Rockwell Automation 1793-OE2S User Manual

Allen-Bradley
FLEX Integra Analog Modules
(Cat. No. 1793-IE4, -IE4S, -OE2,
-OE2S, -IE2XOE1 and -IE2XOE1S)
User Manual
Important User Information
Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this manual we use notes to make you aware of safety considerations:
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss
Attention statements help you to:
identify a hazard
avoid a hazard
recognize the consequences
Important: Identifies information that is critical for successful application
and understanding of the product.
DeviceNetManager, Allen-Bradley, FLEX I/O and FLEX Integra are trademarks of Rockwell Automation
ControlNet is a trademark of ControlNet International.
DeviceNet is a trademark of Open DeviceNet Vendor Association, Inc.
Preface
Using This Manual
Purpose of this Manual This manual shows you how to use your FLEX Integra Analog modules
with Allen-Bradley programmable controllers. The manual helps you install, program and troubleshoot your modules.
Audience You must be able to program and operate an Allen-Bradley programmable
controller to make efficient use of your FLEX Integra modules. In particular, you must know how to program block transfers, and be familiar with DeviceNet or ControlNet software.
Vocabulary We assume that you know how to do this in this manual. If you do not, refer
to the appropriate programming and operations manual before you attempt to program your modules.
In this manual, we refer to:
the analog input or analog output module as the “input module” or
“output module”
the Programmable Controller as the “controller”
Manual Organization This manual is divided into five chapters. The following chart lists each
chapter with its corresponding title and a brief overview of the topics covered in that chapter.
Chapter Title Contents
1 Overview of FLEX Integra and
Analog modules
2 How to Install Your Analog Module How to install and wire the modules 3 Module Programming Explains block transfer programming, sample programs 4 Writing Configuration to and
Reading Status From with a Remote I/O Adapter
5 How Communication Takes Place
and I/O Image Table Mapping with the DeviceNet Adapter
6 Input, Status, Output and
Configuration with ControlNet
Appendix Title Contents
A Specifications Specifications for the analog modules
Describes FLEX Integra Analog modules, features, and how they function
Explains how to configure your modules and read status information from your modules when using a remote I/O adapter
Explains how you communicate with your modules, and how the I/O image is mapped when using a DeviceNet adapter
Explains how you communicate with your modules, and how the I/O image is mapped when using ControlNet.
Publication 1793-6.5.1 - April 1999
P-2 Using This Manual
Conventions We use these conventions in this manual:
In this manual, we show: Like this:
that there is more information about a topic in another chapter in this manual
that there is more information about the topic in another manual
For Additional Information For additional information on FLEX Integra and FLEX I/O systems and
modules, refer to the following documents:
Catalog Number
1793 Series
1793-IB4 4 Input Module 1793-5.1
1793-OB4P
1793-IB2XOB2P
1793-IE4 24V dc 4 Input Analog Module 1793-5.4
1793-IE2XOE1P 24V dc 2 In/1 Protected Output Analog Module 1793-5.6
1793-OW4
1794 1794 FLEX I/O Product Data 1794-2.1
1794-ACN 24V dc ControlNet Adapter 1794-5.8
1794-ACNR 24V dc Redundant Media ControlNet Adapter 1794-5.18
1794-ACN15 24V dc ControlNet Adapter 1794-5.47
1794-ACNR15 24V dc Redundant Media ControlNet Adapter 1794-5.48
1794-ADN 24V dc DeviceNet Adapter 1794-5.14 1794-6.5.5
1794-ASB/C & D 24V dc Remote I/O Adapter 1794-5.50 1794-6.5.9
1794-ASB2/B 24V dc 2-Slot Remote I/O Adapter 1794-5.44 1794-6.5.13
1794-APB 24V dc Profibus Adapter 1794-5.40 1794-6.5.6
1794-IB8 24V dc 8 Sink Input Module 1794-5.30
1794-OB8 24V dc 8 Source Output Module 1794-5.31
1794-IB16 24V dc 16 Sink Input Module 1794-5.4
1794-OB16 24V dc 16 Source Output Module 1794-5.3
1794-IV16 24V dc 16 Source Input Module 1794-5.28
1794-OV16 24V dc 16 Sink Output Module 1794-5.29
1794-OB8EP 24V dc 8 Electronically Fused Output Module 1794-5.20
1794-IB8S 24V dc Sensor Input Module 1794-5.7
Voltage Description
FLEX Integra Product Data 1793-2.1
4 Protected Output Module 1793-5.2
2 In/2 Protected Output Module 1793-5.3
4 Relay Output Module 1793-5.7
Publications
Installation
Instructions
User
Manual
1791-6.5.11793-OE2 24V dc 2 Protected Output Analog Module 1793-5.5
Publication 1793-6.5.1 - April 1999
Table continued on next page
Using This Manual P-3
Catalog Number
1794-IB10XOB6 24V dc 10 Input/6 Output Module 1794-5.24
1794-IE8 24V dc Selectable Analog 8 Input Module 1794-5.6 1794-6.5.2
1794-OE4 24V dc Selectable Analog 4 Output Module 1794-5.5
1794-IE4XOE2 24V dc 4 Input/2 Output Analog Module 1794-5.15
1794-OF4 24V dc 4 Output Isolated Analog Module 1794-5.37
1794-IF2XOF2 24V dc 2 Input/2 Output Isolated Analog Module 1794-5.39
1794-IR8 24V dc 8 RTD Input Analog Module 1794-5.22 1794-6.5.4
1794-IT8 24V dc 8 Thermocouple Input Module 1794-5.21 1794-6.5.7
1794-IRT8 24V dc 8 Thermocouple/RTD Input Module 1794-5.50 1794-6.5.12
1794-IJ2 24V dc 2 Frequency Input Module 1794-5.49 1794-6.5.11
1794-ID2 24V dc 2 Input Incremental Encoder Module 1794-5.63 1794-6.5.15
1794-IP4 24V dc 4 Input Pulse Counter Module 1794-5.64 1794-6.5.16
1794-VHSC 24V dc Very High Speed Counter Module 1794-5.67 1794-6.5.10
1794-IA8 120V ac 8 Input Module 1794-5.9
1794-OA8 120V ac Output Module 1794-5.10
1794-TB2 1794-TB3
1794-TBN Terminal Base Unit 1794-5.16
1794-TBNF Fused Terminal Base Unit 1794-5.17
1794-TB3T Temperature Terminal Base Unit 1794-5.41
1794-TB3S Spring Clamp Terminal Base Unit 1794-5.42
1794-TB3TS Spring Clamp Temperature Base Unit 1794-5.43
1794-TB3G Terminal Base Unit 1794-5.51
1794-TB3GS Spring Clamp Terminal Base Unit 1794-5.59
1794-CE1, -CE3 Extender Cables 1794-5.12
1794-NM1 Mounting Kit 1794-2.13
1794-PS1 24V dc Power Supply 1794-5.35
Voltage Description
2-wire Terminal Base 3-wire Terminal Base
Publications
Installation
Instructions
1794-5.2
User
Manual
1794-6.5.81794-IF4 24V dc 4 Input Isolated Analog Module 1794-5.38
Publication 1793-6.5.1 - April 1999
Using This Manual
How to Install Your Analog Module
Table of Contents
Preface
Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Vocabulary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Manual Organization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
For Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Table of Contents
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Before You Install Your
Analog Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Compliance to
European Union Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Low Voltage Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Power Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Installing the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Connecting Wiring for the Analog Modules . . . . . . . . . . . . . . . . 2-5
Connecting Wiring for the 1793-IE4 Input Module. . . . . . . . 2-5
Connecting Wiring for the 1793-OE2 Output Module. . . . . . 2-6
Connecting Wiring for the 1793-IE2XOE1 Input/Output
Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Module Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Module Programming
Chapter 3
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Block Transfer
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Sample programs for FLEX Integra Analog Modules . . . . . . . . . 3-2
PLC-3 Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
PLC-5 Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
PLC-2 Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Analog Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Publication 1793-6.5.1 - April 1999
ii
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
Chapter 4
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Configuring Your Analog Module . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Range Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Safe State Value Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Data Format. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Reading Data From Your Module . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Mapping Data for the Analog Modules . . . . . . . . . . . . . . . . . . . . 4-2
Analog Input Module (1793-IE4 and -IE4S) Read . . . . . . . . . 4-3
Word/Bit Descriptions for the 1793-IE4 and -IE4S Analog Input
Module Read . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Analog Input Module (1793-IE4 and -IE4S) Write
Configuration Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Range Selection Bits for the 1793-IE4 and -IE4S Analog
Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Word/Bit Descriptions for the 1793-IE4 and -IE4S Analog Input
Module Write . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Analog Output Module (1793-OE2 and -OE2S) Read . . . . . . 4-6
Bit/Word Descriptions for the 1793-OE2 and -OE2S Analog
Output Module Read . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Analog Output Module (1793-OE2 and -OE2S) Write
Configuration Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Range Selection Bits for the 1793-OE2 and -OE2S Analog Output
Module (Word 5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Word/Bit Descriptions for the 1793-OE2 and -OE2S Analog
Output Module Write . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Analog Combo Module (1793-IE4XOE1) Read . . . . . . . . . . . 4-8
Word/Bit Descriptions for the 1794-IE4XOE1 and -IE2XOE1S
Analog Combo Module Read . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Analog Combo Module (1793-IE2XOE1 and -IE2XOE1S) Write
Configuration Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Range Selection Bits for the 1793-IE2XOE1 and -IE2XOE1S
Analog Combo Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Word/Bit Descriptions for the 1793-IE2XOE1 and -IE2XOE1S
Analog Combo Module Write . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
Publication 1793-6.5.1 - April 1999
Chapter 5
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
About DeviceNetManager
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Polled I/O Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
System Throughput . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Mapping Data into the
Image Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Input, Status, Output and Configuration Files using ControlNet
iii
Chapter 6
What this Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
About the ControlNet Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Communication Over the
FLEX I/O Backplane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Scheduled Data-Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Unscheduled Data-Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Module I/O Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
I/O Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Adapter Input Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Safe State Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Device Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Communication Fault Behavior . . . . . . . . . . . . . . . . . . . . . . . 6-5
Idle State Behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Input Data Behavior upon Module Removal . . . . . . . . . . . . . 6-5
Input Word/Bit Descriptions for the 1793-IE4 and -IE4S Analog
Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Range Selection Bits for the 1793-IE4 and -IE4S Analog Input
Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Configuration Word/Bit Descriptions for the 1793-IE4 and -IE4S
Analog Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
ABit/Word Descriptions for the 1793-OE2 and -OE2S Analog
Output Module Read . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Range Selection Bits for the 1793-OE2 and -OE2S Analog
Output Module (Word 5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Output Word/Bit Descriptions for the 1793-OE2 and -OE2S
Analog Output Module Write . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Configuration Word/Bit Descriptions for the 1793-OE2 and
-OE2S Analog Output Module Write . . . . . . . . . . . . . . . . . . . 6-9
Input Word/Bit Descriptions for the 1793-IE2XOE1and
-IE2XOE1S Analog Combo Module . . . . . . . . . . . . . . . . . . . 6-9
Range Selection Bits for the 1793-IE2XOE1and -IE2XOE1S
Analog Combo Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
Output Word/Bit Descriptions for the 1793-IE2XOE1and
-IE2XOE1S Analog Combo Module . . . . . . . . . . . . . . . . . . 6-10
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
Specifications
Data Table Formats
Appendix A
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Appendix B
Two’s Complement Binary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Analog Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Publication 1793-6.5.1 - April 1999
Chapter
1
Overview of FLEX Integra and your Analog Modules
Chapter Objectives In this chapter, we tell you about:
what the FLEX Integra system is and what it contains
types of FLEX Integra analog modules
how FLEX Integra analog modules communicate with programmable controllers
the features of your analog modules
The FLEX Integra System FLEX Integra is a small, modular I/O system for distributed applications
that performs all of the functions of rack-based I/O. The FLEX Integra system contains the following components shown below:
Adapter
Flexbus connector
Remote I/O Connector
adapter/power supply – powers the internal logic for as many as eight
I/O module with integral wiring terminals– contains the bus interface
24V dc field power connection terminals (externally provided)
I/O modules
and circuitry needed to perform specific functions related to your application and connection terminals for connecting wiring.
Integra Module
Flexbus connector
Field wiring terminals
41480
Publication 1793-6.5.1 - April 1999
1-2 Overview of FLEX Integra and your Analog Modules
Types of FLEX Integra Modules We describe the following FLEX Integra Analog modules in this user
manual:
Catalog Number Voltage Inputs Outputs Description
1793-IE4 24V dc 4
1793-IE4S 24V dc 4
1793-OE2 24V dc 2
1793-OE2S 24V dc 2
1793-IE2XOE1 24V dc 2 1
1793-IE2XOE1S 24V dc 2 1
FLEX Integra analog input, output and combination modules are block transfer modules that interface analog signals with any Allen-Bradley programmable controllers that have block transfer capability. Block transfer programming moves input from the module’s memory to a designated area in the processor data table, and output data words from a designated area in the processor data table to the module’s memory. Block transfer programming also moves configuration words from the processor data table to module memory.
analog – 4 input, single-ended, non-isolated; screw-cage connectors
analog – 4 input, single-ended, non-isolated; spring-clamp connectors
analog – 2 output, single-ended, non-isolated; screw-cage connectors
analog – 2 output, single-ended, non-isolated; spring-clamp connectors
analog – 2 input, single-ended, non-isolated and 1 output, single-ended, non-isolated; screw-cage connectiors
analog – 2 input, single-ended, non-isolated and 1 output, single-ended, non-isolated; spring-clamp connectors
How FLEX Integra Analog Modules Communicate with Programmable Controllers
The analog modules have selectable ranges as shown in the table below:
Voltage Current
0 to 10V dc 0 to 20mA
±10V dc 4 to 20mA
The adapter/power supply transfers data to the module (block transfer write) and from the module (block transfer read) using BTW and BTR instructions in your ladder diagram program. These instructions let the adapter obtain input values and status from the module, and let you send output values and establish the module’s mode of operation. Figure 1.1 describes the communication process.
