC+ Bus
L3DC+ Bus
L1DC- Bus
L2DC- Bus
L3DC- Bus
DC+ Bus DC- Bus
DC+ Bus PE
DC Bus PE
❏ 4.Verify that AC line power at the disconnect device is within the rated
value of the Bus Supply. See Appendix
❏ 5.Verify that control power voltage is correct.
❏ 6.Verify that the enable contactor coil K1 (not used on Slave units) is
correctly wired.
❏ 7.Verify that these four outputs are correctly wired:
❏ 8.Verify that the “Line Type” jumper on the Precharge Board shown in
– Bus Supply Overtemperature
– Rectifier Fuse Trip
– Snubber/DC feedback Fuse Trip
– Enable Contactor Feedback (not used on Slave units)
These normally closed contact outputs are used to set alarms and to stop
the drive(s). Verify that they have been wired correctly according to the
user’s specification. Refer to the control wiring example shown in
Figure 1.8 on page 1-12
Figure 2.1
is set to the “3-ph” position (default).
.
A.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Start Up/Troubleshooting2-3
❏ 9.Verify that the SPARE 1 and SPARE 2 jumpers on the Precharge Board
shown in Figure 2.1
(Refer to Jumper Settings
more information).
❏ 10. Verify that the jumper between control terminals 12 and GND (Figure
1.7 on page 1-11) is present on grounded supply lines (default) or is
removed on non-solid grounded supply lines. (Refer to Disconnecting
MOVs on page 1-14 for more information).
Applying AC Power to the Bus Supply
❏ 1.Apply AC power and control voltage (115V AC) to the Bus Supply.
The green POWER OK LED on the Precharge Board should be on if
power is applied to terminals L1 (R), L2 (S), L3 (T) and the enable
contactor for the precharge board (not used on Slave units) is energized.
are set to appropriate positions for the application.
on page 1-12 and Figure 1.9 on page 1-13 for
❏ 2.If the green POWER OK LED is off at this point, refer to Table 2.B
.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
2-4Start Up/Troubleshooting
!
SPARE
2
(Ramp-Up)
Precharge Board
Firmware Version Label
(SCR and
RGU/AFE
Paralleling)
Slow Norm
Yes No
1-ph 3-ph
SPARE
1
LINE
TYPE
POWER
OK
ALARMLEDs
Jumpers shown in
default positions
FAULT
Precharge Board LED
Indicators
The three LEDs on the Precharge Board are visible through a small slot in
the SCR Bus Supply cover. The 400A unit cover has one slot. The 600A
unit cover has two slots but only the lower slot is used to view the LEDs.
Since the Precharge Board for the 1000A unit is mounted either on the
lower carrier plate (on Single Units) or on the upper carrier plate (on Master
Units), the corresponding lower or upper slot is used to view the LEDs. For
slot locations, see Figure A.1 on page A-3
ATTENTION: The SCR Bus Supply LEDs are only operational
when the unit is energized. Servicing energized equipment can be
hazardous. Severe injury or death can result from electrical shock,
burn, or unintended actuation of the controlled equipment. Follow
safety-related practices of NFPA 70E, Electrical Safety For
Employee Workplaces. DO NOT work alone on energized
equipment!
Figure 2.1Location of LED Indicators and Jumpers on the Precharge Board
.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Pause
0.3
sec.
0.3
sec.
0.9 sec.
Start Up/Troubleshooting2-5
Table 2.A Precharge Board LED Indicators
NameColorStateDescription
POWER OK GreenSteadyIlluminates when precharge board power supply is operational.
ALARMYellowFlashing The number [n] of flashes (see flashing pattern in Figure 2.2
indicates one of the following alarms
[1]
Low Line Voltage (< 90%)
Low Line Voltage (< 65%) for SCR and RGU/AFE paralleling
mode
Very Low Line Voltage (< 50%)
[2]
Low Phase (One phase < 80% of line voltage), or
[3]
Low Phase Voltage (One phase < 56% of line voltage) for SCR
and RGU/AFE paralleling mode
Freq. out of range or asymmetry (Line synchronization failed)
[4]
Low DC Bus Voltage (triggers ride-through operation)
[5]
Input Frequency momentarily out of range (40…65 Hz)
[6]
DC Bus Short Circuit testing active (repetitive for appr. 120 s) or
[7]
no inverter connected to the bus
FAULTRedFlashing The number [n] of flashes (see flashing pattern in Figure 2.2
(1)
The ALARM indicator LED will continue the flashing pattern as long as the alarm condition exists. An alarm
might trigger internal actions which may stop SCR gate firing.
