Rockwell Automation 1794-FLA User Manual

Installation Instructions
FlexLogix Controller System
Catalog numbers 1794-L33, 1794-L34, 1794-FLA
Use this document as a guide for installing your FlexLogix™ controller system. This document provides installation instructions for both the FlexLogix controller (1794-L33, -L34) and the FlexLogix extended-local I/O adapter (1794-FLA). You should already be familiar with the FlexLogix system components. See the documentation references for additional information.
You must FLASH upgrade the firmware on your FlexLogix controller before you can use it. The controller ships with firmware revision 1.x but must be upgraded to match the version of RSLogix 5000 that you are using (e.g. if you are using RSLogix 5000 V11, you must upgrade your FlexLogix controller firmware to revision
11.x before using it). For more information on upgrading your controller’s firmware, see page 22.

Tools That You Need

You need the following tools to install your FlexLogix controller system.
slotted screwdriver
phillips screwdriver
mounting hardware (for mounting a DIN rail)
drill (for mounting a DIN rail)
needle-nose pliers

Obtain a User Manual

This product also has a user manual (pub. no. 1794-UM001). To view it, visit: www.theautomationbookstore.com. To purchase a manual, you can:
contact your local distributor or Rockwell Automation representative
visit www.theautomationbookstore.com and place an order
call 800.963.9548 (USA/Canada) or 001.320.725.1574 (outside USA/Canada)
Publication 1794-IN002G-EN-P - January 2004
2 FlexLogix Controller System
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
identify a hazard
avoid a hazard
recognize the consequence
Labels may be located on or inside the drive to alert people that dangerous voltage may be present.
Labels may be located on or inside the drive to alert people that surfaces may be dangerous temperatures.
Publication 1794-IN002G-EN-P - January 2004

Environment and Enclosure

FlexLogix Controller System 3
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as "open type" equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
NOTE: See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 ("Industrial Automation Wiring and Grounding Guidelines"), for additional installation requirements pertaining to this equipment.

Prevent Electrostatic Discharge

ATTENTION
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
If available, use a static-safe workstation.
When not in use, store the equipment in appropriate
static-safe packaging.
Publication 1794-IN002G-EN-P - January 2004
4 FlexLogix Controller System

European Hazardous Location Approval

European Zone 2 Certification (The following applies when the product bears the EEx Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive. The examination and test results are recorded in confidential report No. 28 682 010.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021.
IMPORTANT
When using this product, also consider the following:
This equipment is not resistant to sunlight or other sources of UV radiation.
The secondary of a current transformer shall not be open-circuited when applied in Class I, Zone 2 environments.
Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I, Zone 2 environments.
This equipment shall be used within its specified ratings defined by Allen-Bradley.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Class I, Zone 2 environments.
Publication 1794-IN002G-EN-P - January 2004
FlexLogix Controller System 5

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations:
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
Informations sur l’utilisation de cet équipement en environnements dangereux :
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation.
Publication 1794-IN002G-EN-P - January 2004
6 FlexLogix Controller System
The following information applies when operating this equipment in hazardous locations:
WARNING
EXPLOSION HAZARD
Do not disconnect
equipment unless power has been removed or the area is known to be nonhazardous.
Do not disconnect
connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of
components may impair suitability for Class I, Division
2.
If this product
contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux :
AVERTISSEMENT
RISQUE D’EXPLOSION
Couper le courant
ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement.
Couper le courant
ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de
composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
S’assurer que
l’environnement est classé non dangereux avant de changer les piles.
Publication 1794-IN002G-EN-P - January 2004
FlexLogix Controller System 7

Removal and Insertion Under Power

The FlexLogix controller, the extended-local I/O adapter, the communication daughtercards, and the I/O terminal bases cannot be removed or inserted under power..
However, you can remove and insert FLEX I/O modules while backplane power is applied and the system is operating.
WARNING
Be sure that power is removed or the area is nonhazardous before proceeding.
If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Other Considerations

ATTENTION
Also consider the following before you install your FlexLogix controller:
This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (e.g. aluminum, plastic, etc.) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.
Power connection length should be less than 10 meters.
Publication 1794-IN002G-EN-P - January 2004
8 FlexLogix Controller System

