Rockwell Automation 1790D-NOV2, 1790DTNOV2 User Manual

CompactBlock LDX Analog Modules

1790D-N4CO/TN4CO,
-N4VO/TN4VO, -NOC2/TNOC2,
-NOV2/TNOV2, 1790P-TN4CO,
-TNOC2
User Manual

Important User Information

Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard:
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
!
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
!
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.

Rockwell Automation Support

Before you contact Rockwell Automation for technical assistance, we suggest you please review the troubleshooting information contained in this publication first.
If the problem persists, call your local distributor or contact Rockwell Automation in one of the following ways:
Phone United
States/Canada
Outside United States/Canada
Internet
1.440.646.5800
You can access the phone number for your country via the Internet:
1. Go to http://www.ab.com
2. Click on Product Support (http://support.automation.rockwell.com)
3. Under Support Centers, click on Contact
Information
1. Go to http://www.ab.com
2. Click on Product Support (http://support.automation.rockwell.com)
Your Questions or Comments on this Manual
If you find a problem with this manual, please notify us of it on the enclosed How Are We Doing form.

Preface

Read this preface to familiarize yourself with the rest of the manual. This preface covers the following topics:
who should use this manual
how to use this manual
related publications
conventions used in this manual
Rockwell Automation support

Who Should Use This Manual

How to Use This Manual

Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use Allen-Bradley CompactBlock LDX modules.
As much as possible, we organized this manual to explain, in a task-by-task manner, how to install, configure, program, operate and troubleshoot a control system using the 1790D analog I/O modules.
Manual Contents
If you want... See
An overview of the analog input and output modules Chapter 1
Installation and wiring guidelines Chapter 2
Input module addressing, configuration and status information Chapter 3
Output module addressing, configuration and status information Chapter 4
Information on module diagnostics and troubleshooting Chapter 5
Specifications for the input and output modules Appendix A
PROFIBUS information Appendix B
Definitions of terms used in this manual Glossary
1 Publication 1790-UM001A-EN-P - March 2002
Preface 2
Related Documentation
The table below provides a listing of publications that contain important information about CompactBlock LDX systems.
For Read this document Document number
Introduction to CompactBlock LDX Product Profile 1790-PP002
DeviceNet Analog Base D-Shell CompactBlock LDX 1790D-N4CO, -NOC2, -N4VO, -NOV2
DeviceNet Analog Base Terminal Block CompactBlock LDX 1790D-TN4CO, -TN4VO, -TNOV2, -TNOC2
DeviceNet Cable System Planning and Installation Manual DN-6.7.2
In-depth information on grounding and wiring Allen-Bradley programmable controllers.
Installation Instructions 1790-IN004
Installation Instructions 1790-IN002
Allen-Bradley Programmable Controller Grounding and Wiring Guidelines
1770-4.1
If you would like a manual, you can:
download a free electronic version from the internet at
www.theautomationbookstore.com
purchase a printed manual by:
– contacting your local distributor or Rockwell Automation
representative
– visiting www.theautomationbookstore.com and placing
your order
– calling 1.800.963.9548 (USA/Canada) or 001.330.725.1574
(Outside USA/Canada)

Conventions Used in This Manual

Publication 1790-UM001A-EN-P - March 2002
The following conventions are used throughout this manual:
Bulleted lists (like this one) provide information not procedural
steps.
Numbered lists provide sequential steps or hierarchical
information.
Italic type is used for emphasis.
Text in this font indicates words or phrases you should type.
Overview
Installation and Wiring

