Rockwell Automation 1794-ASBE User Manual

"!
    

  "  

Important User Information
Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Rockwell Automation be responsible or liable for indirect or consequential damage resulting from the use or application of these products.
Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen–Bradley publication SGI–1.1, Safety Guidelines for Application, Installation, and Maintenance of Solid–State Control (available from your local Rockwell Automation office), describes some important differences between solid–state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard. avoid a potential hazard, and recognize the consequences of a potential hazard.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
!
ATTENTION
Identifies information about practices or circumstances that may lead to personal injury or death, property damage, or economic loss.
!
Identifies information that is critical for
IMPORTANT
successful application and understanding of the product.
ATTENTION
!
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664–1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present, and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
ATTENTION
!
See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosures. Also, see the appropriate sections in this publication, as well as the Allen–Bradley publication 1770–4.1, (“Industrial Automation Wiring and Grounding Guidelines”), for additional installation requirements pertaining to this equipment.
FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc plated, yellow chromated steel DIN rail to assure proper grounding. Using other DIN rail material (e.g. aluminum, plastic, etc.) which can corrode, oxidize or are poor conductors can result in improper or intermittent platform grounding.

ATTENTION
!
Preventing Electrostatic Damage This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment.
Touch a grounded object to discharge potential
static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component
boards.
Do not touch components inside the equipment.
If available, use a static–safe workstation.
When not in use, keep modules in appropriate
static–safe packing.
  
  
The information below summarizes the changes to the Remote I/O Adapter User Manual, publication 1794-UM009D–EN–P, since the last release.
The series E adapter is capable of recognizing the safe state data for the FLEX Integra analog modules, and allows use of 32 point FLEX I/O modules. You must use a series D or later adapter when using FLEX Integra analog modules in your system.
New Information
The following new information is included in this version of the publication:
Corrected Switch Positions
Switch positions on S! and S2 were incorrectly identified in the previous version of this publication. Corrections have been made on page 2–11 of Chapter 2.
Additional FLEX I/O Modules
New modules available since the last version of this publication have been added.
Change Bars
The areas in this manual which are different from previous editions are marked with change bars (as shown to the right of this paragraph) to indicate the addition of new or revised information.
Publication 1794ĆUM009D-EN-P - April 2004
soc–ii Summary of Changes
Publication 1794ĆUM009D-EN-P - April 2004
T
Using This Manual
Preface
Preface Objectives
Audience
Vocabulary
Read this preface to familiarize yourself with this manual and to learn how to use it properly and efficiently.
Important:
You must use a series D or later adapter to
IMPORTAN
We assume that you have previously used an Allen–Bradley programmable controller, that you are familiar with its features, and that you are familiar with the terminology we use. If not, read the user manual for your processor before reading this manual.
In this manual, we refer to:
communicate with FLEX Integra analog modules. You must use a series E or later adapter to communicate with 32 point FLEX modules.
the individual adapter module as the “adapter.”
the programmable controller as the “controller” or the
“processor.”
input and output modules as the “module.”
What This Manual Contains
The contents of this manual are as follows:
Table P. A What This Manual Contains
Chapter Title What's Covered
1
2 Installing Your Remote I/O Adapter Procedures and guidelines for installing the module
3 Communicating with FLEX I/O Modules Hardware addressing and configuration options
4 Troubleshooting Troubleshooting aids
Appendix Title What's Covered
A Specifications Module specifications
B
C Safety Approvals
Overview of FLEX I/O and the Remote I/O Adapter Module
Differences Between Series A, B, C, D and E Remote I/O Adapters
Describes features, capabilities, and hardware components.
Publication 1794ĆUM009D-EN-P - April 2004
Using This ManualP–2
Catalog
Conventions
For Additional Information
1794ĆACNR 24V dc Redundant Media ControlNet Adapter
1794ĆACN15 24V dc ControlNet Adapter
1794ĆACNR15 24V dc Redundant Media ControlNet Adapter
1794ĆASB/E 24V dc Remote I/O Adapter 1794ĆIN046 1794ĆUM009
1794ĆASB2/D 24V dc 2ĆSlot Remote I/O Adapter 1794ĆIN044 1794ĆUM059
1794ĆOB16P 24V dc 16 Source Output Module
1794ĆOB32P 24V dc 32 Electronically Fused Output Module
1794ĆOB8EP 24V dc 8 Electronically Fused Output Module
1794ĆOV16P 24V dc 16 Electronically Fused Output Module
1794ĆIB10XOB6 24V dc 10 Input/6 Output Module
1794ĆIB16XOB16P 24V dc 16 Input/16 Output Module
We use these conventions in this manual:
In this manual, we show: Like this:
that there is more information about a topic in another chapter in this manual
that there is more information about the topic in another manual
More
For additional information on FLEX I/O systems and modules, refer to the following documents:
Publications
Number
1794 1794 FLEX I/O Product Data
1794ĆACN 24V dc ControlNet Adapter
1794ĆADN 24V dc DeviceNet Adapter 1794Ć5.14 1794Ć6.5.5
1794ĆAPB 24V dc Profibus Adapter 1794ĆIN040 1794ĆUM057
1794ĆIB8 24V dc 8 Sink Input Module
1794ĆOB8 24V dc 8 Source Output Module
1794ĆIB16 24V dc 16 Sink Input Module
1794ĆIB32 24V dc 16 Source Output Module
1794ĆOB16 24V dc 16 Source Output Module
1794ĆIV16 24V dc 16 Source Input Module
1794ĆOV16 24V dc 16 Sink Output Module
1794ĆIB8S 24V dc Sensor Input Module
Voltage Description
Table continued on next page
Installation
Instructions
1794Ć2.1
1794Ć5.8
1794Ć5.18
1794Ć5.47
1794Ć5.48
1794Ć5.30
1794Ć5.31
1794ĆIN072
1794ĆIN084
1794Ć5.3
1794Ć5.45
1794ĆIN090
1794Ć5.28
1794Ć5.29
1794Ć5.20
1794Ć5.52
1794Ć5.7
1794Ć5.24
1794ĆIN083
User
Manual
Publication 1794ĆUM009D-EN-P - April 2004
Using This Manual P–3
Catalog
Catalog Number
Number
DescriptionVoltage
DescriptionVoltage
Publications
Installation
Instructions
User
Manual
1794ĆOW8 24V dc 8 Relay Output Module 1794Ć5.19
1794ĆIE8 24V dc Selectable Analog 8 Input Module
1794ĆOE4 24V dc Selectable Analog 4 Output Module
1794ĆIE4XOE2 24V dc 4 Input/2 Output Analog Module
1794ĆOF4I 24V dc 4 Output Isolated Analog Module
1794ĆIF4I 24V dc 4 Input Isolated Analog Module
1794ĆIF2XOF2I 24V dc 2 Input/2 Output Isolated Analog Module
1794Ć5.6
1794Ć5.5
1794Ć5.15
1794Ć5.37
1794Ć5.38
1794Ć5.39
1794Ć6.5.2
1794Ć6.5.8
1794ĆIR8 24V dc 8 RTD Input Analog Module 1794Ć5.22 1794Ć6.5.4
1794ĆIT8 24V dc 8 Thermocouple Input Module 1794Ć5.21 1794Ć6.5.7
1794ĆIRT8 24V dc 8 Thermocouple/RTD Input Module 1794Ć5.50 1794Ć6.5.12
1794ĆIJ2 24V dc 2 Frequency Input Module 1794Ć5.49 1794Ć6.5.11
1794ĆID2 24V dc 2 Channel Frequency Input Module 1794Ć5.63 1794Ć6.5.15
1794ĆIP4 24V dc 2 Channel Pulse Counter Module 1794Ć5.64 1794Ć6.5.16
1794ĆHSC 24V dc High Speed Counter Module 1794Ć5.67 1794Ć6.5.10
1794ĆIC16 48V dc 48V dc 16 Input Module
1794ĆOC16 48V dc 48V dc Output Module
1794ĆIA8 120V ac 8 Input Module
1794ĆOA8 120V ac 8 Output Module
1794ĆIA8I 120V ac Isolated 8 Input Module
1794ĆOA8I 120V ac Isolated Output Module
1794ĆIA16 120V ac 16 Input Module
1794ĆOA16 120V ac 16 Output Module
1794ĆIM8 220V
8 Input Module
ac/dc
1794ĆOM8 220V
8 Output Module
ac/dc
1794ĆTB2 1794ĆTB3
2Ćwire Terminal Base 3Ćwire Terminal Base
1794ĆTBN Terminal Base Unit
1794ĆTBNF Fused Terminal Base Unit
1794ĆTB3T Temperature Terminal Base Unit
1794ĆTB3S Spring Clamp Terminal Base Unit
1794ĆTB3TS Spring Clamp Temperature Base Unit
1794ĆTB3G Terminal Base Unit
1794ĆTB3GS Spring Clamp Terminal Base Unit
1794ĆTB32 Cage Clamp Terminal Base Unit
1794ĆTB32S Spring Clamp Terminal Base Unit
1794Ć5.53
1794Ć5.54
1794Ć5.9
1794Ć5.10
1794Ć5.55
1794Ć5.56
1794Ć5.60
1794Ć5.61
1794Ć5.57
1794Ć5.58
1794ĆIN070
1794ĆIN016
1794Ć5.17
1794Ć5.41
1794Ć5.42
1794Ć5.43
1794Ć5.51
1794Ć5.59
1794ĆIN085
1794ĆIN085
Table continued on next page
Publication 1794ĆUM009D-EN-P - April 2004
Using This ManualP–4
Catalog
Catalog Number
Number
1794ĆCE1, ĆCE3 Extender Cables
1794ĆNM1 Mounting Kit
1794ĆPS13 24V dc Power Supply
1794ĆPS3 24V dc Power Supply
1797ĆIBN16 See note 16 NAMUR Digital Input Module 1794ĆIN072
1797ĆOB4D See note 4 NI, Ex Source Digital Output Module 1794Ć5.6
1797ĆIE8 See note 8 Selectable Input Module 1794Ć5.5
1797ĆIE8NF See note 8 Selectable Filter Analog Input Module 1794Ć5.31
1797ĆOE4 See note Selectable Analog 4 Output Module 1794Ć5.3
1797ĆIRT8 See note 8 Thermocouple/RTD Input Module 1794Ć5.4
1797ĆIJ2 See note 2 Frequency Input Module 1794Ć5.9
1797ĆTB3
1797ĆTB3S
1797ĆBIC See note I.S. Bus Isolator 1797Ć5.13
1797ĆCEC See note FLEX Ex Bus Connector 1797Ć5.13
Note: Intrinsically Safe Voltage
3Ćwire Screw Clamp Terminal Base 3Ćwire Spring Clamp Terminal Base
DescriptionVoltage
DescriptionVoltage
FLEX Ex
Installation
Instructions
1794Ć5.12
1794Ć5.13
1794Ć5.35
1794Ć5.71
1797Ć5.1 1797Ć5.2
Publications
User
Manual
ATTENTION
!
FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc plated, yellow chromated steel DIN rail to assure proper grounding. Using other DIN rail materials (e.g. aluminum, plastic, etc.) which can corrode, oxidize or are poor conductors can result in improper or intermittent platform grounding.
Publication 1794ĆUM009D-EN-P - April 2004
Using This Manual P–5
ATTENTION
!
WARNING
!
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential
static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component
boards.
Do not touch circuit components inside the
equipment.
If available, use a static–safe workstation.
When not in use, keep modules in appropriate
static–safe packaging.
Remove field-side power before removing or inserting this module. This module is designed so you can remove and insert it under backplane power. When you remove or insert a module with field-side power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
sending an erroneous signal to your system’s
field devices causing unintended machine motion
causing an explosion in a hazardous environment
Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
Publication 1794ĆUM009D-EN-P - April 2004
Using This ManualP–6

