Rockwell Automation 1790-XXXX User Manual

Page 1
Installation Instructions
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
(Cat. Nos. 1790D-4R0, -4T0, -T4R0, -T4T0)
What This Document Describes
This document describes how to install your CompactBlock LDX™ I/O blocks.
For information on: Refer to page:
EDS File Requirements below Important User Information 2 Installing CompactBlock I/O 5 Wiring the Terminal Blocks 8 Connecting the Field Wiring 9 Connecting the DeviceNet Cable 14 I/O Memory Mapping 15 Troubleshooting with the Indicators 17 Module Specifications 18
Current functionality of CompactBlock LDX I/O blocks requires
current modular EDS file for RSNetWorx for DeviceNet version
3.0 or later software.
These files are easy to install and are available online at: www.ab.com/networks/eds/
EDS files for blocks with matching catalog numbers (for both D-Shell and terminal block versions) are the same. Thus, on the website and in RSNetWorx for DeviceNet, there is only one EDS file for both versions of the blocks. For example, if you want the EDS file for 1790D-T8BV8B, use the EDS file labled 1790D-8BV8B.
Publication 1790-IN011B-EN-P - April 2003
Page 2
2
WARNING
!
WARNING
!

Important User Information

Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Rockwell Automation be responsible or liable for indirect or consequential damage resulting from the use or application of these products.
Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation and Maintenance of Solid-State Control
(available from your local Rockwell Automation office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard:
Publication 1790-IN011B-EN-P - April 2003
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Page 3
3
ATTENTION
!
IMPORTANT
ATTENTION
!
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on
component boards.
Do not touch circuit components inside the equipment.
If available, use a static-safe workstation.
When not in use, store the equipment in
appropriate static-safe packaging.
Publication 1790-IN011B-EN-P - April 2003
Page 4
4
ATTENTION
!
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as "open type" equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 ("Industrial Automation Wiring and Grounding Guidelines"), for additional installation requirements pertaining to this equipment.
Publication 1790-IN011B-EN-P - April 2003
Page 5
5

Installing CompactBlock LDX I/O

Follow these steps to install the block:
1. Set the node address on the base block.
2. Mount the base block.
3. Wire the terminal blocks.
4. Connect field wiring.
5. Connect the DeviceNet cable.
These steps are explained in detail in the following procedures.

Set the Node Address on the Base Block

Each base block comes with its internal program set for node address 63. To reset the node address, adjust the switches on the front of the block. The two switches are most significant digit (MSD) and least significant digit (LSD). The switches can be set between 00 and 63.
The base block reads the rotary switches at power up only. Switch settings between 64 and 99 cause the block to use the last valid node address stored internally
.
Example: Node Address is set at 11
The node address may also be set through RSNetWorx for DeviceNet or a similar configuration tool. When software configuration is used for the node address, the switches must be set between 64 and 99.
Publication 1790-IN011B-EN-P - April 2003
Page 6
6
WARNING
!
WARNING
!

Mount the Base Block

You can mount the base block to a panel or DIN rail. We recommend that you ground the panel or DIN rail before
mounting the block.
IMPORTANT
Panel Mounting
1. Place the block against the panel where you want to mount it.
2. Gently pull and position the expansion cover to the left.
3. Place a center punch, nail or similar device through the
mounting holes in the block and make two marks on the panel (lower left and upper right corners of the module).
4. Remove the block and drill two holes in the panel to accommodate each of the mounting screws.
The RTD and thermocouple base blocks do not support any expansion blocks.
When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with the proper wiring method that complies with the governing electrical codes.
Publication 1790-IN011B-EN-P - April 2003
Page 7
5. Replace the block on the panel and place a screw
through each of the two mounting holes. Tighten the screws until the block is firmly in place.
95 mm
3.74 in
CompactBlock LDX
1790-16BVOX
41 mm
1.6 in
EXPANSION UNIT
0
0
7
16 INPUTS-DCPOWER
7
Expansion Cover
DIN Rail Mounting
1. Hook the top slot of the block over the DIN Rail.
2. Pull down on the locking lever while pressing the block
against the rail.
7
f
Locking Lever
3. Push up on the locking lever to secure the block to the rail when block is flush against the rail.
Publication 1790-IN011B-EN-P - April 2003
Page 8
8

Wire the Terminal Blocks

The following figures show how to wire the terminal blocks.

