Rockwell Automation 1791-16A0 User Manual

16 Input AC Block I/O Module
Cat. No. 1791-16A0 Series B
Installation
Mount the block I/O module in a vertical (recommended) or horizontal position. Allow sufficient room around the block for cooling air flow through the block module. Refer to Figure 1.
Figure 1 Mounting Cat. No. 1791–16A0 Series B (PLC version shown)
Dimensions for the Block I/O Module
2.710 (68.8)
1.71
(43.4)
1791-16A0
120V
1
00 01 02 03 04 05 06
07
INPUT INPUT
00 01 02 03 04 05 06
07
ac INPUT
(12.7)
6.95
(176.5)
0.5
6.60
(167.6)
Inches
(Millimeters) Dimensions
6.95H x 2.710W x 3.85D (176.5H x 68.8W x 98D)
10 11 12 13 14 15 16
17
Block
Equipment
Grounding Stud
30
CAUTION:
10 11 12 13 14 15 16
17
2.0 (50.8) air gap on all 4 sides.
Operating temperature in air gap below module must not
ALLENĆBRADLEY
exceed 60oC (140oF).
2
mounting holes
for #8 screws
When tightening grounding stud nut, do not exceed 15 in-lbs.
12381–I
1
Installation Instructions
Block I/O Cat. No. 1791-16A0 Series B
Figure 2 Mounting
1.
2. While pressing block against rail,
3. When block is flush against rail,
on a DIN Rail
Block
Hook top of slot over DIN rail.
pull down on locking lever
push up on locking lever to secure block to rail.
.
Figure 3 Inserting
Labels
DIN Rail
A-B Pt. No. 199-DR1
46277-3
EN 50022
(35 x 7.5mm)
Locking Lever
12382–I
A set of labels is supplied with your module. Select the proper module designation labels (PLC or SLC) for the front door and terminal strip.
1.
Remove die-cut labels from package. Select correct
labels for your application. (PLC label is numbered
2
00–07 and 10–17. SLC label is numbered 00–07 and 08–15.)
2.
Remove plastic cover on terminal strip by flexing in middle. Slip the terminal designation label into built-in holders in terminal strip cover slightly to install.
3. Open clear front door label into slots that secure it to the door
. Insert module designation
. Flex cover
3
.
12384–I
2
Installation Instructions
Block I/O Cat. No. 1791-16A0 Series B
Connect wiring as shown in Figure 4 or Figure 5.
Figure 4 Wiring
Connections with PLC Family Programmable Controllers (refer
to T
able
A)
PLC
RIO
L2/N
L1
GND
NOT
USED
BLU CLR
COM
1
COM
1
COM
00
in in 01 in 02 in 03 in 04 in 05 in 06 in 07
30
1
L1
N
NOT
USED
SHD
COM
2
COM
2
COM
2
1
in 10
in 1
1
in 12
in 13 in 14 in 15 in 16 in 17
L1
NOTE: COM 1 connections are internally connected together.
COM 2 connections are internally connected together.
L2/N
L2/N
L1
12386–I
3
Installation Instructions
Block I/O Cat. No. 1791-16A0 Series B
Figure 5 Wiring
Connections with SLC Family Processors (refer to T
able
A)
SLC
RIO
L2/N
L1
GND
NOT
USED
BLU CLR
COM
1
COM
1
COM
00
in in 01 in 02 in 03 in 04 in 05 in 06 in 07
30
1
L1
N
NOT
USED
SHD
COM
2
COM
2
COM
2
1
in 08
in 09 in 10
in 1
1 in 12 in 13 in 14 in 15
L1
L2/N
L2/N
L1
NOTE: COM 1 connections are internally connected together.
COM 2 connections are internally connected together.
12389–I
The block I/O module has an equipment grounding stud on the lower left side of the module. Connect this grounding stud to your equipment ground. Torque the nut to 15 in-lbs maximum when connecting to your equipment ground.
ATTENTION: Do not overtighten the nut on the grounding stud
when connecting the wire. Damage to the module could result.
Refer to “Programmable Controller Wiring and Grounding Guidelines” (1770-4.1) for further information.
