Because of the variety of uses for the products described in this
publication, those responsible for the application and use of this control
equipment must satisfy themselves that all necessary steps have been taken
to assure that each application and use meets all performance and safety
requirements, including any applicable laws, regulations, codes
and standards.
The illustrations, charts, sample programs and layout examples shown in
this guide are intended solely for example. Since there are many variables
and requirements associated with any particular installation, Allen-Bradley
does not assume responsibility or liability (to include intellectual property
liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI–1.1, “Safety Guidelines For The
Application, Installation and Maintenance of Solid State Control”
(available from your local Allen-Bradley office) describes some important
differences between solid-state equipment and electromechanical devices
which should be taken into consideration when applying products such as
those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or
in part, without written permission of Allen–Bradley Company, Inc.
is prohibited.
Throughout this manual we make notes to alert you to possible injury to
people or damage to equipment under specific circumstances.
A
TTENTION:
procedures are not followed properly.
A
TTENTION:
or economic loss can occur if procedures are not
followed properly.
Attention helps you:
Identify a hazard.
Avoid the hazard.
Recognize the consequences.
Important: We recommend you frequently backup your application
programs on appropriate storage medium to avoid possible data loss.
Tells readers where people may be hurt if
Tells readers where machinery may be damaged
Using This Manual
Preface
Purpose
of Manual
Audience
Vocabulary
Manual Organization
This manual shows you how to use your Block I/O with an Allen-Bradley
programmable controller. It helps you:
install
program and
troubleshoot your module.
You must be able to program and operate an Allen-Bradley programmable
controller (PLC) to make efficient use of Block I/O modules.
We assume that you know how to do this in this manual. If you do not,
refer to the appropriate PLC programming and operations manual before
you attempt to program this module.
In this manual, we refer to:
the block I/O module as the “block” or the “module”
the programmable controller as the “controller” or “processor.”
This manual is divided into 4 chapters. The following chart shows each
chapter with its corresponding title and brief overview of the topics
covered in that chapter.
ChapterTitleTopics Covered
1Introducing Block I/ODescription of the module, including general and hardware features
2Installing the ModuleModule power requirements, location, and wiring information
3Configuring your block I/OHow to set the configuration switches and address the block I/O.
4TroubleshootingHow to use the indicators to troubleshoot your block I/O module.
How to replace the fuse.
Appendix ASpecificationsSpecifications for the block I/O.
P-1
Preface
Using This Manual
About
Block I/O
Related Publications
Block I/O consists of small, self–contained remote I/O devices complete
with power supply, programmable controller interface, input/output
connections and signal conditioning circuitry.
This publication covers the 1791–IOBX and –IOVX block I/O modules.
The 1791–IOBX has 64 sinking inputs and 64 sourcing outputs; the
1791–IOVX has 64 sourcing inputs and 64 sinking outputs. In all other
aspects, they are identical.
For a list of publications with information on Allen-Bradley programmable
controller products, consult our publication index (SD499).
In this chapter you will learn what block I/O is, its features, and how it
functions.
Block I/O consists of small, self-contained remote I/O devices complete
with power supply, programmable controller interface, input/output
connections and signal conditioning circuitry.
The 1791-IOBX 24V dc module has 64 sink input channels, and 64 source
output channels.
The 1791-IOVX 24V dc module has 64 source input channels, and 64 sink
output channels.
Complete specifications for these modules are contained in Appendix A.
The blocks are compatible with PLC-2
programmable controllers, and the SLC
used with PLC-2 family programmable controllers, a sub-scanner module
is used to communicate with the blocks. When used with PLC-3 and
PLC-5 family programmable controllers, they can be connected directly to
the controller or to a scanner module. When used with SLC 500
controllers, a 1747-SN remote I/O scanner is used to communicate with the
blocks.
, PLC-3, and PLC-5 family
500 modular controllers. When
A
TTENTION:
you must use a 1775-S5 or -SR5 scanner module. Do not use
1775-SR, -S4A or -S4B scanner modules.
Note: The 1791-IOBX and -IOVX block modules are not compatible with
the 1747-DSN scanner module.
Connections are made to removable terminal blocks mounted on the sides
of the block.
Physical features of the block I/O are shown in Figure 1.1.