Table of Contents

Chapter 1
How to Use Analog I/O . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Hardware Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
General Diagnostic Features . . . . . . . . . . . . . . . . . . . . . 1-4
System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Module Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Chapter 2
Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Prevent Electrostatic Discharge . . . . . . . . . . . . . . . . . . . 2-2
Environmnet and Enclosure . . . . . . . . . . . . . . . . . . . . . 2-2
Remove Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Reducing Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Protecting the Circuit Board from Contamination. . . . . . 2-3
Installing CompactBlock LDX I/O . . . . . . . . . . . . . . . . . . . 2-4
Set the Node Address on the Base Block . . . . . . . . . . . 2-4
Mount the Base Block . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Mount the Optional Expansion Blocks . . . . . . . . . . . . . 2-6
Connect the DeviceNet Cable . . . . . . . . . . . . . . . . . . . . 2-7
I/O System Wiring Guidelines . . . . . . . . . . . . . . . . . . . . . . 2-8
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Output Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Effect of Transducer/Sensor and Cable Length
Impedance on Voltage Input Accuracy . . . . . . . . . . . . . 2-9
Effect of Device and Cable Output Impedance
on Output Module Accuracy. . . . . . . . . . . . . . . . . . . . . 2-11
Wiring the Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
1790D-N4C0, 1790D-N4V0 Analog 4 Input Base D-Shell
Modules Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
1790D-TN4C0, 1790D-TN4V0 Analog 4 Input Base Modules
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
1790D-N0C2, 1790D-N0V2 Analog 2 Output Base D-Shell
Modules Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
1790D-TN0C2, 1790D-TN0V2 Analog 4 Input Base Modules
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
i Publication 1790-UM001A-EN-P - March 2002
Table of Contents ii
Module Data, Status, and Channel Configuration for Analog Input Modules
Module Data, Status, and Channel Configuration for Analog Output Modules
Chapter 3
Analog Input Image . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Analog Input Data File . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Analog Input Data File With Discrete Input Expansion
Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Analog Input Data Format . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Configuring Analog Input Module . . . . . . . . . . . . . . . . . . . 3-7
Configuring Analog Modules With RSNetWorx . . . . . . . . . . 3-8
Chapter 4
Analog Output Image. . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Analog Output Data File . . . . . . . . . . . . . . . . . . . . . . . 4-2
Analog Output Data File With Discrete Output Expansion
Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Analog Output Data Format. . . . . . . . . . . . . . . . . . . . . . . . 4-7
Output Fault and Idle States . . . . . . . . . . . . . . . . . . . . . . . 4-7
Configuring Analog Output Module . . . . . . . . . . . . . . . . . . 4-8
Using RSNetWorx for DeviceNet. . . . . . . . . . . . . . . . . . 4-8
Module Diagnostics and Troubleshooting
Specifications
Chapter 5
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Indicator Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Activating Devices When Troubleshooting . . . . . . . . . . 5-2
Stand Clear of the Machine. . . . . . . . . . . . . . . . . . . . . . 5-2
Program Alteration. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Safety Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Module Operation vs. Channel Operation . . . . . . . . . . . . . 5-3
Power-up Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Module Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Network Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Channel Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Out-of-Range Detection (Input Modules Only) . . . . . . . 5-4
Open-Circuit Detection (Input Module Only) . . . . . . . . 5-4
Analog Input Module Error Definition Table. . . . . . . . . . . . 5-5
Module Errors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Channel LED Indicator Operation . . . . . . . . . . . . . . . . . . . 5-6
Contacting Rockwell Automation . . . . . . . . . . . . . . . . . . . . 5-7
Appendix A
DeviceNet Analog Base Terminal Block . . . . . . . . . . . . A-1
4-Channel Analog Current Input Module. . . . . . . . . . . . A-3
2-Channel Analog Current Output Module . . . . . . . . . . A-4
4-Channel Analog Voltage Input Module. . . . . . . . . . . . A-5
2-Channel Analog Voltage Output Module . . . . . . . . . . A-6
Publication 1790-UM001A-EN-P - March 2002
PROFIBUS Modules Installation, Wiring, Module Data, Status and Channel Configuration
Glossary
Table of Contents iii
Appendix B
Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Prevent Electrostatic Discharge . . . . . . . . . . . . . . . . . . . B-2
Environment and Enclosure . . . . . . . . . . . . . . . . . . . . . B-3
Remove Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Reducing Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Protecting the Circuit Board from Contamination. . . . . . B-4
Installing CompactBlock LDX I/O . . . . . . . . . . . . . . . . . . . B-5
Set the Station Address on the Base Block . . . . . . . . . . B-5
Mount the Base Block . . . . . . . . . . . . . . . . . . . . . . . . . B-5
Connect the PROFIBUS DP Terminal Connector . . . . . . B-8
Connect Power to the Block. . . . . . . . . . . . . . . . . . . . . B-9
Connecting I/O Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . B-10
General Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . B-10
Guidelines for Input Modules . . . . . . . . . . . . . . . . . . . B-10
Guidelines for Output Modules . . . . . . . . . . . . . . . . . B-10
Wiring the Modules . . . . . . . . . . . . . . . . . . . . . . . . . . B-11
1790P-TN4C0 Data Structure . . . . . . . . . . . . . . . . . . . . . . B-15
Analog Input Image . . . . . . . . . . . . . . . . . . . . . . . . . . B-15
1790P-TNOC2 Data Structure. . . . . . . . . . . . . . . . . . . . . . B-16
Analog Output Image. . . . . . . . . . . . . . . . . . . . . . . . . B-16
Output Fault and Idle States . . . . . . . . . . . . . . . . . . . . . . B-16
Configuring PROFIBUS Analog Modules . . . . . . . . . . . . . B-16
Configuring Analog Modules with the SST PROFIBUS
Configuration Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-17
Downloading Configuration. . . . . . . . . . . . . . . . . . . . . . . B-21
PROFIBUS DP Specifications . . . . . . . . . . . . . . . . . . . . . . B-24
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-25
Index
Publication 1790-UM001A-EN-P - March 2002
Table of Contents iv
Publication 1790-UM001A-EN-P - March 2002
Chapter
Overview
This chapter explains how analog data is used, and describes CompactBlock LDX analog input and output modules. Included is information about:
the use of analog I/O
the modules’ hardware and diagnostic features
an overview of the analog input system operation
an overview of the analog output system operation
1