This preface gave you information on how to use this manual efficiently. The next chapter introduces you to the remote I/O adapter module.
Publication 1794ĆUM009D-EN-P - April 2004
Table of Contents
Overview of FLEX I/O and your Remote I/O Adapter Module
Installing Your Remote I/O Adapter Module
Chapter 1
Chapter Objectives 1-1...................................
The FLEX I/O System 1-1.................................
How FLEX I/O Modules Communicate with Programmable Controllers 1-2
Hardware Components 1-3................................
Diagnostic Indicators 1-3................................
Reset Pushbutton 1-4..................................
Remote I/O Wiring 1-4..................................
Power Wiring 1-4......................................
Address Switch Assemblies 1-4...........................
Chapter Summary 1-4....................................
Chapter 2
Chapter Objectives 2-1...................................
Power Requirements 2-3..................................
Mounting the Remote I/O Adapter 2-3.........................
Mounting on a DIN Rail before installing the terminal base units 2-3..
Mounting (or Replacing) the Adapter on an Existing System 2-4....
Mounting on a Wall or Panel 2-5...........................
Wiring 2-7.............................................
Setting the Switches 2-8..................................
Starting I/O Group 2-8..................................
I/O Rack Number 2-8...................................
Hold Inputs 2-8.......................................
Rack Fault Select Switch (RFS) 2-9........................
Addressing Mode Selection Switches 2-9....................
Communication Rate 2-10................................
Processor Restart Lockout (PRL) 2-10.......................
Hold Last State (HLS) 2-10...............................
Setting the Mode Selection Switches 2-12.......................
Setting the Address Switches 2-13............................
Setting the Address Switches for Complementary I/O 2-15...........
Primary Rack 2-15.....................................
Complementary Rack 2-15................................
Chapter Summary 2-15....................................
Communicating with FLEX I/O Modules
Chapter 3
Chapter Objectives 3-1...................................
FLEX I/O Module Data 3-1.................................
Addressing I/O 3-2......................................
Analog (Block Transfer) Modules 3-5.........................
Publication 1794ĆUM009D-EN-P - April 2004
Table of Contentsii
Standard Addressing 3-6..................................
Standard - 32 Addressing 3-7..............................
Compact Addressing 3-8..................................
Compact Mode 3-8....................................
Complementary Addressing Mode 3-12........................
Complementary Mode - 16Ćpoint 3-12.......................
Complementary Mode - 8Ćpoint 3-13........................
Complementary - 32 Addressing 3-15.........................
Mapping Data into the Image Tables 3-16.......................
Determining Rack Size 3-16.................................
Operating Modes 3-18.....................................
Chapter Summary 3-18....................................
Troubleshooting
Specifications
Differences Between Remote I/O Adapter Series A, B, C, D and E
Safety Approvals
Chapter 4
Chapter Objectives 4-1...................................
Fault Conditions 4-1.....................................
Troubleshooting with the Indicator Lights 4-1....................
Chapter Summary 4-3....................................
Appendix A
Specifications A-1.......................................
Appendix B
Differences Between Remote I/O Adapter Series A, B, C, D and E B-1..
Appendix C
Safety Approvals C-1.....................................
Publication 1794ĆUM009D-EN-P - April 2004

Overview of FLEX I/O and your Remote I/O Adapter Module
Chapter Objectives
The FLEX I/O System
Adapter
In this chapter, we tell you about:
what the FLEX I/O system is and what it contains
how FLEX I/O modules communicate with programmable
controllers
the features of your adapter module
FLEX I/O is a small, modular I/O system for distributed applications that performs all of the functions of rack-based I/O. The FLEX I/O system contains the following components shown below:
Terminal Base
I/O Module
20125
adapter/power supply – powers the internal logic for as many as
eight I/O modules
terminal base – contains a terminal strip to terminate wiring for
two- or three-wire devices
I/O module – contains the bus interface and circuitry needed to
perform specific functions related to your application
Publication 1794ĆUM009D-EN-P - April 2004
1–2 Overview of FLEX I/O and your Remote I/O Adapter Module
How FLEX I/O Modules Communicate with Programmable Controllers
The adapter transfers your configuration data

PWR
ADAPTER
ACTIVE FAULT
LOCAL FAULT
POWER SUPPLY
RIO ADAPTER
1794ĆASB
24VDC
Your ladder program instructs the
adapter to perform a BTR of the values
and stores them in a data table.
Data transfer to and from the remote I/O adapter/power supply and discrete I/O modules occurs every flexbus scan. This provides the controller with updated data.
The remote I/O adapter/power supply transfers data to the analog I/O module (block transfer write) and from the analog I/O module (block transfer read) using BTW and BTR instructions in your ladder diagram program. These instructions let the adapter obtain input values and status from the I/O module, and let you send output values to establish the module’s mode of operation. The communication process is described in the following illustration.
1
to the module using a BTW.
Flexbus
4

INPUT 0 INPUT 2 INPUT 4 INPUT 6INPUT 1 INPUT 3 INPUT 5 INPUT 7 IVIVIVIVIVIVIVI
ANALOG INPUT
2
External devices transmit
analog signals to the module.
1794-IE8
2
V
5
The adapter and module determine
that the transfer was made without error
and input values are within specified
range.
6
Your ladder program can use and/or move the data (if valid)
before it is written over by the transfer of new data in a
subsequent transfer.
7
Your ladder program performs BTWs to the module when you power
it up, and any time you wish to reconfigure the module.
3
The module converts analog signals
into binary format and stores these
values until the adapter requests their
transfer.
Publication 1794ĆUM009D-EN-P - April 2004
1–3Overview of FLEX I/O and your Remote I/O Adapter Module
Hardware Components
Diagnostic Indicators
Reset Pushbutton
Address/Group Switches
The adapter module consists of the following major components:
diagnostic indicators
reset pushbutton
remote I/O wiring connections
24V dc power wiring connections
address/group switch assemblies
AllenĆBradley
ADAPTER
ACTIVE FAULT
PWR
LOCAL FAULT
24 VDC
POWER SUPPLY
RIO ADAPTER
1794-ASB
24V dc Common Wiring Connections
+24V dc Wiring Connections
Remote I/O Wiring Connections (connector part no. 942029-03)
Diagnostic Indicators
Diagnostic indicators are located on the front panel of the adapter module. They show both normal operation and error conditions in your remote I/O system. The indicators are:
Power ON (green)
Adapter ACTIVE (green)
Adapter FAULT (red)
LOCAL FAULT (red)
A complete description of the diagnostic indicators and how to use them for troubleshooting is explained in chapter 4.
Publication 1794ĆUM009D-EN-P - April 2004
1–4 Overview of FLEX I/O and your Remote I/O Adapter Module
Reset Pushbutton
Use the reset pushbutton to reset the adapter module and resume communication when a communication error occurs. (The adapter’s processor restart lockout switch (PRL) must be in the “locked out” position.) If the adapter is not locked out by the PRL switch, it will be automatically reset via special commands sent over the communication link.
Important: Do not cycle power to the adapter to clear a fault. All
queued block transfer instructions will be lost.
Remote I/O Wiring
The remote I/O wiring termination is made to a plug-in connector on the front of the adapter module. Refer to Chapter 2 for information on wiring the connector.
FlipĆopen
cover
ON
S1
Power Wiring
Connections are provided for connecting the required 24V dc power to the front of the module. The power wiring can be daisy-chained to the terminal base unit located next to the adapter to supply power to the module installed in that base unit. Wiring information is shown in Chapter 2.
Address Switch Assemblies
Multi-position switches are provided for:
starting I/O group
I/O rack number
hold inputs
mode switches for mode 0, mode 1, mode 2, mode 3 and mode 4
rack fault
87654321
87654321
communication rate
processor restart lockout (PRL)
hold last state (outputs)
These switches are accessed by lifting the hinged cover on the front
ON
S2
of the module. Refer to Chapter 2 for switch settings.
Chapter Summary
Publication 1794ĆUM009D-EN-P - April 2004
In this chapter you learned about the FLEX I/O system and features of the remote I/O adapter module.

Installing Your Remote I/O Adapter Module
Chapter Objectives
This chapter describes the procedures for installing your remote I/O adapter module. These include:
power requirements
mounting the remote I/O adapter
setting the module switches
ATTENTION
!
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664–1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present, and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosures. Also, see the appropriate sections in this publication, as well as the Allen–Bradley publication 1770–4.1, (“Industrial Automation Wiring and Grounding Guidelines”), for additional installation requirements pertaining to this equipment.
Publication 1794ĆUM009D-EN-P - April 2004
2–2 Installing Your Remote I/O Adapter Module
ATTENTION
!
ATTENTION
!
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential
static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component
boards.
Do not touch circuit components inside the
equipment.
If available, use a static–safe workstation.
When not in use, keep modules in appropriate
static–safe packaging.
Remove field-side power before removing or inserting this module. This module is designed so you can remove and insert it under backplane power. When you remove or insert a module with field-side power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
ATTENTION
!
sending an erroneous signal to your system’s
field devices causing unintended machine motion
causing an explosion in a hazardous environ-
ment
Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc plated, yellow chromated steel DIN rail to assure proper grounding. Using other DIN rail materials (e.g. aluminum, plastic, etc.) which can corrode, oxidize or are poor conductors can result in improper or intermittent platform grounding.
Publication 1794ĆUM009D-EN-P - April 2004
2–3Installing Your Remote I/O Adapter Module
Power Requirements
Mounting the Remote I/O Adapter
A
The Remote I/O adapter module requires a current of 450mA at 24V dc from an external power supply for flexbus operation. This is sufficient to support the flexbus current requirements of 8 modules. Remember to add this amount to current requirements for other modules using the same 24V supply.
The remote I/O adapter module can be DIN rail or wall/panel mounted. Refer to the specific method of mounting below.
Mounting on a DIN Rail before installing the terminal base units
B

C
C
1. Position the remote I/O adapter module A on a 35 x 7.5mm DIN rail B (A-B pt. no. 199-DR1; 46277-3; EN 50022) at a slight angle.
2. Rotate the adapter module onto the DIN rail with the top of the rail hooked under the lip on the rear of the adapter module.
3. Press the adapter module down onto the DIN rail until flush. Locking tab (C) will snap into position and lock the adapter module to the DIN rail.
If the adapter module does not lock in place, use a screwdriver or similar device to move the locking tab down while pressing the adapter module flush onto the DIN rail and release the locking tab to lock the adapter module in place. If necessary, push up on the locking tab to lock.
4. Connect the adapter wiring as shown under “Wiring” later in this document.
Make certain that the DIN rail is properly
IMPORTANT
grounded to the panel. Refer to “Industrial Automation Wiring and Grounding Guidelines,” publication 1770-4.1.
Publication 1794ĆUM009D-EN-P - April 2004
2–4 Installing Your Remote I/O Adapter Module
Mounting (or Replacing) the Adapter on an Existing System
ATTENTION
!
1. Remove the RIO plug-in connector from the front of the adapter.
2. Disconnect any wiring connected to the adjacent terminal base.
3. Using a screwdriver or similar tool, open the lock and remove the
module from the base unit to which the adapter will be attached.
4. Push the flexbus connector toward the right side of the terminal
base to unplug the backplane connection.
ATTENTION
!
If you connect or disconnect wiring while the field side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Make certain that the flexbus connector is completely clear of the adapter. The slide must be completely to the right and the raised spot on the slide visible.
5. Release the locking tab and remove the adapter.
6. Before installing the new adapter, notice the notch on the right
rear of the adapter. This notch accepts the hook on the terminal base unit. The notch is open at the bottom. The hook and adjacent connection point keep the terminal base and adapter tight together, reducing the possibility of a break in communication over the backplane.
ATTENTION
!
7. Place the adapter next to the terminal base unit and push down to
mate the hook into slot.
Make certain that the hook on the terminal base is properly hooked into the adapter. Failure to lock the hook into the adjacent base/adapter can result in loss of communication on the backplane.
Publication 1794ĆUM009D-EN-P - April 2004
2–5Installing Your Remote I/O Adapter Module
T
8. With the hook on the terminal base inside the notch on the
adapter, and the lip on the rear of the adapter hooked over the DIN rail, press in and down to lock the adapter onto the DIN rail.
C
If the adapter module does not lock in place, use a screwdriver or similar device to move the locking tab down while pressing the adapter module flush onto the DIN rail and release the locking tab (C) to lock the adapter module in place. If necessary, push up on the locking tab to lock.
9. Gently push the flexbus connector into the side of the adapter to complete the backplane connection.
10.Reinstall the module into the terminal base unit.

