This module mounts on a DIN rail. It connects to an adapter or another
FLEX I/O or FLEX Integra module. Note: If using this module with FL EX
I/O modules, do not mount between FLEX I/O modules. Mount Integra
modules to the right of FLEX I/O modules. To mount this module:
1. Remove the cover plug (if used) in the male connector of the unit to
which you are connect ing this module.
2. Position the module on the 35 x 7.5mm DIN rail A (A-B pt. no.
199-DR1).
3. Rotate the module onto the DIN rail with the top of the rail hooked
under the lip on the rear of the module.
A
A
30869-M
FLEX I/O and FLEX Integra are trademarks
of Rockwell Automation Publication 1793-5.11 - December 1999
2FLEX Integra 16 Protected Sink Output Module
30870-M
30871-M
30872-M
4. Press down to lock the module on the DIN rail.l
If the module does not lock in place, use a screwdriver of similar
device to move the locking tab down, press the module flush with the
DIN rail and release the locking tab to lock the module in place.
5. Firmly push the module into the adjacent module/terminal base until
the units lock together.
6. Repeat the above steps to install the next module.
7. T o remove an Integra module, you must work from the right side and
remove one module at a time. To disengage a module from its
neighbor, place a common flat-bladed screwdriver between the 2
modules and turn 1/4 turn to separate the modules.
8. Then slide the module away from its left neighbor, and release the
locking lever to remove the module from the DIN rail.
Publication 1793-5.11 - December 1999
FLEX Integra 16 Protected Sink Output Module3
ATTENTION:Do not remove this module under
power. Removing this module under power will break the
!
electrical backplane (flexbus) connections. This can cause
personal injury or pr operty damage by:
• sending an err oneous signal to yo ur system's field
devices causing unintended machine motion
• causing an explosion in a hazardous environment
• breaking communication to modules beyond this
module
European Union Directive Compliance
If this product has the CE mark it is approved for installation within the
European Union and EEA regions. It has been designed and tested to meet
the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in
whole or in part, documented in a technical construction file:
• EN 50081-2 EMC - Generic Emission Standard, Part 2 - Industrial
Environment
• EN 50082-2 EMC - Generic Immunity Standard, Part 2 - Industrial
Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage,
by applying the safety requirements of EN 61131-2 Programmable
Controllers, Part 2 - Equipment Requirements and Tests.
For specific information required by EN 61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
• Industrial Automation Wiring and Grounding Guidelines For Noise
Immunity, publication 1770-4.1
• Automation Systems Catalog, publication B111
This equipment is classified as open equipment and must be mounted in an
enclosure during operation to provide safety protection.
Publication 1793-5.11 - December 1999
4FLEX Integra 16 Protected Sink Output Module
0 123456789101112131415
A
B
41814
VV
COM
COM
A
B
012345678 9101112131415COM
COM
VV
41816
Wiring
This module is available with 2 styles of connectors; screw-cage
(1793-OV16P) and spring-clamp (1793-OV16PS). Refer to the wiring
figure below.
1793-OV16P
1793-OV16PS
Where: COM = common, V = + 24V dc, 0 thru 15 = outputs
1. Connect individual output wiring to terminals 0 through 15 on row A.
2. Connect associated power terminal to terminals on row B.
3. Connect +24V dc voltage to termina l V on row B.
4. Connect 24V dc common to terminal COM on ro w A.
5. If daisy-chaining +24V dc from th is module to the nex t FLEX Integra
module, connect a jumper from terminal V to terminal 8 on the next 8
point Integra module or terminal V on the next 16 point Integra
module.
6. If daisy-chaining 24V dc common from this module to the next FLEX
Integra module, connect a jumper from terminal COM on this module
to terminal 0 on the next 8 point Integra module or to terminal COM
on the next 16 point Integra module.
.
ATTENTION:Total current draw through t he module’s
(V) voltage terminals is limited to 10A. Separate power
!
connections to the module may be required.
Publication 1793-5.11 - December 1999
FLEX Integra 16 Protected Sink Output Module5
Wiring Connections
ChannelOutputPowerChannelOutputPower
00Connect
1199
221010
331111
441212
551313
661414
771515
+24V dcPower terminals V are internally connected together in the module.
24V dc
common
Common terminals COM are internally connected together in the
module.
associated
power
terminal for
each
channel to
row B
88Connect
associated
power
terminal for
each
channel to
row B
Indicators
24 VDC SINK OUTPUT - PROTECTED
0 1 2 3 4 5 67 8 9 10 1114 1512 13
AB
1793-OV16P
41810
A = Status indicators - shows status of indivi dual outputs
B = Insertable label for writing individual output designations
Memory Mapping
Bit/
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word
ReadReserved
O15O14O13O12O11O10O9O8O7O6O5O4O3O2O1O
Write
Where: O = Output
Important: Input and output wiring must be in accordance with Class I,
Division 2 wiring methods and in accordance with the
authority having jurisdiction.
Publication 1793-5.11 - December 1999
0
6FLEX Integra 16 Protected Sink Output Module
CUS
LISTED
CL I, DIV 2
GP A,B,C,D
TEMP
LISTED
CL I, DIV 2
GP A,B,C,D
TEMP
C-UL and UL Hazardous Location Approval
C-UL and UL certifies products for general use as
well as for use in hazardous locations. Actual
C-UL and UL certification is indicated by the
product label as shown below, and not by
statements in any user documentation.
Example of the
C-UL and UL
certification
product label
To comply with C-UL and UL certification for use
in hazardous locations, the following information
becomes a part of the product literature for this
C-UL and UL-certified industrial constrol product.
Important: Due to the modular nature of a
•
This equipment is suitable for use in Class
I, Division 2, Groups A, B, C, D, or
non-hazardous locations only.