1790D-4R0 RTD Input Module D-Shell Wiring

CH1_B
10
29
COM
CH1_B
10
29
NC
NC
11
CH3_B
CH3_A
11
10
CH3_B
NC
28
NC
28
COM
12
9
COM
9
13
12
NC
8
27
NC
8
27
NC
14
COM
NC
13
CH2_B
CH2_A
CH3_A
7
6
26
24
25
COM
COM COM COM
COM
CH2_B
CH2_A
CH3_A
7
6
26
24
25
NC
NC NC NC
NC
NC
NC
17
15
18
16
NC
NC
NC
NC
17
15
16
14
NC
NC
NC
5
5
NC
19
18
CH3_B
23
COM
CH3_B
23
NC
20
NC
NC
19
4
4
20
NC
NC
NC
NC
3
1
2
22
20
21
COM
NC
NC
NC
3
1
2
22
20
21
NC
+24V
NC
NC
CH0_B
+24V
19
37
GND
18
36
GND
+24V
17
35
GND
NC
16
15
34
33
NC
NC
CH0_A
14
32
NC
13
COM
CH1_A
11
12
30
31
COM
COM
• Wire pins 17, 18, 19 to Field Power (+) 24Vdc Wire pins 35, 36, 37 to Field Power (-) GND

1790D-4T0 Thermocouple Module D-Shell Wiring

+24V
NC
NC
CH0_B
+24V
19
37
GND
18
36
GND
+24V
17
35
GND
NC
16
15
34
33
NC
NC
CH0_A
14
32
NC
CH1_A
11
13
12
30
31
NC
NC
• Wire pins 17, 18, 19 to Field Power (+) 24Vdc Wire pins 35, 36, 37 to Field Power (-) GND

1790D-T4RO RTD Input Module Terminal Block Wiring

+24V
CH0_A
1
2
GND
CH1_A
3
CH0_B
5
4
CH1_B
COM
6
CH2_A
7
8
COM
CH3_A
9
10
CH2_B
• Wire pin 1 to Field Power (+) 24Vdc Wire pin 2 to Field Power (-) GND

1790D-T4T0 Thermocouple Input Module Terminal Block Wiring

+24V
CH1_A
5
4
CH1_B
6
NC
7
CH2_A
9
8
CH2_B
NC
CH0_A
1
2
GND
3
CH0_B
• Wire pin 1 to Field Power (+) 24Vdc Wire pin 2 to Field Power (-) GND
Publication 1790-IN011B-EN-P - April 2003
Page 9
9

Connect Field Wiring

System Wiring Guidelines
Follow these guidelines when wiring your system:
use shielded, twisted pair wire to ensure proper operation and high immunity to electrical noise
to limit noise, locate RTD and resistance device signal wires as far away as possible from power lines, load lines and other sources of electrical noise, such as hard-contact switches, relays and AC motor drives
under normal conditions, the drain wire and shield junction should be connected to earth ground, via a panel or DIN rail mounting screw at the block end
keep shield connection to ground as short as possible
to ensure optimum accuracy, limit overall cable impedance
by keeping the cable as short as possible. Locate the I/O system as close to your field devices as your application will permit.
RTD Wiring Guidelines
Since the operating principle of the RTD module is based on the measurement of resistance, give special consideration when selecting the input cable. For 2-wire or 3-wire configurations, select a cable that has consistent impedance throughout its entire length.
Publication 1790-IN011B-EN-P - April 2003
Page 10
10
IMPORTANT
The RTD block requires three wires to compensate for lead resistance error. We recommend that you do not use 2-wire RTDs if long cable runs are required, as it reduces the accuracy of the system. However, if a 2-wire configuration is required, reduce the effect of the lead wire resistance by using a lower-gauge wire for the cable (for example, use AWG #16 instead of AWG #24). The block’s terminal strip accepts AWG #14 gauge wire.
When using a 3-wire configuration, the block compensates for resistance error due to lead wire length. For example, in a 3-wire configuration, the block reads the resistance due to the length of the wires and assumes that the resistance of the other wire is equal. If the resistance of the individual lead wires are much different, an error may exist. The closer the resistance values are to each other, the greater the amount of error is eliminated.
IMPORTANT
To ensure temperature or resistance value accuracy, the resistance difference of the cable lead wires must be equal to or less than 0.01 ohm.
Publication 1790-IN011B-EN-P - April 2003
Page 11
11
To ensure that the lead values match as closely as possible:
keep lead resistance as small as possible and less than 25 ohms
use quality cable that has a small tolerance impedance rating
use a heavy-gauge lead wire which has less resistance per foot
RTD Wiring Configurations
Three configurations of RTDs can be connected to the blocks:
2-wire RTD, which is composed of an RTD EXC (excitation) lead wire and a RTN (return) wire
3-wire RTD, which is composed of a Sense and 2 RTD lead wires (RTD EXC and RTN)
4-wire RTD, which is composed of a Sense and 2 RTD lead wires (RTD EXC and RTN). The second sense wire of a 4-wire RTD is left open.

