Rockwell Automation 1791-32AO User Manual

32 Input AC Block I/O Module
4.35
Cat. No. 1791-32A0 Series B

Installation

Mount the block I/O module in a vertical (recommended) or horizontal position. Allow sufficient room around the block for cooling air to flow through the block module. Refer to Figure 1.
Figure 1 Mounting Cat. No. 1791–32A0 (PLC version shown)
Dimensions for the Block I/O Module
0.5
(12.7)
6.95
6.60
(176.5)
(167.6)
30
Equipment
Grounding Stud
CAUTION:
When tightening grounding
stud nut, do not exceed 15 in-lbs.
(110.5)
3.35
Inches
(Millimeters)
(85.1)
1791-32A0
120V
1
00 01 02 03 04 05 06
07
00 01 02 03 04 05 06
07
ac INPUT
G
COMM
STATUS
00 01 02 03 04 05 06
07
(G+1)
RACK
#
ALLENĆBRADLEY
10 11 12 13 14 15 16
17
IN
IN
G
G+1
10
00
10
11
01
11
12
02
12
13
03
13
14
04
14
15
05
15
16
06
16
17
07
17
10 11 12 13 14 15 16
17
30
Block
2.0 (50.8) air gap on all 4 sides.
Operating temperature in air gap below module must not exceed 60oC
o
(140
1
F).
2
mounting holes
for #8 screws
Dimensions
6.95H x 4.35W x 3.85D (176.5H x 1
10.5W x 98D)
1
Installation Instructions
Block I/O Cat. No. 1791-32A0 Series B
Figure 2 Mounting
on a DIN Rail
DIN Rail
A-B Pt. No. 199-DR1
46277-3
EN 50022
(35 x 7.5mm)
1. Hook
top of slot over DIN rail.
2. While pressing block against rail, pull down on locking levers.
3.
When block is flush against rail, push up on locking levers to secure block to rail.
Locking levers
Figure 3 Inserting
2
Labels
A
set of die-cut labels is supplied with your module. Select the proper module designation labels (PLC or SLC) for the front door and terminal strips.
1.
Remove labels from package. Select correct labels for your application. (PLC label is numbered 00–07 and 10–17. SLC is numbered 00–07 and 08–15.)
Remove plastic cover on terminal strip
2
2. by flexing in middle. Slip the terminal designation label with power and RIO designations into built-in holders in left terminal strip cover to install. Repeat for the other terminal strip using the remaining label.
3.
Open clear front door designation label into slots in door
. Flex cover slightly
. Insert module
.
3
T
PL
able
A
Acceptable Wiring Cables for Block I/O Connection
Use Cable Type
Remote I/O link Belden 9463
Installation Instructions
Block I/O Cat. No. 1791-32A0 Series B
Input and output wiring
Up to 14AWG (2mm2) stranded with 3/64 inch (1.2mm) insulation
Connect wiring as shown in Figure 4 or Figure 5.
Figure 4 Wiring
Connections with PLC Family Programmable Controllers (refer
to T
able B)
C
1
1
L1
2
GND
N
NOT
USED
RIO
L2/N
L1
NOT
USED
BLU
SHD
CLR
COM
COM
2
1
COM
2
COM
1
COM
2
COM
1
in 10
00
in
in 1
1
in 01
in 12
in 02
in 13
in 03
in 14
in 04
in 15
in 05
in 16
in 06
29
in 17
30 1
in 07
30
L2/N
USED NOT
USED NO
CONN NO
CONN
3
COM
in 00 in 01 in 02 in 03 in 04 in 05 in 06
in 07 1
30
30
NO CONN
NOT
NO CONN
NOT
USED NO
CONN
COM
4
COM
4
3
COM
4
3
in 10 in 1
1
in 12 in 13
in 14 in 15 in 16
2
in 17
L2/N
L1
L2/NL1
29
COM COM
L2/N
L1
L1
NOTE:
COM
1 connections are internally connected together COM 2 connections are internally connected together COM 3 connections are internally connected together COM 4 connections are internally connected together
. . . .
3
Installation Instructions
Block I/O Cat. No. 1791-32A0 Series B
Figure 5 Wiring
Connections with SLC Family Processors (refer to Table B)
SLC
L2/N
L1
RIO
2
30
GND
NOT
USED
BLU CLR
COM
COM
COM
in in 01 in 02 in 03 in 04 in 05 in 06 in 07
1
1
L1
N
NOT
USED
SHD
COM
2
COM
1
2
COM
1
2
1
in 08
00
in 09 in 10
in 1
1 in 12 in 13 in 14
29
in 15
L2/N
L1
L2/N
L2/N
L1
L1
30
NOTE: COM