(2)
If a fault occurs, the FAULT indicator LED will continue the flashing pattern, even if the fault condition no longer
exists. Power must be cycled to clear the fault.
indicates one of the following faults
[2]
DC Bus Short (Udc < 2% after 20ms)
[4]
Line Synchronization failed or Low Line (Uac < 50% Unom)
[5]
Jumper setting wrong
(1)
:
(2)
:
)
)
Figure 2.2Flashing Pattern for ALARM and FAULT LEDs
Example: Flashing pattern for ALARM LED showing a Low Phase alarm (where n = 3 flashes)
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
2-6Start Up/Troubleshooting
Troubleshooting
Table 2.B Possible Faults and Corrective Actions
FaultCauseCorrective Action
Heat sink
Overtemperature
DC Output
Voltage Loss
Heat sink temperature
exceeds maximum rating
DC bus:
- Short Circuit FAULT [2] or
- Low Line FAULT [4] or
- No Load ALARM [7]
Refer to Table 2 . A
Loss of 115V AC power1. Check 115V AC supply input voltage at control
.
Jumper setting
wrong
Wrong jumper settings:
Single phase (1-ph) line
type and one or both of the
SPARE 1 or SPARE 2
jumpers set to their
respective left positions.
1. Verify that maximum ambient temperature has
not been exceeded.
2. Check Overtemperature Switch (N.C. contacts)
at control terminals 10 and 11.
3. Check 115V AC supply input voltage at control
terminals 0 and 115.
4. Check blower for correct operation.
5. Check for excess load on the bus supply.
6. Check for minimum mounting clearance around
the bus supply.
7. Contact your local RA sales office.
1. Check 3-phase AC incoming power for
undervoltage or phase loss.
2. Check all Bus Supply fuse trip indicator switches.
3. Verify the Inverter is connected.
4. Verify the power of the connected Inverter(s) is
minimum 7.5 kW (10 HP). Refer to the 2nd
Attention statement on page 2-1
5. Contact your local RA sales office.
terminals 0 and 115.
2. Check Enable Contactor function.
3. Contact your local RA sales office.
1. Check the jumper setting(s).
2. Set the jumper(s) correctly.
.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Start Up/Troubleshooting2-7
Important:Complete the tests listed in Table 2.C without power applied to
the SCR Bus Supply.
Table 2.C Control Terminal Block Continuity Test Conditions
Test ConditionPossible CauseCorrective Action
N.C. contact on
control terminals
6 and 7 is open
N.C. contact on
control terminals
8 and 9 is open
N.C. contact on
control terminals
10 and 11 is open
400A and 600A Unit: Open
snubber fuse (F6…F8).
1000A Unit: Open snubber
fuse or open DC bus fuse
(F7…F11).
400A and 600A Unit: Open
AC line fuse or open DC bus
fuse (F1…F5).
1000A Unit: Open AC line
fuse (F1…F6).
Open heat sink
Overtemperature Switch
1. Check for evidence of power module failure (see
Step 3 inStart-Up
2. Check for evidence of failure in snubber circuit.
Check the snubber pcb diodes and snubber
resistor and capacitor.
3. Replace entire SCR Bus Supply if any device
has failed.
4. If there is no evidence of a failure, check for open
fuse and replace.
1. Check for evidence of power module failure (see
Step 3 inStart-Up
2. Replace entire SCR Bus Supply if any device
has failed.
3. If there is no evidence of power module failure,
check for open fuse and replace.
1. Verify that maximum ambient temperature is not
exceeded.
2. Replace the Overtemperature Switch.
on page 2-2).
on page 2-2).