2-Wire RTD Configuration

Add Jumper
CH0_A
CH0_B
COM
Cable Shield (to Ground)
RTD EXC RTD EXC
Return Return
Publication 1790-IN011B-EN-P - April 2003
Page 12
12

3-Wire RTD Configuration

Cable Shield (to Ground)
CH0_A
CH0_B
COM
RTD EXC
Sense
Return
RTD EXC
Sense
Return

4-Wire RTD Configuration

Leave this sensor wire open
RTD EXC
Sense
Return
CH0_A
CH0_B
COM
Cable Shield (to Ground)
RTD EXC
Sense
Return

Wiring Resistance Devices (Potentiometers)

Potentiometer wiring requires the same type of cable as that for the RTD. Potentiometers can be connected to the module as a 2-wire or 3-wire connection as shown in the following figures:
2-Wire Potentiometer Interconnection
Add Jumper
CH0_A
CH0_B
COM
Add Jumper
CH0_A
CH0_B
COM
Cable Shield (to Ground)
RTD EXC
Return
Cable Shield (to Ground)
RTD EXC
Return
Publication 1790-IN011B-EN-P - April 2003
Potentiometer
Potentiometer
Page 13
3-Wire Potentiometer Interconnection
TIP
r
The potentiometer wiper arm can be connected to either the EXC or return terminal, depending on whether you want increasing or decreasing resistance.
Cable Shield (to Ground)
CH0_A
CH0_B
COM
CH0_A
CH0_B
COM
RTD EXC
Return
Cable Shield (to Ground)
RTD EXC
Sense
Return
13
Potentiomete
Run Return and sense wires from the module to potentiometer terminal and tie terminal to one point
Potentiometer
Run Return and sense wires from the module to potentiometer terminal and tie terminal to one point
Publication 1790-IN011B-EN-P - April 2003
Page 14
14
WARNING
!
WARNING
!

Connect the DeviceNet Cable

Follow these procedures when connecting the DeviceNet cable to the base block.
The required DeviceNet connector is not supplied with the block - you must purchase it separately. There are three types of connectors that you can order directly from Rockwell Automation or your local distributor:
1799-DNETCON - 5-position open style connector
1799-DNETSCON - 5-position open style connector with
locking screws
1799-DNC5MMS - 5-position open style to 5-pin micro
male connector with locking screws
If you connect or disconnect the DeviceNet cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is re moved or the area is nonhazardous before proceeding.
Connect the DeviceNet wiring (drop line) to one of the DeviceNet connectors as shown below. A color-coded wiring diagram is also printed next to the connector on the left side of the module
CompactBlock LDX
Wiring Diagram for 1799-DNETCON
1790D-8BV8V
8 INPUTS/8OUTPUTS-DC POWER
7
0
7
0
V+ Red
Can_H White
Drain/Shield
Can_L Blue
V- Black
V+ Red
V- Black
Wiring Diagram for 1799-DNC5MMS
Publication 1790-IN011B-EN-P - April 2003
Drain/Shield
Can_H White
Can_L Blue
Page 15
15
Once you have properly wired the drop line to the connector, attach the connector to the block. If applicable, use the locking screws on the connector to fasten it to the block.