Publication 1793-6.5.1 - April 1999
Overview of FLEX Integra and your Analog Modules 1-3
Figure 1.1 An Example of Communication Between an Adapter and an Analog Input Module
ADAPTER
ACTIVE FAULT
Allen-Bradley
LOCAL FAULT
1
The adapter transfers your configuration data to the module using a BTW.
Flexbus
POWER SUPPLY
RIO ADAPTER
24VDC
1794-ASB
4
Your ladder program instructs the adapter to perform a BTR of the values and stores them in a data table.
5
The adapter and module determine that the transfer was made without error and input values are within specified range.
6
Your ladder program can use and/or move the data (if valid) before it is written over by the transfer of new data in a subsequent transfer.
2
External devices transmit analog signals to the module.
Allen-Bradley
3
The module converts analog signals into binary format and stores these values until the adapter requests their transfer.
7
Your ladder program performs BTWs to the module when you power it up, and any time you wish to reconfigure the module.
Publication 1793-6.5.1 - April 1999
1-4 Overview of FLEX Integra and your Analog Modules
Features of your Analog Modules
Each module has a unique label identifying its wiring and module type. A removable label provides space for writing individual designations per your application.
A
4 INPUT ANALOG
INPUT
0
123
1793-IE4S
B
41350
2 CH ANALOG OUTPUT
A
1793-OE2
41368
B
2 INPUT/1 OUTPUT ANALOG
INPUT
0
1
A
1793-IE2XOE1
OUTPUT
0
B
41491
A = status indicator B = insertable label
Chapter Summary In this chapter you learned about the FLEX I/O system and the types of
analog modules and how they communicate with programmable controllers.
Publication 1793-6.5.1 - April 1999
Chapter 2
How to Install Your Analog Module
Chapter Objectives
Before You Install Your Analog Module
In this chapter, we tell you about:
how to install your module
how to wire your module
the indicators
Before installing your analog module in the I/O chassis:
You n e e d to: As described under:
Calculate the power requirements of all modules in each chassis.
ATTENTION: +24V dc power must be applied to your module before operation. If power is not applied, the module position will appear to the adapter as an empty slot in your chassis. If the adapter does not recognize your module after installation is completed, cycle power to the adapter.
Power Requirements, page 2-2
Compliance to European Union Directives
If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file:
EN 50081-2EMC – Generic Emission Standard, Part 2 – Industrial Environment
EN 50082-2EMC – Generic Immunity Standard, Part 2 – Industrial Environment
This product is intended for use in an industrial environment.
Publication 1793-6.5.1 - April 1999
2-2 How to Install Your Analog Module
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 – Equipment Requirements and Tests.
For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications:
Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1
Guidelines for Handling Lithium Batteries, publication AG-5.4
Automation Systems Catalog, publication B111
This equipment is classified as open equipment and must be mounted in an enclosure during operation to provide safety protection.
Power Requirements
Installing the Module
The wiring of the module is determined by the current draw through the terminals. Make certain that the current draw does not exceed 10A.
ATTENTION: Total current draw through the module wiring terminals is limited to 10A. Separate power connections may be necessary.
ATTENTION: Do not daisy chain power or ground from an analog module to any ac or dc discrete module.
Installation of the analog module consists of:
This module mounts on a DIN rail. It connects to an adapter or another FLEX I/O or Integra module. Note: If using this module with FLEX I/O modules, do not mount between FLEX I/O modules. Mount Integra modules to the right of the FLEX I/O modules. To mount this module::
1. Remove the cover plug (if used) in the male connector of the unit to which you are connecting this module.
Publication 1793-6.5.1 - April 1999
How to Install Your Analog Module 2-3
2. Position the module on the 35 x 7.5mm DIN rail A (A-B pt. no. 199-DR1). Rotate the module onto the DIN rail with the top of the rail hooked under the lip on the rear of the module.
A
A
30720-M
3. Press down to lock the module on the DIN rail.l
A
41377
If the module does not lock in place, use a screwdriver of similar device to move the locking tab down, press the module flush with the DIN rail and release the locking tab to lock the module in place
4. Firmly push the module into the adjacent module/terminal base until the units lock together.
41371
41370
5. Repeat the above steps to install the next Integra module.
Publication 1793-6.5.1 - April 1999
2-4 How to Install Your Analog Module
6. To remove an Integra module, you must work from the right side and remove one module at a time. To disengage a module from its neighbor, place a common flat-bladed screwdriver between the 2 modules and turn 1/4 turn to separate the modules.
41373
7. Then slide the module away from its left neighbor, and release the locking lever to remove the module from the DIN rail.
ATTENTION: Do not remove this module under power.
Removing this module under power will break the electrical backplane (flexbus) connections. This can cause personal injury or property damage by:
sending an erroneous signal to your system’s field devices causing unintended machine motion
causing an explosion in a hazardous environment
breaking communication to modules beyond this module
Publication 1793-6.5.1 - April 1999
How to Install Your Analog Module 2-5
Connecting Wiring for the Analog Modules
Connecting Wiring for the 1793-IE4 Input Module
This module is available with 2 styles of connectors; screw-cage and spring clamp. Refer to the wiring figure below.
1793-IE4
Ch 0 Ch 1
CC
01234567
8 9 10 11
CCVV
Ch 2 Ch 3
Where: C = 24V dc common, V = 24V dc power, In = current in, Vn = voltage in
I1I0 V0 V1
I3I2 V2 V3
C
A
B
13 14 1512
41470
C
1. Connect individual analog channel signal wiring to terminals on row A and row C. Use Belden 8761 cable for signal wiring..
ATTENTION: Connect only 1 current or 1 voltage signal per channel. Do not connect both current and voltage on 1 channel.
1793-IE4S
Ch 0 Ch 1
CC
V1 V2I2I1
CC
0 1234567
A
B
8 9 10 11 12 13 14 15
VVCC
V3 V4I4I3
Ch 2 Ch 3
41471
2. Connect the associated channel common to common terminals 1, 6, 9 or 14 according to the wiring table on the next page.
3. Connect +24V dc to terminal 8 on row B.
4. Connect 24V dc common to terminal 0 on row A.
5. If daisy-chaining +24V dc from this module to the next FLEX Integra
module, connect a jumper from terminal 15 to terminal 8 on the next FLEX Integra module.
6. If daisy-chaining 24V dc common from this module to the next FLEX Integra module, connect a jumper from terminal 7 on this module to terminal 0 on the next Integra module.
Publication 1793-6.5.1 - April 1999
2-6 How to Install Your Analog Module
Table 2.A Wiring connections for the 1793-IE4 Analog Module
Channel Signal Type
0
1
2
3
Current I 2 1
Voltage V 3 1
Current I 4 6
Voltage V 5 3
Current I 10 9
Voltage V 11 9
Current I 12 14
Voltage V 13 14
24V dc Common
+24V dc power
Label
Markings
Signal Return
Terminals 0, 1, 6, 9, and 14 are connected together in the module.
Terminals 8 and 15 are internally connected in the module.
Connecting Wiring for the 1793-OE2 Output Module
. This module is available with 2 styles of connectors; 1793-OE2 ­screw-cage and 1793-OE2S - spring clamp. Refer to the figure below.
1793-OE4 1793-OE4S
Out Ch 0 Out Ch 1
01234567
8 9 10 11
Where: C = common; V = +24V dc power;
I = current output; V = voltage output
I1 V1Io VoCVCCC
13 14 1512
41358
VCC
A
B
Ch0 Ch1
CC
V0I0 V1I1
CC
0 1234567
A
B
8 9 10 11 12 13 14 15
CVVC
41359
1. Connect individual analog output channel signal wiring as follows:
Channel 0 - Current output - connect output signal to terminal 2 (current output) on row A. Connect the associated channel common to terminal 1 on row A.
Channel 0 - voltage output - connect output signal to terminal 3 (current output) on row A. Connect the associated channel common to terminal 1 on row A.
Channel 1 - Current output - connect output signal to terminal 4 (current output) on row A. Connect the associated channel common to terminal 6 on row A.
Channel 0 - voltage output - connect output signal to terminal 5 (current output) on row A. Connect the associated channel common to terminal 6 on row A.
Publication 1793-6.5.1 - April 1999
1RWH8VH%HOGHQFDEOHIRUVLJQDOZLULQJ
How to Install Your Analog Module 2-7
$77(17,21 &RQQHFWRQO\YROWDJHRUFXUUHQWVLJQDO
SHUFKDQQHO'RQRWFRQQHFWERWKYROWDJHDQGFXUUHQWRQRQH FKDQQHO
2. Connect +24V dc to terminal 8 on row B
3. Connect 24V common to terminal 0 on row A.
4. If daisy-chaining +24V dc from this module to the next FLEX Integra
module, connect a jumper from terminal 15 to terminal 8 on the next FLEX Integra module.
5. If daisy-chaining 24V dc common from this module to the next FLEX Integra module, connect a jumper from terminal 7 on this module to terminal 0 on the next Integra module.

ATTENTION: Total current draw through the module’s 24V dc terminals is limited to 10A. Separate power connections to the module may be required.
$77(17,21'RQRWUHPRYHWKLVPRGXOHXQGHUSRZHU 5HPRYLQJWKLVPRGXOHXQGHUSRZHUZLOOEUHDNWKHHOHFWULFDO EDFNSODQHIOH[EXVFRQQHFWLRQV7KLVFDQFDXVHSHUVRQDO LQMXU\RUSURSHUW\GDPDJHE\
 VHQGLQJDQHUURQHRXVVLJQDOWR\RXUV\VWHPVILHOG
GHYLFHVFDXVLQJXQLQWHQGHGPDFKLQHPRWLRQ  FDXVLQJDQH[SORVLRQLQDKD]DUGRXVHQYLURQPHQW  EUHDNLQJFRPPXQLFDWLRQWRPRGXOHVEH\RQGWKLV
PRGXOH
ATTENTION: Connect only one current or one voltage signal per channel. Do not connect both current and voltage on one channel.
Publication 1793-6.5.1 - April 1999
2-8 How to Install Your Analog Module
Tabl e 2.B Wiring connections for the 1793-OE2 Analog Module
Channel Type Label Marking Signal Return
Current Signal I 2
0
Current Common RET 1
Voltage Signal V 3
Voltage Common RET 1
Current Signal I 4
1
Current Common RET 6
Voltage Signal V 5
Voltage Common RET 6
24V dc Common Terminals 0, 1, 6, 7, 9 and 14
+24V dc Terminals 8 and 15 are internally connected to +V.
Connecting Wiring for the 1793-IE2XOE1 Input/Output Module
This module is available with 2 styles of connectors; screw-cage and spring clamp. Refer to the wiring figure below.
1793-IE2XOE1
In Ch 1
In Ch 0
CC
01234567
Where: C = common; V = +24V dc power; I V
= voltage in; Io = current out; Vo = voltage out
0,1
V0 V1I1I0
8 9 10 11
CCVV
Out Ch 0
C
A
B
13 14 1512
VoIo
41473
C
= current in;
0,1
1793-IE2XOE1S
In Ch 1
In Ch 0
CC
V0 V1I1I0
CC
0 1234567
A
B
I
8 9 10 11 12 13 14 15
VVCC
VoIo
Out Ch 0
41472
1. Connect individual analog input channel signal wiring to terminals on row A. Use terminals 2 (channel 0) and 4 (channel 1) for current and terminals 3 and 5 for current. Use Belden 8761 cable for signal wiring..
$77(17,21 &RQQHFWRQO\FXUUHQWRUYROWDJHVLJQDO SHUFKDQQHO'RQRWFRQQHFWERWKFXUUHQWDQGYROWDJHRQ FKDQQHO
2. Connect the associated channel common to common terminals 1 and 6 according to the wiring table on the next page.
3. Connect individual analog output channel signal wiring to terminals 10 or 11 on row B. (Use terminal 10 for current, or terminal 11 for voltage ­not both.)
4. Connect the associated channel common to common terminal 9 according to the wiring table on the next page.
Publication 1793-6.5.1 - April 1999
How to Install Your Analog Module 2-9
5. Connect +24V dc to terminal 8 on row B
6. Connect 24V dc common to terminal 0 on row A.
7. If daisy-chaining +24V dc from this module to the next FLEX Integra
module, connect a jumper from terminal 15 to terminal 8 on the next FLEX Integra module.
8. If daisy-chaining 24V dc common from this module to the next FLEX Integra module, connect a jumper from terminal 7 on this module to terminal 0 on the next Integra module.
ATTENTION: Total current draw through the terminal base unit is limited to 10A. Separate power connections to the terminal base unit may be necessary.
Tabl e 2.C Wiring connections for the 1794-IE4XOE2 Analog Module
Channel Signal Type
Input 0 Current I 2 1
Voltage V 3
1 Current I 4 6
Voltage V 5
Output 0 Current I 10 9
Voltage V 11 +24V dc Terminals 8 and 15 are internally connected to +V. 24V dc
common
Terminals 0, 1, 6, 7, 9, 14 are internally connected together
in the module.
ATTENTION: Use a 100Ω, 25W or greater, resistor when connecting to a low-impedence device, i.e., panel meter. Failure to do so can result in damage to output circuitry.
Label
Markings
Signal Return
Publication 1793-6.5.1 - April 1999
2-10 How to Install Your Analog Module
Module Indicators
4 INPUT ANALOG
iNPUT
0
123
A
The analog modules have status indicators that are on when power is applied to the module An insertable label is supplied to identify your inputs and outputs.