1 connections are internally connected together COM 2 connections are internally connected together COM 3 connections are internally connected together COM 4 connections are internally connected together
29
1
USED NO
CONN
NO CONN
COM COM
COM
in in 01 in 02 in 03 in 04 in 05 in 06 in 07
NOT
USED NOT
3 3 3
00
1
30
30
NO CONN
NO CONN
NOT
USED NO
CONN
COM
4
COM COM
4 4
L2/N
in 08 in 09
in 10 in 1
1
in 12
L1
in 13 in 14
2
in 15
. . . .
The block I/O module has an equipment grounding stud on the lower left side of the module. Connect this grounding stud to your equipment ground. Torque the nut to 15 in-lbs maximum when connecting to your equipment ground.
ATTENTION: Do not overtighten the nut on the grounding stud
when connecting the wire. Damage to the module could result.
Refer to “Industrial Automation Wiring and Grounding Guidelines” (1770-4.1) for further information.
4
T
Power
Remote I/O
Input
Input
Input
able B
Wiring
Block Designations
Connections
Installation Instructions
Block I/O Cat. No. 1791-32A0 Series B
1791–32A0 Series B Connector/Terminal
Designation Description Left Conn. Right Conn.
Power
Connections
L1 ac hot 1
N
ac neutral 3
GND Chassis ground 2
Remote I/O
Connections
BLU Blue wire – RIO 6 CLR
Clear wire – RIO 8
SHD Shield – RIO 7
I/O Connections
in 00 thru in 07 Input 00 thru 07
COM 1 L2/N Input Common 10, 12, 14
6
(G)
COM 2 L2/N Input Common 9, 11, 13
PLC: in 10 thru in 17 SLC: in 08 thru in 15
PLC: Input 10 thru 17 SLC: Input 08 thru 15
in 00 thru in 07 Input 00 thru 07
Input
7
(G+1)
1
Connect chassis ground to equipment grounding stud. These are not internally connected.
2
Left connector terminals 10, 12 and 14 are internally connected together
3
Left connector terminals 9, 1
4
Right connector terminals 21, 19 and 17 are internally connected together
5
Right connector terminals 22, 20 and 18 are internally connected together
6
IN (G) = input module group (1 word).
7
IN (G+1) = input module group plus 1 word
COM 3 L2/N Input Common 21, 19, 17 COM 4 L2/N Input Common 22, 20, 18
PLC: in 10 thru in 17 SLC: in 08 thru in 15
Not used
No Conn
1 and 13 are internally connected together
PLC: Input 10 thru 17 SLC: Input 08 thru 15
For internal test only; not for customer use.
No internal connection;
customer can use.
.
1
16, 18, 20, 22, 24, 26,
28, 30
2
3
15, 17, 19, 21, 23, 25,
27, 29
15, 13, 11,
9, 7, 5, 3, 1
4 5
16, 14, 12,
10, 8, 6, 4, 2
4, 5 29, 27, 26
30, 28, 25,
24, 23
5
Installation Instructions
Block I/O Cat. No. 1791-32A0 Series B
Figure 6 Switch
Settings
1
Default Switch
30
Settings = 0
SW2–8
Not used
SW2–7
87654321
Not Used
SW2
30
1
Open cover to access switches
SW1
Position = 1Position = 0
End View
ATTENTION: Cycle power to the module after
setting the switches.
Only block I/O modules with all inputs or all outputs can use complementary I/O.
NOTE:
Set switch SW2–3 to 0 if this rack will have a unique address (not complemented). If this rack address is a duplicate of another I/O block or chassis, set the switch to 1 for primary or 0 for complementary. Refer to Table C for the complementary I/O rack address.
01
01
SW2–6
Last I/O Group
(PLC-2 only)
0 Not last rack 1 Last rack
SW2–5
Processor
Restart/Lockout (PRL)
0 Processor Restart
87654321
1 Processor Lockout
SW2–4 Hold Last State
0 Reset Outputs 1 Hold Last State
SW2–3 Complementary I/O
0 Non-Complemented System 0 Complementary Rack
1 Primary Rack
1
See note.
Communication Rate
SW2–2 SW2–1 Bits/s
0 0 57.6 K 0 1 115.2 K 1 0 230.4 K 1 1 230.4 K
Starting Quarter
SW1–2 SW1–1
0 0 0 (1st) 0 1 2 (2nd) 1 0 4 (3rd) 1 1 6 (4th)
1
1
1
Module
Group
6
Installation Instructions
Ra
Ra
Ra
Ra
Ra
Ra
Block I/O Cat. No. 1791-32A0 Series B
1747-SN Number