4
T
s
Power
Remote I/O
able
A
Block Designations
Wiring
Connection
Installation Instructions
Block I/O Cat. No. 1791-16A0 Series B
1791–16A0 Series B
Designation Description Terminal No.
Power
Connections
L1 ac hot 1
N
ac neutral 3
GND Chassis ground 2
Remote I/O
Connections
BLU Blue wire – RIO 6 CLR
Clear wire – RIO 8
SHD Shield – RIO 7
I/O Connections
Input in 00 thru in 07 Input 00 thru 07
COM 1 L2/N Input Common 10, 12, 14 COM 2 L2/N Input Common 9, 11, 13
Input
PLC: in 10 thru in 17 SLC: in 08 thru in 15
Not used
1
Connect chassis ground to equipment grounding stud. These are not internally connected.
2
T
erminals 10, 12 and 14 are internally connected.
3
T
erminals 9, 11 and 13 are internally connected.
T
able B
PLC: Input 10 thru Input 17 SLC: Input 08 thru Input 15
For internal test only; not for
customer use.
Acceptable Wiring Cables for Block I/O Connection
1
16, 18, 20, 22,
24, 26, 28, 30
2
3
15, 17, 19, 21,
23, 25, 27, 29
4, 5
Use Cable Type
Remote I/O link Belden 9463
Input and output wiring
Up to 14AWG (2mm2) stranded with 3/64 inch (1.2mm) insulation
5
Installation Instructions
Not use
Block I/O Cat. No. 1791-16A0 Series B
Figure 6 Switch
Settings
1791-16A0
120V
1
ac INPUT
Default Switch
Settings = 0
87654321
SW2–8
d
SW2–7
Not used
INPUT INPUT
00 01 02 03 04 05 06
07
10 11 12
SW2
13 14 15 16 17
01
SW1
30
01
Open cover to access switches
Position = 1Position = 0
End View of Switch
ATTENTION: Cycle power to the module after
setting the switches.
Only block I/O modules with all inputs or all outputs can use complementary I/O.
NOTE: Set switch SW2–3 to 0 if this rack will have a
unique address (not complemented). If this rack address is a duplicate of another I/O block or chassis, set the switch to 1 for primary or 0 for complementary. Refer to Table C for the complementary I/O rack address.
Series A block I/O modules do not support complementary I/O. If using series A modules, set switch SW2–3 to 0.
6
SW2–6 Last I/O Group
0 Not last rack 1 Last rack
SW2–5
87654321
0 Processor Restart
Processor
Restart/Lockout (PRL)
1 Processor Lockout
SW2–4 Hold Last State
0 Reset Outputs 1 Hold Last State
SW2–3 Complementary I/O
0 Non-Complemented System 0 Complementary Rack
1 Primary Rack
1
See note.
Communication Rate
SW2–2 SW2–1 Bits/s
0 0 57.6 K 0 1 115.2 K 1 0 230.4 K 1 1 230.4 K
Starting Quarter
SW1–2 SW1–1
0 0 0 (1st) 0 1 2 (2nd) 1 0 4 (3rd) 1 1 6 (4th)
1
1
1
Module
Group
12391–I
Installation Instructions
Ra
Ra
Ra
Ra
Ra
Ra
Block I/O
Cat. No. 1791-16A0 Series B
1747-SN Number
Rack Rack 1 Rack 2 Rack 2 Rack 1 Rack 1 Rack 1 Rack 2 Rack 3 Rack 3 Rack 2 Rack 2 Rack 2 Rack 3 Rack 4 Rack 4 Rack 3 Rack 3 Rack 3
1771-SN
ck
Number
0
Rack 1 Rack 1
Rack 5 Rack 5 Rack 4 Rack 4 Rack 4 Rack 6 Rack 6 Rack 5 Rack 5 Rack 5 Rack 7 Rack 7 Rack 6 Rack 6 Rack 6
PLC–2
ck
Number
PLC–5
ck
PLC–5/250
ck
Number
Not V
alid
Rack 7 Rack 7 Rack 7 Rack 10 Rack 10 Rack 10 Rack 1