1793-IE4S
B
41350
2 CH ANALOG OUTPUT
A
1793-OE2
41368
B
2 INPUT/1 OUTPUT ANALOG
INPUT
0
1
A
1793-IE2XOE1
OUTPUT
0
B
41491
A = status indicator
B = insertable label
Chapter Summary
In this chapter you learned how to install and wire your analog module in an existing programmable controller system.
Publication 1793-6.5.1 - April 1999
Module Programming
Chapter
3
Chapter Objectives
Block Transfer Programming
In this chapter, we tell you about:
analog data format
block transfer programming
sample programs for the PLC-3 and PLC-5 processors
Your module communicates with the processor through bidirectional block transfers. This is the sequential operation of both read and write block transfer instructions.
A configuration block transfer write (BTW) is initiated when the analog module is first powered up, and subsequently only when the programmer wants to enable or disable features of the module. The configuration BTW sets the bits which enable the programmable features of the module, such as scaling, alarms, ranges, etc. Block transfer reads are performed to retrieve information from the module.
Block transfer read (BTR) programming moves status and data from the module to the processor’s data table. The processor user program initiates the request to transfer data from the module to the processor. The transferred words contain module status, channel status and input data from the module.
ATTENTION: If the analog module is not powered up before the remote I/O adapter, the adapter will not recognize the module. Make certain that the analog module is installed and powered before or simultaneously with the remote I/O adapter. If the adapter does not establish communication with the module, cycle power to the adapter.
The following sample programs are minimum programs; all rungs and conditioning must be included in your application program. You can disable BTRs, or add interlocks to prevent writes if desired. Do not eliminate any storage bits or interlocks included in the sample programs. If interlocks are removed, the program may not work properly.
Your program should monitor status bits, block transfer read and block transfer write activity.
Publication 1793-6.5.1 - April 1999
3-2 Module Programming
Sample programs for FLEX Integra Analog Modules
The following sample programs show you how to use your analog module efficiently when operating with a programmable controller.
These programs show you how to:
configure the module
read data from the module
update the module’s output channels (if used)
These programs illustrate the minimum programming required for communication to take place.
PLC-3 Programming
Block transfer instructions with the PLC-3 processor use one binary file in a data table section for module location and other related data. This is the block transfer control file. The block transfer data file stores data that you want transferred to your module (when programming a block transfer write) or from your module (when programming a block transfer read). The address of the block transfer data files are stored in the block transfer control file.
The same block transfer control file is used for both the read and write instructions for your module. A different block transfer control file is
required for every module.
Program Action
At power-up in RUN mode, or when the processor is switched from PROG to RUN, the user program enables a block transfer read. Then it initiates a block transfer write to configure the module if the power - up bit is set.
Thereafter, the program continuously performs read block transfers.
Note: You must create the data file for the block transfers before you enter the block transfer instructions.
The pushbutton allows the user to manually request a block transfer write to configure the module.
A sample program segment with block transfer instructions is shown in Figure 3.1, and described below.
Figure 3.1 PLC-3 Family Sample Program Structure for a 1793-IE4 Module
Block Transfer Read Done Bit
B3:0
1
15
Block Transfer Write Done Bit
Pushbutton
2
Power-up Bit
1
Power-up bit included in Series B modules only.
1
B4:8
15
B3:0
05
BTR
BLOCK XFER READ RACK: 7 GROUP: 0 MODULE: 0 CONTROL: #B3:0 DATA FILE: #B4:0 LENGTH: 9
BTW
BLOCK XFER WRITE RACK: 7 GROUP: 0 MODULE: 0 CONTROL: #B3:0 DATA FILE: #B5:0 LENGTH: 1
Enable
EN
12
Done
DN
15
Error
ER
13
Enable
EN
02
Done
DN
05
Error
ER
03
Publication 1793-6.5.1 - April 1999
Program Action
At power-up in RUN mode, or when the processor is switched from PROG to RUN, the user program enables a block transfer read. Then it initiates a block transfer write to configure the module and send data values.
Thereafter, the program continuously performs read block transfers and write block transfers.
Note: You must create the data file for the block transfers before you enter the block transfer instructions.
Module Programming 3-3
Figure 3.2 PLC-3 Family Sample Program Structure for a 1793-OE2 Module
BTR
Block Transfer
Read Done Bit
1
2
B6:0
15
Block Transfer Write Done Bit
B6:0
05
BLOCK XFER READ RACK: 7 GROUP: 1 MODULE: 0 CONTROL: #B6:0 DATA FILE: #B7:0 LENGTH: 1
BTW
BLOCK XFER WRITE RACK: 7 GROUP: 1 MODULE: 0 CONTROL: #B6:0 DATA FILE: #B8:0 LENGTH: 14
Enable
EN
12
Done
DN
15
Error
ER
13
Enable
EN
02
Done
DN
05
Error
ER
03
Program Action
At power-up in RUN mode, or when the processor is switched from PROG to RUN, the user program enables a block transfer read. Then it initiates a block transfer write to configure the module and send data val­ues
Thereafter, the program continuously performs read block transfers and write block transfers. Note: You must create the data file for the block transfers before you enter the block transfer instructions.
Figure 3.3 PLC-3 Family Sample Program Structure for a 1793-IE2XOE1 Module
BTR
Block Transfer Read Done Bit
B9:0
1
15
Block Transfer Write Done Bit
B9:0
2
05
BLOCK XFER READ RACK: 7 GROUP: 2 MODULE: 0 CONTROL: #B9:0 DATA FILE: #B10:0 LENGTH: 5
BTW
BLOCK XFER READ RACK: 7 GROUP: 2 MODULE: 0 CONTROL: #B9:0 DATA FILE: #B11:0 LENGTH: 8
Enable
EN
12
Done
DN
15
Error
ER
13
Enable
EN
02
Done
DN
05
Error
ER
03
Publication 1793-6.5.1 - April 1999
3-4 Module Programming
Program Action
At power-up in RUN mode, or when the processor is switched from PROG to RUN, the user program enables a block transfer read. Then it initiates a block transfer write to configure the module if the power-up bit is set.
Thereafter, the program continuously performs read block transfers to configure the module.
The pushbutton allows the user to manually request a block transfer write.
1
Power-up bit included in Series B modules only.
PLC-5 Programming
The PLC-5 program is very similar to the PLC-3 program with the following exceptions:
block transfer enable bits are used instead of done bits as the conditions on each rung.
separate block transfer control files are used for the block transfer instructions.
Figure 3.4 PLC-5 Family Sample Program Structure for the 1793-IE4
N12:0
15
BTR Enable Bit
N12:0
15
BTW Enable Bit
N12:5
15
BTR
BLOCK TRANSFER READ RACK: 2 GROUP: 1 MODULE: 0 CONTROL: N12:0 DATA FILE: N13:0 LENGTH: 9 CONTINUOUS: N
BTW
BLOCK TRANSFER WRITE RACK: 2 GROUP: 1 MODULE: 0 CONTROL: N12:5 DATA FILE: N13:20 LENGTH: 1 CONTINUOUS: N
EN
DN
ER
EN
DN
ER
1
2
Pushbutton
Power-up
1
Bit
N13:8
15
BTW Enable Bit
N12:5
15
BTR Enable Bit
Program Action
At power-up in RUN mode, or when the processor is switched from PROG to RUN, the user program enables a block transfer read. Then it initiates a block transfer write to configure the module and send data val­ues.
Thereafter, the program continuously performs read block transfers and write block transfers.
Publication 1793-6.5.1 - April 1999
Figure 3.5 PLC-5 Family Sample Program Structure for the 1793-OE2
BTR Enable Bit
N14:0
1
15
BTW Enable Bit
N14:5
2
15
BTW Enable Bit
N14:5
15
BTR Enable Bit
N14:0
15
BTR
BLOCK TRANSFER READ RACK: 2 GROUP: 2 MODULE: 0 CONTROL: N14:0 DATA FILE: N15:0 LENGTH: 1 CONTINUOUS: N
BTW
BLOCK TRANSFER WRITE RACK: 2 GROUP: 2 MODULE: 0 CONTROL: N14:5 DATA FILE: N15:5 LENGTH: 14 CONTINUOUS: N
EN
DN
ER
EN
DN
ER
Module Programming 3-5
Figure 3.6 PLC-5 Family Sample Program Structure for the 1793-IE2XOE1
Program Action
At power-up in RUN mode, or when the processor is switched from PROG to RUN, the user program enables a block transfer read. Then it initiates a block transfer write to configure the module and send data values.
Thereafter, the program continuously performs read block transfers and write block transfers.
BTW Enable Bit
N16:5
1
15
BTR Enable Bit
N16:0
2
15
PLC-2 Programming
BTR Enable Bit
N16:0
15
BTW Enable Bit
N16:5
15
BTR
BLOCK TRANSFER READ RACK: 2 GROUP: 3 MODULE: 0 CONTROL: N16:0 DATA FILE: N17:0 LENGTH: 5 CONTINUOUS: N
BTW
BLOCK TRANSFER WRITE RACK: 2 GROUP: 3 MODULE: 0 CONTROL: N16:5 DATA FILE: N17:5 LENGTH: 8 CONTINUOUS: N
EN
DN
ER
EN
DN
ER
Analog Data Format
The 1793 analog I/O modules are not recommended for use with PLC-2 family programmable controllers due to the number of digits needed for high resolution. In addition, the data returned from the analog-to-digital converter in the module is 12-bit resolute. This value is left-justified into a 16-bit field, reserving the most significant bit for a sign bit. Refer to Appendix B for more information.
The data returned from the analog-to-digital converter in the module is 12-bit resolute. This value is left-justified into a 16-bit field, reserving the most significant bit for a sign bit.
A/D Unipolar Data
Analog Value
Input
A/D Bipolar Data
Analog Value
D/A Data
Output
Analog Value
11 10 09 08 07 06 05 04 03 02 01 00
14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0*
= Always positive
*
10 09 08 07 06 05 04 03 02 01 00
S
14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
S
11 10 09 08 07 06 05 04 03 02 01 00
S
14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
S
Publication 1793-6.5.1 - April 1999
3-6 Module Programming
Refer to Appendix B for a table of values for various current and voltage modes.
Appendix B also includes an example of scaling.
Chapter Summary
In this chapter, you learned how to program your programmable controller. You were given sample programs for your PLC-3 and PLC-5 family processors.
Publication 1793-6.5.1 - April 1999
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
Chapter
4
Chapter Objectives
Configuring Your Analog Module
In this chapter, we tell you about:
configuring your module’s features
entering your data
reading data from your module
read block format
Note: You must use a 1794-ASB series D or later remote I/O adapter to communicate with the 1793 FLEX Integra analog modules.
Because of the many analog devices available and the wide variety of possible configurations, you must configure your module to conform to the analog device and specific application that you have chosen. The module is configured using a group of data table words that are transferred to the module using a block transfer write instruction.
The software configurable features available are:
input/output range selection, including full range and bipolar
safe state operating value (customer selected analog values the module
will maintain in the event of a network communication error)
Note: PLC-5 family programmable controllers that use 6200 software programming tools can take advantage of the IOCONFIG utility to configure these modules. IOCONFIG uses menu-based screens for configuration without having to set individual bits in particular locations. Refer to your 6200 software literature for details.
Publication 1793-6.5.1 - April 1999
4-2 Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
Range Selection
Safe State Value Selection
Individual input channels are configurable to operate with the following voltage or current ranges:
Bit Settings
Ranges
0-10V dc/0-20mA 0 1
4-20mA 1 0
–10 to +10V dc 1 1
Off 0 0
1
When configured to Off, individual output channels will drive 0V/0mA.
Configure
Select
Full Range
You can select individual channel ranges using the designated words of the write block transfer instruction. Refer to the Bit/Word description for your particular module for word and bit numbers.
You can select the analog values that your output module will maintain in the event of a network communication error. When the multiplex control bits (M) are cleared simultaneously by a communication error, (or by the user), the analog outputs will automatically switch to the values set in the safe state analog words. This allows you to define a safe operating state for controlled devices which depend on the analog output from the module.
Data Format
Reading Data From Your Module
Mapping Data for the Analog Modules
The data returned from the analog-to-digital converter in the module is 12-bit resolute. This value is left-justified into a 16-bit field, reserving the most significant bit for a sign bit. The 4-20mA mode scales in the module and uses all 16 bits.
Refer to Appendix C for a table of values for various current and voltage modes, and an example of scaling to engineering terms.
Read programming moves status and data from the module to the processor’s data table. The processor’s user program initiates the request to transfer data from the input module to the processor.
The following read and write words and bit/word descriptions describe the information written to and read from the analog modules. Each word is composed of 16 bits.
Publication 1793-6.5.1 - April 1999
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter 4-3
8 Input Analog Module (Cat. No. 1793-IE4 and -IE4S)
Module Image
Input Data Channel 0
I/O Image
Input Size
1 to 9 Words
PU
Output Size
0 or 1 Word
Analog Input Module (1793-IE4 and -IE4S) Read
Input Data Channel 1
Input Data Channel 2
Input Data Channel 3
Reserved
Reserved
Reserved
Reserved
Underrange
Configure select
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Read Word 0 S Analog Value Channel 0
Word 1 S Analog Value Channel 1 Word 2 S Analog Value Channel 2 Word 3 S Analog Value Channel 3 Word 4 S Reserved Word 5 S Reserved Word 6 S Reserved Word 7 S Reserved Word 8 PU Not used – set to zero U3 U2 U1 U0
Where: S = sign bit (in 2’s complement)
U = Underrange bits for 4-20mA inputs PU = Power up bit
Publication 1793-6.5.1 - April 1999
4-4 Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
Word/Bit Descriptions for the 1793-IE4 and -IE4S Analog Input Module Read
Word
Read Word 0
Word 1
Word 2
Word 3
Words 4-7 Reserved
Word 8
Decimal Bit
(Octal Bit)
Bits 00-14
(00-16)
Bits 15 (17) Channel 0 analog data sign bit.