What You Need to Do

Before you can install a FlexLogix controller or extended-local adapter, you must:
Install steel, 35 x 7.55mm DIN rails (A-B part number 199-DR1; 46277-3)
where you want to place the FlexLogix system components.
The DIN rails for all FlexLogix system components, including all local and extended-local I/O modules, must be mounted on a common, conductive surface to ensure proper electromagnetic interference (EMI) performance. See 24 and 25 for approximate mounting dimensions and mounting clearances.
For more information about mounting DIN rails and splitting I/O across DIN rails, see the FLEX I/O Product Data, publication 1794-2.1
Use DIN rail locks (A-B catalog number 1492-EA35) to meet the shock and
vibrations specifications listed on 26. A pair of DIN locks comes with the controller.
Mount an appropriate power supply on an appropriate DIN rail. See the
specifications on 26.
To install a FlexLogix controller:
Step 1: Verify That You Have All the Components, see page 9.
Step 2: Install the Battery, see page 10.
Step 3: Install Communication Daughtercards (optional), see page 11
Step 4: Install the Controller, see page 12.
Step 5: Install the Extended-Local Adapter (optional), see page 15.
After you install the FlexLogix controller, you can:
Make an RS-232 Connection to the Controller, see page 18.
Select the Operating Mode of the Controller see page 21.
Monitor the Controller LEDs, see page 22.
Publication 1794-IN002G-EN-P - January 2004
FlexLogix Controller System 9

Step 1: Verify That You Have All the Components

These components ship with the FlexLogix controller:
1756-BA1 battery and label
key
one spring-clip connector plug for 24V power connection
one screw-terminal connector plug for 24V power connection
two 1492-EA35 DIN rail locks
The system components you have depend on your application. You might have:
FlexLogix System Component: Description:
communication card
1788-CNC, -CNCR for ControlNet communications 1788-CNF, -CNFR for ControlNet communications 1788-DNBO for DeviceNet communications 1788-ENBT for EtherNet/IP communications
serial cable
FlexLogix extended-local adapter
extended- local I/O cable
1756-CP3 You can also use the 1747-CP3 cable from the SLC product family.
1794-FLA
1794-CE1 (1 foot) 1794-CE3 (3 foot)
Publication 1794-IN002G-EN-P - January 2004
10 FlexLogix Controller System

Step 2: Install the Battery

ATTENTION
WARNING
Only install a 1756-BA1 battery. If you install a different battery, you may damage the controller.
For safety information on the handling of lithium batteries, in­cluding the handling and disposal of leaking batteries, see Guide- lines for Handling Lithium Batteries, publication AG-5.4. Store batteries in a cool, dry environment. We recommend 25°C with 40% to 60% relative humidity. You may store batteries for up to 30 days between -45° to 85°C, such as during transporta­tion. To avoid possible leakage, do not store batteries above 60°C for more than 30 days.
When you connect or disconnect the battery an electrical arc can occur. This could cause an explosion in hazardous location in­stallations. Be sure that power is removed or the area is nonhaz­ardous before proceeding.
For Safety information on the handling of lithium batteries, including handling and disposal of leaking batteries, see Guidelines for Handling Lithium Batteries, publication AG 5-4.
1. Install a 1756-BA1 battery.
Attach label here.
This jumper is for service use only. Do not use this jumper.
Attach battery here.
top red lead (+)
middle black lead (-)
bottom no connection
2. Attach the battery label:
a. Write on the battery label the date you install the battery. b. Attach the label to the inside of the battery compartment.
Publication 1794-IN002G-EN-P - January 2004
FlexLogix Controller System 11

Step 3: Install Communication Daughtercards (optional)

WARNING
For specific information about configuring the communication card (such as setting a node address), see the installation instructions for the communication card.
1. Turn off power to the controller.
2. If necessary, remove the blank cover from the communication slot.
3. Slide the communication card into the communication slot. Be sure to line
up the card with the card guides in the controller.
4. Record which slot you use for the communication card. You need the slot
number when you develop your controller application.
5. Secure the card with the screws to ensure proper grounding. Do not
over-tighten the screws. The maximum torque for the card screws is 4.8 to
5.2 inch pounds (0.5 to 0.6 Nm)
6. After the controller is installed (see page 12), connect the network cable.
If you insert or remove the card while host power is on, an electrical arc can occur. This could cause an explosion in haz­ardous location installations.
slot 1 slot 2
31032-M
Removing a Communication Card
If you need to remove a communication card from the controller:
1. Turn off power to the controller.
2. Disconnect all cables from the communication card.
3. Loosen the card screws from the communication card.
4. Remove the card from the controller.
5. Replace the card with a blank cover or a different communication card.
Publication 1794-IN002G-EN-P - January 2004
12 FlexLogix Controller System