11. Reconnect the adapter wiring as shown under “Wiring.”
Mounting on a Wall or Panel
To mount the remote I/O adapter module on a wall or panel, you must have the 1794-NM1 mounting kit. The kit contains a special plate and screws necessary for wall/panel mounting. Proceed as follows:
Install the mounting plate on a wall or panel as follows:
1. Lay out the required points on the wall/panel as shown in the drilling dimension drawing.
2. Drill the necessary holes for #6 self-tapping mounting screws.
3. Mount the mounting plate (1) for the adapter module using two
#6 self-tapping screws (18 included).
Make certain that the mounting plate is properly
IMPORTAN
grounded to the panel. Refer to “Industrial Automation Wiring and Grounding Guidelines for Noise Immunity,” publication 1770-4.1.
4. Hold the adapter (2) a slight angle and engage the top of the mounting plate in the indention on the rear of the adapter module.
5. Press the module down flush with the panel until the locking lever locks.
Publication 1794ĆUM009D-EN-P - April 2004
2–6 Installing Your Remote I/O Adapter Module
Inches
(Millimeters)
3.2
(80)
3.4
(87)
.83 (21)
A
1.4
(35)
2.7
(68)
1794 Adapters
3.4H x 2.7W x 2.7D (87H x 68W x 69D)
2.3
(59)
1794 Terminal Base Units
3.7H x 3.7W x 2.7D (94H x 94W x 69D)
(35)
3.7
(94)
1.4
3.7
(94)
= Mounting hole dimensions for optional
A
0.9
(23)
mounting kit
6. Position the termination base unit up against the adapter and push
the female bus connector into the adapter.
7. Secure to the wall with two #6 self-tapping screws.
2.0
(50)
1.2
(30)
3.7
(94)
3.2
(80)
2 - Remote I/O Adapter Module
8. Repeat for each remaining terminal base unit.
Note: The adapter is capable of addressing eight modules. Do not
exceed a maximum of eight terminal base units in your system.
1.4
(35.5)
1 - Adapter Mounting Plate
Mounting Screws(18) -
2 for the mounting plate
and 2 each for the 8
possible modules
Publication 1794ĆUM009D-EN-P - April 2004
2–7Installing Your Remote I/O Adapter Module
Wiring
Connect external wiring to the remote I/O adapter as shown below.
AllenĆBradley
ADAPTER
LOCAL
ACTIVE FAULT
PWR
SH
1
Termination resistor (if required)
2
82or 150(refer to your processor
documentation for size and usage)
FAULT
24 VDC
POWER SUPPLY
RIO ADAPTER
1794-ASB
BC
COM
A
24V
20131
1. Connect the remote I/O cable to the removable plug-in remote
I/O connector.
Connect To
Blue Wire - RIO 1
Shield Wire - RIO SH
Clear Wire - RIO 2
D
For Example:
DaisyĆchaining
24V dc
ATTENTION
If this is the last adapter in your FLEX I/O system, or the last adapter on the remote I/O link, you must use a termination resistor across
!
terminals 1 and 2 on the remote I/O connector. Refer to the information supplied with the processor being used for information on the size of the resistor.
2. Connect +24V dc input to the left side of the lower connector terminal A.
3. Connect 24V common to the left side of the upper connector terminal B.
4. Connections C and D are used to pass 24V dc power and common to the next module in the series (if required).
Wiring when total current draw is less than 10A
Note: Modules must be either all analog or all discrete. Do not mix analog
and discrete modules when using the daisyĆchain wiring scheme.
Note: Refer to the individual instructions for each module for actual wiring information.
Publication 1794ĆUM009D-EN-P - April 2004
2–8 Installing Your Remote I/O Adapter Module
Setting the Switches
The remote I/O adapter module has two 8-position switch assemblies which you set for:
starting I/O group
I/O logical rack number
hold inputs
addressing modes
last chassis
communication rate
processor restart lockout (PRL)
hold last state (outputs)
WARNING
!
The switch settings on the series E adapter are not the same as on the series A, B, C or D adapter. If you are replacing an earlier series adapter with this series E adapter, make certain that the switches are set correctly for your application.
Starting I/O Group
Chapter
An I/O group is an addressing unit that can contain up to 16 input terminals and 16 output terminals. The starting I/O group is the first group of input and output circuits that correspond to one word in both the input and output image tables. These starting I/O groups are numbered 0, 2, 4 and 6. The number of modules that make up an I/O group varies with the mode of addressing.
I/O Rack Number
One logical I/O rack is 8 I/O groups. You cannot have more than 2 logical racks per adapter. Refer to “Determining Rack Size” on page 3–16 for examples.
Hold Inputs
When hold inputs is enabled (S2-7 on), the adapter will retain the last memory image present when you remove a discrete input module from its base. These inputs are held until the correct module is placed back in the base. If the same type of module is reinserted into the base, its inputs will be transferred. If a different type of module is inserted in the base, its memory image will go to zero. Any associated outputs will also go to zero.
Publication 1794ĆUM009D-EN-P - April 2004
2–9Installing Your Remote I/O Adapter Module
Rack Fault Select Switch (RFS)
The rack fault select allows the user to determine what action the adapter takes if communication is lost with one or more I/O modules
ATTENTION
!
When RFS is disabled (S2–6 on), module removal and insertion
under power (RIUP) is possible. If an I/O module stops responding, the adapter declares a local fault and flashes the Local Fault indicator. The adapter also resets the output data (if any) for the module not responding. All other modules remain active.
When the RFS is enabled (S2-6 off), communication error detection is extended to the I/O module level. If an I/O module stops responding, the adapter declares a local fault, flashes the Local Fault indicator and causes the scanner to declare a Rack Fault. The adapter resets the output data (if any) for the module not responding and commands all other outputs to go to the state determined by the Hold Last State switch (S2–1).
ATTENTION
If an I/O module stops responding to the adapter due to a module being removed under power, a problem with the flexbus, or a problem with an I/O module, the adapter declares a Local fault.
Module removal and insertion under power (RIUP) will cause a rack fault when Rack Fault Select is enabled.
!
Addressing Mode Selection Switches
The addressing mode switches are used to select the addressing modes of the adapter: standard, 8-pt compact, 16-pt compact, 8-pt complementary, 16-pt complementary, 32 standard, and 32 complimentary. Refer to the table on page2–12 for information on the interaction of these switches.
Mode switch S1-1 provides different functions. In standard mode, it acts as part of the rack address, providing backward compatibility with the series A or B adapters. In compact mode, it determines 8 or 16-point density. In complementary mode, it specifies whether the rack has a complementary rack at the same address.
Publication 1794ĆUM009D-EN-P - April 2004
2–10 Installing Your Remote I/O Adapter Module
Communication Rate
You set these switches (S2-3 and S2-4) for the desired communication rate (in bits/s). Selections are:
57.6k bits/s
115.2k bits/s
230.4k bits/s Autobaud (used in 32-pt modes)
Processor Restart Lockout (PRL)
When PRL is disabled (switch S2-2 on), the programmable controller can restart communication with the adapter in the event of a communication fault.
Reset
Pushbutton
When PRL is enabled (switch S2-2 off), the programmable controller cannot restart communication with the adapter in the event of a communication fault. In this case, you must press the restart pushbutton on the front of the adapter module to restart communication.
Hold Last State (HLS)
The hold last state option allows the user to determine what action the outputs take in the event of a communication error.
When HLS is enabled (S2–1 off), all digital outputs, and 1794-OE4 and 1794-IE4XOE2 analog modules remain in their last state. All other analog outputs take their configured safe state action
When HLS is disabled (S2–1 on), all digital outputs are reset. All analog outputs take their configured safe state action
ATTENTION
!
Only 1794-OE4 and 1794-IE4XOE2 analog modules hold their last state when Hold Last State is enabled. Refer to the respective module publications for information about configuring analog output safe state actions.
Publication 1794ĆUM009D-EN-P - April 2004
The switch assemblies are located under a flip-open cover on the front of the adapter module.
2–11Installing Your Remote I/O Adapter Module
Starting I/O Group
1
S1-8 S1-7 I/O group
ON ON 0 (1st quarter)
OFF ON 2 (2nd quarter)
ON OFF 4 (3rd quarter)
OFF OFF 6 (4th quarter)
1 In 32 point mode, starting quarter must be 0 (S1-8 and S1-7 on).
I/O Rack Number
S1-6 thru S1-1
Refer to page 2-13
S2-8 Mode Switch 0
Refer to Mode Selection Switches, 2-12
S2-7 Hold Inputs
ON Hold Inputs
OFF Reset Inputs
S2-6 Rack Fault
ON Not Enabled (default)
OFF Enabled
Starting
I/O Group
I/O Rack
Number
Mode Switch 2
ON
S1
FlipĆopen
cover
87654321
87654321
ON
S2
S2-5 Mode Switch 1
Refer to Mode Selection Switches, 2-12
Communication Rate/
32-pt Mode Select
S2-4 S2-3 Bits/s
ON ON 57.6k
OFF ON 115.2k
ON OFF 230.4k
OFF OFF Autobaud (use only with 32Ćpt
1
Cycle power to the 1794ĆASB/E or push the reset
button when baud rate is changed in the scanner.
1
mode
) Use these switches to put the adapter in 32-pt mode and perform autobaud.
Processor Restart Lockout (PRL)
S2-2 Processor:
ON Restart
OFF Locked out
Hold Last State (HLS)
S2-1 Processor will:
ON Reset outputs
OFF Hold last state
ON
S1
87654321
87654321
Mode Switch 0
Hold Inputs Rack Fault
Mode Switch 1
Mode Switch 4
Communication Rate/Mode switches 3 and 4
Mode Switch 3
Processor Restart Lockout Hold Last State
ON
S2
Publication 1794ĆUM009D-EN-P - April 2004
2–12 Installing Your Remote I/O Adapter Module
2
8Ćpoint modules
2
16Ćpoint modules
2
Setting the Mode Selection Switches
When Using this Addressing Mode
Standard
Compact
Complementary See Complementary Rack Addressing Table, page2-15
Primary chassis
Complementary chassis
Complementary See Complementary Rack Addressing Table, page 2-15
Primary chassis
Complementary chassis
1
In standard mode, this switch retains its function as switch position 1 of rack addressing. In Standard mode, the module is functionally interchangeable with a 1794ĆASB series A or B adapter.
2
In compact mode, 32-point modules appear as 8 or 16-point modules.
3
When programming block transfers, address analog modules as module 0 if switch S1Ć1 is on; module 1 if switch S1Ć1 is off.
Set the mode selection switches for the desired mode as follows.
1. Lift the hinged switch cover on the front of the adapter to expose
the switches.
2. Set the switches as shown below.
3. Cycle power to the adapter to activate the settings.
And
1
8 and/or 16Ć point modules
Mode Switch 2
S1Ć1
See note 1 ON ON
8Ćpoint modules OFF ON OFF
16Ćpoint modules ON ON OFF
Ć
Ć
OFF OFF ON
ON OFF ON
OFF OFF OFF
ON OFF OFF
Mode Switch 1
S2Ć5
Mode Switch 0
S2Ć8
When Using this Addressing Mode
Standard - 32
1
And
8, 16 and/or 32Ć point modules
Complementary - 32 Primary chassis
Complementary - 32 Complementary chassis
1
In Standard - 32 mode, any module in the chassis occupies 32 input points and 32 output points in the Input/Output data table.
2
In Complementary - 32 mode, any module in the chassis occupies 32 input points or 32 output points in the Input/Output data table. If using an 8 point or 16 point module, the unused
points in the data table are zeroed out.
2
8, 16 and/or 32Ć point modules
2
Mode Switch 0
S2-8
Mode Switch 1
S2Ć5
Mode Switch 2
S1-1
Mode Switch 3
S2-3
ON ON See note 1 OFF OFF
OFF OFF OFF OFF OFF
OFF OFF ON OFF OFF
Mode Switch 4
S2Ć4
Publication 1794ĆUM009D-EN-P - April 2004
2–13Installing Your Remote I/O Adapter Module
only available in standard and standard 32
Setting the Address Switches
Use the following table to set your address switches. (Refer to page 2–15 to set address switches when in complementary mode.)
Rack Number S1 Switch Position
1747ĆSN PLCĆ5 PLCĆ5/250 PLCĆ3 6 5 4 3 2 1
Rack 0 Not Valid Rack 0 Rack 0 ON ON ON ON ON ON
Rack 1 Rack 1 Rack 1 Rack 1 OFF ON ON ON ON ON
Rack 2 Rack 2 Rack 2 Rack 2 ON OFF ON ON ON ON
Rack 3 Rack 3 Rack 3 Rack 3 OFF OFF ON ON ON ON
Rack 4 Rack 4 Rack 4 ON ON OFF ON ON ON
Rack 5 Rack 5 Rack 5 OFF ON OFF ON ON ON
Rack 6 Rack 6 Rack 6 ON OFF OFF ON ON ON
Rack 7 Rack 7 Rack 7 OFF OFF OFF ON ON ON
Rack 10 Rack 10 Rack 10 ON ON ON OFF ON ON
Rack 11 Rack 11 Rack 11 OFF ON ON OFF ON ON
Rack 12 Rack 12 Rack 12 ON OFF ON OFF ON ON
Rack 13 Rack 13 Rack 13 OFF OFF ON OFF ON ON
Rack 14 Rack 14 Rack 14 ON ON OFF OFF ON ON
Rack 15 Rack 15 Rack 15 OFF ON OFF OFF ON ON
Rack 16 Rack 16 Rack 16 ON OFF OFF OFF ON ON
Rack 17 Rack 17 Rack 17 OFF OFF OFF OFF ON ON
Rack 20 Rack 20 Rack 20 ON ON ON ON OFF ON
Rack 21 Rack 21 Rack 21 OFF ON ON ON OFF ON
Rack 22 Rack 22 Rack 22 ON OFF ON ON OFF ON
Rack 23 Rack 23 Rack 23 OFF OFF ON ON OFF ON
Rack 24 Rack 24 Rack 24 ON ON OFF ON OFF ON
Rack 25 Rack 25 Rack 25 OFF ON OFF ON OFF ON
Rack 26 Rack 26 Rack 26 ON OFF OFF ON OFF ON
Rack 27 Rack 27 Rack 27 OFF OFF OFF ON OFF ON
Rack 30 Rack 30 ON ON ON OFF OFF ON
Rack 31 Rack 31 OFF ON ON OFF OFF ON
Rack 32 Rack 32 ON OFF ON OFF OFF ON
Rack 33 Rack 33 OFF OFF ON OFF OFF ON
Rack 34 Rack 34 ON ON OFF OFF OFF ON
Rack 35 Rack 35 OFF ON OFF OFF OFF ON
Rack 36 Rack 36 ON OFF OFF OFF OFF ON
Rack 37 Rack 37 OFF OFF OFF OFF OFF ON
See note 1 - Rack addresses 40 thru 76 are-Rack 40 ON ON ON ON ON OFF
modes.
Continued on next page
Rack 41
OFF ON ON ON ON OFF
Publication 1794ĆUM009D-EN-P - April 2004
2–14 Installing Your Remote I/O Adapter Module
Rack address 77 is an illegal configuration. PLCĆ5/11 processors can scan rack 03. PLCĆ5/15 and PLCĆ5/20 processors can scan racks 01-03. PLCĆ5/25 and PLCĆ5/30 processors can scan racks 01-07. PLCĆ5/40 and PLCĆ5/40L processors can scan racks 01-17. PLCĆ5/60 and PLCĆ5/60L processors can scan racks 01-27. PLCĆ5/250 processors can scan racks 00-37. PLCĆ3 processors can scan racks 00-76. Note1-Whenusing a 1794ĆASB series C (or later) adapter module, rack addresses 40 to 76 are only available in Standard and Standard-32 modes.
S1 Switch PositionRack Number
123456PLCĆ3PLCĆ5/250PLCĆ51747ĆSN
Rack 42 ON OFF ON ON ON OFF
Rack 43 OFF OFF ON ON ON OFF
Rack 44 ON ON OFF ON ON OFF
Rack 45 OFF ON OFF ON ON OFF
Rack 46 ON OFF OFF ON ON OFF
Rack 47 OFF OFF OFF ON ON OFF
Rack 50 ON ON ON OFF ON OFF
Rack 51 OFF ON ON OFF ON OFF
Rack 52 ON OFF ON OFF ON OFF
Rack 53 OFF OFF ON OFF ON OFF
Rack 54 ON ON OFF OFF ON OFF
Rack 55 OFF ON OFF OFF ON OFF
Rack 56 ON OFF OFF OFF ON OFF
Rack 57 OFF OFF OFF OFF ON OFF
Rack 60 ON ON ON ON OFF OFF
Rack 61 OFF ON ON ON OFF OFF
Rack 62 ON OFF ON ON OFF OFF
Rack 63 OFF OFF ON ON OFF OFF
Rack 64 ON ON OFF ON OFF OFF
Rack 65 OFF ON OFF ON OFF OFF
Rack 66 ON OFF OFF ON OFF OFF
Rack 67 OFF OFF OFF ON OFF OFF
Rack 70 ON ON ON OFF OFF OFF
Rack 71 OFF ON ON OFF OFF OFF
Rack 72 ON OFF ON OFF OFF OFF
Rack 73 OFF OFF ON OFF OFF OFF
Rack 74 ON ON OFF OFF OFF OFF
Rack 75 OFF ON OFF OFF OFF OFF
Rack 76 ON OFF OFF OFF OFF OFF
Not Valid OFF OFF OFF OFF OFF OFF
Publication 1794ĆUM009D-EN-P - April 2004
2–15Installing Your Remote I/O Adapter Module
Setting the Address Switches for Complementary I/O
Use the following table to set your address switches for complementary I/O when using a PLC-5 processor. For all other processors, refer to the programming manual for that specific processor.
Primary Rack
Rack Number S1 Switch Position
1747ĆSN PLCĆ5 6 5 4 3 2 1
Rack 0 Not Valid ON ON ON ON ON OFF
Rack 1 Rack 1 OFF ON ON ON ON OFF
Rack 2 Rack 2 ON OFF ON ON ON OFF
Rack 3 Rack 3 OFF OFF ON ON ON OFF
Rack 4 ON ON OFF ON ON OFF
Rack 5 OFF ON OFF ON ON OFF
Rack 6 ON OFF OFF ON ON OFF
Rack 7 OFF OFF OFF ON ON OFF
Complementary Rack
Rack Number S1 Switch Position
1747ĆSN PLCĆ5 6 5 4 3 2 1
Rack 0 Not Valid ON ON ON OFF ON ON
Rack 1 Rack 1 OFF ON ON OFF ON ON
Rack 2 Rack 2 ON OFF ON OFF ON ON
Rack 3 Rack 3 OFF OFF ON OFF ON ON
Rack 4 ON ON OFF OFF ON ON
Rack 5 OFF ON OFF OFF ON ON
Rack 6 ON OFF OFF OFF ON ON
Rack 7 OFF OFF OFF OFF ON ON
Chapter Summary
In this chapter you learned how to install your adapter module and set your switches. Chapter 3 tells you how to communicate with your system.
Publication 1794ĆUM009D-EN-P - April 2004
2–16 Installing Your Remote I/O Adapter Module
Publication 1794ĆUM009D-EN-P - April 2004
Communicating with FLEX I/O Modules