Bits 00-14
(00-16)
Bits 15 (17) Channel 1 analog data sign bit.
Bits 00-14
(00-16)
Bits 15 (17) Channel 2 analog data sign bit.
Bits 00-14
(00-16)
Bits 15 (17) Channel 3 analog data sign bit.
Bits 00-03
Bits 04-14
(04-16)
Bit 15 (17)
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 1 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 2 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 3 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Underrange bits (U) for individual channels (4-20mA current input only)­Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and so on. When set (1), indicates either a broken or open input wire, or input current at or below 4mA.
Not used – set to 0.
Power Up bit .- This bit is set to 1 when all bits in the configuration register (write word 0) are 0 (unconfigured state). The configuration
register can be cleared by either a reset, or by the user writing all zeroes to it.
Definition
Analog Input Module (1793-IE4 and -IE4S) Write Configuration Block
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Write Word 0 Reserved C3 C2 C1 C0 Reserved F3 F2 F1 F0
Where: C = Configure select bit
F = Full range bit
Publication 1793-6.5.1 - April 1999
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter 4-5
Range Selection Bits for the 1793-IE4 and -IE4S Analog Input Module
Channel No. Channel 0 Channel 1 Channel 2 Channel 3
F0 C0 F1 C1 F2 C2 F3 C3
Decimal Bits
(Octal Bits)
00
08
(10)
01
09
(11)
02
0-10V dc/0-20mA 1 0 1 0 1 0 1 0
4-20mA 0 1 0 1 0 1 0 1
–10 to +10V dc 1 1 1 1 1 1 1 1
1
Off
C = Configure select bit F = Full range bit
1
When configured to off, individual channels will return 0000H on Series B modules, and 4 to 20mA on Series A modules.
0 0 0 0 0 0 0 0
Word/Bit Descriptions for the 1793-IE4 and -IE4S Analog Input Module Write
Word Decimal Bit (Octal Bit) Definition
Full range bits (F) for individual channels – Bit 00 corresponds to input channel
0, bit 01 corresponds to input channel 1, and so on.
Configure select bits (C) for individual channels – Bit 08 corresponds to input channel 0, bit 09 corresponds to input channel 1, and so on. Refer to Range Bit
Write
Word 0
Bits 00-03
Bits 04-07 Reserved
Bits 08-11 (10-13)
Selections.
Bits 12-15 (14-17) Reserved
2 Output Analog Module (Cat. No. 1793-OE2 and -OE2S)
10
(12)
03
11
(13)
Read
Write
I/O Image Input Size
0 or 1 Word
Output Size
1 to 12 Words
Module Image
PU
Not used Not used
Config. Select Full Range
Not used
Analog Data Channel 0
Analog Data Channel 1
Reserved
Reserved
Not used
Not used
Not used
Not used
Not used
Channel 0 Safe State
Channel 1 Safe State
Diagnostics
M
Publication 1793-6.5.1 - April 1999
4-6 Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
Analog Output Module (1793-OE2 and -OE2S) Read
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Read Word 0 PU Not used – set to 0 W1 W0
Where: W = Diagnostic bits for current output wire broken or load resistance high. (Not used on voltage outputs.)
PU = Power up bit
Bit/Word Descriptions for the 1793-OE2 and -OE2S Analog Output Module Read
Word
Decimal Bit
(Octal Bit)
Definition
Current outputs only – When set (1), the wire on the output is broken or the
Bits 00-01
load resistance is too high. Bit 00 corresponds to channel 0, bit 01 corresponds to channel 2, and so on.
Read
Word 0
Bits 02-14
(02-16)
Not used – set to 0
Power Up bit. - This bit is set to 1 when all bits in the configuration
Bit 15 (17)
register (write word 5) are 0 (unconfigured state). The configuration register can be cleared by either a reset, or by the user writing all zeroes to it.
Analog Output Module (1793-OE2 and -OE2S) Write Configuration Block
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Write Word 0 S Analog Data – Channel 0
Word 1 S Analog Data – Channel 1 Word 2 S Reserved Word 3 S Reserved Word 4 0 Not used – set to 0 M1 M0 Word 5 0 Not used – set to 0 C1 C0 Not used – set to 0 F1 F0
Word 6 thru 9 Not used – set to 0
Word 10 S Safe State Value – Channel 0 Word 11 S Safe State Value – Channel 1 Word 12 S Reserved Word 13 S Reserved
Where: S = Sign bit (in 2’s complement)
M = Multiplex control C = Configure select bit F = Full range bit
Publication 1793-6.5.1 - April 1999
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter 4-7
Range Selection Bits for the 1793-OE2 and -OE2S Analog Output Module (Word 5)
Channel No. Channel 0 Channel 1
F0 C0 F1 C1
Decimal Bits (Octal Bits) 00 08 (10) 01 09 (11)
4-20mA 0 1 0 1
0-10V dc/0-20mA 1 0 1 0
–10 to +10V dc 1 1 1 1
1
Off
C = Configure select bit F = Full range bit
1
When configured to off, individual channels will send 0V or 0mV on Series B modules. On Series A modules, 2V or 4mA is output until the module is configured.
0 0 0 0
Word/Bit Descriptions for the 1793-OE2 and -OE2S Analog Output Module Write
Word
Write Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Words 6 thru 9
Word 10
Word 11
Decimal Bit
(Octal Bit)
Bits 00-14
(00-16)
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Definition
Bits 15 (17) Channel 0 analog data sign bit.
Bits 00-14
(00-16)
Channel 1 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 1 analog data sign bit.
Bits 00-14
(00-16)
Channel 2 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 2 analog data sign bit.
Bits 00-14
(00-16)
Channel 3 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 3 analog data sign bit.
Multiplex control bits (M) for individual channels. These bits control the safe state analog outputs. – Bit 00 corresponds to output channel 0, bit 01 corresponds to output channel 1, and so on.
Bits 00-03
1 = use words 0 or 1 as directed by channel number n 0 = use words 10 or 11 as directed by channel number n When bits 00-01 are all cleared (0) simultaneously by a communication error or user choice thru the programmable controller program, word 5 full range and configure select bits are preserved at their last setting.
Bits 04-15 (04-17) Not used – set to 0.
Bits 00-01
Full range bits (F) for individual channels – Bit 00 corresponds to output channel 0, and bit 01 corresponds to output channel 1.
Bits 02-07 Not used – set to 0.
Bits 08-09 (10-11)
Configure select bits (C) for individual channels – Bit 08 corresponds to output channel 0, and bit 09 corresponds to output channel 1.
Bits 10-15 (12-17) Not used – set to 0.
Bits 00-15
(00-17)
Bits 00-14
(00-16)
Not used – set to 0.
Channel 0 Safe State analog value – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 0 Safe State analog data sign bit.
Bits 00-14
(00-16)
Channel 1 Safe State analog value – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 1 Safe State analog data sign bit.
Publication 1793-6.5.1 - April 1999
4-8 Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
Word
Words 12-13
Decimal Bit
(Octal Bit)
Bits 00-15
(00-17)
Definition
Reserved
2 Input/1 Output Analog Combo Module (Cat. No. 1793-IE2XOE1 and -IE2XOE1S)
Module Image
Read
Write
I/O Image
Input Size
0 to 5 Words
Output Size
0 to 7 Words
PU
Not used Full Range and Configure Select
Input Data Channel 0
Input Data Channel 1
Reserved
Reserved
Underrange & Diag.
Output Data Channel 0
Reserved
Not used
Not used
Not used
Output Channel 0 Safe State
M
Analog Combo Module (1793-IE4XOE1) Read
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Read Word 0 S Analog Value Input Channel 0
Word 1 S Analog Value Input Channel 1 Word 2 S Word 3 S Word 4 PU Not used – set to 0 W1 W0
Where: S = sign bit (in 2’s complement)
W = Diagnostic bits for current output wire broken or load resistance high. (Not used on voltage outputs.) PU = Power up bit
Word/Bit Descriptions for the 1794-IE4XOE1 and -IE2XOE1S Analog Combo Module Read
Word
Read
Word 0
Word 1
Words 2
and 3
Decimal Bit
(Octal Bit)
Bits 00-14
(00-16)
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 0 analog data sign bit.
Bits 00-14
(00-16)
Channel 1 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 1 analog data sign bit.
Reserved
Definition
Publication 1793-6.5.1 - April 1999
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter 4-9
Word
Word 4
Decimal Bit
(Octal Bit)
Bits 00-01
Definition
Underrange bits (U) for individual channels (4-20mA current input only)-
Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1. When set (1), indicates either a broken or open input wire, or input current at or below 4mA.
Bits 02-03 Reserved
Wire Off bits (W) – Current outputs only – When set (1), the wire on the
Bits 04
current output is broken or the load resistance is too high. Bit 00 corresponds to channel 0.
Bits 05-14
(05-16)
Reserved
Power Up bit - This bit is set to 1 when all bits in the configuration
Bit 15 (17)
register (write word 3) are 0 (unconfigured state). The configuration register can be cleared by either a reset, or by the user writing all zeroes to it.
Analog Combo Module (1793-IE2XOE1 and -IE2XOE1S) Write Configuration Block
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Write Word 0 S Analog Data – Output Channel 0
Word 1 S Reserved Word 2 0 Not used – set to 0 M0 Word 3 Not used C5 C4 C3 C2 C1 C0 0 0 0 F4 0 0 F1 F0
Words 4 and 5 Not used – set to 0
Word 6 S Safe State Value – Output Channel 0 Word 7 S Reserved
Where: M = Multiplex control bits
S = Sign bit (in 2’s complement) C = Configure select bit F = Full range bit
Publication 1793-6.5.1 - April 1999
4-10 Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
Range Selection Bits for the 1793-IE2XOE1 and -IE2XOE1S Analog Combo Module
Channel No.
Decimal Bits
(Octal Bits)
0-10V dc/0-20mA 1 0 1 0 1 0
–10 to +10V dc 1 1 1 1 1 1
C = Configure select bit F = Full range bit
1
When configured to off, individual channels will return 0000H.
Word/Bit Descriptions for the 1793-IE2XOE1 and -IE2XOE1S Analog Combo Module Write
Word
Write
Word 0
Word 1 Bits 00-15
Word 2
Word 3
Decimal Bit
(Octal Bit)
Bits 00-14
(00-16)
Bits 15
(17)
(00-17
Bit 00
Bits 01-15 (01-17) Not used – set to 0.
Bits 00-01, 04
Bits 02, 03, 05-07 Not used – set to 0.
Bits 08-09, 12 (10,
11, 13-15)
Bits 14-15 (16-17) Not used – set to 0.
Input
Channel 0
Input
Channel 1
Output
Channel 0
F0 C0 F1 C1 F4 C4
00
08
(10)
01
09
(11)
04
12
(14)
4-20mA 0 1 0 1 0 1
Off
1
0 0 0 0 0 0
Definition
Channel 0 analog data – 12-bit left justified two’s complement number; unused
lower bits are zero; 4-20mA uses all 16 bits.
Channel 0 analog data sign bit.
Reserved
Multiplex control bits (M) for individual channel. This bit controls the safe state
analog outputs– Bit 00 corresponds to output channel 0. 1 = use words 0 (analog value) as directed by channel number n 0 = use words 6 (safe state analog value) as directed by channel number n When bit 00 is cleared (0) simultaneously by a communication error or user choice thru the programmable controller program, word 3 full range and configure select bits are preserved at their last setting.
Full range bits (F) for individual channels – Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and bit 04 corresponds to output channel 1. Refer to Range Bit Selections.
Configure select bits (C) for individual channels – Bit 08 corresponds to input channel 0, bit 09 (11) corresponds to input channel 1, bit 12 (14) corresponds to output channel 0. Refer to Range Bit Selections.
Publication 1793-6.5.1 - April 1999
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter 4-11
Chapter Summary
Word
Words 4
and 5
Word 6
Word 7
Decimal Bit
(Octal Bit)
Not used – set to 0.
Bits 00-14
(00-16)
Bits 15 (17) Channel 0 Safe State analog data sign bit.
Bits 00-14
(00-16)
Bits 15 (17) Channel 1 Safe State analog data sign bit.
Channel 0 Safe State analog value – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 1 Safe State analog value – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Definition
In this chapter you learned how to configure your module’s features and enter your data.
Publication 1793-6.5.1 - April 1999
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
Chapter
5
Chapter Objectives
About DeviceNetManager Software
Polled I/O Structure
In this chapter, we tell you about:
DeviceNetManager software
I/O structure
image table mapping
factory defaults
DeviceNetManager software is a tool used to configure your FLEX I/O DeviceNet adapter and its related modules, including any FLEX Integra modules. This software tool can be connected to the adapter via the DeviceNet network.
You must understand how DeviceNetManager software works in order to add a device to the network. Refer to the DeviceNetManager Software User Manual, publication 1787-6.5.3.
Output data is received by the adapter in the order of the installed I/O modules. The Output data for Slot 0 is received first, followed by the Output data for Slot 1, and so on up to slot 7.
The first word of input data sent by the adapter is the Adapter Status Word. This is followed by the input data from each slot, in the order of the installed I/O modules. The Input data from Slot 0 is first after the status word, followed by Input data from Slot 2, and so on up to slot 7.
Network READ
Network WRITE
DeviceNet Adapter
Read Data
Adapter Status
Slot 0 Input Data
Slot 1 Input Data
...
...
Slot 7 Input Data
Write Data
Slot 0 Output Data
Slot 1 Output Data
...