Step 4: Install the Controller

1. Position the FlexLogix controller on the DIN rail at a 5° angle and rotate the
controller onto the DIN rail.
A
A
locking tabs
IMPORTANT
You can mount the FlexLogix controller either vertically or horizontally (as shown).
2. Press the controller down onto the DIN rail until flush. The locking tabs will
snap into position and lock the controller onto the DIN rail.
If the controller does not lock in place, use a screwdriver or similar device to move the locking tabs down while pressing the controller onto the DIN rail. Release the locking tabs to lock the controller in place. If necessary, push up on the locking tabs to lock.
3. Ground the controller. The DIN rail and the common, conductive surface
behind the DIN rail provide functional ground for the controller. Use the grounding stud to meet safety ground requirements.
grounding stud
nuts with captive star washer
Equipment grounding conductor (ground lug with 2.08 sq. mm [#14 AWG] wire) to ground bus
For information about wiring and grounding, see the Industrial Automation Wiring and Grounding Guidelines publication 1770-4.1.
Publication 1794-IN002G-EN-P - January 2004
FlexLogix Controller System 13
4. Make sure power is not applied to the power supply.
5. Connect the power supply to the controller. The graphic below and its
related instructions describe a 1794-PS13 power supply.
WARNING
If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is re­moved or the area is nonhazardous before proceeding.
+ _
+ _
A B C D
FE
HG
a. Connect +24V dc input to the top of the controller connector, terminal A,
to the bottom, left power connector, terminal G.
b. Connect -24V common to top controller connector, terminal B, to the top,
left power connector, terminal E.
c. Use connections C and D on the controller and connection F and H on
the power supply to pass 24V dc power and common to the next module in the series, if required.
Use the screw-terminal connector plug that comes with the controller to meet the requirements for installations in Class I, Division 2 locations.
Publication 1794-IN002G-EN-P - January 2004
14 FlexLogix Controller System
6. Mount the I/O terminal bases on the DIN rail.
A
B
A
31036-M
For information about I/O terminal bases, see the FLEX I/O Terminal Base Installation Instructions, publication 1794-IN092.
7. Install the I/O modules.
To install an I/O module, see the installation instructions for that module.
Removing the controller
If you need to remove the controller, follow these steps:
1. Turn off power to the controller.
2. Disconnect all cables from the controller.
3. Remove the I/O module that is adjacent to the controller.
4. On the terminal base adjacent to the controller, slide the FLEXBUS connector
away from the controller and remove the I/O terminal base.
5. Remove the controller from the DIN rail.
Publication 1794-IN002G-EN-P - January 2004
FlexLogix Controller System 15

Step 5: Install the Extended-Local Adapter (optional)

1. Position the 1794-FLA extended-local I/O adapter on the DIN rail at a 30°
angle and rotate the adapter onto the DIN rail.
2. Press the adapter down onto the DIN rail until flush. The locking tab will
snap into position and lock the adapter onto the DIN rail.
If the adapter does not lock in place, use a screwdriver or similar device to move the locking tab down while pressing the adapter onto the DIN rail. Release the locking tab to lock the adapter in place. If necessary, push up on the locking tab to lock.
3. Ground the adapter. The adapter is grounded through the steel DIN rail and
the common, conductive surface behind the DIN rail. Additionally, use the grounding stud.
grounding stud
nuts with captive star washer
Equipment grounding conductor (ground lug with
2.08 sq. mm [#14 AWG] wire) to ground bus
Publication 1794-IN002G-EN-P - January 2004
16 FlexLogix Controller System
4. Make sure power is not applied to the power supply. Connect the
power supply to the adapter. This diagram and its related instructions describe a 1794-PS13 power supply.
a. Connect +24V dc input to the left adapter connector, terminal A, to the
bottom, left power connector, terminal G.
b. Connect -24V common to left adapter connector, terminal B, to the top,
left power connector, terminal E.
c. Use connections C and D on the adapter and connection F and H on the
power supply to pass 24V dc power and common to the next module in the series, if required.
Use the screw-terminal connector plug that comes with the adapter to meet the requirements for installations in Class I, Division 2 locations.
5. Connect I/O terminal bases and I/O modules to the adapter the same way
you connect them to the controller.
6. Remove the plastic spacer from both ends of the extended-local I/O cable
(1794-CE1 or 1794-CE3).
plastic spacer
Publication 1794-IN002G-EN-P - January 2004
7. Connect the adapter to the controller.
FlexLogix Controller System 17
1794-CE1 or 1794-CE3 cable
LOCAL2 rail
31039-M
The following diagram shows how you can also use the 1794-CE1, -CE3 cable to split a rail of I/O. You can split each rail only once. You can split a rail right after the controller (or adapter) or after any I/O module. For more information about the 1794-CE1, -CE3 cables, see the Interconnect Cable Installation Instructions, publication 1794-5.12.
1794-CE1 or 1794-CE3 cable
LOCAL rail
1794-CE1 or 1794-CE3 cable
1794-CE1 or 1794-CE3 cable
Removing the extended-local adapter
If you need to remove the adapter, follow these steps:
1. Turn off power to the adapter.
2. Disconnect all cables from the adapter.
3. Remove the I/O module that is adjacent to the adapter.
4. On the terminal base adjacent to the adapter, slide the FLEXBUS connector
away from the adapter and remove the I/O terminal base.
5. Remove the adapter from the DIN rail.
Publication 1794-IN002G-EN-P - January 2004
18 FlexLogix Controller System