Chapter Objectives
FLEX I/O Module Data
In this chapter, we tell you about:
FLEX I/O module data
selecting an addressing type
selecting an addressing mode
determining rack size
mapping data into the image tables
operating modes
There are 2 types of data associated with FLEX I/O modules: input data and output data.
input data – data read from the module by the processor
output data – data written to the module by the processor
Some digital I/O modules have both input and output data associated with them. Digital I/O modules map input data and output data to the input and output image tables in the processor. Input and output data can be defined as:
real I/O data – data that represents the actual state of
hardwired inputs and outputs (input data on input modules, output data on output modules)
configuration/status data – data written to configure the
module (such as delay times); and status information (such as a fuse blown indication)
For FLEX analog modules, input and output data is only accessible by the processor using block transfer instructions. The data is contained in block transfer write (BTW) and block transfer read (BTR) data files, not in the input and output image tables. A byte of input image and a byte of output image is required for the module status byte (MSB) and the module control byte (MCB). The MSB uses input image, and the MCB uses output image. These bytes are required for block transfer command communications.
Publication 1794ĆUM009D-EN-P - April 2004
3–2 Communicating with FLEX I/O Modules
Addressing I/O
The 1794-ASB series E adapter supports 5 different modes of addressing: standard, compact, complementary, standard–32 and complementary–32.
For digital modules, the mode of addressing determines what type of data is available to the processor from the module.
standard addressing – input and output data is available for each
digital module connected to the adapter
compact addressing – either input or output data (not both) is
available for each digital module connected to the adapter
complementary addressing – either input or output data (not both)
is available for each digital module connected to the adapter
Analog modules can be used in any mode of addressing with no loss of data because data is not stored in the input and output image table, with the exception of the MCB and MSB. Analog data is stored in BTW and BTR data files.
The following table helps you to select an addressing mode based on the kind of modules you want to use, and the features you need from those modules. The table also lists both advantages and disadvantages of using each addressing type.
Addressing Mode Use this addressing scheme when: Advantages Disadvantages
Standard you need full FLEX I/O module
functionality, including combination modules (1794ĆIB10XOB6), settable input delay times on input modules (1794ĆIB16, ĆIB8S), and fuse blown indication (1794ĆOB8EP) for example. Will work with 32-pt. modules with 16 in and 16 out (1794-IB16XOB16P).
Compact you don't need full FLEX I/O module
functionality, including combination modules (1794ĆIB10XOB6), settable input delay times on input modules (1794ĆIB16, ĆIB8S), and fuse blown indication (1794ĆOB8EP), for example.
you can locate equal numbers of
input and output modules in a single chassis
User has access to 1 word of input, 1
word of output for each digital module.
Eight modules equal 1 logical rack.
No restrictions on module placement
Maximum use of configuration/status and
combination modules
Eight 8 point modules equal 1/4 logical
racks (when input and output modules are installed in alternate slots).
Eight 16 point modules equal 1/2 logical
racks (when input and output modules are installed in alternate slots).
Provides maximum use of I/O image table
by a single FLEX chassis (when input and output modules are installed in alternate slots).
Inefficient I/O image table
utilization
You must configure all modules
in the chassis as either 8Ćpoint orĆ16 point.
No combination modules
allowed
Configuration/status data is not
accessible to user
Publication 1794ĆUM009D-EN-P - April 2004
3–3Communicating with FLEX I/O Modules
Complementary you  need full FLEX I/O module
functionality, including combination modules (1794ĆIB10XOB6), settable input delay times on input modules (1794ĆIB16, ĆIB8S), and fuse blown indication (1794ĆOB8EP), for example.
you can locate equal numbers of
input and output modules in separate chassis
Standard - 32 you need full FLEX I/O module
functionality, including 32 point modules, combination modules (1794ĆIB10XOB6), settable input delay times on input modules (1794ĆIB16, ĆIB8S), and fuse blown indication (1794ĆOB8EP) for example.
Complementary - 32 you  need full FLEX I/O module
functionality, including combination modules (1794ĆIB10XOB6), settable input delay times on input modules (1794ĆIB16, ĆIB8S), and fuse blown indication (1794ĆOB8EP), for example.
you can locate equal numbers of
input and output modules in separate chassis
Eight 8 point modules in each chassis
equal 1/2 logical rack (when input modules are installed in 1 chassis, and output modules are installed in the complementary chassis).
Eight 16 point modules in each chassis
equal 1 logical rack (when input modules are installed in 1 chassis, and output modules are installed in the complementary chassis).
Provides maximum use of I/O image table
in 2 FLEX chassis (when input modules are installed in 1 chassis, and output modules are installed in the complementary chassis).
User has access to 2 words of input, 2
words of output for each digital module.
Four modules equal 1 logical rack.
No restrictions on module placement
Maximum use of configuration/status and
combination modules
Eight modules in each chassis equal 2
logical racks
Provides maximum use of I/O image table
in 2 FLEX chassis (when input modules are installed in 1 chassis, and output modules are installed in the complementary chassis).
You must configure all modules
in both chassis as either 8Ćpoint or 16Ćpoint.
No combination modules
allowed
Configuration/status data is not
accessible to user
Inefficient I/O image table
utilization
All digital I/O modules are
configured as 32Ćpoint.
No combination modules
allowed
Configuration/status data may
not be accessible to user (depending on module type).
The amount of data accessible to the processor in the 5 addressing modes is illustrated below. Note that the shaded areas represent data not accessible by the processor.
Publication 1794ĆUM009D-EN-P - April 2004
3–4 Communicating with FLEX I/O Modules
Digital I/O Modules
Input Module Example Output Module Example
Input Word
Output Word
8 Bits 8 Bits
8 Bits8 Bits
Note: If 32 pt. modules are used in standard mode, only the lower word (16 bits) will be sent to the processor. All 32 bits of the 32-pt combo module are available.
8 Bits 8 Bits
8 Bits8 Bits
Standard Mode
16 bits of input AND
16 bits of output available
Input Word 0
Input Word 1
Output Word 0
Output Word 1
Input Word
Output Word
Input Word
Output Word
Input Module Example
8 Bits 8 Bits
8 Bits8 Bits
8 Bits 8 Bits
8 Bits8 Bits
Input Module Example Output Module Example
8 Bits 8 Bits
8 Bits8 Bits
Note: If 32 pt. modules are used in 16 pt. compact mode, only the low word (16 bits) will be sent to the processor.
Input Module Example Output Module Example
8 Bits 8 Bits
8 Bits8 Bits
Note: If 16Ćpt or 32Ćpt modules are used in 8Ćpt compact addressing, only the information in the lowest byte (8 bits) will be sent to the processor.
Output Module Example
8 Bits 8 Bits
8 Bits8 Bits
8 Bits 8 Bits
8 Bits8 Bits
8 Bits 8 Bits
8 Bits8 Bits
8 Bits 8 Bits
8 Bits8 Bits
Standard - 32 Mode
32 bits of input AND
32 bits of output available
Compact Mode
16Ćpt Density
16 bits of input OR
16 bits of output available
Compact Mode
8Ćpt Density
8 bits of input OR
8 bits of output available
16Ćbit Input modules complemented by 16Ćbit output modules
Input Module Example Output Module Example
Input Word
Output Word
Input Word
Output Word
Publication 1794ĆUM009D-EN-P - April 2004
8 Bits 8 Bits
Input Module Example Output Module Example
8 Bits 8 Bits
Primary Chassis
8 Bits 8 Bits
8 Bits8 Bits
Complement Chassis
8 Bits8 Bits
8 Bits 8 Bits
8 Bits8 Bits
Note: If 32Ćpt modules are used in 16Ćpt complimentary addressing,
only the information in the lower word will be sent to the processor.
8 Bits8 Bits
Complementary Mode
16Ćpt Density
16 bits of input OR
16 bits of output available
Input Word
Output Word
Input Word
Output Word
Input Word 0
Input Word 1
Output Word 0
Output Word 1
8Ćbit Input modules complemented by 8Ćbit output modules
Primary Chassis
Input Module Example Output Module Example
8 Bits 8 Bits
8 Bits8 Bits
Complement Chassis
Input Module Example Output Module Example
8 Bits 8 Bits
8 Bits8 Bits
Note: If 16Ćpt or 32Ćpt modules are used in 8Ćpt complementary addressing,
only the information in the lowest byte will be sent to the processor.
8 Bits 8 Bits
8 Bits8 Bits
8 Bits 8 Bits
8 Bits8 Bits
32Ćbit Input modules complemented by 32Ćbit output modules
Primary Chassis
Input Module Example Output Module Example
8 Bits 8 Bits
8 Bits8 Bits
8 Bits 8 Bits
8 Bits 8 Bits
8 Bits 8 Bits
8 Bits 8 Bits
8 Bits 8 Bits
8 Bits8 Bits
3–5Communicating with FLEX I/O Modules
Complementary Mode
8Ćpt Density
8 bits of input OR
8 bits of output available
Complementary - 32 Mode
32-pt density
32 bits of input OR
32 bits of output available
Input Module Example Output Module Example
Input Word 0
Input Word 1
Output Word 0
Output Word 1
8 Bits 8 Bits
8 Bits 8 Bits
Note: Shaded areas represent data not accessible by the processor.
Analog (Block Transfer) Modules
Complement Chassis
8 Bits 8 Bits
8 Bits8 Bits
8 Bits 8 Bits
8 Bits 8 Bits
8 Bits 8 Bits
8 Bits8 Bits
Complementary - 32 Mode
32 bits of input OR
32 bits of output available
Analog modules use block transfers, which require 1 byte (8 bits) of input image for the module status byte, and 1 byte (8 bits) of output image for the module control byte. This is true for any addressing mode selected.
Input Word
Output Word
Input or Output Example
8 Bits 8 Bits
MSB
MCB
Any Mode
Block transfers require
8 bits of input image and
8 bits of output image
Publication 1794ĆUM009D-EN-P - April 2004
3–6 Communicating with FLEX I/O Modules
Standard Addressing
Standard Addressing
Input Output Input Output Analog Analog Output Input
Adapter
Use standard addressing when:
you need full FLEX I/O module functionality, such as delay time
selection on input modules, fuse-blown indication on the 1794-OB8EP, etc.
using combination modules, such as the 1794-IB10XOB6 10 in/6
out module
In standard mode, each module position equals one I/O group – 1 word of input image and 1 word of output image. If 32-pt input or output modules are used, only the lower 16 bits are available. All 32 bits of the 32–pt combination modules are available.
Any combination of digital or analog modules.
Eight terminal bases per adapter (maximum)
Each terminal base represents 1 I/O group
20128
Standard Addressing Example
I/O Group 0 I/O Group 1 I/O Group 2 I/O Group 3
M0 M1 M2 M3 M4 M5 M6 M7
ASB/E
IL = Input Low Byte IH = Input High Byte OL = Output Low Byte
OH = Output High Byte
IH IL IH IL
OH OL OH OL OH OL
IB16 IB16IB16
I/O Group
IH IL IH IL IH IL
OH OL
MCB = Module Control Byte (output data) MSB = Module Status Byte (input data)
0 1
2 3 4 5 6 7
- 8 modules = 1 logical rack = 8 I/O groups
I/O Group 4 I/O Group 5 I/O Group 6 I/O Group 7
MSB
OH OL
OB16
Legal Module Placement in Standard Addressing
Any module in any slot
1 module position is an I/O group
Input Image Table Output Image Table
00071017 00071017
M0ĆIH M1ĆIH
M0ĆIL M1ĆIL
M2ĆILM2ĆIH M2ĆOLM2ĆOH M3ĆILM3ĆIH
M4ĆMSB M5ĆMSB
M6ĆILM6ĆIH M7ĆILM7ĆIH
MCB
IE8 IE8
MSB MCB
M0ĆOH M1ĆOH
M4ĆMCB
M5ĆMCB M6ĆOH M7ĆOH
IH IL
OH OL
OB16OB16
M0ĆOL M1ĆOL
M3ĆOLM3ĆOH
M6ĆOL M7ĆOL
Publication 1794ĆUM009D-EN-P - April 2004
3–7Communicating with FLEX I/O Modules
Standard - 32 Addressing
Use standard 32 point addressing when:
you use 32 point modules in your system
you need full FLEX I/O module functionality, such as delay time
selection on input modules, fuse-blown indication on the 1794-OB8EP, etc.
using combination modules, such as the 1794-IB16XOB16 16
in/16 out module
In standard – 32 mode, each module position equals two I/O groups – 2 words of input image and 2 words of output image.
Standard 32 Addressing Example - 8 modules = 2 logical racks, N and N+1 = 16 I/O groups
Rack N RackN+1
M0 M1 M2 M3 M4 M5 M6 M7
Gr. 0
Gr. 1 Gr. 2 Gr. 3 Gr. 4 Gr. 5 Gr. 6 Gr. 7
IHH IHL
ILH ILL IH IL
ASB/E
OLH
OLL
OHH OHL
ILH ILL
IHH IHL
OH OL OLL
OHH OHLOLH OLL
ILH ILL
OHH OHLOLH OLL
IB32 OB32IB16 IB32 Analog Analog IB8OB32
Note: Shaded areas represent data which is not available.
Eight terminal bases per adapter (maximum) Each terminal base represents 2 I/O groups.
ILL, OLL = Bits 0 thru 7 for input and output words of 32 point modules ILH, OLH = Bits 8 thru 15 for input and output words of 32 point modules IHL, OHL = Bits 16 thru 23 for input and output words of 32 point modules IHH, OHH = Bits 24 thru 32 for input and output words of 32 point modules IL, OL = Bits 0 thru 7 for input and output words for 16 and 8 point modules
IH, OH = Bits 8 thru 15 for input and output words for 16 point modules
MCB = Module Control Byte (output data) MSB = Module Status Byte (input data)
Input Image Table for Rack N Output Image Table for Rack N
Input Image Table for Rack N Output Image Table for Rack N
I/O Group
I/O Group
0
0 1
1 2
2 3
3 4
4 5
5 6
6 7
7
M0ĆILH
M0ĆILH
M0ĆIHH
M0ĆIHH
M1ĆILH M1ĆOLLM1ĆOLLM1ĆOLHM1ĆOLH
M1ĆILH
M1ĆIHH
M1ĆIHHM1ĆIHH
M2ĆIH
M2ĆILHM2ĆILH
M2ĆIHHM2ĆIHH M3ĆILH
M3ĆILHM3ĆILH
M3ĆIHH
M3ĆIHH
M0ĆILLM0ĆILL
M0ĆILL
M0ĆIHLM0ĆIHL M1ĆILLM1ĆILL
M1ĆILL
M1ĆIHL
M1ĆIHLM1ĆIHL
M2ĆILLM2ĆILL
M2ĆIHLM2ĆIHL
M3ĆILL
M3ĆILLM3ĆILL M3ĆIHL
M3ĆIHLM3ĆIHL
00071017 00071017
00071017 00071017
M2ĆIL
Gr. 0 Gr. 1 Gr. 2 Gr. 3 Gr. 4 Gr. 5 Gr. 6 Gr. 7
IHH IHL ILH
MSB
MCB
Legal Module Placement in Standard Addressing
Any module in any slot
1 module position is 2 I/O groups
I/O GroupI/O Group
I/O GroupI/O Group
00
00 11
11 22
22 33
33 44
44 55
55 66
66 77
77
MSB
MCB
M0ĆOLH
M0ĆOLH M0ĆOHH
M0ĆOHH M1ĆOLH
M1ĆOHH M2ĆOLHM2ĆOLH
M2ĆOH
M2ĆOHHM2ĆOHH M3ĆOLH
M3ĆOLH M3ĆOHH
M3ĆOHH
OL
M0ĆOLL
M0ĆOLL
M0ĆOHL
M0ĆOHL
M1ĆOLL
M1ĆOHL
M1ĆOHLM1ĆOHLM1ĆOHHM1ĆOHH
M2ĆOLH
M2ĆOL
M2ĆOHL
M3ĆOLL
M3ĆOLL
M3ĆOHL
M3ĆOHL
OLH
ILL
IHH
IHL
OHH
OHL
IL
I/O Group
0
0 1
1 2
2 3
3 4
4 5
5 6
6 7
7
Input Image Table for Rack N+1 Output Image Table for Rack N+1
00071017 00071017
M4ĆMSB
M1ĆILH M1ĆOLLM1ĆOLLM1ĆOLHM1ĆOLH
M1ĆIHHM1ĆIHH
M2ĆILHM2ĆILH
M2ĆIHHM2ĆIHH M7ĆILH
M3ĆILHM3ĆILH
M7ĆIHH
M3ĆIHH
M5ĆMSB
M1ĆILLM1ĆILL
M1ĆIHLM1ĆIHL
M6ĆIL
M2ĆILLM2ĆILL
M2ĆIHLM2ĆIHL
M7ĆILL
M3ĆILLM3ĆILL
M7ĆIHL
M3ĆIHLM3ĆIHL
I/O Group
00
00 11
11 22
22 33
33 44
44 55
55 66
66 77
77
M4ĆMCB
M0ĆOLH M0ĆOHH
M0ĆOLL
M0ĆOHL M5ĆMCB
M1ĆOHLM1ĆOHLM1ĆOHHM1ĆOHH M2ĆOLHM2ĆOLH M2ĆOHHM2ĆOHH
M7ĆOLH
M3ĆOLH M3ĆOHH
M7ĆOHH
Publication 1794ĆUM009D-EN-P - April 2004
M6ĆOL
M2ĆOLH M2ĆOHL
M7ĆOLL
M3ĆOLL
M3ĆOHL
M7ĆOHL
3–8 Communicating with FLEX I/O Modules
Compact Addressing
Use compact addressing when:
you are not using combination modules
you are using only digital input, digital output and analog
modules
you don’t need all the features of digital FLEX I/O modules (You
can only access the input word on an input module, or the output word of an output module. Any status information/configuration information in the corresponding input/output word is not accessible.)
you can locate equal numbers of input and output modules in a
single chassis
you want more efficient use of the input/output data table
Compact Mode
Compact mode maximizes single chassis I/O image table usage when using either 8- or 16-point modules and block transfer modules.
Compact mode allows more than 1 module to occupy a single I/O group. How many modules depends on the density selected (16- or 8-point).
In compact mode, with 16-point density, 2 digital modules (1 input and 1 output module) can occupy 1 I/O group. In addition, 2 block transfer modules can occupy 1 I/O group. If higher density modules are used, only the lowest 16 bits will be available.
In compact mode, with 8-point density, 4 digital modules (2 input and 2 output modules) mounted in module pairs can occupy 1 I/O group. In addition, 2 block transfer modules can occupy 1 I/O group. If higher density modules are used, only the lowest 8 bits will be available.
Publication 1794ĆUM009D-EN-P - April 2004
3–9Communicating with FLEX I/O Modules
16Ćpoint Compact Addressing
Group 0 Group 1 Group 2 Group 3
Input Output Input Output Output InputAnalog Analog
Adapter
Compact 16Ćpoint Addressing Example
I/O Group 0 I/O Group 1 I/O Group 2 I/O Group 3
M0 M1 M2 M3 M4 M5 M6 M7
ASB/E
IL = Input Low Byte IH = Input High Byte OL = Output Low Byte
OH = Output High Byte
Note: Shaded areas represent unavailable data
IH IL IH IL
OH OL
IB16 IB16IB16
MCB = Module Control Byte (output data) MSB = Module Status Byte (input data)
Input modules and Output modules in pairs, or analog modules.
Eight terminal bases per adapter (maximum)
Each module represents 1/2 of an I/O group
2 modules represent 1 I/O group
8 modules = 1/2 I/O rack
- 8 modules = 1/2 logical rack = 4 I/O groups
OH OL
OB16
MSB MCB
IE8 IE8
Legal Module Placement in 16Ćpt Compact Addressing
A 16Ćpoint input module and a 16Ćpoint output module (or an empty slot) in an I/O group. A 16Ćpt output module and a 16Ćpt input module (or an empty slot) in an I/O group.
A block transfer module with another block transfer module (or an empty slot) in an I/O group.
An empty slot with any module, or another empty slot in an I/O group.
2 module positions = an I/O group