When using PLC-3 programmable controllers,
1-1
Chapter 1
Introducing Block I/O
Figure 1.1
Major
Features of the 1791-IOBX and -IOVX Block I/O Modules
(-IOBX shown)
Rack Address
Switch
, Active,
Power
Comm and Fuse
LED Indicators
Removable
Input Terminal
Blocks
87654321
CONFIGURATION
SWITCHES
RACK
ADDR
INPUT
DISPLAY
SELECT
OUTPUT
POWER
ACTIVE
COMM
FUSE
1791-IOBX
128
POINT
24V DC DISTRIBUTED
I/O MODULE
64
24VDC SINK INPUTS
64 24VDC SOURCE OUTPUTS
CONFIGURATION SWITCHES
Configuration Switches
(on top of unit)
Input/Output
Status LED
Array
Display Select
Pushbuttons
Removable
Output Terminal
Blocks
Terminal Block
Removal Screws
(same on all 4
terminal blocks)
1-2
GROUP
No.
RIO Wiring Block
+24V dc Power
GROUP No.
Termination
Resistor
Switch
10914-I
Wiring Terminals - The remote I/O field wiring is made to 4 separate
removable 37-pin terminal blocks mounted on the sides of the module.
Terminal assignments are shown in chapter 3.
A separate nonremovable terminal block is provided for connection of the
remote I/O link and external 24V dc power supply.
Chapter 1
P
A
F
Introducing Block I/O
Switch Assemblies - Two DIP switches are provided for setting the I/O
configuration and rack address.
The configuration switch lets you select baud rate, last state, processor
restart lockout, last rack and I/O group.
The rack addr
ess switch
lets you select the system rack address for the
block.
A third switch is provided for selection of the termination resistor.
Status Indicators - Indicators are provided for power, active,
communication and fuse blown indications. An LED array provides
input/output status.
Status Indicators - Bi-color LED indicators provide power, active,
communication and fuse blown indications. An LED array provides
input/output status.
IndicatorIndication
ower (green/wht)
ctive (green/red)
Comm (green/wht)
use (red/wht)
On (green)Customer voltage is present
Of
f (wht)
On (green)CPU operating correctly
Of
f (red)
On (green)Communication correctly established
Of
f (wht)
On (red)One of the 4 output fuses is open
Of
f (wht)
No customer voltage (less than 2V)
CPU not running
Communication not established
All fuses are intact
The I/O status array is an 8 by 8 array of 64 LEDs capable of displaying
the status of 32 inputs and 32 outputs at any one time. Pushbuttons are
provided to toggle the display between the lower 32 bits and the upper
32 bits.
How
the Block I/O Fits in a
PLC System
Block I/O is a complete I/O interface that includes the functionality of the
I/O rack, adapter, power supply, and I/O modules in a single unit. Simply
connect sensors and actuators to the module and use the remote I/O cable
to connect the block I/O to your programmable controller (Figure 1.6).
The 1791-IOBX block uses sinking inputs and sourcing outputs.
1-3
Chapter 1
Introducing Block I/O
In sinking inputs, the dc common is bussed on the block. and the current is
sourced from the field device. The sourcing field device switches the hot
side of the power supply bus causing current to flow through the sourcing
device to the sinking input on the block. Refer to Figure 1.2.
Figure 1.2
Sinking
Input Example
+V
Bus
DC Power
Supply
Field
Device
Field
Device
-V
Block I/O
Sinking
Input
Common
10826-I
Sourcing outputs have the power bussed in the block. When the output is
on, current is supplied to the field control device, which sinks the current.
The field circuit and the equipment remain at ground potential until the
output is turned on. Refer to Figure 1.3.
Note: The outputs must be externally fused to protect the device output
against overcurrent or short circuit conditions.
1-4
Figure 1.3
Sourcing
Block I/O
Common
Output Example
+V
Fuse
Fuse
Field
Device
Field
Device
Common
DC Power
Supply
-V
Bus
The 1791-IOVX block uses sourcing inputs and sinking outputs.
10827-I
Chapter 1
Introducing Block I/O
In sourcing input modules (Figure 1.4), the +V on dc circuits is bussed on
the module supplying (sourcing) the current for each input circuit. The
field device switches the circuit to the common (side of the power supply,
sinking the circuit and causing current to flow from the module’s input.
Figure 1.4
Sourcing
Input Example
DC Power
Supply
-V
+V
Block
I/O
Field
Device
Input
dc Common Bus
10917-I
In sinking outputs (Figure 1.5), the current flow is reversed. The dc
common is bussed on the module and the current is sourced from the field
device being actuated. When an output is turned on, the output switch in
the module sinks the circuit, causing current to flow from the +V bus
through the field device to the module.
Note: The outputs must be externally fused to protect the device output
against overcurrent or short circuit conditions.
Figure 1.5
Sinking
Output Example
Block I/O
Fuse
Fuse
Field
Device
Field
Device
+V
Bus
Common
Common
DC Power
Supply
-V
10918-I
1-5
Chapter 1
Introducing Block I/O
Block I/O functions exactly like any Allen-Bradley remote I/O product.