Make an RS-232 Connection to the Controller

The RS-232 port is a non-isolated serial port built-in to the front of the controller.
serial port
To connect to the serial port:
1. Determine whether you need an optical isolator.
If you connect the controller to a device outside of the system’s enclosure, consider installing an isolator between the controller and device.
One possible isolator is the 1761-NET-AIC interface converter.
baud rate selector switch
port 1: DB-9 RS-232, DTE
Publication 1794-IN002G-EN-P - January 2004
port 2: mini-DIN 8 RS-232
dc power source selector switch
terminals for external 24V dc power supply
2. Select the appropriate cable.
5
8
Are you using an isolator?
no The 1756-CP3 cable attaches the controller directly to the controller.
Use this cable:
FlexLogix Controller System 19
1 CD
2 RDX
3 TXD
4 DTR
COMMON
6 DSR
7 RTS
8 CTS
9
1 CD
2 RDX
3 TXD
4 DTR
COMMON
6 DSR
7 RTS
8 CTS
9
If you make your own cable, it must be shielded and the shields must be tied to the metal shell (that surrounds the pins) on both ends of the cable. You can also use a 1747-CP3 cable (from the SLC product family). This cable has a taller right-angle connector housing than the 1756-CP3 cable.
yes The 1761-CBL-AP00 cable (right-angle connector to controller) or the 1761-CBL-PM02 cable
(straight connector to the controller) attaches the controller to port 2 on the 1761-NET-AIC isolator. The mini-DIN connector is not commercially available, so you cannot make this cable.
6
7
9
1
2
3
4
5
678
3
4
12
DB-9 right-angle or straight cable end 8-pin, mini-DIN cable end
Pin: DB-9 end: Mini-DIN end:
1DCD DCD
2RxD RxD
3TxD TxD
4DTR DTR
5 ground ground
6DSR DSR
7RTS RTS
8CTS CTS
9na na
Publication 1794-IN002G-EN-P - January 2004
20 FlexLogix Controller System
3. Connect the appropriate cable to the serial port on the controller.
WARNING
Be sure that power is removed or the area is nonhazardous before proceeding.
4. If necessary, attach the controller to the isolator.
If you connect or disconnect the serial cable with power applied to this module or the serial device on the other end of the cable, an electrical arc can occur. This could cause an explosion in hazardous location installations.
system enclosure
1761 cable 1761-NET-AIC isolator
user-supplied modem cable
Publication 1794-IN002G-EN-P - January 2004
modem
FlexLogix Controller System 21

Select the Operating Mode of the Controller

1. Use this table to determine the operating mode of the controller:
If you want to: Select one of these modes:
Run Program Remote
Run Program Test
turn outputs to the state commanded by the logic of the project
turn outputs to their configured state for Program mode
execute (scan) tasks YES YES YES
change the mode of the controller through software
download a project YES YES
schedule a ControlNet network YES YES
while online, edit the project YES YES YES YES
2. Turn the key on the front panel of the controller to select the mode.
YES YES
YES YES YES
YES YES YES
keyswitch
To select: Turn the key to:
Remote Run RUN and then to REM
Remote Program PROG and then to REM
Remote Test REM and then go online and select Test mode via the programming software
Publication 1794-IN002G-EN-P - January 2004
22 FlexLogix Controller System