MSB
MCB
20128
IH IL
OH OL
OB16OB16
Input Image Table Output Image Table
I/O Group
0 1
2 3 4 5 6 7
Note: When using block transfer modules in 16Ćpt compact addressing, address module positions M0, M2, M4 and M6 as module 0" in a block transfer instruction block; address module positions M1, M3, M5 and M7 as module 1" in a block transfer instruction block.
M0ĆIH M2ĆIH
M5ĆMSB
M7ĆIH
M4ĆMSB
I/O groups 4-7 are available for another adapter.
00071017 00071017
M0ĆIL M2ĆIL
M7ĆIL
M1ĆOH M3ĆOH
M5ĆMCB
M6ĆOH
M1ĆOL M3ĆOL
M4ĆMCB
M6ĆOL
Publication 1794ĆUM009D-EN-P - April 2004
3–10 Communicating with FLEX I/O Modules
8Ćpoint Compact Addressing - Digital Modules
Input modules and Output modules in the same group.
Group 0 Group 1
Input Output Input Output Output Input
Adapter
Eight terminal bases per adapter (maximum)
Each module represents 1/4 of an I/O group
4 modules represent 1 I/O group
Compact 8Ćpoint Addressing Example - 8 digital modules = 1/4 logical rack
I/O Group 0 I/O Group 1
M0 M1 M2 M3 M4 M5 M6 M7
ASB/E
IL = Input Low Byte IH = Input High Byte OL = Output Low Byte
OH = Output High Byte
Note: Shaded areas represent unavailable data
IL IL
OL
IA8 IA8IA8
OL
OW8
Legal Module Placement in 8Ćpoint Compact Addressing
Two 8Ćpoint input modules and two 8Ćpoint output modules (or empty slots) in an I/O group. Module type must alternate within an I/O group: input, output, etc.
One block transfer module with 3 empty slots One block transfer module, followed by an empty slot, another
block transfer module and another empty slot.
4 module positions to an I/O group
OW8 IA8
OL
InputOutput
20128
IL
OL
OA8OA8
IL
I/O Group
0 1
2 3
4 5 6 7
Input Image Table Output Image Table
00071017 00071017
M2ĆIL M7ĆIL
I/O groups 2-7 are available to additional adapters.
M0ĆIL M5ĆIL
M3ĆOL M6ĆOL
M1ĆOL M4ĆOL
Publication 1794ĆUM009D-EN-P - April 2004
3–11Communicating with FLEX I/O Modules
8Ćpoint Compact Addressing - Analog Modules
Adapter
Analog Empty Analog Empty Analog Empty Analog Empty
Adapter
Group 0 Group 1
Each module and adjacent empty base represents 1/2 of an I/O group
Compact 8Ćpoint Addressing Example
I/O Group 0 I/O Group 1
M0 M1 M2 M3 M4 M5 M6 M7
ASB/C
MCB = Module Control Byte (output data) MSB = Module Status Byte (input data)
Note: Shaded areas represent unavailable data
MSB
MCB
IE8
Analog modules in the same group.
Eight terminal bases per adapter (maximum)
- 4 Analog modules = 1/4 logical rack = 2 I/O groups
MSB
MCB
IE8
Legal Module Placement in 16Ćpt Compact Addressing
A 16Ćpoint input module and a 16Ćpoint output module (or an empty slot) in an I/O group
A block transfer module and another block transfer module (or an empty slot) in an I/O group.
An empty slot and any module (or another empty slot) in an I/O grouop.
2 module positions = an I/O group
MSB MCB
IE8 IE8
20128
MSB MCB
I/O Group
0 1
2 3 4
5 6 7
Input Image Table Output Image Table
00071017 00071017
M2ĆMSB M6ĆMSB
Note: When using block transfer modules in 16Ćpt compact addressing, address module positions
M0, M2, M4 and M6 as module 0" in a block transfer instruction block; address module positions
M1, M3, M5 and M7 as module 1" in a block transfer instruction block.
M0ĆMSB M4ĆMSB
I/O groups 4-7 are available for another adapter.
M2ĆMCB M6ĆMCB
M0ĆMCB M4ĆMCB
Publication 1794ĆUM009D-EN-P - April 2004
3–12 Communicating with FLEX I/O Modules
Complementary Addressing Mode
Use complementary addressing when:
you are not using combination modules
you don’t need all the features of FLEX I/O modules
you can locate equal numbers of input and output modules in
separate chassis
you want more efficient use of the input/output image table
Complementary Mode - 16Ćpoint
Complementary mode maximizes 2 chassis I/O image table usage when input modules are installed in 1 chassis, and output modules are installed in another chassis. This mode allows 2 modules to occupy a single I/O group.
In complementary mode, with 16-point density, 1 digital input module in the primary chassis, and 1 digital output module in the complementary chassis, or vice versa, form an I/O group. In addition, analog modules can be complemented by another analog module or an empty base. If 32-pt modules are used, only the lowest 16 bits will be available.
16Ćpoint Complementary Addressing
Primary
Adapter Input
S1Ć1 OFF
Complementary
Adapter
S1Ć1 ON
Note: When programming block transfers, address analog modules as module 0 if switch S1Ć1 is on; module 1 if switch S1Ć1 is off.
Output Empty Analog
I/O Group 1 I/O Group 2 I/O Group 3 I/O Group 4 I/O Group 5 I/O Group 6 I/O Group 7I/O Group 0
Output Output Output
Any combination of digital or analog modules.
Empty
Complement of modules in primary chassis, or analog or empty for analog.
Eight terminal bases per adapter (maximum)
2 modules, 1 in primary and 1 in complement represent 1 I/O group
Analog
AnalogInput
Input
Output
Input
Input
Output
20128
Publication 1794ĆUM009D-EN-P - April 2004
3–13Communicating with FLEX I/O Modules
Complementary 16Ćpoint Addressing Example
1 I/O Group
M0 M1 M2 M3 M4 M5 M6 M7
ASB/E
Primary
ASB/E Comp.
IL = Input Low Byte IH = Input High Byte OL = Output Low Byte
OH = Output High Byte
Note: Shaded areas represent unavailable data
IH
IB16
CĆM0 CĆM1 CĆM2 CĆM3 CĆM4 CĆM5 CĆM6 CĆM7
OHILOL
OB16
I/O Group
IH IL
IB16
OH OL OH OL
OB16
MCB = Module Control Byte
MSB = Module Status Byte
Input Image Table Output Image Table
0 1
2 3 4 5 6 7
M0ĆIH M1ĆIH
M3ĆMSB
Empty
OB16
CĆM4ĆMSB
CĆM6ĆILCĆM6ĆIH
- Up to 16 modules = 1 logical rack
MSB
MCB
OE4
Empty
00071017 00071017
M0ĆIL M1ĆIL
M5ĆIL
M7ĆILM7ĆIH
MSB
MCB
IE8 IB16
MSB
MCB
IE8
Legal Module Placement in 16Ćpoint Complementary
Any module or empty slot in any I/O position of the primary chassis; input modules complemented by output modules, or empty slots; output modules complemented by input modules or empty slots; block transfer modules complemented by block transfer modules or empty slots; or empty slots complemented by input, output, or empty slots.
IH IL
OH OL
OB16
CĆM0ĆOH CĆM1ĆOH CĆM2ĆOH
M3ĆMCB M4ĆMCBM4ĆMSB
CĆM5ĆOHM5ĆIH
OH OL
OB16
IH
IB16 OB16
CĆM0ĆOL CĆM1ĆOL CĆM2ĆOL
CĆM4ĆMCB
CĆM5ĆOL
M6ĆOLM6ĆOH
CĆM7ĆOLCĆM7ĆOH
IH IL
IB16
IL
OH OL
Note: When programming block transfer instructions, address analog modules in the primary rack as module
1," and analog modules in the complementary rack as module 0."
Complementary Mode - 8Ćpoint
Complementary mode maximizes chassis I/O image table usage when input modules are installed in one chassis, and output modules are installed in a complementary chassis. This allows four modules to occupy a single I/O group.
In complementary mode, with 8-point density, 2 digital input modules in the primary chassis, and 2 digital output modules in the complementary chassis, or vice versa, form an I/O group. In addition, analog modules must be complemented by an empty base. If higher density modules are used, only the lowest 8 bits will be available.
Publication 1794ĆUM009D-EN-P - April 2004
3–14 Communicating with FLEX I/O Modules
8Ćpoint Complementary Addressing
Any combination of digital or analog modules.
Primary
Input
Adapter
Complementary
Output EmptyEmpty
Adapter
Output Output Output Output Output
Complement of modules in primary chassis, or empty for analog.
Four modules, 2 in the primary and 2 in the complement, represents 1 I/O group
Complementary 8Ćpoint Addressing Example
I/O Group 0
M0 M1 M2 M3 M4 M5 M6 M7
ASB/E
Primary
IL
IA8
IL IL
IA8
IA8
AnalogAnalogInput Input Input Input Input
I/O Group 1 I/O Group 2 I/O Group 3I/O Group 0
Eight terminal bases per adapter (maximum)
- up to 16 digital or 8 analog modules = 1/2 logical rack
IL
IA8
MSB MSB
MCB
IE8 IE8
MCB
OL OL
OA8
20128
OA8
CĆM0 CĆM1 CĆM2 CĆM3 CĆM4 CĆM5 CĆM6 CĆM7
ASB/E Comp.
IL = Input Low Byte IH = Input High Byte OL = Output Low Byte
OH = Output High Byte
Note: Shaded areas represent unavailable data
OL
OA8
I/O Group
0 1
2 3 4
5 6 7
OL OL
OA8
MCB = Module Control Byte
MSB = Module Status Byte
Input Image Table Output Image Table
M1ĆIL M3ĆIL
M5ĆMSB
CĆM7ĆIL
OL
OA8
M0ĆIL M2ĆIL
M4ĆMSB
CĆM6ĆIL
I/O groups 4-7 are available to additional adapters.
OA8
Legal Module Placement in 8Ćpoint Complementary
2 inputs in a group complemented by 2 outputs or empty slots 2 outputs in a group complemented by 2 inputs or empty slots 2 block transfer modules complemented by 2 empty slots 1 block transfer module and 1 input in a group complemented
by 1 empty slot and 1 output module Empty slots complemented by an empty slot, input or output slot
00071017 00071017
Empty Empty
CĆM1ĆOL CĆM3ĆOL
M5ĆMCB
M7ĆOL
IL IL
IA8 IA8
CĆM0ĆOL CĆM2ĆOL M4ĆMCB
M6ĆOL
Publication 1794ĆUM009D-EN-P - April 2004
3–15Communicating with FLEX I/O Modules
Complementary - 32 Addressing
Use complementary 32 point addressing when:
you use 32 point modules in your system
you need full FLEX I/O module functionality, such as delay time
selection on input modules, fuse-blown indication on the 1794-OB8EP, etc.
using combination modules, such as the 1794-IB16XOB16 16
in/16 out module In complementary mode, each module position equals two I/O groups – 2 words of input image and 2 words of output image.
Complementary 32 Addressing Example - 16 modules = 2 logical racks, N, (N+1), NC and (N + 1)C
Rack N Rack (N + 1)
Group4&5 Group6&7
OHL
OLH OLL OL IHH IHL
OHH
OHL
Group0&1
MSB
MCB
Group2&3
MSB MCB
Rack NC Rack (N + 1)C
OH OL
Input 32
Empty
Analog Input 8
MSB
MCB
ASB/E
Primary
ASB/E Comp.
Group0&1
Group2&3
M0 M1 M2 M3 M4 M5 M6 M7
Input 32 Output 32 Empty
ILH ILL
IHH IHL
CĆM0 CĆM1 CĆM2 CĆM3 CĆM4 CĆM5 CĆM6 CĆM7
Output 32
OHH
OLH OLL IHH IHLILH ILL
OHL
OHH
OLH OLL OL
Input 32 Output 16
Group4&5 Group6&7
Output 8 Input 32Analog AnalogOutput 32
ILH ILL
Output 32
IL
OHH
OLH OLLIHH IHLILH ILL
OHL
Eight terminal bases per adapter (maximum) 1 module in primary chassis, 1 module in complementary
chassis represents 2 I/O groups. ILL, OLL = Bits 0 thru 7 for input and output words of 32 point modules ILH, OLH = Bits 8 thru 15 for input and output words of 32 point modules
IHL, OHL = Bits 16 thru 23 for input and output words of 32 point modules IHH, OHH = Bits 24 thru 32 for input and output words of 32 point modules IL, OL = Bits 0 thru 7 for input and output words for 16 and 8 point modules
IH, OH = Bits 8 thru 15 for input and output words for 16 point modules
Note: Shaded areas represent unavailable data
Input Image Table for Rack N and NC Output Image Table for Rack N and NC
I/O Group
I/O Group
0
0 1
1 2
2 3
3 4
4 5
5 6
6 7
7
M0ĆILH
M0ĆILH
M0ĆIHH
M0ĆIHH
M1ĆILH M1ĆOLLM1ĆOLLM1ĆOLHM1ĆOLH
CM1ĆILH
CM1ĆIHH
M1ĆIHHM1ĆIHH
CM3ĆILH
M3ĆILHM3ĆILH
CM3ĆIHH
M3ĆIHH
M0ĆILL
M0ĆILLM0ĆILL M0ĆIHLM0ĆIHL
M1ĆILLM1ĆILL
CM1ĆILL
CM1ĆIHL
M1ĆIHLM1ĆIHL
CM3ĆILL
M3ĆILLM3ĆILL
CM3ĆIHL
M3ĆIHLM3ĆIHL
00071017 00071017
00071017 00071017
Input Image Table for Rack N+1 and (N+1)C
I/O Group
0
0 1
1 2
2 3
3 4
4 5
5 6
6 7
7
M4ĆMSB
M5ĆMSB
M1ĆILH
M7ĆILH
M3ĆILHM3ĆILH
M7ĆIHH
M3ĆIHH
CM5ĆMSB
M1ĆILLM1ĆILL
CM6ĆIL M6ĆOL
M2ĆILLM2ĆILL
M3ĆILLM3ĆILL
M3ĆIHLM3ĆIHL
00071017
M7ĆILL M7ĆIHL
Legal Module Placement in 32Ćpoint Complementary
Any module in any slot in primary chassis. Complement of primary chassis module in complementary chassis slot. Any input module complemented by an output module or empty slot. Any output module complemented by an input module or empty slot. Any block transfer module complemented with a block transfer module or empty slot.
An empty slot complemented by an empty slot, input or output module
I/O GroupI/O Group
I/O GroupI/O Group
00
00 11
11 22
22 33
33 44
44 55
55 66
66 77
77
CM0ĆOLH
M0ĆOLH
CM0ĆOHH
M0ĆOHH M1ĆOLH
M1ĆOHH M2ĆOLHM2ĆOLH
CM2ĆOH
M2ĆOHHM2ĆOHH M3ĆOLH
M3ĆOLH M3ĆOHH
M3ĆOHH
CM0ĆOLL
M0ĆOLL
CM0ĆOHL
M0ĆOHL
M1ĆOLL
M1ĆOHL
M1ĆOHLM1ĆOHLM1ĆOHHM1ĆOHH
CM2ĆOL
M2ĆOLH M2ĆOHL
M3ĆOLL
M3ĆOLL
M3ĆOHL
M3ĆOHL
Output Image Table for Rack N+1 and (N+1)C
I/O Group
0
0 1
1 2
2 3
3 4
4 5
5 6
6 7
7
M4ĆMCB
M5ĆMCB
CM7ĆOLH
M3ĆILHM3ĆILH
CM7ĆOHH
M3ĆIHH
CM5ĆMCB
M1ĆIHLM1ĆIHL
M2ĆILLM2ĆILL
CM7ĆOLL
M3ĆILLM3ĆILL
CM7ĆOHL
M3ĆIHLM3ĆIHL
00071017
Publication 1794ĆUM009D-EN-P - April 2004
3–16 Communicating with FLEX I/O Modules
T
Mapping Data into the Image Tables
After the rack size has been determined by the remote I/O adapter, the data from the modules must be mapped into the data tables. Data associated with digital modules is mapped into the input and output image table.
Data transfer to and from the remote I/O adapter and digital modules occurs every flexbus scan. This data is mapped into the input/output image table.
The switch settings on the adapter module
IMPORTAN
For analog modules, only the MSB and MCB block transfer bytes are mapped into the input and output image table. The remote I/O adapter transfers data to analog I/O modules (block transfer write) and from analog I/O modules (block transfer read) using BTW and BTR instructions in your ladder diagram program. This data is mapped to the data files selected in the ladder logic block transfer instructions.
The adapter identifies the type of module in each base unit when the module is added, and stores this information for later use, if necessary.
determine whether both the input and output bits are transferred. Standard addressing is the only mode that maps both input and output bits for each module.
Determining Rack Size
If you are changing your configuration, you
IMPORTANT
ATTENTION
!
After the remote I/O adapter has identified the modules present in its system, it creates a “rack image” so data transfer can take place using the remote I/O protocol.
Building a rack image consists of:
must power down, then power back up after changing a module type in a terminal base unit.
In Standard Addressing Mode, FLEX I/O modules do not support complementary I/O. Do not attempt to use the complementary image table word of a module in Standard Addressing Mode. The complementary word is reserved for use by the module.
mapping each module to an I/O group (16 bits of input and 16
bits of output)
determining rack size – all empty terminal bases are counted
unless they occur at the end of the rack
automatically sizing the rack image, based upon the mode switch
setting
Publication 1794ĆUM009D-EN-P - April 2004
smallest rack size is 1/4, regardless of the mode switch settings
Some examples of rack definition are shown below.
Example 1-8Terminal Bases, 8 Modules
Adapter
= 2 Logical Racks in Standard 32 mode, any density or analog module mix = 1 Logical Rack in Standard mode, any density or analog module mix
= 1/4 Rack in Compact mode with 8Ćpt modules; 1/2 Rack in Compact mode (with 16Ćpt modules)
Module Module Module Module
Module Module Module Module
Example 2 - 16 Terminal Bases, 16 Modules, Complementary Mode
PrimaryĆ
Adapter
Module Module Module Module
Module Module Module Module
3–17Communicating with FLEX I/O Modules
Complement
Adapter
Module Module Module Module Module Module Module Module
= 2 Logical Racks in Complementary 32 mode (16 modules total, any density), = 1 Logical Rack in Complementary mode (16 16Ćpt modules), primary input modules - complement
output modules and vice versa; analog complemented with another analog module or an empty slot
= 1/2 Rack in Complementary mode (16 8Ćpt modules), primary input modules - complement output
modules and vice versa; analog complemented with an empty slot
Last
Module
Position
0 1/4 rack 1/4 rack 1/4 rack 1/4 rack 1/4 rack 1/4 rack 1/4 rack
1 1/2 rack 1/4 rack 1/4 rack 1/4 rack 1/2 rack 1/4 rack 1/4 rack
2 3/4 rack 1/2 rack 1/4 rack 1/4 rack 3/4 rack 1/2 rack 1/4 rack
3 Full rack 1/2 rack 1/4 rack 1/4 rack Full rack 1/2 rack 1/4 rack
4 1-1/4 rack 3/4 rack 1/2 rack 1/4 rack 1-1/4 rack 3/4 rack 1/2 rack
Standard32Standard Compact16Compact8Complement32Complement16Complement 8
Rack Size for each Addressing Mode
5 1-1/2 rack 3/4 rack 1/2 rack 1/4 rack 1-1/2 rack 3/4 rack 1/2 rack
6 1-3/4 rack Full rack 1/2 rack 1/4 rack 1-3/4 rack Full rack 1/2 rack
7 2 Full racks Full rack 1/2 rack 1/4 rack 2 Full racks Full rack 1/2 rack
Publication 1794ĆUM009D-EN-P - April 2004
3–18 Communicating with FLEX I/O Modules
If a rack size offset by the selected quarter results in more than a full rack, the adapter will declare a rack fault and error as indicated.
In 32 point mode, the starting quarter should always be 0 (switches S1–8 and S1–7 on).
Operating Modes
ATTENTION
!
Most reset commands are issued by the processor when it is placed in the PROG mode. However, the processor automatically issues a special command to any rack declared faulted regardless of the processor mode.
When this special command is received by the faulted remote I/O adapter, and processor restart lockout (PRL) has not been selected, the adapter will:
Do not use the auto-config feature of 6200 software when using a PLC-3 processor with 1775-S4A or 1775-S4B scanner modules. If you do an auto-config for a scanner channel containing 1 or more 1794-ASB adapters with that configuration, the adapters may not show up in the scan list for that scanner channel. Manually insert these adapters into the scan list for the scanner.
continue to read output image data from the link, and queue block
transfers if MCBs are detected
reset all bits in the output words of digital modules
reset all bits in the write words of analog modules up to but not
including the write words of the safe state values
assigns safe state values to outputs of analog modules
issue a reply command
If processor restart lockout (PRL) has been selected, the adapter does not update data, does not issue a reply command, and does not clear the fault.
Chapter Summary
Publication 1794ĆUM009D-EN-P - April 2004
In this chapter, you learned how to address your I/O, how to determine rack size, and how the modules are mapped