Rack Rack 1 Rack 2 Rack 2 Rack 1 Rack 1 Rack 1 Rack 2 Rack 3 Rack 3 Rack 2 Rack 2 Rack 2 Rack 3 Rack 4 Rack 4 Rack 3 Rack 3 Rack 3
1771-SN
ck
Number
0
Rack 1 Rack 1
Rack 5 Rack 5 Rack 4 Rack 4 Rack 4 Rack 6 Rack 6 Rack 5 Rack 5 Rack 5 Rack 7 Rack 7 Rack 6 Rack 6 Rack 6
PLC–2
ck
Number
PLC–5
ck
PLC–5/250
ck
Number
Not V
alid
Rack 7 Rack 7 Rack 7 Rack 10 Rack 10 Rack 10 Rack 1
1 Rack 12 Rack 12 Rack 12 Rack 13 Rack 13 Rack 13 Rack 14 Rack 14 Rack 14 Rack 15 Rack 15 Rack 15 Rack 16 Rack 16 Rack 16 Rack 17 Rack 17 Rack 17 Rack 20 Rack 20 Rack 20 Rack 21 Rack 21 Rack 21 Rack 22 Rack 22 Rack 22 Rack 23 Rack 23 Rack 23 Rack 24 Rack 24 Rack 24 Rack 25 Rack 25 Rack 25 Rack 26 Rack 26 Rack 26 Rack 27 Rack 27 Rack 27
PLC–3
ck
Number
Rack 0 Rack 0
Rack 1
Rack 30 Rack 30 Rack 31 Rack 31 Rack 32 Rack 32 Rack 33 Rack 33 Rack 34 Rack 34 Rack 35 Rack 35 Rack 36 Rack 36 Rack 37 Rack 37
Number
1
Rack 1
Rack 40 Rack 41 Rack 42 Rack 43 Rack 44 Rack 45 Rack 46 Rack 47 Rack 50
ck
SW1 Switch Position
8 7 6 5 4 3
0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 1 0 0 0 0 0 1 1 0 0 0 1 0 0 0 0 0 1 0 1 0 0 0 1 1 0 0 0 0 1 1 1 0 0 1 0 0 0
1 0 0 1 0 0 1
0 0 1 0 1 0 0 0 1 0 1 1 0 0 1 1 0 0 0 0 1 1 0 1 0 0 1 1 1 0 0 0 1 1 1 1 0 1 0 0 0 0 0 1 0 0 0 1 0 1 0 0 1 0 0 1 0 0 1 1 0 1 0 1 0 0 0 1 0 1 0 1 0 1 0 1 1 0 0 1 0 1 1 1 0 1 1 0 0 0 0 1 1 0 0 1 0 1 1 0 1 0 0 1 1 0 1 1 0 1 1 1 0 0 0 1 1 1 0 1 0 1 1 1 1 0 0 1 1 1 1 1 1 0 0 0 0 0 1 0 0 0 0 1 1 0 0 0 1 0 1 0 0 0 1 1 1 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 1 1 1 0 1 0 0 0
7
Installation Instructions
Ra
Ra
Block I/O Cat. No. 1791-32A0 Series B
Rack
Rack
PLC–5/250
PLC–5/250
1747-SN
1747-SN
Rack
Rack
Number
Number
Rack address 77 is an illegal configuration. PLC-5/1 PLC-5/15 and PLC-5/20 processors can scan racks 01–03. PLC-5/25 and PLC-5/30 processors can scan racks 01–07. PLC-5/40 and PLC-5/40L processors can scan racks 01–17. PLC-5/60 and PLC-5/60L processors can scan racks 01–27. PLC-5/250 processors can scan racks 00–37.
1771-SN
1771-SN
Rack
Rack
Number
Number
1 processors can scan rack 03.
PLC–2
PLC–2
Rack
Rack
Number
Number
PLC–5
PLC–5
Number
Number
Rack
Rack
Number
Number
PLC–3
PLC–3
Rack
Rack
Number
Number
Rack
51 Rack 52 Rack 53 Rack 54 Rack 55 Rack 56 Rack 57 Rack 60 Rack 61 Rack 62 Rack 63 Rack 64 Rack 65 Rack 66 Rack 67 Rack 70 Rack 71 Rack 72 Rack 73 Rack 74 Rack 75 Rack 76
Not V
alid 1 1 1 1 1 1
SW1 Switch Position
1 0 1 0 0 1 1 0 1 0 1 0 1 0 1 0 1 1 1 0 1 1 0 0 1 0 1 1 0 1 1 0 1 1 1 0 1 0 1 1 1 1 1 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 1 0 1 1 0 0 1 1 1 1 0 1 0 0 1 1 0 1 0 1 1 1 0 1 1 0 1 1 0 1 1 1 1 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 1 0 1 1 1 0 1 1 1 1 1 1 0 0 1 1 1 1 0 1 1 1 1 1 1 0
345678
T
able C
PLC–2
and PLC–5 With Complementary I/O
PLC–2
Number
Rack Rack 2 Rack 1 Rack 3 Rack 2 Rack 4 Rack 3 Rack 5 Rack 4 Rack 6 Rack 5 Rack 7 Rack 6
ck
PLC–5
ck
Number
1
Not V
alid 0 0 1 0 0 0
Rack 7
SW1 Switch Position
8 7 6 5 4 3
0 0 1 0 0 1 0 0 1 0 1 0 0 0 1 0 1 1 0 0 1 1 0 0 0 0 1 1 0 1 0 0 1 1 1 0 0 0 1 1 1 1
8
When
configured as complementary I/O: PLC-2 can scan racks 01–07 PLC-5/1
1 can scan rack 03 PLC-5/20, PLC-5/30, PLC-5/40, PLC-5/60 can scan racks 01–07
NOTE:
Remote rack numbers which can have a complementary rack are rack numbers 01 thru 07 only
.
Installation Instructions
Block I/O Cat. No. 1791-32A0 Series B
The SLC 500 controllers communicate with the block I/O using an I/O Scanner module (cat. no. 1747-SN series A). Refer to the user manual for the 1747-SN/A Scanner module for more information.
Important: This block I/O module is not compatible with the 1747-DSN Distributed I/O Scanner module.

