Rockwell Automation 1793-OV16 User Manual

Installation Instructions
FLEX Integra 16 Protected Sink Output Module
(Cat. No. 1793-OV16P and -OV16PS)

Module Installation

This module mounts on a DIN rail. It connects to an adapter or another FLEX I/O or FLEX Integra module. Note: If using this module with FL EX I/O modules, do not mount between FLEX I/O modules. Mount Integra modules to the right of FLEX I/O modules. To mount this module:
1. Remove the cover plug (if used) in the male connector of the unit to
which you are connect ing this module.
2. Position the module on the 35 x 7.5mm DIN rail A (A-B pt. no.
199-DR1).
3. Rotate the module onto the DIN rail with the top of the rail hooked
under the lip on the rear of the module.
A
A
30869-M
FLEX I/O and FLEX Integra are trademarks of Rockwell Automation Publication 1793-5.11 - December 1999
2 FLEX Integra 16 Protected Sink Output Module
30870-M
30871-M
30872-M
4. Press down to lock the module on the DIN rail.l
If the module does not lock in place, use a screwdriver of similar device to move the locking tab down, press the module flush with the DIN rail and release the locking tab to lock the module in place.
5. Firmly push the module into the adjacent module/terminal base until
the units lock together.
6. Repeat the above steps to install the next module.
7. T o remove an Integra module, you must work from the right side and
remove one module at a time. To disengage a module from its neighbor, place a common flat-bladed screwdriver between the 2 modules and turn 1/4 turn to separate the modules.
8. Then slide the module away from its left neighbor, and release the
locking lever to remove the module from the DIN rail.
Publication 1793-5.11 - December 1999
FLEX Integra 16 Protected Sink Output Module 3
ATTENTION: Do not remove this module under power. Removing this module under power will break the
!
electrical backplane (flexbus) connections. This can cause personal injury or pr operty damage by:
• sending an err oneous signal to yo ur system's field devices causing unintended machine motion
• causing an explosion in a hazardous environment
• breaking communication to modules beyond this module

European Union Directive Compliance

If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file:
• EN 50081-2 EMC - Generic Emission Standard, Part 2 - Industrial Environment
• EN 50082-2 EMC - Generic Immunity Standard, Part 2 - Industrial Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 - Equipment Requirements and Tests.
For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications:
• Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1
• Automation Systems Catalog, publication B111
This equipment is classified as open equipment and must be mounted in an enclosure during operation to provide safety protection.
Publication 1793-5.11 - December 1999
4 FLEX Integra 16 Protected Sink Output Module
0 123456789101112131415
A
B
41814
VV
COM
COM
A
B
012345678 9101112131415COM
COM
VV
41816

Wiring

This module is available with 2 styles of connectors; screw-cage (1793-OV16P) and spring-clamp (1793-OV16PS). Refer to the wiring figure below.
1793-OV16P
1793-OV16PS
Where: COM = common, V = + 24V dc, 0 thru 15 = outputs
1. Connect individual output wiring to terminals 0 through 15 on row A.
2. Connect associated power terminal to terminals on row B.
3. Connect +24V dc voltage to termina l V on row B.
4. Connect 24V dc common to terminal COM on ro w A.
5. If daisy-chaining +24V dc from th is module to the nex t FLEX Integra
module, connect a jumper from terminal V to terminal 8 on the next 8 point Integra module or terminal V on the next 16 point Integra module.
6. If daisy-chaining 24V dc common from this module to the next FLEX
Integra module, connect a jumper from terminal COM on this module to terminal 0 on the next 8 point Integra module or to terminal COM on the next 16 point Integra module.
.
ATTENTION: Total current draw through t he module’s (V) voltage terminals is limited to 10A. Separate power
!
connections to the module may be required.
Publication 1793-5.11 - December 1999
FLEX Integra 16 Protected Sink Output Module 5