I/O Memory Mapping

1790D-4R0, -T4R0 Input Data File

Word Bit Position
1514131211109876543210
0 RTD Input Data Channel 0
1 RTD Input Data Channel 1
2 RTD Input Data Channel 2
3 RTD Input Data Channel 3
4 Not Used S11 S10 S9 S8 Not Used S3 S2 S1 S0

Word/Bit Descriptions for 1790D-4R0, -T4R0 RTD Module

Word Decimal Bit Description
Read Word 0 Bits 00-15 Channel 0 input data
Read Word 1 Bits 00-15 Channel 1 input data
Read Word 2 Bits 00-15 Channel 2 input data
Read Word 3 Bits 00-15 Channel 3 input data
Read Word 4
Bits 00-03 Underrange for individual channels - Bit 00 corresponds to
Bits 04-07 Not used: Set to 0
Bits 08-11 Overrange for individual channels - Bit 08 corresponds to
Bits 12-15 Not used: Set to 0
input channel 0, bit 01 corresponds to input channel 1 and so on. When set (1) the input signal is below the input channel’s minimum range.
input channel 0, bit 09 corresponds to input channel 1 and so on. When set (1) the input signal is above the input channel’s maximum range, or open RTD is detected.
Publication 1790-IN011B-EN-P - April 2003
Page 16
16

1790D-4T0, -T4T0 Input Data File

Word Bit Position
1514131211109876543210
0 Thermocouple Input Data Channel 0
1 Thermocouple Input Data Channel 1
2 Thermocouple Input Data Channel 2
3 Thermocouple Input Data Channel 3
4 Not Used S11 S10 S9 S8 Not Used S3 S2 S1 S0

Word/Bit Descriptions for 1790D-4T0, -T4T0 Thermocouple Module

Word Decimal Bit Description
Read Word 0 Bits 00-15 Channel 0 input data
Read Word 1 Bits 00-15 Channel 1 input data
Read Word 2 Bits 00-15 Channel 2 input data
Read Word 3 Bits 00-15 Channel 3 input data
Read Word 4
Bits 00-03 Underrange for individual channels - Bit 00 corresponds to
Bits 04-07 Not used: Set to 0
Bits 08-11 Overrange for individual channels - Bit 08 corresponds to
Bits 12-15 Not used: Set to 0
input channel 0, bit 01 corresponds to input channel 1 and so on.
When set (1) the input signal is below the input channel’s minimum range.
input channel 0, bit 09 corresponds to input channel 1 and so on. When set (1) the input signal is above the input channel’s maximum range, or open thermocouple is detected.
Publication 1790-IN011B-EN-P - April 2003
Page 17

