Rockwell Automation 1791-16A0 User Manual

16 Input AC Block I/O Module
Cat. No. 1791-16A0 Series B
Installation
Mount the block I/O module in a vertical (recommended) or horizontal position. Allow sufficient room around the block for cooling air flow through the block module. Refer to Figure 1.
Figure 1 Mounting Cat. No. 1791–16A0 Series B (PLC version shown)
Dimensions for the Block I/O Module
2.710 (68.8)
1.71
(43.4)
1791-16A0
120V
1
00 01 02 03 04 05 06
07
INPUT INPUT
00 01 02 03 04 05 06
07
ac INPUT
(12.7)
6.95
(176.5)
0.5
6.60
(167.6)
Inches
(Millimeters) Dimensions
6.95H x 2.710W x 3.85D (176.5H x 68.8W x 98D)
10 11 12 13 14 15 16
17
Block
Equipment
Grounding Stud
30
CAUTION:
10 11 12 13 14 15 16
17
2.0 (50.8) air gap on all 4 sides.
Operating temperature in air gap below module must not
ALLENĆBRADLEY
exceed 60oC (140oF).
2
mounting holes
for #8 screws
When tightening grounding stud nut, do not exceed 15 in-lbs.
12381–I
1
Installation Instructions
Block I/O Cat. No. 1791-16A0 Series B
Figure 2 Mounting
1.
2. While pressing block against rail,
3. When block is flush against rail,
on a DIN Rail
Block
Hook top of slot over DIN rail.
pull down on locking lever
push up on locking lever to secure block to rail.
.
Figure 3 Inserting
Labels
DIN Rail
A-B Pt. No. 199-DR1
46277-3
EN 50022
(35 x 7.5mm)
Locking Lever
12382–I
A set of labels is supplied with your module. Select the proper module designation labels (PLC or SLC) for the front door and terminal strip.
1.
Remove die-cut labels from package. Select correct
labels for your application. (PLC label is numbered
2
00–07 and 10–17. SLC label is numbered 00–07 and 08–15.)
2.
Remove plastic cover on terminal strip by flexing in middle. Slip the terminal designation label into built-in holders in terminal strip cover slightly to install.
3. Open clear front door label into slots that secure it to the door
. Insert module designation
. Flex cover
3
.
12384–I
2
Installation Instructions
Block I/O Cat. No. 1791-16A0 Series B
Connect wiring as shown in Figure 4 or Figure 5.
Figure 4 Wiring
Connections with PLC Family Programmable Controllers (refer
to T
able
A)
PLC
RIO
L2/N
L1
GND
NOT
USED
BLU CLR
COM
1
COM
1
COM
00
in in 01 in 02 in 03 in 04 in 05 in 06 in 07
30
1
L1
N
NOT
USED
SHD
COM
2
COM
2
COM
2
1
in 10
in 1
1
in 12
in 13 in 14 in 15 in 16 in 17
L1
NOTE: COM 1 connections are internally connected together.
COM 2 connections are internally connected together.
L2/N
L2/N
L1
12386–I
3
Installation Instructions
Block I/O Cat. No. 1791-16A0 Series B
Figure 5 Wiring
Connections with SLC Family Processors (refer to T
able
A)
SLC
RIO
L2/N
L1
GND
NOT
USED
BLU CLR
COM
1
COM
1
COM
00
in in 01 in 02 in 03 in 04 in 05 in 06 in 07
30
1
L1
N
NOT
USED
SHD
COM
2
COM
2
COM
2
1
in 08
in 09 in 10
in 1
1 in 12 in 13 in 14 in 15
L1
L2/N
L2/N
L1
NOTE: COM 1 connections are internally connected together.
COM 2 connections are internally connected together.
12389–I
The block I/O module has an equipment grounding stud on the lower left side of the module. Connect this grounding stud to your equipment ground. Torque the nut to 15 in-lbs maximum when connecting to your equipment ground.
ATTENTION: Do not overtighten the nut on the grounding stud
when connecting the wire. Damage to the module could result.
Refer to “Programmable Controller Wiring and Grounding Guidelines” (1770-4.1) for further information.
4
Loading...
+ 8 hidden pages