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
2-8Start Up/Troubleshooting
Notes:
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Appendix A
Specifications
This appendix provides electrical, environmental, functional and physical
specifications for the PowerFlex SCR Bus Supply, and selection tables for
AC input devices.
TopicPage
PowerFlex SCR Bus Supply
Bus Supply DimensionsA-3
AccessoriesA-7
Spare PartsA-14
A-1
PowerFlex SCR Bus Supply
Category Specification
Input
Ratings
Output
Ratings
(1)
Includes appropriate AC line reactor.
Specifications Dependent on Power and Voltage
SCR Bus Supply Catalog Number
20SD400… 20SD600… 20SD1K0… 20SF1K0…
Nominal AC Input Voltage:400/480V600/690V
Frequency:47…63 Hz47…63 Hz
Operational AC Input Voltage Range:187…528V528…759V
Input Current (Max. Continuous rms):355521843843
Input kVA at Max. Continuous rms Amps:246/295361/433584/700876/1007
DC Bus AmpsNormal Duty/Heavy Duty
Continuous:
1 minute:
3 Sec. every minute:
Max. Continuous DC Bus Amps
without Overload:
Power Dissipation
Maximum Continuous Amps:
The derate for each additional slave is 5% plus 5% for the master. See
Parallel Connection of Slave Units
(1)
— Watts at
300/240
330/360
450/480
40060010001000
1200160027002800
on page 1-15.
500/400
550/600
750/800
800/720
880/1080
1200/1440
800/720
880/1080
1200/1440
Specifications Dependent on Voltage
AC Input
Vol ta ge
400V540V750V
480V650V750V
600V810V1080V
690V930V1080V
DC Bus Voltage
NominalMaximum
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
A-2Specifications
Specifications Common to All SCR Bus Supplies
CategorySpecification
Input/Output
Ratings
Control Input Enable Contactor Coil:Single Phase 115V AC, 30 VA (pick-up), 4.5 VA (hold)
Control
Output
Approvals and
Standards
Compliance
Voltage Tolerance:–10% of minimum, +10% of maximum
Frequency Tolerance:47…63 Hz.
Displacement Power Factor:0.92 lagging (entire load range)
Efficiency:99.5% at rated amps, nominal line volts
Line Transients:Up to 6000 volts peak per IEEE C62.41-1991
Max. Short Circuit Current Rating:85 kA
CoolingForced ventilation cooled by tangential blower below heat sink
Blower Power Consumption:
Cooling Air:
Blower Current Consumption:Single Phase 115V AC,50/60 Hz, 1 A
Heat Sink Temperature Sensor:The temperature sensor trips if heat sink temperature exceeds
NC Contact Output Rating (Max.):Resistive Rating: 15A at 125V AC, 10A at 250V AC,
Fuse Trip Indication
Microswitches F1…F5 (400A & 600A)
Microswitches F1…F6 (1000A)
NC Contact Output Rating (Max.):Resistive Rating: 10A at 30…250V AC, 8A at 30V DC
Fuse Trip Indication
Microswitches F6…F8 (400A & 600A)
Microswitches F7…F11 (1000A)
NC Contact Output Rating (Max.):Resistive Rating: 10A at 30…250V AC, 8A at 30V DC
Enable Contactor K1,
NC Contact Output Rating (Max.):Resistive Rating: 10A at 24…230V AC, 3A at 30V DC
NFPA 70- US National Electrical Code
NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and Operation
of Adjustable Speed Drive Systems.
NEMA 250- Enclosures for Electrical Equipment
IEC 146- International Electrical Code.
U
c
L
®
US
200 VA
3
/hr.
600 m
maximum temperature.