1 Rack 12 Rack 12 Rack 12 Rack 13 Rack 13 Rack 13 Rack 14 Rack 14 Rack 14 Rack 15 Rack 15 Rack 15 Rack 16 Rack 16 Rack 16 Rack 17 Rack 17 Rack 17 Rack 20 Rack 20 Rack 20 Rack 21 Rack 21 Rack 21 Rack 22 Rack 22 Rack 22 Rack 23 Rack 23 Rack 23 Rack 24 Rack 24 Rack 24 Rack 25 Rack 25 Rack 25 Rack 26 Rack 26 Rack 26 Rack 27 Rack 27 Rack 27
PLC–3
ck
Number
Rack 0 Rack 0
Rack 1
Rack 30 Rack 30 Rack 31 Rack 31 Rack 32 Rack 32 Rack 33 Rack 33 Rack 34 Rack 34 Rack 35 Rack 35 Rack 36 Rack 36 Rack 37 Rack 37
Number
1
Rack 1
Rack 40 Rack 41 Rack 42 Rack 43 Rack 44 Rack 45 Rack 46 Rack 47 Rack 50
ck
SW1 Switch Position
8 7 6 5 4 3
0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 1 0 0 0 0 0 1 1 0 0 0 1 0 0 0 0 0 1 0 1 0 0 0 1 1 0 0 0 0 1 1 1 0 0 1 0 0 0
1 0 0 1 0 0 1
0 0 1 0 1 0 0 0 1 0 1 1 0 0 1 1 0 0 0 0 1 1 0 1 0 0 1 1 1 0 0 0 1 1 1 1 0 1 0 0 0 0 0 1 0 0 0 1 0 1 0 0 1 0 0 1 0 0 1 1 0 1 0 1 0 0 0 1 0 1 0 1 0 1 0 1 1 0 0 1 0 1 1 1 0 1 1 0 0 0 0 1 1 0 0 1 0 1 1 0 1 0 0 1 1 0 1 1 0 1 1 1 0 0 0 1 1 1 0 1 0 1 1 1 1 0 0 1 1 1 1 1 1 0 0 0 0 0 1 0 0 0 0 1 1 0 0 0 1 0 1 0 0 0 1 1 1 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 1 1 1 0 1 0 0 0
7
Installation Instructions
Ra
Ra
Block I/O Cat. No. 1791-16A0 Series B
Rack
Rack
PLC–5/250
PLC–5/250
1747-SN
1747-SN
Rack
Rack
Number
Number
Rack address 77 is an illegal configuration. PLC-5/1 PLC-5/15 and PLC-5/20 processors can scan racks 01–03. PLC-5/25 and PLC-5/30 processors can scan racks 01–07. PLC-5/40 and PLC-5/40L processors can scan racks 01–17. PLC-5/60 and PLC-5/60L processors can scan racks 01–27. PLC-5/250 processors can scan racks 00–37.
1771-SN
1771-SN
Rack
Rack
Number
Number
1 processors can scan rack 03.
PLC–2
PLC–2
Rack
Rack
Number
Number
PLC–5
PLC–5
Number
Number
Rack
Rack
Number
Number
PLC–3
PLC–3
Rack
Rack
Number
Number
Rack
51 Rack 52 Rack 53 Rack 54 Rack 55 Rack 56 Rack 57 Rack 60 Rack 61 Rack 62 Rack 63 Rack 64 Rack 65 Rack 66 Rack 67 Rack 70 Rack 71 Rack 72 Rack 73 Rack 74 Rack 75 Rack 76
Not V
alid 1 1 1 1 1 1
SW1 Switch Position
1 0 1 0 0 1 1 0 1 0 1 0 1 0 1 0 1 1 1 0 1 1 0 0 1 0 1 1 0 1 1 0 1 1 1 0 1 0 1 1 1 1 1 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 1 0 1 1 0 0 1 1 1 1 0 1 0 0 1 1 0 1 0 1 1 1 0 1 1 0 1 1 0 1 1 1 1 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 1 0 1 1 1 0 1 1 1 1 1 1 0 0 1 1 1 1 0 1 1 1 1 1 1 0
345678
T
able C
PLC–2
and PLC–5 With Complementary I/O
PLC–2
Number
Rack Rack 2 Rack 1 Rack 3 Rack 2 Rack 4 Rack 3 Rack 5 Rack 4 Rack 6 Rack 5 Rack 7 Rack 6
ck
PLC–5
ck
Number
1
Not V
alid 0 0 1 0 0 0
Rack 7
SW1 Switch Position
8 7 6 5 4 3
0 0 1 0 0 1 0 0 1 0 1 0 0 0 1 0 1 1 0 0 1 1 0 0 0 0 1 1 0 1 0 0 1 1 1 0 0 0 1 1 1 1
8
When
configured as complementary I/O,: PLC-2 can scan racks 01–07 PLC-5/1
1 can scan rack 03 PLC-5/20, PLC-5/30, PLC-5/40, PLC-5/60 can scan racks 01–07
NOTE:
Remote rack numbers which can have a complementary rack are rack numbers 01 thru 07 only
.
