Micro800 8-Point Input and 8-Point Output
AC Modules
Catalog Numbers 2085-IA8, 2085-IM8, 2085-OA8
http://www.rockwellautomation.com/literature/
Cette publication est disponible en français
sous forme électronique (fichier PDF). Pour la
FR
télécharger, rendez-vous sur la page Internet
indiquée ci-dessus.
Questa pubblicazione è disponibile in Italiano
in formato PDF. Per scaricarla collegarsi al sito
IT
Web indicato sopra.
Diese Publikation ist als PDF auf Deutsch
verfügbar. Gehen Sie auf die oben genannte
DE
Web-Adresse, um nach der Publikation zu
suchen und sie herunterzuladen.
Esta publicación está disponible en español
como PDF. Diríjase a la dirección web indicada
ES
arriba para buscar y descarga esta publicación.
Esta publicação está disponível em portugués
como PDF. Vá ao endereço web que aparece
PT
acima para encontrar e fazer download da
publicação.
ZH
ZC
KO
Table of Contents
TopicPage
Important User Information2
Additional Resources5
Overview5
Module Description6
Mount the Module6
Wire the Modules8
Specifications9
2 Micro800 8-Point Input and 8-Point Output AC Modules
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines
for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
Automation sales office or online at http://www.rockwellautomation.com/literature/
between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that
each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc.,
is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the
consequences.
Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage
may be present.
Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach
dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
available from your local Rockwell
) describes some important differences
Publication 2085-IN005B-EN-P - September 2012
Micro800 8-Point Input and 8-Point Output AC Modules 3
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up
to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial
equipment according to IEC/CISPR 11. Without appropriate precautions, there may be
difficulties with electromagnetic compatibility in residential and other environments due to
conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure
that is suitably designed for those specific environmental conditions that will be present and
appropriately designed to prevent personal injury resulting from accessibility to live parts. The
enclosure must have suitable flame-retardant properties to prevent or minimize the spread of
flame, complying with a flame spread rating of 5VA or be approved for the application if
nonmetallic. The interior of the enclosure must be accessible only by the use of a tool.
Subsequent sections of this publication may contain additional information regarding specific
enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of
protection provided by enclosures.
, for
Preventing Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Publication 2085-IN005B-EN-P - September 2012
4 Micro800 8-Point Input and 8-Point Output AC Modules
North American Hazardous Location Approval
The following modules are North American Hazardous Location approved:
2085-IA8, 2085-IM8, 2085-OA8
The following information applies when operating
this equipment in hazardous locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for
use in Class I Division 2 Groups A, B, C, D, Hazardous
Locations and nonhazardous locations only. Each product is
supplied with markings on the rating nameplate indicating
the hazardous location temperature code. When combining
products within a system, the most adverse temperature
code (lowest "T" number) may be used to help determine the
overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of
installation.
WARNING: EXPLOSION HAZARD
• Do not disconnect equipment unless
power has been removed or the area is
known to be nonhazardous.
• Do not disconnect connections to this
equipment unless power has been
removed or the area is known to be
nonhazardous. Secure any external
connections that mate to this
equipment by using screws, sliding
latches, threaded connectors, or other
means provided with this product.
• Substitution of components may impair
suitability for Class I, Division 2.
• If this product contains batteries, they
must only be changed in an area known
to be nonhazardous.
WARNING: When you connect or disconnect the Removable Terminal Block (RTB) with field side
power applied, an electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be
mounted in a suitable enclosure with proper wiring method that complies with the governing
electrical codes.
WARNING: If you connect or disconnect wiring while the field-side power is on, an electrical arc
can occur. This could cause an explosion in hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
WARNING: If you insert or remove the module while backplane power is on, an electrical arc can
occur. This could cause an explosion in hazardous location installations. Be sure that power is
removed before proceeding.
WARNING: Do not unscrew the RTB hold down screws and remove the RTB while power is on.
This could cause an explosion in hazardous location installations. Be sure that power is removed
before proceeding.
Informations sur l’utilisation de cet équipement en
environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements de Classe
I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque
d'identification qui indiquent le code de température pour les
environnements dangereux. Lorsque plusieurs produits sont
combinés dans un système, le code de température le plus
défavorable (code de température le plus faible) peut être
utilisé pour déterminer le code de température global du
système. Les combinaisons d'équipements dans le système
sont sujettes à inspection par les autorités locales qualifiées
au moment de l'installation.
WARNING: RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher l'équipement.
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher les connecteurs.
