ArmorBlock MaXum 12 Input/
4 Output Module Series B
(Cat. No. 1792D-12BVT4D)
O-0
O-3
O-1
O-2
I-0
I-11
I-1
I-10
I-2
I-9
I-3
I-8
I-4
I-7
I-5
I-6
Auxilary Power
Logic Status
Net/Mod Status
42338
This ArmorBlock MaXum™ I/O module (Cat. No. 1792D-12BVT4D) is
a stand-alone 24V dc I/O product which communicates via a
DeviceNet™ network. The sealed housing of this module requires no
enclosure.
This model has 12 inputs and 4 outputs accessed through Y splitter
cables. Inputs are 24V dc automatically configured for PNP (sourcing)
or NPN (sinking) devices. Four self-protected 24V dc outputs can
provide up to 2.0 amp each. Diagnostic features are short circuit,
open wire and no load detection reported to the connector level for
inputs, to point level for outputs. Local logic control has been added
to the Series B version of this product.
Publication 1792D-IN004B-EN-P - August 2000
2 ArmorBlock MaXum 12 Input/ 4 Output Module Series B
Check Package Contents
Your package contains:
• 1 ArmorBlock MaXum Module
• Installation Instructions
(Please note: Cable bases are ordered and shipped separately.)
European Union Directive Compliance
If this product has the CE mark it is approved for installation within
the European Union and EEA regions. It has been designed and
tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in
whole or in part, documented in a technical construction file:
• EN 50081-2 EMC - Generic Emission Standard, Part 2 Industrial Environment
• EN 50082-2 EMC - Generic Immunity Standard, Part 2 Industrial Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low
Voltage, by applying the safety requirements of EN 61131-2
Programmable Controllers, Part 2 - Equipment Requirements and
Tests.
For specific information required by EN 61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
• Industrial Automation Wiring and Grounding Guidelines For
Noise Immunity, publication 1770-4.1
• Automation Systems Catalog, publication B113
Publication 1792D-IN004B-EN-P - August 2000
ArmorBlock MaXum 12 Input/ 4 Output Module Series B 3
Install Your ArmorBlock MaXum I/O Module
To install the module you must:
• Set the node address
• Mount the module to the cable base
• Connect the input/output cord sets to the MaXum module
• Communicate with your ArmorBlock MaXum I/O module
Each of these steps is explained in the following procedures.
Set the Node Address
Valid node addresses are 00 to 63.
Set the node address using the rotary switches, RSNetWorx for
DeviceNet™, or other software configuration tool. Setting the
switches between 64 to 99 lets the software have address control.
Each module is shipped set for node address 63. The switches are
located on the underside of the module. The two switches are:
• MSD (most significant digit)
• LSD (least significant digit)
To reset the node address, use a small blade screwdriver to rotate the
switches. Line up the small black dot on the switch with the number
setting you wish to use.
The rotary switches are read at module power up only. Settings
between 64 and 99 cause the module to use the last valid node
address stored internally. Example: The last setting was 40. If a
change is made to 68, and then you power up, the address will
default to 40.
Publication 1792D-IN004B-EN-P - August 2000
4 ArmorBlock MaXum 12 Input/ 4 Output Module Series B
Refer to the illustration of the node address below.
41462
The module is equipped with AutoBaud detect. AutoBaud lets the
module read the settings already in use on your DeviceNet network
and automatically adjusts to follow those settings.
Mount the Module to the Cable Base
This module mounts to the following cable bases:
• 1792D-CBFM for KwikLink™ flat media installation
• 1792D-CB12 for 12mm drop cable installation
• 1792D-CB18P for round media DeviceNet and output power
• or other optional cable base assembly
IMPORTANT
Publication 1792D-IN004B-EN-P - August 2000
The cable base should already be installed. See
publication 1792D-IN036B-EN-P (CB18P) or
1792D-IN009B-EN-P (CBFM, CB12) to install the
cable base.
ArmorBlock MaXum 12 Input/ 4 Output Module Series B 5
e
e
To install the module:
IMPORTANT
Proper alignment of the screws is necessary to
complete the connections between the module
contacts and the cable contacts.
1. Position the module over the mounted cable base. Align the
three captive screws in the module with the accepting
receptacles in the base.
2. Tighten the screws with a torque of 8 inch-pounds to secure
the module to the base.