How to Use Analog I/O

Analog refers to the representation of numerical quantities by the measurement of continuous physical variables. Analog applications are present in many forms. The following application shows a typical use of analog data.
In this application, the processor controls the amount of fluid in a holding tank by adjusting the valve opening. The valve is initially open 100%. As the fluid level in the tank approaches the preset point, the processor modifies the output to close the valve 90%, 80%, and so on, continuously adjusting the valve to maintain the fluid level.
Analog output wired to valve
Valve
Controller
Level Sensor
Analog input wired
to tank
Analog I/O
Module
1 Publication 1790-UM001A-EN-P - March 2002
1-2 Overview

General Description

The analog input module converts and digitally stores analog data for retrieval by controllers, such as the SLC-500 programmable controller. The module supports connections from any combination of up to four voltage or current analog sensors. The four high-impedance input channels can be wired as single-ended inputs.
The output module provides two single-ended analog output channels, either voltage or current, depending on the module selected.
Table 1.1 lists the CompactBlock LDX module types and corresponding operating ranges:
Table 1.1 CompactBlock LDX Module Types and Operating Ranges
CompactBlock LDX
Module
1790D-N4CO
1790D-TN4CO
1790D-NOC2
1790D-TNOC2
Type: Operating Range:
Current Input 4-20mA
or
0-20mA
Current Output 0-20mA
1790D-N4VO
1790D-TN4VO
1790D-NOV2
1790D-TNOV2
Voltage Input 0-10V dc
Voltage Output 0-10V dc
Each analog base module supports up to two CompactBlock LDX discrete expansion modules.
Publication 1790-UM001A-EN-P - March 2002
DIN rail slot
DeviceNet network connector
Overview 1-3
Hardware Features
The modules contain either removable D-shell connectors or fixed terminal blocks. The CompactBlock LDX four input channels are single-ended. The CompactBlock LDX two output channels are also single-ended. Module configuration is normally done via the
controllers programming software. In addition, some controllers support configuration via the user program.
Figure 1.1 shows the CompactBlock LDX analog modules hardware features.
Figure 1.1
Node address switches
Panel mount hole
Expansion connector under cover
Module indicators
Panel mount hole
Analog I/O connections (D-shell shown)
43218
Publication 1790-UM001A-EN-P - March 2002
1-4 Overview
General Diagnostic Features
The CompactBlock LDX modules contain diagnostic features that can help you identify the source of problems that may occur during power-up or during normal channel operation. These power-up and channel diagnostics are explained in Chapter 5, Module Diagnostics and Troubleshooting.