Installation Instructions
Block I/O
Cat. No. 1791-16A0 Series B
The SLC 500 controllers communicate with the block I/O using an I/O Scanner module (cat. no. 1747-SN series A). Refer to the user manual for the 1747-SN/A Scanner module for more information.
Note: This block I/O module is not compatible with the 1747-DSN Distributed I/O Scanner module.
Termination Resistor
A
termination resistor must be installed on the last block in a series. Connect the
resistor as shown in Figure 7.
Figure 7 Installing
Connect terminals 6 (BLU) and 8 (CLR).
150 ohm – 57.6K and 115.2K baud 82 ohm – 230.4K baud
the T
ermination Resistor
termination resistor across
Termination
Resistor
BLU CLR
SHD
12392–I
ATTENTION: Devices that are operating at 230.4K baud must have
82 ohm terminators in place for proper operation.
9
Installation Instructions
Block I/O Cat. No. 1791-16A0 Series B
Indicators
PLC SLC
INPUT INPUT
00 01 02 03 04 05 06 07
COMM
STATUS
10 11 12 13 14 15 16 17
Indicator Description
COMM OFF
ON Flashing
STATUS OFF
ON Flashing
COMM
and STATUS will alternately flash when processor restart lockout is selected, a fault has occurred and the processor
is communicating with the block.
Communications not established Communication established Processor in Program mode
Normal Error (hardware or software), block power low COMM F
AIL – Communication cable of than 255 valid frames between valid frames addressed to block, 20ms idle time exceeded.
INPUT INPUT
00 01 02 03 04 05 06 07
COMM
STATUS
f, 100ms between valid frames, no more
08 09 10 11 12 13 14 15
12394–I
Fusing
The block I/O module is internally fused to protect the module. No external power fusing is required.
10
Installation Instructions
Block I/O
Cat. No. 1791-16A0 Series B
1791-16A0 Series B Specifications
Input Specifications
Inputs per Block 16 (2 groups of 8) Nominal Input Current 11.0mA Nominal Input Voltage 120V ac On–state Voltage Range 79–132V ac, 47–63Hz Off-state Voltage Maximum 35V On-state Current Minimum 5mA @ 79V, 60Hz Off-state Current Minimum 2.3mA (60Hz) Input Impedance Maximum 15K ohms @ 60Hz Input Signal Delay Off to on
On to off
General Specifications
External Power (Internally protected
- no external fuse required) Voltage Current
Dimensions Inches
Millimeters
Isolation Power supply to RIO
I/O Group-to-Group
I/O Group-to-Logic Power Dissipation Maximum 8.9 Watts Thermal Dissipation Maximum 30.35 BTU/hr Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity Conductors Wire Size
Category
1
You
use this conductor category information for planning conductor routing as described in the
system level installation manual.
1.0ms 26ms (maximum) (allows for 1/2 cycle dropout)
85–132V ac, 47–63Hz 150mA
6.95H X 2.7W X 3.85D
176.5H X 68.8W X 98D 500V ac
1250V ac 1250V ac
0 to 60oC (32 to 140oF) –40 to 85oC (–40 to 185oF) 5 to 95% noncondensing
14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum
1
1
11
Installation Instructions
Block I/O Cat. No. 1791-16A0 Series B
Publication 1791-5.24 – May 1995
Supersedes publication 1791-2.24 – March 1994
12
Copyright 1995 Allen-Bradley Company, Inc. Printed in USA
PN 955122–59
Loading...