•
The products having the appropriate C-UL
and UL markings (that is, Class I, Division 2,
Groups A, B, C, D) are certified for use in
other equipment where the suitability of
combination (that is, application or use) is
determined by the C-UL and UL or the local
inspection office having jurisdiction
•
Peripheral equipment must be suitable for
the location in which it is used.
programmable control system, the
product with the highest temperature
rating determines the overall
temperature code rating of a
programmable control system in a Class
I, Division 2, location. The temperature
code rating is marked on the product
label as shown.
Approbation d’utilisation dans des
environnements dangereux par la C-UL and UL
La C-UL and UL certifie des produits pour une
utilisation générale aussi bien que pour une
utilisation en environnements dangereux. La
certification C-UL and UL en vigueur est indiquée
par l'étiquette produit et non par des indications
dans la documentation utilisateur.
Exemple
d'étiquette de
certification d'un
produit par la
C-UL and UL
Importa nt: De par la nature modulaire des systèmes de
EPour satisfaire à la certification C-UL and UL en
environnements dangereux, les informations
suivantes font partie intégrante de la
documentation des produits de commande
industrielle certifiés.
•
Cet équipement ne convient qu’à une
utilisation dans
des environnements de Classe I, Division 2,
Groupes A, B, C, D ou non dangereux.
•
Les produits portant le marquage C-UL and
UL approprié (c'est-à-dire Classe I, Division
2, Groupes A, B, C, D) sont certifiés pour une
utilisation avec d'autres équipements, les
combinaisons d’applications et d’utilisation
étant déterminées par la C-UL and UL ou le
bureau local d'inspection.
•
L'équipement périphérique doit convenir à
l'emplacement d'utilisation.
commande programmables, le produit
ayant le code de température le plus élevé
détermine le code de température global du
système dans un environnement de Classe
I, Division 2. Le code de température est
indiqué sur l'étiquette produit.
7HPSHUDWXUHFRGHUDWLQJ&RGHGHWHPSpUDWXUH
CL I, DIV 2
GP A,B,C,D
TEMP
CUS
LISTED
The following warnings apply to products having
C-UL and UL certification for use in hazardous
locations.
Look for temperature
code rating here.
CUS
LISTED
Les avertissements suivants s'appliquent aux
produits ayant la certification C-UL and UL pour une
utilisation dans des environnements dangereux.
CUS
CL I, DIV 2
GP A,B,C,D
TEMP
Le code de température
est indiqué ici.
Publication 1793-5.11 - December 1999
FLEX Integra 16 Protected Sink Output Module7
C-UL and UL Hazardous Location Approval
WARNING:Explosion Hazard
•
Substitution of components may impair
suitability for Class I, Division 2.
•
Do not replace components unless power
has been switched off or the area is known
to be non-hazardous.
•
Do not disconnect equipment unless power
has been switched off or the area is known
to be non-hazardous.
•
Do not disconnect connectors unless
power has been switched off or the area is
known to be non-hazardous. Secure any
user-supplied connectors that mate to
external circuits on this equipment by using
screws, sliding latches, threaded
connectors, or other means such that any
connection can withstand a 15 Newton (3.4
lb.) separating force applied for a minimum
of one minute.
•
Batteries must only be changed in an area
known to be non-hazardous.
C-UL and UL logo is a registered trademark of the
Underwriters Laboratories.
Approbation d’utilisation dans des
environnements dangereux par la C-UL and UL
$9(57,66(0(175LVTXHGH[SORVLRQ
La substitution de composants peut rendre ce
•
matériel inadapté à une utilisation en
environnement de
Classe I, Division 2.
•
Couper le courant ou s'assurer que
l’environnement est classé non dangereux
avant de remplacer des composants.
•
Couper le courant ou s’assurer que
l’environnement est classé non dangereux
avant de débrancher l'équipement.
•
Couper le courant ou s'assurer que
l’environnement est classé non dangereux
avant de débrancher les connecteurs. Fixer
tous les connecteurs fournis par l'utilisateur
pour se brancher aux circuits externes de cet
appareil à l 'aide de vis, loquets coulissants,
connecteurs filetés ou autres, de sorte que les
connexions résistent à une force de séparation
de 15 Newtons (1,5 kg - 3,4 lb.) appliquée
pendant au moins une minute.
•
S'assurer que l'environnement est classé non
dangereux avant de changer les piles.
Le sigle C-UL and UL est une marque déposée de
la Underwriters Laboratories.
1793-OV16PS - spring-clamp terminations
Module LocationDIN rail mounting
Number of Channels1 groups of 16, nonisolated, sinking
On-state Voltage10V dc minimum
24V dc nominal
31.2V dc maximum
On-state Current1mA minimum per channel
500mA maximum per channel
Surge Current2A for 50ms, repeatable every 2s
Off-state Voltage31.2V dc maximum
Off-state Current0.5mA maximum leakage
On-state Voltage Drop0.2V dc maximum
Isolation Voltage100% tested at 850V dc for 1s between user and
1.0ms maximum
Flexbus Current80mA maximum
Power Dissipation4.2W @ 31.2V dc
Thermal Dissipation14.3 BTU/hr @ 31.2V dc
Indicators16 yellow channel status indicators
FusingOutputs are electronically protected
External dc Power Voltage
Current
DimensionsInches
(Millimeters)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
ShockOperating
Nonoperating
Vibration
ConductorsWire Size
Category
19.2-31.2V dc (5% ac ripple)
49mA
2.72H x 3.7D x 3.2W
(69H x 94D x 80W)
o
C (32 to +131oF)
0 to +55
-40 to +85
o
C (-40 to +185oF)
5 to 95% noncondensing
Tested to 30g peak acceleration, 11(+
Tested to 50g peak acceleration, 11(+