7A at 24V DC
Inductive Rating: 10A at 125V AC, 6A at 250V AC
Inductive Rating: L/R = 25 ms, 10A at 30…250V AC
Inductive Rating: L/R = 25 ms, 10A at 30…250V AC
Inductive Rating: 2.2A at 24…230V AC
UL and cUL Listed to UL508C and
CAN/CSA-C22.2
EnvironmentAltitude:1000 m (3300 ft.) max. without derating. Above 1000 m, the
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Marked for all applicable European Directives:
• EMC Directive (89/336/EEC)
Ambient Operating Temperature
without Derating Open Type / IP00:
Storage Temperature (all const.):–40…70 °C (–40…158 °F)
Relative Humidity:5…95% non-condensing
• Emissions: EN 61800-3 Adjustable Speed electrical power
drive systems Part 3
• Immunity: EN 61800-3 Second Environment, Restricted
Distribution
• Low Voltage Directive (73/23/EEC)
• EN 50178 Electronic Equipment for Use in Power
Installations
derating for the output current is 1% per 100 m (330 ft.).
0…40 °C (32…104 °F); above 40 °C up to 50 °C (122 °F)
maximum temperature, the output Amps must be derated by:
1.2% per °C (2.2% per °F) for 400A unit
1.0% per °C (1.8% per °F) for 600A unit
1.0% per °C (1.8% per °F) for 1000A unit
CategorySpecification
Side ViewFront View
Environment
(continued)
Permitted
Maximum
Capacitance
Shock:15G peak for 11 ms duration (± 1.0 ms)
Vibration:0.152 mm (0.006 in.) displacement, 1G peak
Atmosphere:Important: The bus supply must
Surrounding Environment:The fan has a L10 rated life of 74,000 hours in a clean
Maximum Capacitance for Connection
to the DC Bus Supply
SpecificationsA-3
where the ambient atmosphere contains volatile or corrosive
gas, vapors or dust. If the bus supply is not going to be installed
for a period of time, it must be stored in an area where it will not
be exposed to a corrosive atmosphere.
environment. Execessive dust and heat will degrade fan life.
This is the total DC Bus capacitance sum of the permitted
drives to connect. See Minimum Capacitance
Jumper Settings
on page 1-12.
not be installed in an area
on page 1-6 and
Bus Supply Dimensions
The overall dimensions and mounting holes of the PowerFlex SCR Bus
Supply are shown in Figure A.1
in Figure A.2
600A740 (29.1)490 (19.3)785 (30.9)276 (10.9)104.5 (4.1)43 kg (95 lb.)
1000A740 (29.1)490 (19.3)785 (30.9)276 (10.9)104.5 (4.1)67 kg (147 lb.)
29
(1.14)
D
Dimensions
17 x 5 (0.67 x 0.2)
Slots for Precharge
Board LEDs
Dimensions are in millimeters and (inches).
WeightABCDE
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
A-4Specifications
Side ViewFront View
Figure A.2 400A Unit Bus Bar Customer Connection Point Dimensions/Locations
L3
DC+
15 (0.6)
77.5
(3.05)
190
(7.5)
PE
50
(1.97)
144 (5.7)
DC-
L1
L2
58
(2.3)58(2.3)
Dimensions are in millimeters and (inches).
233 (9.2)
PE
M8
243 (9.6)
304 (12)
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
SpecificationsA-5
DC+
DC-
F5
F4
L1
L2
L3
PE
100
(3.94)
40
(1.57)
160
(7.5)
243
(9.6)
243
(9.6)
PE
304
(12)
40 (1.57)
50
(1.97)
70
(2.56)70(2.56)
147
(5.8)
68
(2.7)
Dimensions are in millimeters and (inches).
F12
F6-F8
F1
F2
F3
Side ViewFront View
Figure A.3 600A Unit Bus Bar Customer Connection Point Dimensions/Locations
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
A-6Specifications
PE
L1
PE
L3
L2
DC-
DC+
100
(3.94)
249
(9.8)
40
(1.57)
40 (1.57)
50 (1.97)
70
(2.56)70(2.56)
Dimensions are in millimeters and (inches).
249
(9.8)
338.5
(13.3)
157.5
(6.2)
57
(2.24)
61.5
(2.4)
Side ViewFront View
Figure A.4 1000A Unit Bus Bar Customer Connection Point Dimensions/Locations
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
SpecificationsA-7
Accessories
Line Reactors
A minimum reactance is required to limit peak currents in the AC line and
the bridge circuit. This can be accomplished either by a matched supply
transformer or by adding line reactors to ensure the requested minimum
voltage drop over the total line impedance. The preferred method is to
install a minimum 3% line reactor, which will also reduce line harmonics.