Troubleshoot with the Indicators

The 1790D I/O block has the following indicators:
module status
network status
I/O status
Mod/Net Status Indicator
LED Indicator: Status: Description:
Module Status Solid Red Unrecoverable fault in base unit
Flashing Red Recoverable fault
Solid Green Normal operation - OK
Flashing Green Standby
Off No power
LED Indicator: Status: Description:
Network Status Solid Red Unrecoverable communication fault
Flashing Red Recoverable communication fault
Solid Green Communication path complete - OK
Flashing Green Communication path incomplete
Off Device not online or not powered
17
I/O Channel LED Status Indicator
Status: Description:
Flashing Green/Red Power up
Off Off line
Red On line and no field power
Red DeviceNet connection and no field power
Flashing Red Field power and open wire
Green Field power and valid input
Flashing Red Input over range
Flashing Red Input under range
Flashing Red Recoverable fault
Publication 1790-IN011B-EN-P - April 2003
Page 18
18
DeviceNet RTD and Thermocouple Base Block Specifications
The following table contains specifications that are common to all of the blocks in this document. Individual base block
specifications are detailed after this table.
Environmental Specifications
Operating Temperature 0 to 55°C (32 to 131°F) - Analog I/O
Storage Temperature -40 to 85°C (-40 to 185°F)
Relative Humidity 5-90% non-condensing
Operating Altitude 2000m
Vibration 2g @ 10-500Hz
Shock Operating Non-operating
Emissions Group 1, Class A
ESD Immunity 8kV air discharges
Radiated RF Immunity 10V/m with 1kHz sine-wave 80%AM from 80MHz to 1000MHz
EFT/B Immunity 1kV @ 5kHz on power ports
Surge Transient Immunity +
Conducted RF Immunity 10Vrms with 1kHz sine-wave 80%AM from 150kHzto 80MHz
Enclosure Type Rating None (open style)
Mounting DIN rail or screw
Dimensions 52x104x42mm (2.03x4.07x1.64in)
Weight 0.3lb (0.1kg)
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry
Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock)
IEC 60068-2-30 (Test Db, Un-packaged Non-operating)
IEC60068-2-6 (Test Fc, Operating)
10g 30g EC60068-2-27 (Test Ea, Unpackaged Shock)
CISPR 11
IEC 61000-4-2
10V/m with 200Hz 50% Pulse 100%AM @ 900Mhz
IEC 61000-4-3
+
2kV @ 5kHz on signal ports
+
2kV @ 5kHz on communications ports
IEC 61000-4-4
1kV line-line(DM) and +2kV line-eath(CM) on signal ports
2kV line-earth(CM) on shielded ports
+
EC 61000-4-5
IEC 61000-4-6
Publication 1790-IN011B-EN-P - April 2003
Page 19
19
DeviceNet Specifications
Network protocol I/O Slave messaging:
Network length 500 meters maximum @ 125Kbps
Indicators 1 red/green module status
Number of nodes 64 maximum - rotary switch type node address setting
Communication rate 125Kbps, 250Kbps, 500Kbps - auto baud rate selection
Isolation Type test 1250Vac rms for 60 seconds between field power and
Wiring Refer to publication DN-6.7.2
General Specifications
Wiring Category
Product Certifications (when product is marked)
1
Refer to publication 1770-4.1, Programmable Controller Wiring and Grounding Guidelines.
2
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other
certification details.
- Poll command
- Bit Strobe command
- Cyclic command
- COS command
100 meters maximum @ 500Kbps
1 red/green network status
DeviceNet (I/O to logic)
1
2
c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada
2
CE
with:
European Union 89/336/EEC EMC Directive, compliant
EN 50082-2; Industrial Immunity EN 61000-6-4; Industrial Emissions
EN61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
2
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR11; Industrial Emissions
ODVA ODVA conformance tested to DeviceNet specifications
Publication 1790-IN011B-EN-P - April 2003
Page 20
20
4-Channel Input RTD Base Module Specification
1790D-4R0, 1790D-T4R0
Inputs per module 4 channel, RTD/Resistance Input Input Range 1-625 Sensors Supported Sensor Type Degree Counts Resolution
Resistance 100m Resistance 10m 1 to 327100 to
100ohm Pt/α =0.00385 -200 to
200ohm Pt/
500ohm Pt/α =0.00385 -200 to
100ohm Pt/
200ohm Pt/α =0.003916 -200 to
500ohm Pt/
100ohm Nickel -60 to
120ohm Nickel -80 to
200ohm Nickel -60 to
500ohm Nickel -60 to
Resolution 16 bits across 625ohms, 0.1°C/bit or 0.1°F/bit (RTD Sensors)
20bit Sigma-Delta modulation converter Data Format 16 bit Integer (2s compliment) Module Scan Time 8ms/channel @ Notch Filter = 60Hz Overall accuracy 0.2% Full scale @0°C-60°C Settable Notch Filter 10Hz (default), 25Hz, 50Hz, 60Hz, 100Hz, 250Hz, 500Hz Open Wire Detection Out of range, open wiring Excitation Current 1mA Input Impedance 5M ohm
1 to 62510 to 6250 100m
α =0.00385 -200 to
α =0.003916 -200 to
α =0.003916 -200 to
s
+850°C
+850°C
+650°C
+640°C
+640°C
+640°C
250°C
260°C
250°C
250°C
32700
-2000 to +8500
-2000 to +8500
-2000 to +6500
-2000 to +6400
-2000 to +6400
-2000 to +6400
-600 to 2500
-800 to 2600
-600 to 2500
-600 to 2500
10m
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
0.1°C
Specifications continured on next page.
Publication 1790-IN011B-EN-P - April 2003
Page 21
General Specifications
DeviceNet Power Supply voltage - 24V dc nominal
Field Power Supply Voltage - 24Vdc nominal
Isolation I/O to logic: photocoupler isolation
Indicators 4 red/green I/O status Wiring
1790D-4R0 1790D-T4R0
IMPORTANT: This module does not support any expansion modules.
Voltage range - 11-28.8V dc
Power dissipation - 1.2W maximum @ 28.8V dc
Voltage Range - 21.6-26.4V dc (+
Power Dissipation - 1.5W maximum @26.4V dc
Isolation voltage: Type Test 1250V ac rms for 60 seconds
DeviceNet to logic: non-isolated
Field power: non-isolated
37-pin D-Shell connector
Terminal block connector
screw torque: 7 inch pounds maximum
10%)