Note: Dimensions change according to the cable base and module
combination used.
2
.
7
(
6
8
6
.
)
1.9 (48.26)
Cable Base
1792D-CBFM is used for
this example.
6.85 (174)
Align the
screws to
properly
assemble th
module to th
base.
Assembled
dimensions
in (mm)
41522
Connect the Input / Output Cord Sets to the MaXum
Module
Eight micro caps cover the connectors on your module. Remove the
caps and connect your cord sets to the appropriate ports. This
product has two inputs or outputs per I/O connector. Use a “Y”
splitter cable for access to all I/O connections.
Publication 1792D-IN004B-EN-P - August 2000
6 ArmorBlock MaXum 12 Input/ 4 Output Module Series B
Use the micro caps to cover and seal unused ports. Pinout diagrams
for the connectors are shown next.
Input Micro-Connector
(View into Socket)
Pin 1 Sensor Source voltage
Pin 2 Input B
Pin 3 Return Logic Ground
Pin 4 Input A
Pin 5 Not Used
Output Micro-Connector
(View into Socket)
Pin 1 Not Used
Pin 2 Output B
Pin 3 Auxiliary Power Ground
Pin 4 Output A
Pin 5 Not Used
1
Logic Ground is approximately 0.4V above DeviceNet V- measured at the module.
1
41452
Molded I/O cables with LEDs embedded in the connector are
incompatible with MaXum universal sink/source inputs. Please refer
to publication 889-5.0 for Rockwell Automation cables and cord sets
offerings.
IMPORTANT
If the devices (sensors) connected to the input
connections require Class 2 power to operate, the
DeviceNet connections of this equipment must be
powered by a Class 2 source.
ATTENTION
• Make sure all connectors and caps are
securely tightened to properly seal the
connections against leaks and maintain
IP67 requirements.
!
• For maximum noise immunity, input and
output cable return wires must be properly
terminated. When inputs and outputs are
connected in loopback, return wires should
be connected together.
• I/O cable length should be less than 30
meters.
Publication 1792D-IN004B-EN-P - August 2000
ArmorBlock MaXum 12 Input/ 4 Output Module Series B 7
I/O connectors for this module are shown below.
O-0
O-3
O-1
Logic Status
O-2
I-0
I-11
I-1
I-10
I-2
I-9
I-3
I-8
I-4
I-7
I-5
I-6
Auxiliary Power
Net/Mod Status
Output 3
Output 2
Input 11
Input 10
Input 9
Input 8
Input 7
Input 6
Connector F
Connector E
Connector D
42339
Connector A
Connector B
Connector C
Output 0
Output 1
Input 0
Input 1
Input 2
Input 3
Input 4
Input 5
Output Power and DeviceNet Cables
Output power and DeviceNet cables are described in the installation
publications for the cable base assembly of your choice. Refer to the
following publications:
• 1792D-IN009B-EN-P ArmorBlock MaXum Cable Base
Installation Guide
• DN-6.7.2 DeviceNet Cable Planning and Installation Manual
Communicate With Your ArmorBlock MaXum I/O
Module
This ArmorBlock module’s I/O is exchanged with the master through
a poll, change-of-state, or cyclic connection.
The module consumes and produces I/O data as follows:
Type of I/O ConnectionsConsumesProduces
Cyclic1 Byte4 Bytes
Polled1 Byte4 Bytes
Change-of-State1 Byte4 Bytes
Publication 1792D-IN004B-EN-P - August 2000
8 ArmorBlock MaXum 12 Input/ 4 Output Module Series B
Cyclic - allows configuration of the block as an I/O client. The block
will produce and consume its I/O cyclically at the rate configured.
Polled device - a master initiates communication by sending its
polled I/O message to the module. The 12 input / 4 output module
consumes the message, updates outputs, and produces a response.
The response has input data, input faults, output faults, and the status
of the Auxiliary power.
Change-of-State device - productions occur when an input changes
or a fault condition occurs. If no input or fault condition change
occurs within the expected packet rate, a heartbeat production
occurs. This heartbeat production tells the scanner module that the
I/O module is alive and ready to communicate. Consumption occurs
when data changes and the master produces new output data to the
I/O block.
Refer to the table below for the word/bit definitions.
