Rockwell Automation 2085-IRT4 User Manual

Page 1
Installation Instructions
Micro800 4-channel Thermocouple/RTD Input Module
Catalog Number 2085-IRT4
http://www.rockwellautomation.com/literature/
Cette publication est disponible en français sous forme électronique (fichier PDF). Pour la
FR
Questa pubblicazione è disponibile in Italiano in formato PDF. Per scaricarla collegarsi al sito
IT
Web indicato sopra.
Diese Publikation ist als PDF auf Deutsch verfügbar. Gehen Sie auf die oben genannte
DE
Web-Adresse, um nach der Publikation zu suchen und sie herunterzuladen. Esta publicación está disponible en español como PDF. Diríjase a la dirección web indicada
ES
arriba para buscar y descarga esta publicación.
Esta publicação está disponível em portugués como PDF. Vá ao endereço web que aparece
PT
acima para encontrar e fazer download da publicação.
CS
CT
KR
Table of Contents
Topic Page
Important User Information 2
Additional Resources 5
Overview 5
Module Description 6
Mount the Module 6
Wire the Outputs 9
Specifications 9
Page 2
2 Micro800 4-channel Thermocouple/RTD Input Module

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 Automation sales office or online at http://www.rockwellautomation.com/literature/ between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
available from your local Rockwell
) describes some important differences
Publication 2085-IN007A-EN-P - September 2012
Page 3
Micro800 4-channel Thermocouple/RTD Input Module 3
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 additional installation requirements.
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
, for
Preventing Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Publication 2085-IN007A-EN-P - September 2012
Page 4
4 Micro800 4-channel Thermocouple/RTD Input Module

North American Hazardous Location Approval

The following modules are North American Hazardous Location approved: 2085-IRT4
The following information applies when operating this equipment in hazardous locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING: EXPLOSION HAZARD
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
WARNING: RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non dangereux avant de changer les piles.
WARNING: When you connect or disconnect the Removable Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
WARNING: If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING: Do not connect directly to line voltage. Line voltage must be supplied by a suitable, approved isolating transformer or power supply having short circuit capacity not exceeding 100 VA maximum or equivalent.
WARNING: If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed before proceeding.
WARNING: Do not unscrew the RTB hold down screws and remove the RTB while power is on. This could cause an explosion in hazardous location installations. Be sure that power is removed before proceeding.
Publication 2085-IN007A-EN-P - September 2012
Page 5
Micro800 4-channel Thermocouple/RTD Input Module 5
4532445323
1
1
7
Front view
Right top view
1
2
6
5
4
4
4
3
3

Additional Resources

Resource Description
Micro830 and Micro850 Programmable Controller User Manual, publication 2080-UM002
Micro 800 Bus Terminator Installation Instructions, publication 2085-IN002
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
A detailed description of how to install and use a Micro850 Programmable Controller.
Information on installing the bus terminator module.
More information on proper wiring and grounding techniques.
If you would like a manual, you can:
• download a free electronic version from the Internet:
http://www.rockwellautomation.com/literature/
.
• purchase a printed manual by contacting your local Allen-Bradley distributor or Rockwell Automation representative

Overview

The Micro800™ expansion I/O is a modular I/O that complements and extends the capabilities of Micro850™ controllers. These expansion I/O modules interface with Micro850 controllers using an I/O expansion port.
I/O Module Overview
Publication 2085-IN007A-EN-P - September 2012
Page 6
6 Micro800 4-channel Thermocouple/RTD Input Module
Module Description
Description Description
1 Mounting screw hole / mounting foot 5 Module interconnect latch
2 Removable Terminal Block (RTB) 6 DIN rail mounting latch
3 Thermistor 7 I/O status LED
4 RTB hold down screws
This equipment is sensitive to electrostatic discharge (ESD). Follow ESD prevention guidelines when handling this equipment.
ATTENTION: To comply with UL restrictions, this equipment must be powered from a source compliant with the following:
Class 2 or Limited Voltage/Current. ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connected I/O must be
powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