4-Channel Input Thermocouple Base Module Specifications

1790D-4T0, 1790D-T4T0
Inputs per module 4 channel, Thermocouple/mV Input Input Range + Sensors Supported Sensor Type Range Scaling
Resolution 16 bits, 0.1°C/bit or 0.1°F/bit (Thermocouple Sensors)
Data Format 16 bit Integer (2s compliment) Module Scan Time 140ms/channel @ Notch Filter = 60Hz Overall accuracy 0.2% Full scale @0°C-60°C Settable Notch Filter 10Hz (default), 25Hz, 50Hz, 60Hz, 100Hz, 250Hz, 500Hz Open Wire Detection Out of range, open wiring Cold Junction
Compensation Range
76.50mV
Voltage 10V -76.50 to +76.50mV -7650 to +7650 Type B 300 to 1800°C 3000 to 18000 Type E -270 to 1000°C -2700 to 10000 Type J -210 to 1200°C -2100 to 12000 Type K -270 to 1370°C -2700 to 13700 Type R -50 to 1768°C -500 to 17680 Type S -50 to 1768°C -500 to 17680 Type T -270 to 400°C -2700 to 4000 Type N -270 to 1300°C -2700 to 13000
20bit Sigma-Delta modulation converter
0 to 70°C
21
Publication 1790-IN011B-EN-P - April 2003
Page 22
22
Input Impedance 5M ohm
General Specifications
DeviceNet Power Supply voltage - 24V dc nominal
Field Power Supply Voltage - 24Vdc nominal
Isolation I/O to logic: photocoupler isolation
Indicators 4 red/green I/O status Wiring
1790D-4T0 1790D-T4T0
IMPORTANT: This module does not support any expansion modules.
Voltage range - 11-28.8V dc Power dissipation - 1.2W maximum @ 28.8V dc
Voltage Range - 21.6-26.4V dc (+ Power Dissipation - 1.5W maximum @26.4V dc
Isolation voltage: Type Test 1250V ac rms for 60 seconds DeviceNet to logic: non-isolated Field power: non-isolated
37-pin D-Shell connector Terminal block connector screw torque: 7 inch pounds maximum
10%)
Publication 1790-IN011B-EN-P - April 2003
Page 23
23
IMPORTANT
Input and output wiring must be in accordance with Class 1, Division 2 wiring methods and in
accordance with the authority having jurisdiction.
The following information applies when operating this equipment in hazardous locations:
Products marked CL I, DIV 2, GP A, B, C, D are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
EXPLOSION HAZARD
Do not disconnect
WARNING
!
equipment unless power has been removed or the area is known to be nonhazardous.
Do not disconnect
connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of
components may impair suitability for Class I, Division 2.
If this product
contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux :
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque didentification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation.
RISQUE D’EXPLOSION
Couper le courant ou
AVERTISSEMENT
!
sassurer que lenvironnement est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou
s'assurer que lenvironnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de
composants peut rendre cet
équipement inadapté à une utilisation en
environnement de Classe I, Division 2.
Sassurer que
lenvironnement est classé non dangereux avant de changer les piles.
Publication 1790-IN011B-EN-P - April 2003
Page 24
This product has been tested at an Open Device Vendors Association, Inc. (ODVA) authorized independent test laboratory and found to comply with ODVA Conformance Test. Please contact the ODVA website (http://www.odva.org) for listing of products tested by ODVA independent test labs for further details.
CompactBlock LDX and RSNetWorx for DeviceNet are trademarks of Rockwell Automation. DeviceNet is a trademark of Open DeviceNet Vendor Association.
Publication 1790-IN011B-EN-P - April 2003 PN20957657-64
Supersedes Publication 1790-IN011A-EN -P - January 2002
© 2 003 Roc kw ell Automation. Printed in USA
Loading...