Use Table A.A
of the drive’s connected DC Amps and the supply transformer rating.
For more details on the 1321-Series line reactors, see the 1321 Power Conditioning Products Technical Data (publication 1321-TD001).
Table A.A 400V, 50Hz Line Reactor Selection
DrivesRanges of Drives DC Amp Sum for Typical Supply Transformers
The inductance value of the supply transformers includes 2.5 µH for 10 m feeder cable.
(2)
The number in the catalog string represents the fundamental AC current of the reactor.
(3)
Connect two reactors in series.
SpecificationsA-11
4mm
2
Wire
41.5
(1.63)
PE
500
(19.7)
100
(3.94)
Ø 4.2
(0.17)
Ø 4.5
(0.18)
15.5
(0.61)
35
(1.38)
35
(1.38)
20
(0.8)
18
(0.7)
110
(4.3)
110
(4.3)
120
(4.7)
HF Filter
It is recommended to install one HF filter (Catalog No. 20S-RFC) in every
system. When this filter is used, the HF emission limits for class A, group
2* (EN 55011) in the 2nd environment (industrial supply network)
according to the product standard EN 61800-3 are met and the Bus Supply
fulfills CE conformity.
The HF filter is connected in front of the AC line reactor between the three
AC line input phases and the protection earth conductor PE (Figure A.5
Figure A.5HF Filter Wiring Diagram
AC
HF
Filter
).
…
SCR
Bus Supply
Figure A.6 20S-RFC Filter Dimensions
SCR
Bus Supply
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
A-12Specifications
Solid Ground Systems
Using the hole location dimensions from Figure A.6, install the HF filter
using the four (4) M4 x 20 screws through the four holes in the plastic body
of the HF filter (Figure A.7
through the PE grounding plate. Do NOT use the nylon standoffs.
Figure A.7Mounting the HF Filter
). Then install the three (3) M4 x 8 screws
M4 x 8
3 Places
(for solid ground
system only)
PE
Grounding
Plate
Non-Solid Ground Systems
The HF filter may be installed with floating or HRG ground systems for
line-to-line transient protection. In this type of installation, the PE
grounding plate should NOT be connected to ground, but remain isolated
from ground.
Important:The HF filter PE grounding plate will be floating with potential
high voltage with respect to earth ground when AC line power
is applied.
M4 x 20
4 Places
M4 x 19
Nylon Standoffs
4 Places
(for floating or
HGR system only)
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Using the hole location dimensions from Figure A.6
using the four (4) M4 x 19 nylon standoffs and four (4) M4 x 20 screws
through the four holes in the plastic body of the HF filter (Figure A.7
Finger tighten the nylon standoffs.Do NOT install the three (3) M4 x 8
screws through the PE grounding plate.
Install the High Voltage Warning label onto the PE grounding plate when
the HF filter is installed with a floating or HRG ground system.
, install the HF filter
).
This page intentionally left blank.
SpecificationsA-13
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
A-14Specifications
20
35
38
30
21
6
8
3
25
33
24
12
27
4
16
18
13
31
32
7
9
Spare Parts
400A SCR Bus Supply
Important:SCR Bus Supplies are NOT designed to be field repaired, but
can be field maintained.
Figure A.8 400A Unit Spare Part Locations
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
SpecificationsA-15
Table A.E 400A Unit Spare Part Numbers/Descriptions
SK-20S-F070B040S or
Westcode Type F070B040S or
Ferraz Shawmut Type 6.921CPgRC14.51 40
SK-20S-069UR0S0400B or
Westcode Type 069UR0S0400B or
Ferraz Shawmut Type 6.9URD30TTF0400
SK-20S-069UR0S0450B or
Westcode Type 069UR0S0450B or
Ferraz Shawmut Type 6.9URD30TTF0450
SK-20S-IN5515203
SK-20S-IN5514502
(4)
SK-D9-SCRPRE1-D1
3
3
2
(1)
Important: SCR Bus Supplies are designed to be field maintained only. Normal maintenance components (fan, fuses, fuse
monitor switch, printed circuit boards (precharge, gate, and snubber), and precharge relay are available. Additional catalog
numbers are provided for troubleshooting and technical support information only.