...
Slot 7 Output Data
Read
Write
I/O Module
Slot 0
I/O Module
Publication 1793-6.5.1 - April 1999
Slot 1
...
I/O Module
Slot 7
5-2 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
Adapter Input Status Word
The input status word consists of:
I/O module fault bits – 1 status bit for each slot
node address changed – 1 bit
I/O status – 1 bit
10 through 15
15Bit: 012345678
9
I/O Module Fault Bits
Not Used
I/O State Bit
Node Address Changed Bit
Slot 7
Slot 6
Slot 5
Slot 4
Slot 3
Slot 2
Slot 1
Slot 0
The adapter input status word bit descriptions are shown in the following table.
Bit Description Bit Explanation
0 This bit is set (1) when an error is detected in slot position 0.
1 This bit is set (1) when an error is detected in slot position 1.
2 This bit is set (1) when an error is detected in slot position 2.
I/O Module Fault
Node Address Changed 8
I/O State 9
3 This bit is set (1) when an error is detected in slot position 3.
4 This bit is set (1) when an error is detected in slot position 4.
5 This bit is set (1) when an error is detected in slot position 5.
6 This bit is set (1) when an error is detected in slot position 6.
7 This bit is set (1) when an error is detected in slot position 7.
This bit is set (1) when the node address switch setting has been changed since power up.
Bit = 0 – idle Bit = 1 – run
10 thru 15 Not used – sent as zeroes.
Publication 1793-6.5.1 - April 1999
Possible causes for an I/O Module Fault are:
transmission errors on the Flex I/O backplane
a failed module
a module removed from its terminal base
incorrect module inserted in a slot position
the slot is empty
The node address changed bit is set when the node address switch setting has been changed since power up. The new node address does not take affect until the adapter has been powered down and then powered back up.
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter 5-3
System Throughput
Mapping Data into the Image Table
System throughput, from analog input to backplane, is a function of:
the data format selected
the type and mode of sensors selected
whether filtering is selected
The A/D converter which converts channel 0 through 7 analog data to a digital word provides a programmable single low pass filter. You can set the frequency of this filter during module configuration. The selection influences the A/D output data rate, thus affecting system throughput.
FLEX Integra analog input module data table mapping is shown below.
4 Input Analog Module (Cat. No. 1793-IE4 and -IE4S)
Module Image
Input Data Channel 0
I/O Image
Input Size
1 to 9 Words
PU
Output Size
0 or 6 Words
Input Data Channel 1
Input Data Channel 2
Input Data Channel 3
Reserved
Reserved
Reserved
Reserved
Underrange
Configure select
Reserved
Reserved
Reserved
Reserved
Reserved
Publication 1793-6.5.1 - April 1999
5-4 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
Analog Input Module (1793-IE4 and -IE4S) Read
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Read Word 1 S Analog Value Channel 0
Word 2 S Analog Value Channel 1 Word 3 S Analog Value Channel 2 Word 4 S Analog Value Channel 3 Word 5 S Reserved Word 6 S Reserved Word 7 S Reserved Word 8 S Reserved Word 9 PU Not used – set to zero U3 U2 U1 U0
Where: S = sign bit (in 2’s complement)
U = Underrange bits for 4-20mA inputs PU = Power up bit
Word/Bit Descriptions for the 1793-IE4 and -IE4S Analog Input Module Read
Word
Read Word 1
Word 2
Word 3
Word 4
Words 5-8 Reserved
Word 9
Decimal Bit
(Octal Bit)
Bits 00-14
(00-16)
Bits 15 (17) Channel 0 analog data sign bit.
Bits 00-14
(00-16)
Bits 15 (17) Channel 1 analog data sign bit.
Bits 00-14
(00-16)
Bits 15 (17) Channel 2 analog data sign bit.
Bits 00-14
(00-16)
Bits 15 (17) Channel 3 analog data sign bit.
Bits 00-03
Bits 04-14
(04-16)
Bit 15 (17)
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 1 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 2 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 3 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Underrange bits (U) for individual channels (4-20mA current input only)­Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and so on. When set (1), indicates either a broken or open input wire, or input current at or below 4mA.
Not used – set to 0.
Power Up bit .- This bit is set to 1 when all bits in the configuration register (write word 0) are 0 (unconfigured state). The configuration
register can be cleared by either a reset, or by the user writing all zeroes to it.
Definition
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Write Word 1 Reserved C3 C2 C1 C0 Reserved F3 F2 F1 F0
Where: C = Configure select bit
Publication 1793-6.5.1 - April 1999
Analog Input Module (1793-IE4 and -IE4S) Write Configuration Block
2 Reserved 3 Reserved 4 Reserved 5 Reserved 6 Reserved
F = Full range bit
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter 5-5
Range Selection Bits for the 1793-IE4 and -IE4S Analog Input Module
Channel No. Channel 0 Channel 1 Channel 2 Channel 3
F0 C0 F1 C1 F2 C2 F3 C3
Decimal Bits
(Octal Bits)
00
08
(10)
01
09
(11)
02
0-10V dc/0-20mA 1 0 1 0 1 0 1 0
4-20mA 0 1 0 1 0 1 0 1
–10 to +10V dc 1 1 1 1 1 1 1 1
1
Off
C = Configure select bit F = Full range bit
1
When configured to off, individual channels will return 0000H on Series B modules, and 4 to 20mA on Series A modules.
0 0 0 0 0 0 0 0
Word/Bit Descriptions for the 1793-IE4 and -IE4S Analog Input Module Write
Word Decimal Bit (Octal Bit) Definition
Bits 00-03
Write
Word 1
Bits 04-07 Reserved
Bits 08-11 (10-13)
Bits 12-15 (14-17) Reserved 2 Bits 01-15 (01-17) Reserved 3 Bits 01-15 (01-17) Reserved 4 Bits 01-15 (01-17) Reserved 5 Bits 01-15 (01-17) Reserved 6 Bits 01-15 (01-17) Reserved
Full range bits (F) for individual channels – Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and so on.
Configure select bits (C) for individual channels – Bit 08 corresponds to input channel 0, bit 09 corresponds to input channel 1, and so on. Refer to Range Bit Selections.
10
(12)
03
11
(13)
Publication 1793-6.5.1 - April 1999
5-6 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
2 Output Analog Module (Cat. No. 1793-OE2 and -OE2S)
Read
Write
I/O Image Input Size
0 or 1 Word
PU
Module Image
Not used
Analog Data Channel 0
Analog Data Channel 1
Reserved
Reserved
Not used
Output Size
1 to 14 Words
Not used Not used
Config. Select
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Analog Output Module (1793-OE2 and -OE2S) Read
Diagnostics
M
Full Range
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Read Word 1 PU Not used – set to 0 W1 W0
Where: W = Diagnostic bits for current output wire broken or load resistance high. (Not used on voltage outputs.)
PU = Power up bit
Bit/Word Descriptions for the 1793-OE2 and -OE2S Analog Output Module Read
Word
Read
Word 1
Decimal Bit
(Octal Bit)
Bits 00-01
Bits 02-14
(02-16)
Bit 15 (17)
Definition
Current outputs only – When set (1), the wire on the output is broken or the load resistance is too high. Bit 00 corresponds to channel 0, bit 01 corresponds to channel 2, and so on.
Not used – set to 0
Power Up bit. - This bit is set to 1 when all bits in the configuration register (write word 5) are 0 (unconfigured state). The configuration
register can be cleared by either a reset, or by the user writing all zeroes to it.
Publication 1793-6.5.1 - April 1999
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter 5-7
Analog Output Module (1793-OE2 and -OE2S) Write Configuration Block
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Write Word 1 S Analog Data – Channel 0
Word 2 S Analog Data – Channel 1 Word 3 S Reserved Word 4 S Reserved Word 5 0 Not used – set to 0 M1 M0 Word 6 0 Not used – set to 0 C1 C0 Not used – set to 0 F1 F0
Word 7 thru 10 Not used – set to 0
Word 11 S Reserved Word 12 S Reserved Word 13 S Reserved Word 14 S Reserved
Where: S = Sign bit (in 2’s complement)
M = Multiplex control C = Configure select bit F = Full range bit
Range Selection Bits for the 1793-OE2 and -OE2S Analog Output Module (Word 5)
Channel No. Channel 0 Channel 1
F0 C0 F1 C1
Decimal Bits (Octal Bits) 00 08 (10) 01 09 (11)
4-20mA 0 1 0 1
0-10V dc/0-20mA 1 0 1 0
–10 to +10V dc 1 1 1 1
1
Off
C = Configure select bit F = Full range bit
1
When configured to off, individual channels will send 0V or 0mV on Series B modules. On Series A modules, 2V or 4mA is output until the module is configured.
0 0 0 0
Publication 1793-6.5.1 - April 1999
5-8 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
Word/Bit Descriptions for the 1793-OE2 and -OE2S Analog Output Module Write
Word
Write Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Words 7 thru
10
Words 11-14
Decimal Bit
(Octal Bit)
Bits 00-14
(00-16)
Bits 15 (17) Channel 0 analog data sign bit.
Bits 00-14
(00-16)
Bits 15 (17) Channel 1 analog data sign bit.
Bits 00-14
(00-16)
Bits 15 (17) Channel 2 analog data sign bit.
Bits 00-14
(00-16)
Bits 15 (17) Channel 3 analog data sign bit.
Bits 00-03
Bits 04-15 (04-17) Not used – set to 0.
Bits 00-01
Bits 02-07 Not used – set to 0.
Bits 08-09 (10-11)
Bits 10-15 (12-17) Not used – set to 0.
Bits 00-15
(00-17)
Bits 00-15
(00-17)
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 1 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 2 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 3 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Multiplex control bits (M) for individual channels. These bits control the safe state analog outputs. – Bit 00 corresponds to output channel 0, bit 01 corresponds to output channel 1, and so on. 1 = use words 0 or 1 as directed by channel number n 0 = use words 10 or 11 as directed by channel number n When bits 00-01 are all cleared (0) simultaneously by a communication error or user choice thru the programmable controller program, word 6 full range and configure select bits are preserved at their last setting.
Full range bits (F) for individual channels – Bit 00 corresponds to output channel 0, and bit 01 corresponds to output channel 1.
Configure select bits (C) for individual channels – Bit 08 corresponds to output channel 0, and bit 09 corresponds to output channel 1.
Not used – set to 0.
Reserved
Definition
Publication 1793-6.5.1 - April 1999
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter 5-9
odu e age
2 Input/1 Output Analog Combo Module (Cat. No. 1793-IE2XOE1 and -IE2XOE1S)
Read
Write
I/O Image
Input Size
0 to 5 Words
Output Size
0 to 10 Words
PU
Not used Full Range and Configure Select
Input Data Channel 0
Input Data Channel 1
Reserved
Reserved
Underrange & Diag.
Output Data Channel 0
Reserved
Not used
Not used
Not used
Reserved
Reserved
Reserved
Reserved
M
Analog Combo Module (1793-IE2XOE1 and -IE2XOE1S) Read
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Read Word 1 S Analog Value Input Channel 0
Word 2 S Analog Value Input Channel 1 Word 3 S Reserved Word 4 S Reserved Word 5 PU Not used – set to 0 W1 W0
Where: S = sign bit (in 2’s complement)
W = Diagnostic bits for current output wire broken or load resistance high. (Not used on voltage outputs.) PU = Power up bit
Word/Bit Descriptions for the 1793-IE2XOE1 and -IE2XOE1S Analog Combo Module Read
Word
Read
Word 1
Word 2
Words 3
and 4
Decimal Bit
(Octal Bit)
Bits 00-14
(00-16)
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 0 analog data sign bit.
Bits 00-14
(00-16)
Channel 1 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 1 analog data sign bit.
Reserved
Definition
Publication 1793-6.5.1 - April 1999
5-10 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
Word
Word 5
Decimal Bit
(Octal Bit)
Bits 00-01
Definition
Underrange bits (U) for individual channels (4-20mA current input only)-
Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1. When set (1), indicates either a broken or open input wire, or input current at or below 4mA.
Bits 02-03 Reserved
Wire Off bits (W) – Current outputs only – When set (1), the wire on the
Bits 04
current output is broken or the load resistance is too high. Bit 00 corresponds to channel 0.
Bits 05-14
(05-16)
Reserved
Power Up bit - This bit is set to 1 when all bits in the configuration
Bit 15 (17)
register (write word 3) are 0 (unconfigured state). The configuration register can be cleared by either a reset, or by the user writing all zeroes to it.
Analog Combo Module (1793-IE2XOE1 and -IE2XOE1S) Write Configuration Block
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Write Word 1 S Analog Data – Output Channel 0
Word 2 S Reserved Word 3 0 Not used – set to 0 M0 Word 4 Not used C5 C4 C3 C2 C1 C0 0 0 0 F4 0 0 F1 F0
Words 5 and 6 Not used – set to 0
Word 7 Reserved Word 8 Reserved Word 9 Reserved
Word 10 Reserved
Where: M = Multiplex control bits
S = Sign bit (in 2’s complement) C = Configure select bit F = Full range bit
Publication 1793-6.5.1 - April 1999
Range Selection Bits for the 1793-IE2XOE1 and -IE2XOE1S Analog Combo Module
Channel No.
Input
Channel 0
F0 C0 F1 C1 F4 C4
Decimal Bits
(Octal Bits)
00
08
(10)
4-20mA 0 1 0 1 0 1
0-10V dc/0-20mA 1 0 1 0 1 0
–10 to +10V dc 1 1 1 1 1 1
1
Off
C = Configure select bit F = Full range bit
1
When configured to off, individual channels will return 0000H.