Chapter Objectives
Fault Conditions
In this chapter, we tell you:
about the indicators on the module front plate
how to use the indicators for troubleshooting the module
Three conditions can cause the remote I/O adapter to declare a communication fault.
no remote I/O (link) communication for more than 100ms
no commands issued to this address over the remote I/O link
within the last 255 link transactions
communication is lost to a module when Rack Fault Select is
enabled
When any of these conditions exist, the adapter will:
reset all digital outputs or leave them in their last state (depending
on the position of the last state switch, S2-1). Refer to page 2–9 for an explanation of analog module responses.
A communication fault will be automatically cleared by a command from the processor if PRL (processor restart lockout) is not selected, or by pressing the reset switch on the front of the module if PRL is selected.
Troubleshooting with the Indicator Lights
ADAPTER
FAULT
LOCAL

FAULT
Local Fault
Adapter Fault
Adapter Active
Power ON/OFF
Reset Switch
PWR
ACTIVE
Important: Cycling power to the adapter will also reset faults.
However, any queued block transfers will be lost, and all outputs will turn off, regardless of the position of the last state switch.
The module has indicators on the front plate as shown below. Use these indicators for troubleshooting the module. The following tables describes problems that may occur, probable causes, and recommended courses of action.
Publication 1794ĆUM009D-EN-P - April 2004
4–2 Troubleshooting
Possibly module removed
All other modules: Outputs active
py
Adapter Fault
Adapter Active
Local Fault
Table 4.A Remote I/O System Troubleshooting Guide