(2)
Extensive disassembly is required to replace the fan assembly. Please consider using Rockwell Automation Remanufacturing
Services.
(3)
When replacing these fuses, always properly position them so that their fuse trip indicators (plungers) point toward the fuse trip
detection board.
(4)
This is an ESD sensitive component.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
A-16Specifications
19
35
38
22
31
29
2
6
27
32
4
12
10
71311
15
18
25
24
27
600A SCR Bus Supply
Important:SCR Bus Supplies are NOT designed to be field repaired, but
can be field maintained.
Figure A.9 600A Unit Spare Part Locations
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
SpecificationsA-17
Table A.F 600A Unit Spare Part Numbers/Descriptions
SK-20S-F070B040S or
Westcode Type F070B040S or
Ferraz Shawmut Type 6.921CPgRC14.51 40
SK-20S-069UR5S0630B or
Westcode Type 069UR2S0630B or
Ferraz Shawmut Type 6.9URD32TTF0630
SK-20S-069UR2S1000B or
Westcode Type 069UR2S1000B or
Ferraz Shawmut Type 6.9URD32TTF1000
SK-20S-IN5515205
(4)
SK-D9-SCRPRE1-D1
3
3
2
(1)
Important: SCR Bus Supplies are designed to be field maintained only. Normal maintenance components (fan, fuses, fuse
monitor switch, printed circuit boards (precharge, gate, and snubber), and precharge relay are available. Additional catalog
numbers are provided for troubleshooting and technical support information only.
(2)
Extensive disassembly is required to replace the fan assembly. Please consider using Rockwell Automation Remanufacturing
Services.
(3)
When replacing these fuses, always properly position them so that their fuse trip indicators (plungers) point toward the fuse trip
detection board.
(4)
This is an ESD sensitive component.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
A-18Specifications
19
34
38
37
36
35
22
31
32
27
14
1312
5
1
23
26
4
28
17
71111
12
1000A SCR Bus Supply
Important:SCR Bus Supplies are NOT designed to be field repaired, but
can be field maintained.
Figure A.10 1000A Unit Spare Part Locations
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
SpecificationsA-19
Precharge Board
SK-D9-SCRPRE1-x
Gate Drive Board
SK-D9-SCRGDB1
1000A
Slave Unit
1000A
Master Unit
1000A
Standalone Unit
Gate Driver Board
SK-D9-SCRGDB1
Precharge Board
SK-D9-SCRPRE1-x
Table A.G 1000A Unit Spare Part Numbers/Descriptions
SK-20S-F070B040S or
Westcode Type F070B040S or
Ferraz Shawmut Type 6.921CPgRC14.51 40
SK-20S-069UR2S1000B or
Westcode Type 069UR2S1000B or
Ferraz Shawmut Type 6.9URD32TTF1000
SK-20S-IN5515205
SK-D9-SCRGDB11
SK-D9-SCRPRE1-D1
SK-D9-SCRPRE1-F1
(7)
SK-20S-D9-CBL1-DF1
5
6
(1)
Important: SCR Bus Supplies are designed to be field maintained only. Normal maintenance components (fan, fuses, fuse monitor
switch, printed circuit boards (precharge, gate, and snubber), and precharge relay are available. Additional catalog numbers are
provided for troubleshooting and technical support information only.
(2)
Extensive disassembly is required to replace the fan assembly. Please consider using Rockwell Automation Remanufacturing Services.
(3)
When replacing these fuses, always properly position them so that their fuse trip indicators (plungers) point toward the fuse trip
detection board.
(4)
This is an ESD sensitive component.
(5)
Not required for 1000A Standalone unit, but required for 1000A Master unit or 1000A Slave unit (both mounted in lower location).
(6)
Not required for 1000A Slave unit, but required for 1000A Standalone unit (mounted in lower location) or 1000A Master unit (mounted in
upper location).