0 0 0 0 0 0
Input
Channel 1
09
01
(11)
Output
Channel 0
12
04
(14)
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter 5-11
Word/Bit Descriptions for the 1793-IE2XOE1 and -IE2XOE1S Analog Combo Module Write
Word
Write
Word 1
Word 2 Bits 00-15
Word 3
Word 4
Words 5
and 6
Words 7
thru 10
Decimal Bit
(Octal Bit)
Bits 00-14
(00-16)
Bits 15
(17)
(00-17
Bit 00
Bits 01-15 (01-17) Not used – set to 0.
Bits 00-01, 04
Bits 02, 03, 05-07 Not used – set to 0.
Bits 08-09, 12 (10,
11, 13-15)
Bits 14-15 (16-17) Not used – set to 0.
Bits 01-15 (01-17) Not used – set to 0.
Bits 01-15 (01-17) Reserved
Definition
Channel 0 analog data – 12-bit left justified two’s complement number; unused
lower bits are zero; 4-20mA uses all 16 bits.
Channel 0 analog data sign bit.
Reserved
Multiplex control bits (M) for individual channel. This bit controls the safe state
analog outputs– Bit 00 corresponds to output channel 0. 1 = use words 0 (analog value) as directed by channel number n 0 = use words 6 (safe state analog value) as directed by channel number n When bit 00 is cleared (0) simultaneously by a communication error or user choice thru the programmable controller program, word 4 full range and configure select bits are preserved at their last setting.
Full range bits (F) for individual channels – Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and bit 04 corresponds to output channel 1. Refer to Range Bit Selections.
Configure select bits (C) for individual channels – Bit 08 corresponds to input channel 0, bit 09 (11) corresponds to input channel 1, bit 12 (14) corresponds to output channel 0. Refer to Range Bit Selections.
Defaults
Each I/O module has default values associated with it. At default, each module will generate inputs/status and expect outputs/configuration.
Module Defaults for: Factory Defaults Real Time Size
Catalog Number
1793-IE4 4-Input Module 11 4 8 0
1793-OE2 2-Output Module 11 4 8 0
1793-IE2XOE1 2-Input/1 Output Module 11 4 8 0
Description
Input
Default
Output Default
Input
Default
Output
Default
Factory defaults are the values assigned by the adapter when you:
first power up the system, and
no previous stored settings have been applied.
For analog modules, the defaults reflect the actual number of input words/ output words. For example, for the 4-input module, you have 11 input words, and 4 output words.
Publication 1793-6.5.1 - April 1999
5-12 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
You can change the I/O data size for a module by reducing the number of words mapped into the adapter module, as shown in “real time sizes.”
Real time sizes are the settings that provide optimal real time data to the adapter module.
Analog modules have 15 words assigned to them. This is divided into input words/output words. You can reduce the I/O data size to fewer words to increase data transfer over the backplane.
For information on using DeviceNetManager software to configure your adapter, refer to the DeviceNetManager Software User Manual, publication 1787-6.5.3.
Chapter Summary
In this chapter, you learned how this module communicates over the DeviceNet network, and the image table mapping for the module.
Publication 1793-6.5.1 - April 1999
Chapter
6
Input, Status, Output and Configuration Files using ControlNet
What this Chapter Contains
About the ControlNet Adapter
Communication Over the FLEX I/O Backplane
Read this chapter to familiarize yourself with input, output and configuration files for analog I/O modules on ControlNet.This chapter talks about:
the ControlNet Adapter
I/O structure
fault state data
communication fault data
idle state behavior
input data behavior upon module removal
The FLEX I/O ControlNet adapter (cat. no. 1794-ACN15 or -ACNR15) interfaces up to 8 FLEX I/O and/or FLEX Integra modules and a ControlNet processor or scanner. The adapter can support ControlNet real-time data connections to individual modules or module groups. Each connection is independent of the others and can be from different processors or scanners.
One ControlNet adapter can interface up to eight terminal base units with installed FLEX I/O and/or FLEX Integra modules, forming a FLEX I/O system of up to eight slots. The adapter communicates to other network system components (typically one or more controllers or scanners, and/or programming terminals) over the ControlNet network. The adapter communicates with its I/O modules over the flexbus backplane.
Network
ControlNet Adapter
Write
Read
I/O Module I/O ModuleI/O Module
Inputs Inputs Inputs
Status
Outputs
Configuration Configuration Configuration
Slot 0 Slot 1 Slot 7
0
Read Words
Write Words
X
Publication 1793-6.5.1 - April 1999
StatusStatus
OutputsOutputs
41626
6-2 Input, Status, Output and Configuration Files using ControlNet
Scheduled Data-Transfer
Scheduled data transfer:
is continuous.
is asynchronous to the controller program scan.
occurs at the actual rate displayed in the Actual Packet Interval field on
the programming software ControlNet I/O mapping (monitor) screen
Unscheduled Data-Transfer
Unscheduled operations include:
unscheduled non-discrete I/O data transfers–through ControlNet I/O Transfer (CIO) instructions
peer-to-peer messaging–through Message (MSG) instructions
messaging from programming devices
Unscheduled messaging on a ControlNet network is non-deterministic. Your application and your configuration – number of nodes, application program, network update time (NUT), amount of scheduled bandwidth used, etc.– determine how much time there is for unscheduled messaging.
Module I/O Mapping
The I/O map for a module is divided into read words and write words. Read words consist of input and status words, and write words consist of output and configuration words. The number of read words or write words can be 0 or more. The length of each I/O module’s read words and write words vary in size depending on module complexity. Each I/O module will support at least 1 input word or 1 output word. Status and configuration are optional, depending on the module.
For example, a 16 point discrete input module will have up to 2 read words and 1 write word.
ControlNet Image
Input Size
1 or 2 Words
Module Image
Input
Not used
Publication 1793-6.5.1 - April 1999
Configuration Size
0 or 1 Words
Not used
Delay Time
Check the I/O map for each module for the exact mapping.
Delay Time
41627
Input, Status, Output and Configuration Files using ControlNet 6-3
I/O Structure
Network READ
Network WRITE
Output data is received by the adapter in the order of the installed I/O modules. The output data for slot 0 is received first, followed by the output data for slot 1, and so on up to slot 7.
The first word of input data sent by the adapter is the Adapter status word. This is followed by the input data from each slot, in the order of the installed I/O modules. The input data from slot 0 is first after the status word, followed by input data from slot 2, and so on up to slot 7.
ControlNet Adapter
Read Data
Adapter Status
Slot 0 Input Data
Slot 1 Input Data
Slot 7 Input Data
Slot 0 Input Data Slot 1 Input Data
Read
Write
I/O
Module
Slot 0
I/O
Module
Slot 1
I/O
Module
Slot 7
Slot 7 Input Data
Adapter Input Status Word
The input status word consists of:
I/O module fault bits – 1 status bit for each slot
Additionally, in the case of a PLC-5 controller, it adds:
node address changed – 1 bit (created by PLC-5 controller)
I/O status – 1 bit (created by PLC-5 controller)
Resulting in the following ControlNet adapter status word for a PLC-5 controller.
I/O Module Fault Bits
Bit: 15 910 through 15 876543210
41628
Created by PLC-5 controller
I/O Status Bit
Node Address Changed Bit
41629
Publication 1793-6.5.1 - April 1999
6-4 Input, Status, Output and Configuration Files using ControlNet
As an example, in a PLC-5 system, the adapter input status word bit descriptions are shown in the following table.
Bit Description: Bit: Explanation:
0 This bit is set (1) when an error is detected in slot position 0.
1 This bit is set (1) when an error is detected in slot position 1.
2 This bit is set (1) when an error is detected in slot position 2.
I/O Module Fault
3 This bit is set (1) when an error is detected in slot position 3.
4 This bit is set (1) when an error is detected in slot position 4.
5 This bit is set (1) when an error is detected in slot position 5.
6 This bit is set (1) when an error is detected in slot position 6.
7 This bit is set (1) when an error is detected in slot position 7.
Safe State Data
Node Address Changed (Created by PLC-5 controller.)
I/O State (Created by PLC-5 controller.)
Possible causes for an I/O Module Fault are:
transmission errors on the flexbus backplane
a failed module
a module removed from its terminal base
incorrect module inserted in a slot position
the slot is empty
the slot contains a non-discrete module
The ControlNet adapter provides storage for alternate module output data during communication faults or processor idle state. This “safe state data” assures that a known output will be applied to the output devices during the previously mentioned failure modes. The processor or scanner software must include the means to specify this safe state data for each module. If applicable, this data is sent in the configuration block (see Image Table Mapping later in this chapter).
8 This bit is set (1) when the node address switch setting has
been changed since power-up.
9 Bit = 0 -idle
bit = 1 - run
10 though 15 Not used – set to 0
Device Actions
Publication 1793-6.5.1 - April 1999
Device actions include:
communication fault behavior
idle state behavior
input data behavior upon module removal
Input, Status, Output and Configuration Files using ControlNet 6-5
Communication Fault Behavior
You can configure the adapter response to a communication fault for each I/ O module in its system. Upon detection of a communication fault, the adapter can:
leave the module output data in its last state (hold last state)
reset the module output data to zero (reset)
apply fault state data to the module output
Idle State Behavior
The ControlNet adapter can detect the state of the controlling processor or scanner. Only 2 states can be detected: run mode, or program mode (idle).
When run mode is detected, the adapter copies the output data received from the processor to the corresponding module output. When program mode is detected, the adapter can be configured to:
leave the module output data in its last state (hold last state)
reset the module output data to zero (reset)
apply fault state data to the module output
Input Data Behavior upon Module Removal
I/O module input data sent by the adapter upon module removal is configurable. The adapter can:
reset the module input data sent by the adapter to zero (reset)
leave the module input data sent by the adapter in the last state before
module removal (hold last state)
Publication 1793-6.5.1 - April 1999
6-6 Input, Status, Output and Configuration Files using ControlNet
4 Input Analog Module (Cat. No. 1793-IE4 and -IE4S)
ControlNet Files
Input File Size
1 to 9 Words
Configuration File Size
0 or 6 Words
Input Word/Bit Descriptions for the 1793-IE4 and -IE4S Analog Input Module
PU
Module Image
Input Data Channel 0
Input Data Channel 1
Input Data Channel 2
Input Data Channel 3
Reserved
Reserved
Reserved
Reserved
Underrange
Configure select
4-01CN
Input Word
Input Word 0
Decimal Bit
(Octal Bit)
Bits 00-14
(00-16)
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 0 analog data sign bit.
Word 1
Bits 00-14
(00-16)
Channel 1 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 1 analog data sign bit.
Word 2
Bits 00-14
(00-16)
Channel 2 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 2 analog data sign bit.
Word 3
Bits 00-14
(00-16)
Channel 3 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 3 analog data sign bit.
Words 4-7 Reserved
Underrange bits (U) for individual channels (4-20mA current input only)-
Bits 00-03
Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and so on. When set (1), indicates either a broken or open input wire, or input current at or below 4mA.
Word 8
Bits 04-14
(04-16)
Not used – set to 0.
Power Up bit .- This bit is set to 1 when all bits in the configuration
Bit 15 (17)
register (write word 0) are 0 (unconfigured state). The configuration register can be cleared by either a reset, or by the user writing all zeroes to it.
Definition
Publication 1793-6.5.1 - April 1999
Input, Status, Output and Configuration Files using ControlNet 6-7
Range Selection Bits for the 1793-IE4 and -IE4S Analog Input Module
Channel No. Channel 0 Channel 1 Channel 2 Channel 3
F0 C0 F1 C1 F2 C2 F3 C3
Configuration
Word
Write Word 0
Decimal Bits
(Octal Bits)
00
08
(10)
01
09
(11)
02
10
(12)
03
0-10V dc/0-20mA 1 0 1 0 1 0 1 0
4-20mA 0 1 0 1 0 1 0 1
–10 to +10V dc 1 1 1 1 1 1 1 1
1
Off
C = Configure select bit F = Full range bit
1
When configured to off, individual channels will return 0000H .
0 0 0 0 0 0 0 0
Configuration Word/Bit Descriptions for the 1793-IE4 and -IE4S Analog Input Module
Decimal Bit (Octal Bit) Definition
Bits 00-03
Full range bits (F) for individual channels – Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and so on.
Bits 04-07 Reserved
Configure select bits (C) for individual channels – Bit 08 corresponds to input
Bits 08-11 (10-13)
channel 0, bit 09 corresponds to input channel 1, and so on. Refer to Range Bit Selections.
Bits 12-15 (14-17) Reserved
2 Output Analog Module (Cat. No. 1793-OE2 and -OE2S)
11
(13)
ControlNet Files
Read
Output File Size
Write
Write
0 to 4 Words
Configuration File Size
1 to 2 Words
Input File Size
0 or 1 Word
Module Image
PU
Not used Not used
Config. Select
Not used
Analog Data Channel 0
Analog Data Channel 1
Reserved
Reserved
Not used
Diagnostics
M
Full Range
-
Publication 1793-6.5.1 - April 1999
6-8 Input, Status, Output and Configuration Files using ControlNet
ABit/Word Descriptions for the 1793-OE2 and -OE2S Analog Output Module Read
Input
Words
Read
Word 0
Decimal Bit
(Octal Bit)
Bits 00-01
Bits 02-14
(02-16)
Bit 15 (17)
Definition
Current outputs only – When set (1), the wire on the output is broken or the load resistance is too high. Bit 00 corresponds to channel 0, bit 01 corresponds to channel 2, and so on.
Not used – set to 0
Power Up bit. - This bit is set to 1 when all bits in the configuration register (write word 5) are 0 (unconfigured state). The configuration
register can be cleared by either a reset, or by the user writing all zeroes to it.