Monitor the Controller LEDs

Indicator: Color: Description:
RUN off
green
OK off no power applied
red flashing after initially installing the controller - the controller requires a
red
green controller OK
BATTERY off battery will support memory
red
I/O off
green communicating to all devices
green flashing one or more devices are not responding
LOCAL and LOCAL2
RS232 off no activity
FORCE off no forces present
off rail is inhibited
green communicating to all devices on that rail
green flashing one or more devices on that rail not responding
red flashing no modules exist on that rail
green data being received or transmitted
amber forces present
no task(s) running
controller in Program mode
one or more tasks are running
controller is in Run mode
FLASH upgrade to the proper firmware revision; see below. after the controller is operating - recoverable fault
controller faulted
clear faults, clear memory, or replace the controller
battery may not support memory
replace battery
controller project not downloaded (the condition after power up)
no I/O or communications configured

FLASH Upgrade the Controller’s Firmware Revision

To update the firmware of a controller, first install a firmware upgrade kit.
An upgrade kit ships on a supplemental CD along with RSLogix 5000 software.
To download an upgrade kit, go to http://support.rockwellautomation.com. Choose Firmware Updates.
Publication 1794-IN002G-EN-P - January 2004

Update the Controller

FlexLogix Controller System 23
TIP
1. Connect the controller to the same network as your workstation.
2. Start ControlFLASH software.
3. Choose N
4. Select the catalog number of the controller and choose Next >.
5. Expand the network until you see the controller. If the required network is
not shown, first configure a driver for the network in RSLinx software.
6. Select the controller and choose OK.
RSLogix 5000 software, revision 10.0 or later, lets you update controller firmware as part of the download sequence. To update the controller, download your project and follow the prompts of the software.
ext >.
42900
7. Select the revision level to which you want to update the controller and choose N
IMPORTANT
8. To start the update of the controller, choose Finish and then Yes.
After the controller is updated, the status box displays Update complete.
9. Choose OK.
10. To close ControlFLASH software, choose Cancel and then Yes.
ext >.
If the Revision list is empty, download a new upgrade kit. Some older upgrade kits do not work with new controllers.
Publication 1794-IN002G-EN-P - January 2004
24 FlexLogix Controller System

FlexLogix Controller Approximate Mounting Dimensions

104.57mm (4.12in)
8.85mm (0.35in)
199.49mm (7.85in)
185.3mm (7.30in)
84.9mm (3.34in)
50.43mm (1.99in)
6.4mm (0.25in)
6.0mm (0.24in)
121.97mm (4.81in)
101.6mm (4.00in)
13.5mm (0.53in)
182.96mm (7.203in)
88.57mm (3.49in)
87.24mm (3.43in)
80.14mm (3.16in)
92.96mm (3.66in)
88.57mm (3.49in)
8.25mm (0.33in)
105.96mm (4.17in)
centerline of
64.36mm
(2.53in)
centerline of DIN rail
101.49mm (3.99in)
MTG Hole
Publication 1794-IN002G-EN-P - January 2004
FlexLogix Controller System 25

FlexLogix Extended-Local I/O Adapter Approximate Mounting Dimensions

94mm (3.7in)
117.12mm (4.61in)
88.94mm (3.5in)

Approximate Mounting Clearance

25.4 mm (1 in)
25.4 mm (1 in)
25.4 mm (1 in)
25.4 mm (1 in)
69mm
(2.72in)
81.06mm (3.19in)
25.4 mm (1 in)
25.4 mm (1 in)
25.4 mm (1 in)
Publication 1794-IN002G-EN-P - January 2004
26 FlexLogix Controller System

Other Publications

You can use the following manuals with this product:
Documents required for installation details: Publication number:
Industrial Automation Wiring and Grounding Guidelines 1770-4.1
Flex 1794-PS3 Power Supply Installation Instructions 1794-5.71
Flex 1794-PS13 Power Supply Installation Instructions 1794-5.69
Flex I/O Terminal Base Installation Instructions 1794-5.16
1794-CE1, -CE3 Interconnect Cable Installation Instructions 1794-5.12
FLEX I/O and FLEX Integra I/O Technical Data 1794-2.1
Documents available for further reference Publication number:
FlexLogix System User Manual 1794-UM001
Logix5000 Controllers Common Procedures Reference Manual 1756-PM001
Logix5000 Controllers General Instruction Set Reference Manual 1756-RM003
Guidelines for Handling Lithium Batteries AG-5.4
You can obtain manuals at www.theautomationbookstore.com.