Wiring Connections

Channel Output Power Channel Output Power
0 0 Connect 11 99 22 1010 33 1111 44 1212 55 1313 66 1414
77 1515 +24V dc Power terminals V are internally connected together in the module. 24V dc
common
Common terminals COM are internally connected together in the module.
associated
power
terminal for
each
channel to
row B
8 8 Connect
associated
power
terminal for
each
channel to
row B

Indicators

24 VDC SINK OUTPUT - PROTECTED
0 1 2 3 4 5 6 7 8 9 10 11 14 1512 13
AB
1793-OV16P
41810
A = Status indicators - shows status of indivi dual outputs B = Insertable label for writing individual output designations

Memory Mapping

Bit/
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word
Read Reserved
O15O14O13O12O11O10O9O8O7O6O5O4O3O2O1O
Write
Where: O = Output
Important: Input and output wiring must be in accordance with Class I,
Division 2 wiring methods and in accordance with the authority having jurisdiction.
Publication 1793-5.11 - December 1999
0
6 FLEX Integra 16 Protected Sink Output Module
CUS
LISTED
CL I, DIV 2
GP A,B,C,D
TEMP
LISTED
CL I, DIV 2
GP A,B,C,D
TEMP
C-UL and UL Hazardous Location Approval
C-UL and UL certifies products for general use as well as for use in hazardous locations. Actual
C-UL and UL certification is indicated by the product label as shown below, and not by
statements in any user documentation.
Example of the C-UL and UL certification product label
To comply with C-UL and UL certification for use in hazardous locations, the following information becomes a part of the product literature for this C-UL and UL-certified industrial constrol product.
Important: Due to the modular nature of a
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only.
The products having the appropriate C-UL and UL markings (that is, Class I, Division 2, Groups A, B, C, D) are certified for use in other equipment where the suitability of combination (that is, application or use) is determined by the C-UL and UL or the local inspection office having jurisdiction
Peripheral equipment must be suitable for the location in which it is used.
programmable control system, the product with the highest temperature rating determines the overall temperature code rating of a programmable control system in a Class I, Division 2, location. The temperature code rating is marked on the product label as shown.
Approbation d’utilisation dans des environnements dangereux par la C-UL and UL
La C-UL and UL certifie des produits pour une
utilisation générale aussi bien que pour une utilisation en environnements dangereux. La certification C-UL and UL en vigueur est indiquée par l'étiquette produit et non par des indications dans la documentation utilisateur.
Exemple d'étiquette de certification d'un produit par la C-UL and UL
Importa nt: De par la nature modulaire des systèmes de
EPour satisfaire à la certification C-UL and UL en environnements dangereux, les informations suivantes font partie intégrante de la documentation des produits de commande industrielle certifiés.
Cet équipement ne convient qu’à une utilisation dans des environnements de Classe I, Division 2, Groupes A, B, C, D ou non dangereux.
Les produits portant le marquage C-UL and UL approprié (c'est-à-dire Classe I, Division 2, Groupes A, B, C, D) sont certifiés pour une utilisation avec d'autres équipements, les combinaisons d’applications et d’utilisation étant déterminées par la C-UL and UL ou le bureau local d'inspection.
L'équipement périphérique doit convenir à l'emplacement d'utilisation.
commande programmables, le produit ayant le code de température le plus élevé détermine le code de température global du système dans un environnement de Classe I, Division 2. Le code de température est indiqué sur l'étiquette produit.
7HPSHUDWXUHFRGHUDWLQJ &RGHGHWHPSpUDWXUH
CL I, DIV 2
GP A,B,C,D
TEMP
CUS
LISTED
The following warnings apply to products having C-UL and UL certification for use in hazardous locations.
Look for temperature code rating here.
CUS
LISTED
Les avertissements suivants s'appliquent aux produits ayant la certification C-UL and UL pour une utilisation dans des environnements dangereux.