Range Selection Bits for the 1793-OE2 and -OE2S Analog Output Module (Word 5)
Channel No. Channel 0 Channel 1
F0 C0 F1 C1
Decimal Bits (Octal Bits) 00 08 (10) 01 09 (11)
4-20mA 0 1 0 1
0-10V dc/0-20mA 1 0 1 0
–10 to +10V dc 1 1 1 1
1
Off
C = Configure select bit F = Full range bit
1
When configured to off, individual channels will send 0V or 0mV.
0 0 0 0
Output Word
Configuration
Word 0
Word 1
Word 2
Word 3
Output Word/Bit Descriptions for the 1793-OE2 and -OE2S Analog Output Module Write
Decimal Bit
(Octal Bit)
Bits 00-14
(00-16)
Bits 15 (17) Channel 0 analog data sign bit.
Bits 00-14
(00-16)
Bits 15 (17) Channel 1 analog data sign bit.
Bits 00-14
(00-16)
Bits 15 (17) Channel 2 analog data sign bit.
Bits 00-14
(00-16)
Bits 15 (17) Channel 3 analog data sign bit.
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 1 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 2 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 3 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Definition
Publication 1793-6.5.1 - April 1999
Input, Status, Output and Configuration Files using ControlNet 6-9
Configuration Word/Bit Descriptions for the 1793-OE2 and -OE2S Analog Output Module Write
Configuration
Word
Decimal Bit
(Octal Bit)
Definition
Multiplex control bits (M) for individual channels. These bits control the safe
state analog outputs. – Bit 00 corresponds to output channel 0, bit 01 corresponds to output channel 1, and so on. 1 = use words 0 or 1 as directed by channel number n 0 = use words 10 or 11 as directed by channel number n
Word 4
Bits 00-03
When bits 00-01 are all cleared (0) simultaneously by a communication error or user choice thru the programmable controller program, word 5 full range and configure select bits are preserved at their last setting.
Bits 04-15 (04-17) Not used – set to 0.
Full range bits (F) for individual channels – Bit 00 corresponds to output channel 0, and bit 01 corresponds to output channel 1.
Configure select bits (C) for individual channels – Bit 08 corresponds to output channel 0, and bit 09 corresponds to output channel 1.
Word 5
Bits 00-01
Bits 02-07 Not used – set to 0.
Bits 08-09 (10-11)
Bits 10-15 (12-17) Not used – set to 0.
2 Input/1 Output Analog Combo Module (Cat. No. 1793-IE2XOE1 and -IE2XOE1S)
Module Image
Read
ControlNet Files
Input File Size
0 to 5 Words
PU
Output File Size
0 to 1 Words
Input Data Channel 0
Input Data Channel 1
Reserved
Reserved
Underrange & Diag.
Output Data Channel 0
Configuration File Size
0 to 2 Words
Write
Input Word/Bit Descriptions for the 1793-IE2XOE1and -IE2XOE1S Analog Combo Module
Input Word
Input
Word 0
Word 1
Not used Full Range and Configure Select
Decimal Bit
(Octal Bit)
Bits 00-14
(00-16)
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 0 analog data sign bit.
Bits 00-14
(00-16)
Channel 1 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15 (17) Channel 1 analog data sign bit.
Not used
Definition
M
4-03CN
Publication 1793-6.5.1 - April 1999
6-10 Input, Status, Output and Configuration Files using ControlNet
Input Word
Words 2
and 3
Word 4
Decimal Bit
(Octal Bit)
Bits 00-01
Definition
Reserved
Underrange bits (U) for individual channels (4-20mA current input only)-
Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1. When set (1), indicates either a broken or open input wire, or input current at or below 4mA.
Bits 02-03 Reserved
Wire Off bits (W) – Current outputs only – When set (1), the wire on the
Bits 04
current output is broken or the load resistance is too high. Bit 00 corresponds to channel 0.
Bits 05-14
(05-16)
Reserved
Power Up bit - This bit is set to 1 when all bits in the configuration
Bit 15 (17)
register (write word 3) are 0 (unconfigured state). The configuration register can be cleared by either a reset, or by the user writing all zeroes to it.
Range Selection Bits for the 1793-IE2XOE1and -IE2XOE1S Analog Combo Module
Channel No.
Input
Channel 0
F0 C0 F1 C1 F4 C4
Decimal Bits
(Octal Bits)
00
08
(10)
4-20mA 0 1 0 1 0 1
0-10V dc/0-20mA 1 0 1 0 1 0
–10 to +10V dc 1 1 1 1 1 1
1
Off
C = Configure select bit F = Full range bit
1
When configured to off, individual channels will return 0000H.
0 0 0 0 0 0
Input
Channel 1
09
01
(11)
Output
Channel 0
12
04
(14)
Publication 1793-6.5.1 - April 1999
Output
Word
Write
Word 0
Output Word/Bit Descriptions for the 1793-IE2XOE1and -IE2XOE1S Analog Combo Module
Decimal Bit
(Octal Bit)
Bits 00-14
(00-16)
Bits 15
(17)
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Channel 0 analog data sign bit.
Definition
Input, Status, Output and Configuration Files using ControlNet 6-11
Configuration Word/Bit Descriptions for the 1793-IE2XOE1 and -IE2XOE1S Analog Combo Module
Chapter Summary
Configuration
Word
Word 2
Word 3
Decimal Bit
(Octal Bit)
Multiplex control bits (M) for individual channel. This bit controls the safe state
analog outputs– Bit 00 corresponds to output channel 0. 1 = use words 0 (analog value) as directed by channel number n
Bit 00
Bits 01-15 (01-17) Not used – set to 0.
Bits 00-01, 04
Bits 02, 03, 05-07 Not used – set to 0.
Bits 08-09, 12 (10,
11, 13)
Bits 14-15 (16-17) Not used – set to 0.
0 = use words 6 (safe state analog value) as directed by channel number n When bit 00 is cleared (0) simultaneously by a communication error or user choice thru the programmable controller program, word 3 full range and configure select bits are preserved at their last setting.
Full range bits (F) for individual channels – Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and bit 04 corresponds to output channel 1. Refer to Range Bit Selections.
Configure select bits (C) for individual channels – Bit 08 corresponds to input channel 0, bit 09 (11) corresponds to input channel 1, bit 12 (14) corresponds to output channel 0. Refer to Range Bit Selections.
Definition
In this chapter, you learned how this module communicates over the ControlNet network, and the image table mapping for the module.
Publication 1793-6.5.1 - April 1999
Specifications
Specifications - 4 Input Analog Module, Cat. No. 1793-IE4 and -IE4S
Module Type 4 analog inputs
Module Location DIN rail mounting
Number of Channels 4
Data Format 16-bit 2’s complement, left-justified
Conversion Type Successive approximation
Conversion Rate 256μs all channels
Resolution
Voltage Current
Input Current Terminal 4-20mA (user configurable)
Input Voltage Terminal +
Normal Mode Rejection Ratio
Voltage Terminal
Current Terminal
Step Response to 63%
Voltage Terminal Current Terminal
Impedance
Voltage Terminal Current Terminal
Absolute Accuracy
Voltage Terminal Current Terminal
Accuracy Drift
Voltage Terminal Current Terminal
Maximum Overload
Voltage Terminal Current Terminal
Isolation Voltage Channel to system - 850V dc for 1s
Flexbus Current 20mA maximum
Power Dissipation 1.0W @ 31.2V dc
1793-IE4 - 16 screw-cage terminals 1793-IE4S - 16 spring-clamp terminals
12-bits - unipolar; 11-bit plus sign - bipolar
2.56mV/cnt unipolar; 5.13mV/cnt bipolar
5.13μA/cnt
0-20mA (user configurable)
10V (user configurable)
0-10V (user configurable)
-3db @ 17Hz; -20db/decade
-10db @ 50Hz; -11.4db @ 60Hz
-3db @ 17Hz; -20db/decade
-15.3db @ 50Hz; -16.8db @ 60Hz
9.4ms
18.2ms
100K Ω; 200K Ω @ dc 238Ω
o
0.20% FS @ 25
0.20% FS @ 25
0.00428% FS per
0.00407% FS per
Single channel, continuous 30V 32mA
Channel to channel - None
C
o
C
o
C
o
C
Appendix
A
Publication 1793-6.5.1 - April 1999
A-2 Specifications
Specifications - 4 Input Analog Module, Cat. No. 1793-IE4 and -IE4S
Thermal Dissipation 3.4 BTU/hr @ 31.2V dc
Indicators 1 green power indicators
External dc Power Voltage
Current
Dimensions in
(mm)
19.2-31.2V dc (5% ac ripple) 60mA maximum
2.72H x 3.15D x 2.17W (69H x 80D x 55W)
Environmental Conditions
Operational Temperature Storage Temperature Relative Humidity Shock Operating
Nonoperating
Vibration
Conductors Wire Size
Category
Agency Certification (when product is marked)
o
C (32 to +131oF)
0 to +55
-40 to +85
o
C (-40 to +185oF) 5 to 95% noncondensing Tested to 30g peak acce leration, 11(+ Tested to 50g peak acceleration, 11(+
Tested 5g @ 10-500Hz per IEC68-2-6
2
12 gauge (4mm
) stranded wire 3/64 in (1.2mm) maximum insulation 2
• CSA certified
• CSA Class 1, Division 2 Groups A, B, C and D
certified
• UL listed
• CE marked for all applicable directives
User Manual • Publication 1793-6.5.1
1 Use this categor y information for planning conductor routing as described in publication
1770-4.1, “Wiring and Grounding Guidelines for Noise Immunity.”
1)ms pulse width
1)ms pulse width
Publication 1793-6.5.1 - April 1999
Specifications - 2 Output Analog Module, Cat. No. 1793-OE2 and -OE2S
Module Type 2 analog output
1793-OE2 - 16 screw-cage terminals 1793-OE2S - 16 spring-clamp terminals
Module Location DIN rail mounting
Number of Channels 2 out - nonisolated
Output
Resolution
Voltage Current
12-bits plus sign
2.56mV/cnt
5.13μA/cnt
Data Format left justified 16-bit 2’s complement
Conversion Type Pulse width modulation
Conversion Rate 1.024ms all channels
Current Terminal 4-20mA (user configurable)
0-20mA (user configurable)
Voltage Terminal +
10V (user configurable) 0-10V (user configurable) 3A maximum
Step Response to 63%
Voltage Terminal Current Terminal
24ms 24ms
Impedance
Voltage Terminal Current Terminal
15-750 Ω resistive 15-750 Ω resistive
Absolute Accuracy
Voltage Terminal Current Terminal
0.133% FS @ 25
0.425% FS @ 25
o
C
o
C
Accuracy Drift
Voltage Terminal Current Terminal
0.0045% FS per
0.0069% FS per
o
C
o
C
Isolation Voltage Channel to system - 850V dc for 1s
Channel to channel - None
General
Flexbus Current 20mA maximum
Power Dissipation 2.5W @ 31.2V dc
Thermal Dissipation 8.5 BTU/hr @ 31.2V dc
Indicators 1 green power indicators
External dc Power Voltage
Current
Dimensions in
(mm)
19.2-31.2V dc (5% ac ripple) 70mA maximum
2.72H x 3.15D x 2.17W (69H x 80D x 55W)
Environmental Conditions
Operational Temperature Storage Temperature Relative Humidity Shock Operating Nonoperating Vibration
Conductors Wire Size
Category
Agency Certification (when product is marked)
o
C (32 to +131oF)
0 to +55
-40 to +85
o
C (-40 to +185oF) 5 to 95% noncondensing Tested to 30g peak acceleration, 11(+ Tested to 50g peak acceleration, 11(+
1)ms pulse width
1)ms pulse width
Tested 5g @ 10-500Hz per IEC68-2-6
2
12 gauge (4mm
) stranded wire 3/64 in (1.2mm) maximum insulation 2
•CSA certified
• CSA Class 1, Division 2 Groups A, B, C and D
certified
•UL listed
• CE marked for all applicable directives
Publications • Installation Instructions - 1793-5.6
• User Manual - 1793-6.5.1
1 Use this categor y information for planning conductor routing as described in publication
1770-4.1, “Wiring and Grounding Guidelines for Noise Immunity.”