Termination Resistor

A
termination resistor must be installed on the last block in a series. Connect the
resistor as shown in Figure 7.
Figure 7 Installing
Connect terminals 6 (BLU) and 8 (CLR).
150 ohm – 57.6K and 115.2K baud 82 ohm – 230.4K baud
the T
ermination Resistor
termination resistor across
Termination
Resistor
BLU CLR
SHD
10835–I
ATTENTION: Devices that are operating at 230.4K baud must have
82 ohm terminators in place for proper operation.
9
Installation Instructions
Block I/O Cat. No. 1791-32A0 Series B

Indicators

PLC SLC
ININ
COMM
STATUS
Indicator Description
COMM OFF
STATUS OFF
COMM is communicating with the block.
ON Flashing
ON Flashing
and STATUS will alternately flash when processor restart lockout is selected, a fault has occurred and the processor
G G+1
10
00
11
01
12
02
13
03
14
04
15
05
16
06
17
07
10
00
11
01
12
02
13
03
14
04
15
05
16
06
17
07
COMM
STATUS
00 01 02 03 04 05 06 07
Communication not established Communication established Processor in Program mode
Normal Error (hardware or software), block power low COMM F
AIL – communication cable disconnected, 100ms between valid frames, no more than 255 valid frames between valid frames addressed to block, 20ms idle time exceeded.
ININ
G G+1
00
08
01
09
02
10
03
11
04
12
05
13
06
14
07
15
08 09 10 11 12 13 14 15

Fusing

The block I/O module is internally fused to protect the module. No external power fusing is required.
10
Installation Instructions
Block I/O Cat. No. 1791-32A0 Series B

1791-32A0 Specifications

Input Specifications
Inputs per Block 32 (4 groups of 8) Nominal Input Current 11.0mA Nominal Input Voltage 120V ac On–state Voltage Range 79–132V ac, 47–63Hz Off-state Voltage Maximum 35V On-state Current Minimum
Maximum Off-state Current Minimum 2.3mA (60Hz) Input Impedance Maximum 15K ohms @ 60Hz Input Signal Delay Off to on
On to off
Specifications continued on next page
5mA @ 79V, 60Hz
12.3mA @ 132V, 60Hz
1.0ms 26ms (maximum) (allows for 1/2 cycle dropout)
11
Installation Instructions
Block I/O Cat. No. 1791-32A0 Series B

General Specifications

External Power (internally protected ­no external fuse required)
Voltage
Current Dimensions Inches
Millimeters Isolation Power supply to RIO
I/O Group-to-Group
I/O Group-to-Logic Power Dissipation Maximum 13.62 Watts Thermal Dissipation Maximum 46.44 BTU/hr Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity Conductors Wire Size
Category
1
You
use this conductor category information for planning conductor routing as described in
the system level installation manual.
85–132V ac, 47–63Hz 150mA
6.95H X 4.35W X 3.85D
176.5H X 110.5W X 98D 500V ac
1250V ac 1250V ac
0 to 60oC (32 to 140oF) –40 to 85oC (–40 to 185oF) 5 to 95% noncondensing
14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum
1
1
WORLD HEADQUARTERS Allen-Bradley 1201 South Second Street Milwaukee, WI 53204 USA
Tel: (414) 382-2000 Telex: 43 11 016 FAX: (414) 382-4444
With offices in major cities worldwide
Publication 1791-5.14 – May 1995
Supersedes publication 1791-2.14 – March 1994
12
Copyright 1995 Allen-Bradley Company, Inc. Printed in USA
PN 955122–60
Loading...