ADAPTER
ACTIVE
FAULT
LOCAL
FAULT
PWR
Communication States and Module Display
Local
Fault
Off Off On Normal Communications
Adapter
Fault
Adapter
Active
Operating State Actions Fault Reset
Outputs enabled. Communicating with scanner
Outputs disabled
Off Off Blinking Program or Test mode
Communicating with scanner Sending current input status back to scanner.
All modules; digital outputs in the
Off Off Off
Communication (lack of communications)
rack follow HLS setting. Refer to page 2-9 for analog output action.
Off Blinking alternately
Processor lockout in effect during communications by scanner
Outputs follow last state switch setting. No replies sent to scanner
Module Faults
Local
Fault
Adapter
Fault
Adapter
Active
Fault Condition Actions Fault Reset
On On Off Noise problems on I/O bus All outputs off. Communications off.
Following
On Off
Link
Status
Blinking Off On
Processor in RUN mode
Rack Fault Select NOT enabled
Different module installed replacing removed module.
Module not responding.
under power. Only module removed is affected.
Old inputs maintained. Outputs set to zero.
Module not responding: Old inputs maintained. Outputs set to zero.
(enabled). Sending current input status back to scanner.
Not applicable
Not applicable
Resume proper communications (if no processor restart lockout)
Press Reset button on front of adapter module (or cycle power) and resume proper communication.
Cycle power. (This fault is a fatal fault.)
AutoĆreset when incorrect module is removed; or cycle power to establish new identification for module.
Replace same module; or cycle power to establish new identification for module.
Publication 1794ĆUM009D-EN-P - April 2004
Local
Possibly module removed
All other modules: Outputs
py
Possibly module removed
py
Not applicable. SW2
)
correct fault.)
d
Fault
Blinking OFF Blinking
Processor in PROG/TEST mode
Rack Fault Select NOT enabled
Adapter
Fault
Adapter
Active
Module not responding.
under power. Only module removed is affected.
Module Faults
Module not responding: Old inputs maintained. Outputs set to to zero.
disabled. Sending current input status back to scanner.
4–3Troubleshooting
Fault ResetActionsFault Condition
Replace same module; or cycle power to establish new identification for module.
Blinking Off Blinking
Processor in RUN/PROG/TEST
Rack Fault Select enabled
Local
Fault
Off Blinking in unison Incorrect starting I/O group number.
On On On Incorrect baud rate setting.
Blinking On Off
Local Fault
Off On Off
Adapter
Fault
Blinking in sequence
Adapter
Fault
Adapter
Active
Adapter
Active
Module not responding.
under power. Only module removed is affected.
Configuration Faults
Fault Condition Actions Fault Reset
Another adapter on the link has the same address.
Illegal module placement - compact addressing mode selected.
Additional Faults and Module Displays
Fault Condition Actions Fault Reset
Random Access Memory fault.
Read Only Memory fault (on powerup only).
Internal watchdog timer timed out.
Module not responding. All outputs set to 0. All other modules; digital outputs in the rack follow HLS setting. Refer to page 2-9 for analog output action. No replies sent to scanner.
Not applicable.
Not applicable.
Reset outputs. Stop communicating on remote I/O link.
Outputs remain reset. Communication never starts.
Try to reset outputs. Stops communicating on the remote I/O link.
Replace same module; or cycle power to establish new identification for module.
Turn power off. Set SW1 and
correctly.Turn power on.
Correct module placement and cycle power.
Cycle power. (This may not correct fault. If this does not correct the fault, replace the module with a known goodmodule, andreturntheba module to the factory for repair.
Chapter Summary
In this chapter you learned how to use the indicators on the front of the module to troubleshoot your module.
Publication 1794ĆUM009D-EN-P - April 2004
4–4 Troubleshooting
Publication 1794ĆUM009D-EN-P - April 2004