Specifications A-3
Publication 1793-6.5.1 - April 1999
A-4 Specifications
Specifications - 2 Input/1 Output Analog Module, Cat. No. 1793-IE2XOE1 and -IE2XOE1S
Module Type 2 analog inputs, 1 analog output
1793-IE2XOE1 - 16 screw-cage terminals 1793-IE2XOE1S - 16 spring-clamp terminals
Module Location DIN rail mounting
Number of Channels 3 - 2 in, 1 out - nonisolated
Input
Resolution
Voltage Current
12-bits - unipolar; 11-bit plus sign - bipolar
2.56mV/cnt unipolar; 5.13mV/cnt bipolar
5.13μA/cnt
Data Type left justified 16-bit 2’s complement
Conversion Type Successive approximation
Conversion Rate 256μs all channels
Input Current Terminal 4-20mA (user configurable)
0-20mA (user configurable)
Input Voltage Terminal +
10V (user configurable)
0-10V (user configurable)
Normal Mode Rejection Ratio
Voltage Terminal
-3db @ 17Hz; -20db/decade
-10db @ 50Hz; -11.4db @ 60Hz
Current Terminal
-3db @ 17Hz; -20db/decade
-15.3db @ 50Hz; -16.8db @ 60Hz
Step Response to 63%
Voltage Terminal Current Terminal
9.4ms
18.2ms
Impedance
Voltage Terminal Current Terminal
9.4ms100K Ω; 200K Ω @ dc 238Ω
Absolute Accuracy
Voltage Terminal Current Terminal
0.20% FS @ 25
0.20% FS @ 25
o
C
o
C
Accuracy Drift
Voltage Terminal Current Terminal
Maximum Overload
Voltage Terminal Current Terminal
0.00428% FS per
0.00407% FS per
Single channel, continuous 30V 32mA
o
C
o
C
Output
Resolution
Voltage Current
12-bits plus sign
2.56mV/cnt
5.13μA/cnt
Data Type left justified 16-bit 2’s complement
Conversion Type Pulse width modulation
Conversion Rate 1.024ms all channels
Current Terminal 4-20mA (user configurable)
0-20mA (user configurable)
Voltage Terminal +
10V (user configurable) 0-10V (user configurable) 3A maximum
Step Response to 63%
Voltage Terminal Current Terminal
24ms 24ms
Impedance
Voltage Terminal Current Terminal
15-750 Ω resistive 15-750 Ω resistive
Absolute Accuracy
Voltage Terminal Current Terminal
0.133% FS @ 25
0.425% FS @ 25
o
C
o
C
Publication 1793-6.5.1 - April 1999
Specifications A-5
Specifications - 2 Input/1 Output Analog Module, Cat. No. 1793-IE2XOE1 and -IE2XOE1S
Accuracy Drift
Voltage Terminal Current Terminal
0.0045% FS per
0.0069% FS per
Isolation Voltage Channel to system - 850V dc for 1s
Channel to channel - None
General
Flexbus Current 20mA maximum
Power Dissipation 2.5W @ 31.2V dc
Thermal Dissipation 8.5 BTU/hr @ 31.2V dc
Indicators 1 green power indicators
External dc Power Voltage
Current
Dimensions in
(mm)
19.2-31.2V dc (5% ac ripple) 100mA maximum
2.72H x 3.15D x 2.17W (69H x 80D x 55W)
Environmental Conditions
Operational Temperature Storage Temperature Relative Humidity Shock Operating
Nonoperating
Vibration
Conductors Wire Size
Category
Agency Certification (when product is marked)
0 to +55
-40 to +85 5 to 95% noncondensing Tested to 30g peak acceleration, 11(+1)ms pulse width Tested to 50g peak acceleration, 11(+1)ms pulse width
Tested 5g @ 10-500Hz per IEC68-2-6
12 gauge (4mm 3/64 in (1.2mm) maximum insulation 2
• CSA certified
• CSA Class 1, Division 2 Groups A, B, C and D certified
• UL listed
• CE marked for all applicable directives
Publications • Installation Instructions - 1793-5.7
• User Manual - 1793-6.5.1
1 Use this categor y information for planning conductor routing as described in publication
1770-4.1, “Wiring and Grounding Guidelines for Noise Immunity.”
o
C
o
C
o
C (32 to +131oF)
o
C (-40 to +185oF)
2
) stranded wire
Publication 1793-6.5.1 - April 1999
Data Table Formats
Appendix
B
Two’s Complement Binary
Two’s complement binary is used when performing mathematical calculations internal to the processor. To complement a number means to change it to a negative number. For example, the following binary number is equal to decimal 22.
10110
First, the two’s complement method places an extra bit (sign bit) in the left-most position, and lets this bit determine whether the number is positive or negative. The number is positive if the sign bit is 0 and negative if the sign bit is 1. Using the complement method:
0 10110 = 22
To get the negative using the two’s complement method, you must invert each bit from right to left after the first “1” is detected.
In the above example:
0 10110 = +22
Its two’s complement would be:
1 01010 = –22
Note that in the above representation for +22, starting from the right, the first digit is a 0 so it is not inverted; the second digit is a 1 so it is not inverted. All digits after this one are inverted.
= 22
2
10
If a negative number is given in two’s complement, its complement (a positive number) is found in the same way:
1 10010 = –14 0 01110 = +14
All bits from right to left are inverted after the first “1” is detected.
The two’s complement of 0 is not found, since no first “1” is ever encountered in the number. The two’s complement of 0 then is still 0.
Publication 1793-6.5.1 - April 1999
B-2 Data Table Formats
Analog Data Format
Output
Current (mA) 4-20mA Mode 0-20mA Mode Voltage (V)
The data returned from the analog-to-digital converter in the module is 12-bit resolute. This value is left-justified into a 16-bit field, reserving the most significant bit for a sign bit.
A/D Unipolar Data
Analog Value
Input
A/D Bipolar Data
Analog Value
D/A Data
Analog Value
0.00 0000 –10.00 8620 8618
1.00 0618 –9.00 9250 9248
2.00 0C30 –8.00 9E80 9E78
3.00 1248 –7.00 AAB0 AAA8
4.00 0000 1860 –6.00 B6E0 B6D8
5.00 0787 1E78 –5.00 C310 C310
6.00 0F0F 2490 –4.00 CF40 CF40
7.00 1696 2AA8 –3.00 DB70 DB70
8.00 1E1E 30C0 –2.00 E7A0 E7A0
9.00 25A5 36D8 –1.00 F3D0 F3D0
10.00 2D2D 3CF0 0.00 0000 0000 0000
11.00 34B4 4310 1.00 0C30 0C30 0C30
12.00 3C3C 4928 2.00 1860 1860 1860
13.00 43C3 4F40 3.00 2490 2490 2490
14.00 4B4B 5558 4.00 30C0 30C0 30C0
15.00 52D2 5B70 5.00 3CF0 3CF0 3CF0
16.00 5A5A 6188 6.00 4920 4928 4928
17.00 61E1 67A0 7.00 5550 5558 5558
18.00 6969 6DB8 8.00 6180 6188 6188
19.00 70F0 73D0 9.00 6DB0 6DB8 6DB8
20.00 7878 79E8 10.00 79E0 79E8 79E8
21.00 7FFF 7FF8 10.50 7FF0 7FF8 7FF8
11 10 09 08 07 06 05 04 03 02 01 00
14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0*
= Always positive
*
10 09 08 07 06 05 04 03 02 01 00
S
14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
S
11 10 09 08 07 06 05 04 03 02 01 00
S
14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
S
±10 Volt Mode
Input Output
–10.50 8000 8000
0-10 Volt Mode
Publication 1793-6.5.1 - April 1999
Data Table Formats B-3
Scaling Example
To scale your data to a different range:
SLC 500 - use the scaling instruction.
PLC-5 - determine a constant (slope) by dividing the desired range by the actual range. Multiply the result by your data, and add or subtract any offset.
Example: A 4-20mA input places data at N13:0 (Figure 3.4 on page 3-4), with a range of 0 to 30,840. (30,840 = 7878 hex - see data format on page C-2).
You want the 4-20mA (0 to 30,840) to be 32 to 1000 degrees in the PLC-5. Use the following formula:
Scaled Data (degrees) @ N30:0 = {[(Desired Range)/Actual Range] X Analog Input Data} + Offset
= {[(1000 - 32)/30,840] X N13:0} + 32
F8:0
= F8:0 + 32
Scaled Data (degrees) @ N30:0 (See ladder logic below)= F8:0 + 32
Example using Compute Instructions
This rung will scale FLEX I/O analog data to a different range. In this example, we want the 4-20mA input data to represent 32 to 1000 degrees in the PLC-5. For this example, N13:0 = 30,840 (7878 in hex). Two compute instructions are needed because of the way the destination value will be rounded if we use an integer location instead of floating point in the first compute instruction. The second compute instruction has a final destination of an integer location.
CPT
COMPUTE
Scaled Data
DESTINATION: F8:0
EXPRESSION: ((1000.000 - 32.00000) | 30840) * n13:0
CPT
COMPUTE
DESTINATION: N30:0
EXPRESSION: F8:0 + 32.00000
968.0001
1000
Publication 1793-6.5.1 - April 1999
Index
A
DGDSWHULQSXWVWDWXVZRUG5-1 DQDORJPRGXOHV
types1-2
B
ELWZRUGGHVFULSWLRQ
4 output/4 input module4-65-6
6-8
block transfer read
1793-IE2XOE14-8 1793-IE45-46-6 1793-IE44-4 1793-IE4XOE14-8 1793-OE25-6 1793OE24-6 1793-IE2XOE15-9
block transfer write
1793-IE2XOE14-105-11 1793-IE45-5 1793-IE44-5 1793-OE25-8 1793-OE24-7
EORFNWUDQVIHU
read1-2 write1-2
EORFNWUDQVIHUSURJUDPPLQJ3-1 EORFNWUDQVIHUUHDG4-2
1793-IE2XOE15-9 1793-IE45-4 1793-OE25-6 1793-OE24-6
EORFNWUDQVIHUZULWH
1793-IE2XOE14-84-95-10 1793-IE45-3 1793-IE44-3 1793-OE24-5 1793-OE26-7 configuration block4-95-10
1793-IE44-45-4 1793-OE24-65-7
input range selection4-2
C
FRPPXQLFDWLRQ
between module and adapter1-3
FRQILJXUDWLRQEORFN
block transfer write
1793-IE45-4 1793-IE44-4 1793-OE25-7 1793-OE24-6
FRQILJXUDWLRQZRUGELWZRUG
GHVFULSWLRQ
1793-IE2XOE16-11 1793-OE26-9
FRQILJXUDWLRQZRUGELWGHVFULSWLRQ
1793-IE46-7 FRQILJXULQJIHDWXUHV4-1 FRQQHFWLQJZLULQJ
1793-IE2XOE12-9
1793-IE42-6
1793-OE22-8
FRQQHFWLQJZLULQJ,(;2(
2-8
FRQQHFWLQJZLULQJ,(2-5 FRQQHFWLQJZLULQJ2(2-6 FRQQHFWRUW\SHV2-5 FRQVLGHUDWLRQV
pre-installation2-1 &RQWURO1HWPDSSLQJ
1793-IE2XOE16-9
1793-IE46-6
1793-OE26-7 FXUUHQWGUDZ2-2
D
GDWDPDSSLQJ5-3 GHIDXOWYDOXHV5-11 GHVFULSWLRQ
adapter1-1
I/O modules1-1
terminal base1-1 GHYLFHDFWLRQV6-4
idle state behavior6-5
input data behavior upon module
removal6-5
'HYLFH1HW0DQDJHU
software5-1
Publication 1793-6.5.1 - April 1999
I-2
F
IHDWXUHV
configuring4-1 of the module1-4
I
,2PRGXOHIDXOW5-26-4 LQGLFDWRUV
status2-10
LQSXWUDQJHV4-2
program selectable1-2 LQSXWVWDWXVZRUG5-26-3 LQSXWZRUGELWZRUGGHVFULSWLRQ
1793-IE2XOE16-9
1793-OE26-8 LQVWDOOLQJWKHPRGXOH2-2
L
OHIWMXVWLILHGGDWD3-54-2B-2 ORZYROWDJHGLUHFWLYH2-2
M
PDSSLQJ
1793-IE2XOE15-9
1793-OE25-6
data5-3
PRGXOHIDXOW5-2 PRGXOHIHDWXUHV1-4 PRGXOHPDSSLQJ6-2
O
RSWLPDOGHIDXOWV5-11 RXWSXWZRUGELWZRUGGHVFULSWLRQ
1793-IE2XOE16-10
1793-OE26-8
P
3/&SURJUDPPLQJ3-5 3/&VDPSOHSURJUDP
,(;2(3-3
3/&VDPSOHSURJUDP,(
3-2
3/&VDPSOHSURJUDP2(
3-3
3/&VDPSOHSURJUDP
,(;2(3-5
SURJUDPPLQJH[DPSOH
PLC-33-2 PLC-53-4
R
UDQJH
selecting4-2
UDQJHVHOHFWLRQ
1793-IE2XOE14-10
5-106-10 1793-IE45-56-7 1793-IE44-5 1793-OE25-76-8 1793-OE24-7
UHPRYLQJDPRGXOH2-4
S
VDIHVWDWH
selection of4-2
VDPSOHSURJUDPV3-6 VFKHGXOHGGDWDWUDQVIHU6-2 VRIWZDUH
DeviceNetManager5-1
VSHFLILFDWLRQV
1793-IE2XOE1 and -IE2XOE1S
A-4
1793-IE4 and -IE4SA-1 1793-OE2 and -OE2SA-3
VWDWXVLQGLFDWRUV2-10 V\VWHPWKURXJKSXW5-3
U
XQVFKHGXOHGGDWDWUDQVIHU6-2
W
ZLULQJ
to terminal bases2-1
ZLULQJFRQQHFWLRQV
1793-IE2XOE12-9 1793-IE42-6 1793-OE22-8
Publication 1793-6.5.1 - April 1999
Allen-Bradley Publication Problem Report
If you find a problem with our documentation, please complete and return this form.
Pub. Name FLEX Integra Analog Modules User Manual
Cat. No.
Check Problem(s) Type: Describe Problem(s)
What information is missing?
What is unclear?
1793-IE4, OE2, IE2XOE1 Pub. No. 1793-6.5.1 Pub. Date April 1999 Part No. 955132-30
Internal Use Only
Technical Accuracy t ex t illustration
Completeness procedure/step illustration definition info in manual
example guideline feature (accessibility)
explanation other info not in
Clarity
Sequence
What is not in the right order?
Other Comments
Use back for more comments.
Your Name Location/Phone
Return to: Marketing Communications, Allen-Bradley., 1 Allen-Bradley Drive, Mayfield Hts., OH 44124-6118Phone: (440) 646-3176
FAX: (440) 646-4320
Publication ICCG-5.21- August 1995 PN 955107-82
Other Comments
PLEASE FASTEN HERE (DO NOT STAPLE)
PLEASE FOLD HERE
BUSINESS REPLY MAIL
FIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OH
POSTAGE WILL BE PAID BY THE ADDRESSEE
1 ALLEN BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705
NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES
PLEASE REMOVE
Publication 1793-6.5.1 - April 1999 PN 955132-30
© (1999) Rockwell International Corporation. Printed in the U.S.A.
Loading...