Mount the Module

For more information on proper grounding guidelines, see the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Module Spacing
Maintain spacing from objects such as enclosure walls, wireways and adjacent equipment. Allow
50.8 mm (2 in.) of space on all sides for adequate ventilation, as shown.
Publication 2085-IN007A-EN-P - September 2012
Page 7
Micro800 4-channel Thermocouple/RTD Input Module 7
TIP
45325
Mounting dimensions do not include mounting feet or DIN rail latches.
90 mm (3.54 in.)
150 mm (5.91 in.)
Micro850 Controller
Bus terminator
2085-IRT4
44.5 mm (1.75 in.)
87 mm (3.42 in.)
Mounting Dimensions and DIN Rail Mounting
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm x 1 mm (EN 50 022 - 35 x 7.5)
For environments with greater vibration and shock concerns, use the panel mounting method, instead of DIN rail mounting.
.
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
Before mounting the module on a DIN rail, use a flat-blade screwdriver in the DIN rail latch and pry it downwards until it is in the unlatched position.
1. Hook the top of the DIN rail mounting area of the module onto the DIN rail, and then press the bottom until the module snaps onto the DIN rail.
2. Push the DIN rail latch back into the latched position. Use DIN rail end anchors (Allen-Bradley part number 1492-EAJ35 or 1492-EAHJ35) for vibration or shock environments.
To remove your module from the DIN rail, pry the DIN rail latch downwards until it is in the unlatched position.
Publication 2085-IN007A-EN-P - September 2012
Page 8
8 Micro800 4-channel Thermocouple/RTD Input Module
Panel Mounting
The preferred mounting method is to use two M4 (#8) per module. Hole spacing tolerance: ±0.4 mm (0.016 in.). For mounting dimensions, refer to Micro830 and Micro850 Programmable Controller User Manual, publication 2080-UM002
Follow these steps to install your module using mounting screws.
1. Place the module next to the controller against the panel where you are mounting it. Make sure the controller and module are spaced properly.
2. Mark drilling holes through the mounting screw holes and mounting feet then remove the module.
3. Drill the holes at the markings, then replace the module and mount it. Leave the protective debris strip in place until you are finished wiring the module and any other devices.
.
System Assembly
The Micro800 expansion I/O module is attached to the controller or another I/O module by means of interconnecting latches and hooks, as well as the bus connector. The Micro850 controller and expansion I/O modules must terminate with a 2085-ECR Bus Terminator module.
Be sure to lock the module interconnect latches and tighten the RTB hold down screws before applying power to the module.
For installation of the 2085-ECR module, refer to Micro800 Bus Terminator Module Installation Instructions, publication 2085-IN002
ATTENTION: Failure to connect a bus terminator module to the last expansion I/O module will result in a controller hard fault.
.

Field Wiring Connections

In solid-state control systems, grounding and wire routing helps limit the effects of noise due to electromagnetic interference (EMI).
ATTENTION: Do not wire more than 2 conductors on any single terminal.
Publication 2085-IN007A-EN-P - September 2012
Page 9
Micro800 4-channel Thermocouple/RTD Input Module 9
TIP
CH0+
CH0H
CH0L
CH0-
CH1+
CH1H
CH1L
CH1-
NC
NC
NC
NC
CH2+
1
2
1
2a
1a
2
CH2H
CH2L
CH2-
CH3+
CH3H
CH3L
CH3-
CJC+
CJC+
TH
CJC-
TH
CJC-
NC
Shielded cable
Shielded cable
1
2
1
2
1a
Shielded cable
2-wire RTD
4-wire RTD
3-wire RTD
Thermocouple
Shielded cable
mV
OR
45326
If a thermocouple is used, the use of the supplied CJC assembly is compulsory.
Terminal Block 1 Terminal Block 2

Wire the Outputs

Included with your module are two 12-pin Removable Terminal Blocks (RTB). Basic wiring of the module is shown below.
Basic Wiring to the 2085-IRT4 Module
The module currently ships with the CJC assembly fixed to the module.