System Overview

The modules communicate to the controller through the DeviceNet network. Module power is derived from DeviceNet. Additionally, the analog I/O requires 24V dc field power separate from DeviceNet. CompactBlock LDX analog bases support up to two discrete LDX expansion modules.
System Operation
At power-up, the analog base module performs a check of its internal circuits, memory, and basic functions. During this time, the module status LED remains off. If no faults are found during power-up diagnostics, the module status LED is turned on.
After power-up checks are complete, the module waits for valid channel configuration data. If an invalid configuration is detected, the module generates a configuration error. Once a channel is properly configured and enabled, it begins the analog-to-digital or digital-to-analog conversion process.
Publication 1790-UM001A-EN-P - March 2002
Overview 1-5
Module Operation
Input Module
The input modules input circuitry consists of four analog inputs multiplexed into a single analog-to-digital (A/D) converter. The A/D converter reads the selected input signal and converts it to a digital value that is presented to the network. The multiplexer sequentially switches each input channel to the modules A/D converter. Figure 1.2 on page 1-5 shows a block diagram of the circuitry.
Figure 1.2
Isolation
Input 0
Input 1
Input 2 Input 3
24V dc Field Power
Data
Signal
A/D
Control
Multiplexer
Select
Analog power supply
Analog power
Optocouplers
Microcontroller
DeviceNetXCVR
43219
Each time the input module reads a channel, the module tests that analog data value for an overrange or underrange condition. If such a condition is detected, a unique bit is set in the channel status word. The channel status word is described in Chapter 4, Module Data, Status, and Channel Configuration for Analog Output Modules.
Publication 1790-UM001A-EN-P - March 2002
1-6 Overview
Output 0
Analog output
Output Module
The output module uses a digital-to-analog (D/A) converter to read the digital output data from the network and convert it to an analog output signal. Figure 1.3 below shows a block diagram of the circuitry.
Figure 1.3
Isolation
Optocouplers
Data
Output 1
24V dc Field Power
Analog output
Analog power supply
D/A
Control
Analog power
Microcontroller
DeviceNetXCVR
43220
Publication 1790-UM001A-EN-P - March 2002
Installation and Wiring
This chapter tells you how to:
determine the power requirements for the modules
avoid electrostatic damage
install the module
wire the modules terminal block
wire input devices
wire output devices
Chapter
2

Power Requirements

Module Installation

The modules receive power through the DeviceNet network and from an auxilary 24V dc field supply. The maximum power drawn by the modules is shown in Table 2.1.
Table 2.1 CompactBlock LDX Module Power Requirements
Voltage Range: Power:
DeviceNet Power: 11-28.8 V dc 1.2W @ 28.8V dc
Auxilary 24V dc Field Power: 21.6-26.4V dc 1.5W @ 26.4V dc
CompactBlock LDX is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution
(1)
degree 2
) and to circuits not exceeding Over Voltage Category II
(IEC 60664-1).
(3)
(2)
(1)
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
1 Publication 1790-UM001A-EN-P - March 2002
2-2 Installation and Wiring
Prevent Electrostatic Discharge
ATTENTION
!
Electrostatic discharge can damage integrated circuits or semiconductors if you touch analog I/O module bus connector pins or the terminal block on the input module. Follow these guidelines when you handle the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When it is not in use, keep the module in its box.
Environmnet and Enclosure
ATTENTION
!
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as "open type" equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
Publication 1790-UM001A-EN-P - March 2002
See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 ("Industrial Automation Wiring and Grounding Guidelines"), for additional installation requirements pertaining to this equipment.
Remove Power
Installation and Wiring 2-3