Bit0706050403020100
Produces 0I7I6I5I4I3I2I1I0
Produces 1ISC-DISC-CISC-BISC-AI11I10I9I8
Produces 2OW-FOW-EOW-D OW-COW-B OW-AISC-FISC-E
Produces 3RSVDOPWR RSVDRSVDOFLT3 OFLT2 OFLT1OFLT0
Consumes 0RSVDRSVDRSVDRSVDO3O2O1O0
Where: OW = Off Wire RSVD= Reserved I = Input O = Output OPWR= Output Power
(Auxiliary Power) OFLT = Output fault ISC=Input Short Circuit in Sensor Source Voltage
ByteBitDescription
Produces 000-07Input Status bits: When the bit is set (1), the input is on.
Produces 100-03
04-07
Publication 1792D-IN004B-EN-P - August 2000
Bit 00=input 0, bit 01=input 1, bit 02=input 2,
bit 03= input 3, bit 04=input 4, bit 05=input 5, bit
06=input 6, bit 07=input 7.
Input Status bits: When the bit is set (1), the input is on.
Bit 08=input 8, bit 09=input 9, bit 010=input 10,
bit 011= input 11.
Input short circuit fault (ISC): (ISC-A indicates a short
circuit fault for connector A.
Input short circuit fault ((ISC): (ISC-B indicates a short
circuit fault for connector B.
Input short circuit fault ((ISC): (ISC-C indicates a short
circuit fault for connector C.
Input short circuit fault ((ISC): (ISC-D indicates a short
circuit fault for connector D.
ArmorBlock MaXum 12 Input/ 4 Output Module Series B 9
ByteBitDescription
Produces 200-01
Produces 300-03
Consumes 000-03
ISC
02-07
Off Wire
OFLT0-3
06
04, 05, 07
04-07
Input short circuit fault (ISC): (ISC-E indicates a short
circuit fault for connector E.
Input short circuit fault ((ISC): (ISC-F indicates a short
circuit fault for connector F.
Input off wire fault (OW): OW-A indicates an off-wire fault
for connector A.
Input off wire fault (OW): OW-B indicates an off-wire fault
for connector B.
Input off wire fault (OW): OW-C indicates an off-wire fault
for connector C.
Input off wire fault (OW): OW-D indicates an off-wire fault
for connector D.
Input off wire fault (OW): OW-E indicates an off-wire fault
for connector E.
Input off wire fault (OW): OW-F indicates an off-wire fault
for connector F.
Output no load or overload fault (OFLT): - When the bit is
set (1) an output fault has occurred. OFLT0 corresponds to
output 0, OFLT1 corresponds to output 1, OFLT2
corresponds to output 2, OFLT3 corresponds to output 3
Output Power Fault (OPWR): When the bit is set (1)
Auxiliary Power is not present.
RSVD = Reserved
Output bits: When the bit is set (1), the output will be
turned on. Bit 00 corresponds to output O0, bit 01
corresponds to output 01, bit 02 to output 02, bit 03 to
output 03.
RSVD = Reserved
The DeviceNet Network uses advanced network technology,
producer/consumer communication, to increase network
functionality and throughput. Visit our web site at
http://www.ab.com/networks
for producer/consumer technology
information and updates.
Troubleshoot with the Indicators
This module has the following indicators:
• Network/Module status indicator
• Logic status indicator
• Auxiliary Power indicator
• Individual I/O status indicators
Publication 1792D-IN004B-EN-P - August 2000
10 ArmorBlock MaXum 12 Input/ 4 Output Module Series B
Refer to the following table for point indicators.
Point indicators for
outputs 0 and 1
Point indicators for
inputs 0 and 1
Connector A
Point indicators for
inputs 2 and 3
Connector B
Point indicators for
inputs 4 and 5
Connector C
Module Status
Indicators
Logic Status
O-0
O-3
O-1
O-2
I-0
I-11
I-1
I-10
I-2
I-9
I-3
I-8
I-7
I-4
I-5
I-6
Auxiliary Power
Net/Mod Status
Point indicators for
outputs 2 and 3
Point indicators for
inputs 10 and 11
Connector F
Point indicators for
inputs 8 and 9
Connector E
Point indicators for
inputs 6 and 7
Connector D
LED Assignments
The following table describes the network and module status
indicator.