Specifications

General Specifications
Attribute Value
Number of I/O 4
Dimensions HxWxD
Shipping weight, approx. 220 g (7.76 oz)
Bus current draw, max 5V DC, 160 mA
Wire size 0.25... 2.5 mm
Wiring category
Terminal screw torque 0.5…0.6 Nm
(1)
44.5 x 90 x 87 mm (1.75 x 3.54 x 3.42 in.)
24V DC, 50 mA
greater, 1.2 mm (3/64 in.) insulation max
2 – on signal ports
(4.4…5.3 lb-in.)
2
(22...14 AWG) solid or stranded copper wire rated at 75 °C (167 °F ), or
(2)
Publication 2085-IN007A-EN-P - September 2012
Page 10
10 Micro800 4-channel Thermocouple/RTD Input Module
General Specifications
Attribute Value
Input type Thermocouple type: B, C, E, J, K, TXK/XK (L), N, R, S, T
Resolution 16 bits
Channel update time, typical 12…500 ms per enabled channel Input impedance > 10 M Ω
Power dissipation, total 2 W
Enclosure type rating None (open-style)
Status indicators 1 health status indicators
Isolation voltage 50V (continuous), Reinforced Insulation Type, channel to system.
North American temp code T4
(1)
Use this Conductor Category information f or planning conductor routing. Refer to Industrial Automation Wirin g and Grounding Guidelines, publication 1770-4.1.
(2)
RTB hold down screws should be tightened by ha nd. They should not be tightened using a power tool.
RTD type: 100 Ω Pt α = 0.00385 Euro 200 Ω Pt α = 0.00385 Euro 100 Ω Pt α = 0.003916 U.S 200 Ω Pt α = 0.003916 U.S. 100 Ω Nickel 618 200 Ω Nickel 618 120 Ω Nickel 672 10 Ω Copper 427 mV range: 0…100 mV Ohm input: 0…500 Ω
Type tested at 720V DC for 60 s
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
Temperature, surrounding air, max 65 °C (149 °F)
Temperature, non-operating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
Vibration IEC 60068-2-6 (Test Fc, Operating):
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Shock, non-operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
5…95% non-condensing
2 g @ 10…500 Hz
25 g
25 g – DIN rail mount 35 g – Panel mount
Publication 2085-IN007A-EN-P - September 2012
Page 11
Micro800 4-channel Thermocouple/RTD Input Module 11
Environmental Specifications
Attribute Value
Emissions CISPR 11
ESD immunity IEC 61000-4-2:
Radiated RF immunity IEC 61000-4-3:
EFT/B immunity IEC 61000-4-4:
Surge transient immunity IEC 61000-4-5:
Conducted RF immunity IEC 61000-4-6:
Group 1, Class A
6 kV contact discharges 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
±2 kV at 5 kHz on signal ports
±2 kV line-earth(CM) on shielded ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications
Certification (when product
(1)
is marked)
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.
CE European Union 2004/108/EC EMC Directive, compliant with:
C-Tick Australian Radiocommunications Act, compliant with:
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
(1)
See the Product Certification link athttp://www.rockwellautomation.com/p roducts/certification/ for Declaration of Conformity, Certificates, and other certification details.
Valu e
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and
Canada. See UL File E334470
EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
AS/NZS CISPR 11; Industrial Emissions
Article 58-2 of Radio Waves Act, Clause 3
Publication 2085-IN007A-EN-P - September 2012
Page 12
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/
application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/support/
, you can find technical manuals, a knowledge base of FAQs, technical and
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States or Canada 1.440.646.3434 Outside United States or
Canada
Use the Worldwide Locator
http://www.rockwellautomation.com/support/americas/phone_en.html
Rockwell Automation representative.
at
, or contact your local
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
number above to obtain one) to your distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
, available at http://www.rockwellautomation.com/literature/.
Allen-Bradley, Rockwell Automation, Micro800 , and TechConnect are trademarks of R ockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 2085-IN007A-EN-P - September 2012 PN-101627
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.
Loading...