General Considerations

ATTENTION
Remove power before removing or inserting this module or an expansion module. When you remove or insert a module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
!
sending an erroneous signal to your system’s field
devices, causing unintended machine motion
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its mating connector and may lead to premature failure.
Reducing Noise
Most applications require installation in an industrial enclosure to reduce the effects of electrical interference. Analog inputs and outputs are highly susceptible to electrical noise. Electrical noise coupled to the analog inputs will reduce the performance (accuracy) of the module.
Group your modules in the enclosure to minimize adverse effects from radiated electrical noise and heat. Consider the following conditions when selecting a location for the analog module. Position the module:
away from sources of electrical noise such as hard-contact
switches, relays, and AC motor drives
away from modules which generate significant radiated heat.
In addition, route shielded, twisted-pair analog input and output wiring away from any high voltage I/O wiring.
Protecting the Circuit Board from Contamination
The printed circuit boards of the analog modules must be protected from dirt, oil, moisture, and other airborne contaminants. To protect these boards, the system must be installed in an enclosure suitable for the environment. The interior of the enclosure should be kept clean and the enclosure door should be kept closed whenever possible.
Publication 1790-UM001A-EN-P - March 2002
2-4 Installation and Wiring

Installing CompactBlock LDX I/O

Follow these steps to install the block:
1. Set the Node Address on the Base Block
2. Mount the Base Block
3. Mount the Optional Expansion Blocks
4. Connect the DeviceNet Cable
Set the Node Address on the Base Block
Each base block comes with its internal program set for node address
63. To reset the node address, adjust the switches on the front of the block. The two switches are most significant digit (MSD) and least significant digit (LSD). The switches can be set between 00 and 63.
The rotary switches are read at block power up only. Switch settings between 64 and 99 cause the block to use the last valid node address stored internally
.
Node Address is set to 11
Figure 2.1
NODE ADDRESS
MOD NET
STATUS
LSDMSD
43216
The node address may also be set through RSNetWorx for DeviceNet or a similar configuration tool. When software configuration is used for the node address, the switches must be set between 64 and 99.
Publication 1790-UM001A-EN-P - March 2002
Installation and Wiring 2-5
Mount the Base Block
You can mount the base block to a panel or DIN rail. We recommend that you ground the panel or DIN rail before mounting the block.
IMPORTANT
WARNING
The analog base module can accommodate a maximum of two discrete expansion modules.
When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
!
Panel Mounting
1. Place the block against the panel where you want to mount it.
2. Gently pull and position the expansion cover to the left.
3. Place a center punch, nail or similar device through the
mounting holes in the block and make two marks on the panel (lower left and upper right corners of the module).
4. Remove the block and drill two holes in the panel to
accommodate each of the mounting screws.
5. Replace the block on the panel and place a screw through each of the
two mounting holes. Tighten the screws until the block is firmly in place.
95 mm
3.74 in
X
LD
k
c
lo
CompactB
1790-16BVOX
41 mm
1.6 in
EXPANSION UNIT
0
0
7
16 INPUTS-DCPOWER
7
Expansion Cover
Publication 1790-UM001A-EN-P - March 2002
2-6 Installation and Wiring
Compact
PULL
PULL
Compact
PULL
PULL
Compact
PULL
PULL
Compact
Block LDX
PULL
PULL
Compact
PULL
PULL
Compact
PULL
PULL
Compact
PULL
PULL
DIN Rail Mounting
1. Hook the top of slot of the block over the DIN Rail.
2.
Pull down on the locking lever while pressing the block against the rail.
f
Locking Lever
3. Push up on the locking lever to secure the block to the rail
when block is flush against the rail.
Mount the Optional Expansion Blocks
Mount the expansion block by connecting it to a previously-installed CompactBlock LDX I/O base or expansion block.
Beginning with the base block, you can mount your expansion blocks horizontally or vertically:
horizontally (left to right) - add expansion blocks in a
end-to-end configuration
vertically (up or down) - add expansion blocks either up or
down in a back-to-back configuration. In this configuration, you must use the optional 15cm ribbon cable (1790-15CMCBL) and alternately position the blocks in a right-side up, upside-down fashion.
Compact
Block LDX
Compact
Block LDX
EXPANSION UNIT
PULL
RIGHT SIDE UP
Horizontal mounting
EXPANSION UNIT
PULL
PULL
RIGHT SIDE UP
Vertical mounting
Compact
Block LDX
PULL
PULL
PULL
PULL
Compact
EXPANSION UNIT
RIGHT SIDE UP
UPSIDE DOWN
Compact
Block LDX
Compact
EXPANSION UNIT
EXPANSION UNIT
PULL
RIGHT SIDE UP
Block LDX
PULL
EXPANSION UNIT
Block LDX
PULL
Compact
Block LDX
The longer expansion cable (1790-15CMCBL) will allow up to 7cm of space in between blocks.
PULL
EXPANSION UNIT
PULL
PULL
PULL
RIGHT SIDE UP
RIGHT SIDE UP
You can mount your blocks on a panel or DIN rail as described in the previous section.
Publication 1790-UM001A-EN-P - March 2002
Installation and Wiring 2-7
Connect the DeviceNet Cable
Follow these procedures when connecting the DeviceNet cable to the base block.
The required DeviceNet connector is not supplied with the block ­you must purchase it separately. There are three types of connectors that you can order directly from Rockwell Automation or your local distributor:
1799-DNETCON - 5-position open style connector
1799-DNETSCON - 5-position open style connector with locking
screws
1799-DNC5MMS - 5-position open style to 12mm connector with
locking screws
WARNING
If you connect or disconnect the DeviceNet cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location
!
installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Connect the DeviceNet wiring (drop line) to one of the DeviceNet connectors as shown below. A color-coded wiring diagram is also printed next to the connector on the left side of the module
CompactBlock LDX
V
8
V
B
8
-
D
0
9
7
Wiring Diagram for 1799-DNETCON
1
W
O
P
C
D
-
S
T
U
P
T
U
O
8
/
S
T
U
P
N
I
8
7
0
7
0
V+ Red
Can_H White
Drain/Shield
V+ Red
R
E
V- Black
Wiring Diagram for 1799-DNC5MMS
Can_L Blue
V- Black
Drain/Shield
Can_H White
Can_L Blue
Once you have properly wired the drop line to the connector, attach the connector to the block. If applicable, use the locking screws on the connector to fasten it to the block.
Publication 1790-UM001A-EN-P - March 2002
2-8 Installation and Wiring