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
ConductorsPublication DN-6.7.2
EnclosureMeets or exceeds IP67
Agency Certification (when
product is marked)
Technical Data (user information) Publication 1792-TD001B-EN-P
1.0
Sensor Source
Current - Amp
Note: This is an
illustration of total
current for all 12
inputs. Divide by
12 for current per
input.
0.8
0.6
0.4
0.2
0.0
-25 to 60° (-13 to 140°F)
-25 to 80° (-13 to 176°F)
5 to 100%
30g peak acceleration, 11 (+1) ms pulse width
50g peak acceleration, 11 (+1) ms pulse width
Tested 10g @ 10-500Hz per IEC 86-2-6
CSA certified
CSA Class 1, Division 2, Groups A, B, C, D certified
UL listed
CE marked for all applicable directives
Temperature=60°C
15 172511 13
DeviceNet Voltage -Vdc
21
1923
42574
Publication 1792D-IN004B-EN-P - August 2000
14 ArmorBlock MaXum 12 Input/ 4 Output Module Series B
Hazardous Location Approval
The following information applies only to products marked
with Hazardous Location Approval, when operating in
hazardous locations:
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in
Class I Division 2 Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is supplied with markings
on the rating nameplate indicating the hazardous location
temperature code. When combining products within a system, the
most adverse temperature code (lowest “T” number) may be used to
help determine the overall temperature code of the system.
Combinations of equipment in your system are subject to
investigation by the local Authority Having Jurisdiction at the time of
installation.
WARNING
!
WARNING
EXPLOSION HAZARD -
• Do not disconnect equipment unless power
has been removed or the area is known to be
nonhazardous.
• Do not disconnect connections to this
equipment unless power has been removed
or the area is known to be nonhazardous.
Secure any external connections that mate to
this equipment by using screws, sliding
latches, threaded connectors, or other means
provided with this product.
• Substitution of components may impair
suitability for Class I, Division 2.
• If this product contains batteries, they must
only be changed in an area known to be
nonhazardous.
Use supply wires suitable for 30°C above
surrounding ambient.
!
Publication 1792D-IN004B-EN-P - August 2000
ArmorBlock MaXum 12 Input/ 4 Output Module Series B 15
WARNING
When used in a Class I, Division 2, hazardous
location, this equipment must be mounted in a
suitable enclosure with proper wiring method that
complies with the governing electrical codes.
!
Les informations suivantes ne concernent que les produits
marqués pour une utilisation en environnements dangereux :
Les produits marqués « CL I, DIV 2, GP A, B, C, D » ne conviennent
qu’à une utilisation en environnements de Classe I Division 2
Groupes A, B, C, D dangereux et non dangereux. Chaque produit est
livré avec des marquages sur sa plaque d’identification qui indiquent
le code de température pour les environnements dangereux. Lorsque
plusieurs produits sont combinés dans un système, le code de
température le plus défavorable (code de température le plus faible)
peut être utilisé pour déterminer le code de température global du
système. Les combinaisons d’équipements dans le système sont
sujettes à inspection par les autorités locales qualifiées au moment de
l’installation.
AVERTISSEMENT
!
RISQUE D’EXPLOSION -
• Couper le courant ou s’assurer que
l’environnement est classé non dangereux
avant de débrancher l’équipement.
• Couper le courant ou s’assurer que
l’environnement est classé non dangereux
avant de débrancher les connecteurs. Fixer
tous les connecteurs externes reliés à cet
équipement à l’aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.
• La substitution de composants peut rendre cet
équipement inadapté à une utilisation en
environnement de Classe I, Division 2.
• S’assurer que l’environnement est classé non
dangereux avant de changer les piles.
Publication 1792D-IN004B-EN-P - August 2000
AVERTISSEMENT
!
Utiliser des fils d’alimentation qui conviennent à
une température de 30°C au-dessus de la
température ambiante.
AVERTISSEMENT
Pour une utilisation en environnement de classe i,
division 2 dangereux, cet equipement doit etre
monte dans un boitier avec un cablage approprie
conforme aux normes electriques en vigueur.
!
This product has been tested at an Open DeviceNet Vendor
Association, Inc. (ODVA) authorized independent test laboratory and
found to comply with ODVA Conformance Test. Please contact the
ODVA website (http://www.odva.org) for listing of products tested by
ODVA independent test labs for further details.