Fixer tous les connecteurs externes reliés
à cet équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.
• La substitution de composants peut
rendre cet équipement inadapté à une
utilisation en environnement de Classe I,
Division 2.
• S'assurer que l'environnement est classé
non dangereux avant de changer les piles.
Publication 2085-IN005B-EN-P - September 2012
Micro800 8-Point Input and 8-Point Output AC Modules 5
1
1
45308
6
Front view
Right top view
45307
1
2085-IA8 shown
2
5
4
3
3
3
Additional Resources
ResourceDescription
Micro830 and Micro850 Programmable
Controller User Manual,
publication 2080-UM002
Micro 800 Bus Terminator Installation
Instructions, publication 2085-IN002
Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
A detailed description of how to install and use a Micro850
Programmable Controller.
Information on installing the bus terminator module.
More information on proper wiring and grounding techniques.
If you would like a manual, you can:
• download a free electronic version from the Internet:
http://www.rockwellautomation.com/literature/
• purchase a printed manual by contacting your local Allen-Bradley distributor or
Rockwell Automation representative
Overview
The Micro800™ expansion I/O is a modular I/O that complements and extends the capabilities
of Micro850™ controllers. These expansion I/O modules interface with Micro850 controllers
using an I/O expansion port.
I/O Module Overview
Publication 2085-IN005B-EN-P - September 2012
6 Micro800 8-Point Input and 8-Point Output AC Modules
45312
Mounting dimensions do not include mounting feet or DIN rail latches.
This equipment is sensitive to electrostatic discharge (ESD).
Follow ESD prevention guidelines when handling this equipment.
Mount the Module
For more information on proper grounding guidelines, see the Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1.
Module Spacing
Maintain spacing from objects such as enclosure walls, wireways and adjacent equipment. Allow
50.8 mm (2 in.) of space on all sides for adequate ventilation, as shown.
Mounting Dimensions and DIN Rail Mounting
Publication 2085-IN005B-EN-P - September 2012
Micro800 8-Point Input and 8-Point Output AC Modules 7
TIP
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm x 1 mm
(EN 50 022 - 35 x 7.5)
For environments with greater vibration and shock concerns, use the panel mounting
method, instead of DIN rail mounting.
Before mounting the module on a DIN rail, use a flat-blade screwdriver in the DIN rail latch and
pry it downwards until it is in the unlatched position.
1. Hook the top of the DIN rail mounting area of the module onto the DIN rail, and then
press the bottom until the module snaps onto the DIN rail.
2. Push the DIN rail latch back into the latched position.
Use DIN rail end anchors (Allen-Bradley part number 1492-EAJ35 or 1492-EAHJ35)
for vibration or shock environments.
.
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated
yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials
(for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result
in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every
200 mm (7.8 in.) and use end-anchors appropriately.
To remove your module from the DIN rail, pry the DIN rail latch downwards until it is in the
unlatched position.
Panel Mounting
The preferred mounting method is to use two M4 (#8) per module. Hole spacing tolerance:
±0.4 mm (0.016 in.). For mounting dimensions, refer to Micro830 and Micro850
Programmable Controller User Manual, publication 2080-UM002
Follow these steps to install your module using mounting screws.
1. Place the module next to the controller against the panel where you are mounting it.
Make sure the controller and module are spaced properly.
2. Mark drilling holes through the mounting screw holes and mounting feet then remove
the module.
3. Drill the holes at the markings, then replace the module and mount it.
Leave the protective debris strip in place until you are finished wiring the module and
any other devices.
Publication 2085-IN005B-EN-P - September 2012
.
8 Micro800 8-Point Input and 8-Point Output AC Modules
System Assembly
The Micro800 expansion I/O module is attached to the controller or another I/O module by
means of interconnecting latches and hooks, as well as the bus connector. The Micro850
controller and expansion I/O modules must terminate with a 2085-ECR Bus
Terminator module.
Be sure to lock the module interconnect latches and tighten the RTB hold down screws before
applying power to the module.
For installation of the 2085-ECR module, refer to Micro800 Bus Terminator Module
Installation Instructions, publication 2085-IN002
ATTENTION: Failure to connect a bus terminator module to the last expansion I/O module will
result in a controller hard fault.
.
Field Wiring Connections
In solid-state control systems, grounding and wire routing helps limit the effects of noise due to
electromagnetic interference (EMI).
ATTENTION: Do not wire more than 2 conductors on any single terminal.
Wire the Modules
Included with your module is a single 12-pin Removable Terminal Block (RTB). Basic wiring of
the module is shown below.