CUS
CL I, DIV 2
GP A,B,C,D
TEMP
Le code de température est indiqué ici.
Publication 1793-5.11 - December 1999
FLEX Integra 16 Protected Sink Output Module 7
C-UL and UL Hazardous Location Approval
WARNING: Explosion Hazard
Substitution of components may impair
suitability for Class I, Division 2.
Do not replace components unless power has been switched off or the area is known to be non-hazardous.
Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
Do not disconnect connectors unless power has been switched off or the area is known to be non-hazardous. Secure any user-supplied connectors that mate to external circuits on this equipment by using screws, sliding latches, threaded connectors, or other means such that any connection can withstand a 15 Newton (3.4 lb.) separating force applied for a minimum of one minute.
Batteries must only be changed in an area known to be non-hazardous.
C-UL and UL logo is a registered trademark of the Underwriters Laboratories.
Approbation d’utilisation dans des environnements dangereux par la C-UL and UL
$9(57,66(0(175LVTXHGH[SORVLRQ
La substitution de composants peut rendre ce
matériel inadapté à une utilisation en environnement de Classe I, Division 2.
Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de remplacer des composants.
Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs fournis par l'utilisateur pour se brancher aux circuits externes de cet appareil à l 'aide de vis, loquets coulissants, connecteurs filetés ou autres, de sorte que les connexions résistent à une force de séparation de 15 Newtons (1,5 kg - 3,4 lb.) appliquée pendant au moins une minute.
S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Le sigle C-UL and UL est une marque déposée de la Underwriters Laboratories.
Specifications - 16 Protected Output Module Cat. No. 1793-OV16P and -OV16PS
Module Type 16 digital output - sinking, protected
1793-OV16P - screw-cage terminations
1793-OV16PS - spring-clamp terminations Module Location DIN rail mounting Number of Channels 1 groups of 16, nonisolated, sinking On-state Voltage 10V dc minimum
24V dc nominal
31.2V dc maximum
On-state Current 1mA minimum per channel
500mA maximum per channel Surge Current 2A for 50ms, repeatable every 2s Off-state Voltage 31.2V dc maximum Off-state Current 0.5mA maximum leakage On-state Voltage Drop 0.2V dc maximum Isolation Voltage 100% tested at 850V dc for 1s between user and
system.
No isolation between individual channels
Publication 1793-5.11 - December 1999
Specifications - 16 Protected Output Module Cat. No. 1793-OV16P and -OV16PS
Output Signal Delay Time
Off to On On to Off
0.5ms maximum
1.0ms maximum Flexbus Current 80mA maximum Power Dissipation 4.2W @ 31.2V dc Thermal Dissipation 14.3 BTU/hr @ 31.2V dc Indicators 16 yellow channel status indicators Fusing Outputs are electronically protected External dc Power Voltage
Current
Dimensions Inches
(Millimeters)
Environmental Conditions
Operational Temperature Storage Temperature Relative Humidity Shock Operating
Nonoperating
Vibration
Conductors Wire Size
Category
19.2-31.2V dc (5% ac ripple)
49mA
2.72H x 3.7D x 3.2W
(69H x 94D x 80W)
o
C (32 to +131oF)
0 to +55
-40 to +85
o
C (-40 to +185oF) 5 to 95% noncondensing Tested to 30g peak acceleration, 11(+ Tested to 50g peak acceleration, 11(+
Tested 5g @ 10-500Hz per IEC68-2-6
2
12 gauge to 18 gauge (4mm stranded wire rated @ 75
to 0.75mm2 )
o
C minimum
3/64 in (1.2mm) maximum insulation
1
2
1)ms pulse width
1)ms pulse width
Screw Terminal Torque 5-7 lb-in (0.5-0.6Nm) Agency Certification
(when product is marked)
• C-UL Listed
• C-UL Class I, Division 2 Groups A, B, C and D certified
• UL listed
• CE marked for all applicable directives
• C-Tick marked for all applicable acts
1 Use this category information for planning conductor routing as described in publication 1770-4.1, “Wiring and
Grounding Guidelines for Noise Immunity.”
Publication 1793-5.11 - December 1999 PN957259-18
Supersedes publication 1793-5.11 - September 1999 © (1999) Rockwell International Corporation.Printed in USA