Input and output data is scanned asynchronously and transferred back and
forth between the block and the controller input and output image table.
You connect the block I/O to your remote I/O link as you would any other
device. The block looks like a 1/2 I/O rack to the processor, and uses 4
words of input image table memory and 4 words of output image table
memory. The block is addressed directly on the remote I/O link.
Figure 1.6
Block
I/O Connection in a PLC System
Blocks are daisy-chained to
a programmable controller
or scanner.
,
Programmable Controller,
or Scanner
Summary
Block I/O - each block
is 1/2 I/O rack.
10915-I
In this chapter you learned what block I/O is, its features and
how it functions.
1-6
Installing Block I/O
Chapter
2
Chapter
Pre-installation
Considerations
Installing the Block I/O
Objectives
In this chapter you will learn how to mount the block, how to connect the
remote I/O link, how to connect the input and output wiring to the block,
and how to terminate the remote I/O link.
Before installation, you must determine:
the number of blocks desired
the total distance of the installation
transmission rate desired
Mounting dimensions for the block I/O module are shown in Figure 2.1.
Mount the blocks horizontally with a minimum of 2” between blocks. This
air gap is necessary to maintain proper cooling air flow through the block.
2-1
Chapter 2
Installing Block I/O
0.67
(17.105)
Figure 2.1
Mounting
and -IOVX)
Dimensions for the Block I/O Module (Cat. No. 1791-IOBX
6.15
(156.21)
4.8
(122.0)
87654321
CONFIGURATION
SWITCHES
RACK
ADDR
Dimensions:
6.15W x 13.0H x 1.72D
(156.21W x 334.0H x 43.7D)
Inches
(Millimeters)
12.7
(322.0)
GROUP
POWER
ACTIVE
COMM
FUSE
INPUT OUTPUT
1791-IOBX
128 POINT
24V DC
DISTRIBUTED
I/O MODULE
CONFIGURATION SWITCHES
No.
DISPLAY
SELECT
GROUP No.
12.28
(312.0)
13.0
(334.0)
2-2
10916-I
The operating temperature in the air gap between block I/O modules must
not exceed 60
o
C (140oF). The dimensions of the air gap required are
shown in Figure 2.2.
Figure 2.2
Clearance
Chapter 2
Installing Block I/O
Required for Block I/O Modules
2
(50.8)
Connecting Wiring
2
(50.8)
2
(50.8)
2
(50.8)
Inches
(Millimeters)
10919-I
Connections to the block I/O module are made to the removable terminal
blocks on each side of the module. Input connections are on the left side,
and output connections are on the right side. The input terminal blocks are
keyed differently than the output blocks to prevent incorrect insertion.
TTENTION:
A
Both input terminal blocks are keyed alike. If
removed for wiring, or module replacement, make certain that
the terminal blocks are placed in their proper position
when reinstalling.
Wiring connections for the 1791-IOBX and -IOVX are shown in Tables
2.A through 2.H.
Catalog Number 1794-IOBXCatalog Number 1794-IOVX
Input Terminal WiringInput Terminal Wiring
Groups 0 and 1 (TRM1)Table 2.A, page 2-4Groups 0 and 1 (TRM1) Table 2.E, page 2-8
Groups 2 and 3 (TRM2)Table 2.B, page 2-5Groups 2 and 3 (TRM2) Table 2.F, page 2-9
Output Terminal WiringOutput Terminal Wiring
Groups 0 and 1 (TRM3)Table 2.C, page 2-6Groups 0 and 1 (TRM3) Table 2.G, page 2-10
Groups 2 and 3 (TRM4)Table 2.D, page 2-7Groups 2 and 3 (TRM4) Table 2.H, page 2-11
Remote I/O link wiring connections are shown in Figure 2.3.
2-3
Chapter 2
Numb
Numb
Installing Block I/O
T
able 2.A
1791-IOBX
Input T
erminal W
iring for Groups 0 and 1 (TRM1) for PLC
Family Controllers and SLC Processors
Terminal
er
Input Assignment
Group 0
PLCSLC
Terminal
er
Input Assignment
Group 1
PLCSLC
1Common A Common A19Common B Common B
2Input 00Input 0020Input 00Input 00
3Input 01Input 0121Input 01Input 01
4Input 02Input 0222Input 02Input 02
5Input 03Input 0323Input 03Input 03
6Input 04Input 0424Input 04Input 04
7Input 05Input 0525Input 05Input 05
8Input 06Input 0626Input 06Input 06