Specifications

Category: FlexLogix controller
user memory 1794-L33 64 KBytes
input voltage
rating (nominal) range
isolation voltage (continuous-voltage withstand rating)
input current
power dissipation
backplane (FLEXBUS) current output
thermal dissipation 87BTU/hour @ 19.2V 25.6BTU/hour @ 19.2V
weight 1794-L33 .71 kg (1.56 lbs oz.)
(1)
(2)
(1794-L33, -L34)
1794-L34 512 KBytes
24V dc
19.2V to 31.2V dc (includes 5% ac ripple)
30V dc Qualification tested to withstand 850V dc for 60 seconds
1.33A maximum at 19.2V dc
0.85A maximum at 24V dc
25.5W maximum at 19.2V
20.4W maximum at 24V dc
653mA maximum @ 5.1V dc 653mA maximum @ 5.1V dc
1794-L34 .75 g (1.66 lbs.) (no communication cards installed)
FlexLogix extended-local I/O adapter (1794-FLA)
na
0.39A maximum at 19.2V dc
0.25A maximum at 24V dc
7.5W maximum at 19.2V
6.0W maximum at 24V dc
.28 kg (.62 lbs.)
Publication 1794-IN002G-EN-P - January 2004
FlexLogix Controller System 27
Category: FlexLogix controller
(1794-L33, -L34)
FlexLogix extended-local I/O adapter (1794-FLA)
power supply 1794-PS3 or 1794-PS13 – In applications that must be compliant with CSA
!
requirements, use a Separated Extra-Low Voltage (SELV) power supply that is compliant with IEC 61010.1, Annex H
power conductors 60° C (140° F) minimum, copper
#22 to #14 AWG (0.324 to 2.08 sq. mm) stranded 3/64 inch (1.2mm) insulation maximum length 10m or less
category 3
(2)
power connector torque 5 to 7 inch-pounds (0.6 to 0.8Nm)
battery 1756-BA1 (AB part number 94194801)
na
0.59g lithium
serial cable 1761-CBLPM02 to 1761-NET-AIC
na
1761-CBLPA00 to 1761-NET-AIC 1756-CP3 directly to controller 1747-CP3 directly to controller
category 3
(4)
extended local I/O cable 1794-CE1 cable (1 foot)
1794-CE3 cable (3 feet)
category 3
(2)
DIN rail steel, 35 x 7.55mm DIN rail
A-B part number 199-DR1; 46277-3; EN 50022
operating temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0 to 60°C (32 to 140°F)
storage temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock): –40 to 85°C (–40 to 185°F)
relative humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5 to 95% non-condensing
vibration
(3)
shock
(3)
operating non-operating
IEC60068-2-6 (Test Fc, Operating): 5g @ 10-500Hz
IEC60068-2-27: (Test Ea, Unpackaged shock):
30g 50g
emissions CISPR 11:
Group 1, Class A (with appropriate enclosure)
ESD immunity IEC 61000-4-2:
6kV contact discharges 8kV air discharges
Publication 1794-IN002G-EN-P - January 2004
Category: FlexLogix controller
(1794-L33, -L34)
FlexLogix extended-local I/O adapter (1794-FLA)
radiated RF immunity IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
EFT/B immunity IEC 61000-4-4:
±4kV at 2.5kHz on power ports ±2kV at 5kHz on communications ports
surge transient immunity IEC 61000-4-5:
±2kV line-earth (CM) on shielded ports
conducted RF immunity IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
enclosure type rating none (open-style)
Certifications: (when product is marked)
UL UL Listed Industrial Control Equipment c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada CSA CSA Certified Process Control Equipment CSA CSA Certified Process Control Equipment for Class I, Division 2
Group A,B,C,D Hazardous Locations
(5)
CE
European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions
(5)
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
(5)
EEx
European Union 94/9/EEC ATEX Directive, compliant with:
EN 50021; Potentially Explosive Atmospheres, Protection "n" (Zone 2)
(1)
This specification is also known as Power Consumption.
(2)
This specification is also known as Heat Dissipation.
(3)
To maintain these vibration and shock specifications, you must use DIN rail locks.
(4)
Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1, "Industrial Automation Wiring and Grounding Guidelines".
(5)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Publication 1794-IN002G-EN-P - January 2004 PN 957867-01
Supersedes Pub lication 1794-IN002F-E N-P - October 2002 Copyright © 20 04 Rockwell Automatio n, Inc. All rights reser ved. Printed in the U.S.A.
Loading...