I/O System Wiring Guidelines

Consider the following when wiring your system:
General
All module commons (COM) are connected in the analog
module. The analog common (COM) is not connected to earth ground inside the module.
Channels are not isolated from each other.
Do not use the analog modules NC terminals as connection
points.
To ensure optimum accuracy, limit overall cable impedance by
keeping your cable as short as possible. Locate the I/O system as close to your sensors or actuators as your application will permit.
Use Belden 8761, or equivalent, shielded wire.
Keep shield connection to ground as short as possible.
Under normal conditions, the drain wire and shield junction
must be connected to earth ground via a panel or DIN rail mounting screw at the analog I/O module end.
(1)
Input Modules
If multiple power supplies are used with analog inputs, the
power supply commons must be connected together.
The module does not provide loop power for analog inputs. Use
a power supply that matches the input transmitter specifications.
Output Modules
Voltage outputs (CH0 and CH1) of the 1790D-NOV2/TNOV2
modules are referenced to COM. Load resistance for a voltage output channel must be equal to or greater than 1K
Current outputs (CH0 and CH1) of the 1790D-NOC2/TNOC2
modules source current that returns to COM. Load resistance for a current output channel must remain between 0 and 600
Ω.
Ω.
Publication 1790-UM001A-EN-P - March 2002
(1)
In environments where high-frequency noise may be present, it may be necessary to directly ground cable shields to earth at the module end and via a 0.1µF capacitor at the sensor end.
Installation and Wiring 2-9
Effect of Transducer/Sensor and Cable Length Impedance on Voltage Input Accuracy
For voltage inputs, the length of the cable used between the transducer/sensor and the module can affect the accuracy of the data provided by the module.
RcRs
+
Ri
Where:
Vs
V in
-
Rc
Rc = DC resistance of the cable (each conductor) depending on cable length
Rs = Source impedance of analog transducer/sensor output
Ri = Impedance of the voltage input (500K
for
1790D-N4VO/TN4VO)
Vs = Voltage source (voltage at the transducer/sensor input device)
Vin = Measured potential at the module input
%Ai = Percent added inaccuracy in a voltage-based system due to source and cable impedance.
Ri Vs
Vin
-------------------------------------------------------
=
Rs 2 Rc×()Ri++[]
×[]
Publication 1790-UM001A-EN-P - March 2002
2-10 Installation and Wiring
For example, for Belden 8761 two conductor, shielded cable:
Rc = 16
/1000 ft
Rs = 0 (ideal source)
Vin