Publication 2085-IN005B-EN-P - September 2012
Micro800 8-Point Input and 8-Point Output AC Modules 9
L1
L2
I-00
I-01
COM
I-02
I-03
COM
I-04
I-05
COM
COM
I-06
I-07
120V AC (2085-IA8)
240V AC (2085-IM8)
45313
O-00
O-01
L1
O-02
O-03
L1
O-04
O-05
L1
L1
O-06
O-07
L1
L2
120V / 240V AC
45314
2085-IA8 or 2085-IM82085-OA8
Basic Wiring to the 2085-IA8, 2085-IM8, 2085-OA8 Modules
Specifications
General Specifications
Attribute2085-IA82085-IM82085-OA8
Number of I/O8
Dimensions
HxWxD
Shipping weight, approx.140 g (4.93 oz)
Bus current draw, max5V DC, 150 mA5V DC, 180 mA
Wire size0.25... 2.5 mm
Insulation stripping length10 mm (0.39 in.)pdf
Wiring category
(1)
Wire typeCopper
Terminal screw torque, max0.5…0.6 Nm
Input/output circuit type120V AC input240V AC input120V/240V AC output
Power supply120V AC240V AC120V/240V AC
Power dissipation, total2.36 W2.34 W5.19 W
Enclosure type ratingNone (open-style)
28 x 90 x 87 mm
(1.10 x 3.54 x 3.42 in.)
2
greater, 1.2 mm (3/64 in.) insulation max
(22...14 AWG) solid or stranded copper wire rated at 75 °C (167 °F ), or
2 – on signal ports
(4.4…5.3 lb-in.)
(2)
Publication 2085-IN005B-EN-P - September 2012
10 Micro800 8-Point Input and 8-Point Output AC Modules
General Specifications
Attribute2085-IA82085-IM82085-OA8
Status indicators8 yellow indicators
Isolation voltage150V (continuous), Reinforced
North American temp codeT4
(1)
Use this Conductor Category information f or planning conductor routing. Refer to Industrial Automation Wirin g and Grounding Guidelines,
publication 1770-4.1.
(2)
RTB hold down screws should be tightened by ha nd. They should not be tightened using a power tool.
Insulation Type, channel to
system
Type tested at 1950V DC for 60 s
240V (continuous), Reinforced Insulation Type, channel
to system
Type tested at 3250V DC for 60 s
Input Specifications – 2005-IA8 and 2085-IM8
Attribute2085-IA82085-IM8
Number of Inputs8
Voltage category120V AC240V AC
Operating voltage range74…120V AC159…240V AC
Off-state voltage, max20V AC40V AC
Off-state current, max2.5 mA
On-state current, min5.0 mA @ 74V AC4.0 mA @ 159V AC
On-state current, max12.5 mA @ 120V AC7.0 mA @ 240V AC
Input impedance, max22.2 kΩ
Inrush current, max450 mA
Input filter time
Off to On
On to Off
IEC type complianceType 3
≤ 20 ms
Output Specifications - 2085-OA8
AttributeValue
Number of Outputs8
Voltage category120V/230V AC
Operating voltage range120…240V AC
Output voltage, min85V AC
Output voltage, max240V AC
Off-state current, max2.5 mA
On-state current, min10 mA per output
On-state current, max0.5 A per output
On-state current,
per module, max
4 A
Publication 2085-IN005B-EN-P - September 2012
Micro800 8-Point Input and 8-Point Output AC Modules 11
Output Specifications - 2085-OA8
AttributeValue
Off-state voltage drop, max1.5V AC @ 0.5 A
FusingNot protected. A suitable rating fuse is recommended to protect outputs.
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
±2 kV at 5 kHz on signal ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Publication 2085-IN005B-EN-P - September 2012
Certifications
Certification (when product
(1)
is marked)
Valu e
c-UL-usUL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and
Canada. See UL File E334470
CEEuropean Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
KCKorean Registration of Broadcasting and Communications Equipment, compliant with:
(1)
See the Product Certification link athttp://www.rockwellautomation.com/p roducts/certification/ for Declaration of Conformity, Certificates, and
other certification details.
AS/NZS CISPR 11; Industrial Emissions
Article 58-2 of Radio Waves Act, Clause 3
Allen-Bradley, Rockwell Automation, Micro800, Micro850 and TechConnect are trademarks of Rockwell Automation, Inc..
Trademarks not belonging to Rockwell Automation are property of their respe ctive companies.
Publication 2085-IN005B-EN-P - September 2012PN-101625