(7)
Not required for a 1000A Standalone unit, but required to connect an existing 1000A Master or Slave unit to another 1000A Slave unit
(gate driver circuit board mounted in lower location).
Figure A.11 1000A Unit Printed Circuit Board Locations (top view)
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
A-20Specifications
Notes:
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Appendix B
History of Changes
TopicPage
20S-UM001F-EN-P, March 2011
This appendix summarizes the revisions to this manual. Reference this
appendix if you need information to determine what changes have been
made across multiple revisions. This may be especially useful if you are
deciding to upgrade your hardware or software based on information added
with previous revisions of this manual.
B-1
20S-UM001F-EN-P, March
2011
Change
Reformatted document from half size (5.5 x 8.5 in.) to full size (8.5 x 11 in.).
Removed reactors by DC Bus outputs on 12-Pulse System Configuration drawing.
Added Atmosphere specification to the Environmental section.
Added Surrounding Environment specification to the Environment section.
Revised 400A, 600A, and 1000A Bus Supply spare part drawings and related tables.
Added index to User Manual.
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
B-2History of Changes
Notes:
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Index
A
AC input
HF filter, A-11
line reactors, A-7 to A-10
voltages, A-1
wiring guidelines, 1-7
dimensions, A-3toA-6
discharging DC bus capacitors, P-3
disconnecting MOVs, 1-14
distribution systems
non-grounded, 1-4
unbalanced, 1-4
documentation, related, P-1
E
earthing, see grounding
ESD, static discharge, P-3
M
manual
conventions, P-2
web site, P-2
master unit (1000A only) conversion to
slave unit, 1-16
standalone unit, 1-16
maximum loading, 1-6
minimum capacitance, 1-6
minimum mounting clearances, 1-3
MOVs, disconnecting, 1-14
O
opening the cover, 1-2
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Index-2
operating temperature, 1-3
P
parallel connection of slave units (1000A only),
1-15
PE ground, 1-5
power wiring, 1-7
powering up bus supply, 2-2
precautions, general, P-3
R
related documentation, P-1
removing cover, 1-2
replacing fuses
1000A unit, A-19
400A unit, A-15
600A unit, A-17
RFI filter grounding, 1-5
S
safety ground, 1-5
SCR bus supply
12-pulse configuration, 1-18
ambient operating temperature, 1-3
catalog number explanation, P-4
control wiring, 1-11
DC bus capacitor discharging, P-3
dimensions, A-3toA-6
jumper settings, 1-12
line reactors, A-7 to A-10
power wiring, 1-7
redundancy (1000A unit only), 1-17
spare parts, A-14 to A-19
specifications, A-1toA-3
setting jumpers, 1-12
short circuit protection, 1-7
slave unit (1000A only)
parallel connection, 1-15
spare parts, A-14 to A-19
specifications, A-1toA-3
start-up checklist, 2-2
static discharge, ESD, P-3
status indicators, 2-4
supply source for AC, 1-4
system grounding, 1-5
T
technical support, P-2
troubleshooting, 2-6
U
unbalanced/non-grounded supply, 1-4
W
web site
related documentation, P-2
Rockwell Automation technical support, P-2
wiring
control, 1-11
power, 1-7
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Rockwell Automation Support
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support/
application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the
best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect
support programs. For more information, contact your local distributor or Rockwell Automation representative,
or visit http://www.rockwellautomation.com/support/
For U.S. Allen-Bradley Drives Technical Support — Tel: (1) 262.512.8176, Fax: (1) 262.512.2222,
Email: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives
, you can find technical manuals, a knowledge base of FAQs, technical and
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual.
You can contact Customer Support for initial help in getting your product up and running.
United States or Canada1.440.646.3434
Outside United States or
Canada
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact
your local Rockwell Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing
facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United StatesContact your distributor. You must provide a Customer Support case number (call the phone number above to obtain
Outside United StatesPlease contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document,
complete this form, publication RA-DU002
www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street,
/
Middle East/Africa: Rockwell Automati
Europe
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846