1794ĆASB Series E Specifications
Note: This adapter cannot be used with PLCĆ2 processors This adapter can communicate with FLEX Integra analog
modules and 32-point FLEX modules.
I/O Capacity 8 modules
Power Supply Note: In order to comply with CE Low Voltage Directives, you must use a Safety
Input Voltage Rating 24V dc nominal
Input Voltage Range 11.0V to 31.2V dc (includes 5% ac ripple)
Communication Rate 57.6k bps
Indicators Power - green
Flexbus Output Current 640mA maximum
Isolation Voltage 500V ac between user power and flexbus
Power Consumption 330mA at 24V; 730mA at 12V
Power Dissipation 4.6W maximum @ 31.2V dc
Thermal Dissipation 15.7 BTU/hr @ 31.2V dc
Environmental Conditions
Operating Temperature
Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)
Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat)
Shock
Operating Nonoperating
Vibration IEC 60068-2-6 (Test Fc, Operating)
ESD Immunity IEC 61000-4-2
Radiated RF Immunity IEC 61000-4-3
EFT/B Immunity IEC 61000-4-4
Specifications continued on next page
Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to power this adapter.
115.2k bps
230.4k bps
Adapter Active - green Adapter fault - red Local fault - red
IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
32 to 131°F(0to55°C)
IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal Shock)
-40 to 185°F (-40 to 85°C)
5 to 95%, noncondensing
IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30g 50g
5g @ 10-500Hz
4kV contact discharges 8kV air discharges
10V/m with 1kHz sine-wave 80% AM from 30MHz to 2000MHz
+4kV @ 2.5kHz on power ports
2kV @ 5kHz on communications ports
+
Publication 1794ĆĆUM009D-EN-P - April 2004
Specifications A–2
1794ĆASB Series E Specifications
Surge Transient Immunity IEC 61000-4-5
1kV line-line (DM) and +2kV line-earth (CM) on signal ports
+
Conducted RF Immunity IEC 61000-4-6
10V rms with 1kHz sine wave 80% AM from 150kHz to 80MHz
Emissions CISPR 11
Group 1, Class A (with appropriate enclosure)
Enclosure Type Rating None (open-style)
Remote I/O Cable Belden 9463 or equivalent as specified in publication ICCGĆ2.2
Remote I/O Connector Plug Part Number 942029-03
Power Conductors
Wire Size
Category
Agency Certification (when product is marked)
Publications Installation Instructions 1794-IN046
1 Use this conductor category information for planning conductor routing. Refer to publication
1770Ć4.1, Industrial Automation Wiring and Grounding Guidelines."
2
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details
12 gauge (4mm2) maximum sokid or stranded wire rated at 75oC or greater 3/64 inch (1.2mm) insulation max.
1
2
UL UL Listed Industrial Control Equipment
UL UL Listed for Class I, Division 2 Group A, B, C and D Hazardous Locations CSA CSA Certified Process Control Equipment for Class I, Division 2 Group A, B,
C, D Hazardous Locations
2
European Union 94/9/EEC ATEX Directive, compliant with
EEx
EN 50021; Potentially Explosive Atmospheres, Protection n"
2
European Union 89/336/EEC EMC Directive, compliant with:
CE
EN 50081-2, Industrial Emissions EN 50082-2, Industrial Immunity EN 61326, Meas./Control/Lab., Industrial Requirements EN 61000-6-2, Industrial Immunity
2
Australian Radiocommunications Act,compliant with:
C-Tick
AS/NZS 2064, Industrial Emissions
Publication 1794ĆĆUM009D-EN-P - April 2004
Specifications A–3
European Zone 2 Certification
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/CE.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive. The examination and test results are recorded in confidential report No. 28 682 010.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021 (1999).
IMPORTANT
Observe the following additional Zone 2 certification requirements:
This equipment is not resistant to sunlight or other sources of UV
radiation.
The secondary of a current transformer shall not be open-circuited.
The marking ALCR" is to be considered as applicable" to individual
products.
Equipment of lesser Enclosure Type Rating must be installed in an
enclosure providing at least IP54 protection when applied in Class I, Zone 2 environments.
This equipment must be powered by energy limited associated
equipment as defined in EN 50021 when applied in Class I, Zone 2 environments.
Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40% when applied in Class I, Zone 2 environments.
Publication 1794ĆĆUM009D-EN-P - April 2004
Specifications A–4
Publication 1794ĆĆUM009D-EN-P - April 2004
Addressing
Standard,Compact,and
Appendix
Differences Between Remote I/O Adapter Series A, B, C, D and E
Major differences between adapter series are indicated in the following table.
Series A Series B Series C Series D Series E
Processor compatibility Can be used with PLCĆ2 processors Cannot be used with PLCĆ2 processors
Standard Mode - Analog module removal under power
Local Fault Indication Local Fault Indicator only
Hold Inputs
European Union Directives Compliance
Module Removal and Insertion Under Power (RIUP)
Recognize 1793 Integra analog modules
Block transfers continue when a block transfer module is removed from its base.
No complementary addressing
Standard mode of addressing only
When hold inputs is enabled, the adapter retains the last memory image present when a module is removed from the terminal base.
Does not comply with European Union Directives. NO CE mark.
Always enabled.
Cannot recognize 1793 Integra analog modules
Ceases to do block transfers and a block transfer bit is set when a block transfer module is removed from the chassis. This error bit provides feedback to the processor that a block transfer module has been removed.
The hold inputs feature applies only to digital modules. When hold inputs is enabled, the adapter retains the last memory image present when a digital module is removed from the terminal base. This feature does not apply to analog modules. If you need this feature for analog modules, you must simulate it in your programming.
Complies with European Union Directives. Has CE mark.
With Rack Fault Select enabled, local fault indication sent to scanner, and local fault indicator lighted. With Rack Fault Select disabled, local fault indicator lights.
Three modes of addressing:
Complementary
No module removal and insertion under power when Rack Fault Select is enabled.
Can recognize 1793 Integra analog modules
Five modes of addressing: Standard, Compact, Complementary, Standard 32, and Complementary 32
B
Publication 1794ĆĆUM009D-EN-P - April 2004
Differences Between Remote I/O Adapter Series A, B, C, D and E B–2
Publication 1794ĆĆUM009D-EN-P - April 2004
Appendix
C
Safety Approvals
The following information applies when operating this equipment in hazardous locations:
Products marked CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, and D Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING
!
Informations sur l'utilisation de cet équipement en environnements dangereux:
Les produits marqués CL I, DIV 2, GP A, B, C, D ne conviennent que une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un systéme, le code de température le plus défavorable (code de température le plus faible) peut eatre utilisé pour déterminer le code de température global du systéme. Les combinaisons d'equipements dans le systéme sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
EXPLOSION HAZARD -
Do not disconnect equipment unless power has been removed or the area is known to
be nonhazardous.
Do not disconnect connections to this equipment unless power has been removed or
the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of components may impair suitability for Class I, Division 2.
If this product contains batteries, they must only be changed in an area known to be
nonhazardous.
AVERTISSEMENT
!
!
RISQUE D'EXPLOSION -
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant
de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant
de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet équipement inadapté à une utilisation
en environnement de Classe 1, Division 2.
S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Publication 1794ĆĆUM009D-EN-P - April 2004
Safety Approvals C–2
Publication 1794ĆĆUM009D-EN-P - April 2004
Index
A
adapter switch settings, 2-8
addressing, 32 point standard, 3-7, 3-15
addressing mode selection switches, 2-9
addressing modes, 3-2
B
block transfer
read, 1-2 write, 1-2
C
communication rate switch, 2-10
compact mode, 3-8
complementary addressing mode, 3-12
complementary rack switch settings, 2-15
components, hardware, 1-3
connecting wiring, 2-7
D
data table mapping, 3-16
defining racks in Flex I/O, 3-17
determining rack size, 3-16
diagnostic indicators, 1-3
F
fault conditions, 4-1
L
last chassis switch, 2-9
M
mapping, data into image tables, 3-16
mode
addressing, 3-2 compact, 3-8 complementary addressing, 3-12 standard, 3-6
mode selection switches, 2-12
mode switches, 2-9
mounting on a DIN rail
before installing terminal bases, 2-3 on an existing system, 2-4
mounting on a wall or panel, 2-5
P
power requirements, 2-3
primary rack switch settings, with
complementary, 2-15
processor lockout switch, 2-10
R
rack definition, 3-17
rack image, 3-16
remote I/O cable, connecting the wiring,
2-7
removing the adapter, 2-4
replacing an adapter, 2-4
H
hold inputs, 2-8
hold inputs switch, 2-8
hold last state switch, 2-10
I
I/O rack number, 2-8
I/O rack number switches, 2-8
indicators, 4-1
S
safe state values, 3-18
selecting the mode, 2-12
setting the address switches, 2-13, 2-15
specifications, A-1
standard mode, 3-6
starting I/O group, 2-8
switch settings, 2-8
Publication 1794ĆUM009D-EN-P - April 2004
IndexI–2
troubleshooting, fault conditions, 4-1
troubleshooting guide, 4-2
troubleshooting indicators, 4-1
Publication 1794ĆUM009D-EN-P - April 2004
AllenĆBradley
Publication Problem Report
If you find a problem with our documentation, please complete and return this form.
Pub. Name
Cat. No. Pub. No. Pub. Date Part No.
Check Problem(s) Type: Describe Problem(s): Internal Use Only
Completeness
What information is missing?
Remote I/O Adapter User Manual
1794ĆASB/E 1794ĆUM009D-EN-P Aprio 2004
text illustrationTechnical Accuracy
procedure/step
example
explanation
illustration
guideline
other
definition
feature
info in manual
(accessibility)
info not in
manual
Clarity
What is unclear?
Sequence
What is not in the right order?
Other Comments
Use back for more comments.
Your Name Location/Phone
Return to: Marketing Communications, AllenĆBradley Co., 1 AllenĆBradley Drive, Mayfield Hts., OH 44124Ć6118 Phone: (216)646Ć3176
FAX: (216)646Ć4320
Publication ICCGĆ5.21ĆMay 1990 PN 955107Ć82
I–2
Other Comments
PLEASE FOLD HERE
BUSINESS REPLY MAIL
FIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OH
POSTAGE WILL BE PAID BY THE ADDRESSEE
TECHNICAL COMMUNICATION
1 ALLEN BRADLEY DR
MAYFIELD HEIGHTS OH 44124-9705
NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES
PLEASE REMOVE
Publication 1794ĆUM009D-EN-P - April 2004
Publication 1794ĆUM009D-EN-P - April 2004
Publication 1794ĆUM009D-EN-P - April 2004
Support Services
At Allen-Bradley, customer service means experienced representatives at Customer Support Centers in key cities throughout the world for sales service and support. Our value-added services include:
Technical Support
SupportPlus programs
telephone support and 24-hour emergency hotline
software and documentation updates
technical subscription services
Engineering and Field Services
application engineering assistance
integration and start-up assistance
field service
maintenance support
Technical Training
lecture and lab courses
self-paced computer and video-based training
job aids and workstations
training needs analysis
Repair and Exchange Services
your only “authorized” source
current revisions and enhancements
worldwide exchange inventory
local support
Publication 1794ĆUM009D-EN-P - April 2004
AllenĆBradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.
Worldwide representation.
Argentina Australia Austria Bahrain Belgium Brazil Bulgaria Canada Chile China, PRC Colombia Costa Rica Croatia Cyprus Czech Republic Denmark Ecuador Egypt El Salvador Finland France Germany Greece Guatemala Honduras Hong Kong Hungary Iceland India Indonesia Ireland Israel Italy Jamaica Japan Jordan Korea Kuwait Lebanon Malaysia Mexico Netherlands New Zealand Norway Pakistan Peru Philippines Poland Portugal Puerto Rico Qatar Romania Russia-CIS Saudi Arabia Singapore Slovakia Slovenia South Africa, Republic Spain Sweden Switzerland Taiwan Thailand Turkey United Arab Emirates United Kingdom United States Uruguay Venezuela Yugoslavia
AllenĆBradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382Ć2000 Fax: (1) 414 382Ć4444
Publication 1794ĆUM009D-EN-P - April 2004
Supersedes publication 1794ĆUM009C-EN-P - MARCH 2003 Copyright 2004 AllenĆBradley Company, Inc. Printed in USA
Publication 1794ĆUM009D-EN-P - April 2004
Loading...