%Ai 1
Table 2.2 Effect of Cable Length on Input Accuracy
Length of Cable (m) dc resistance of the
cable, Rc (
50 2.625 0.00105%
100 5.25 0.00210%
200 10.50 0.00420%
300 15.75 0.00630%
---------

Vs
100×=
Ω)
Accuracy impact at the
input module
As input source impedance (Rs) and/or resistance (dc) of the cable (Rc) get larger, system accuracy decreases. If you determine that the inaccuracy error is significant, implementing the following equation in the control program can compensate for the added inaccuracy error due to the impedance of the source and cable.
Vs Vin
Rs 2 Rc
-------------------------------------------------------
×=
×()Ri++[]
Ri
Publication 1790-UM001A-EN-P - March 2002
TIP
In a current loop system, source and cable impedance do not impact system accuracy.
Installation and Wiring 2-11
Effect of Device and Cable Output Impedance on Output Module Accuracy
The maximum value of the output impedance is shown in the example below, because it creates the largest deviation from an ideal voltage source.
Rs Rc
+
+
Vs
Where:
Vload Rload
-
Rc
Rc
Ri
43266
Rc = DC resistance of the cable (each conductor) depending on cable length
Rs = Source impedance of 1790D-NOV2/TNOV2 (0.5
R
= Impedance of the load device
load
Ω)
Vs = Voltage at the output of 1790D-NOV2/TNOV2
= Measured potential at the load device
V
load
%Ai = Percent added inaccuracy in a voltage-based system due
to source and cable impedance.
[R
x Vs]
load
V
=
load
[Rs + (2 x Rc) + R
load
]
For example, for Belden 8761 two conductor, shielded cable and a 1790D-NOV2/TNOV2 module:
Rc = 16
/1000 ft
Rs = 0.5
%AV
load
V
= (1 - ) x 100
load
V
s
Publication 1790-UM001A-EN-P - March 2002
2-12 Installation and Wiring
Table 2.3 Effect of Output Impedance and Cable Length on Accuracy
Length of Cable
(m)
dc resistance of
the cable, Rc (
Ω)
Accuracy impact at the load
10,000 100,000
1,000
1 0.0525 0.0605% 0.00605% 0.000605%
10 0.525 0.155% 0.0155% 0.00155%
50 2.625 0.575% 0.0575% 0.00575%
100 5.25 1.1% 0.11% 0.011%
As output impedance (Rs) and/or resistance (dc) of the cable (Rc) get larger, system accuracy decreases. If you determine that the inaccuracy error is significant, implementing the following equation in the control program can compensate for the added inaccuracy error due to the impedance of the output module and cable.
+ (2 x Rc) + R
[R
Vs = V
TIP
s
x
load
[R
In a current loop system, source and cable impedance do not impact system accuracy.
load
load
]
Publication 1790-UM001A-EN-P - March 2002
Wiring the Modules
Installation and Wiring 2-13
ATTENTION
To prevent shock hazard, care should be taken when wiring the module to analog signal sources. Before wiring any analog module, disconnect power from the system power supply and from any other source to the analog module.
!
After the analog module is properly installed, follow the wiring procedure below. To ensure proper operation and high immunity to electrical noise, always use Belden 8761 (shielded, twisted-pair) or
equivalent wire.
ATTENTION
Never connect a voltage or current source to an analog output channel.
!
signal wire
signal wire
drain wire
cable
foil shield
signal wire
Cut foil shield and drain wire
signal wire
Publication 1790-UM001A-EN-P - March 2002
2-14 Installation and Wiring
To wire your module follow these steps.
1. At each end of the cable, strip some casing to expose the
individual wires.
2. Trim the signal wires to 2-inch lengths. Strip about 3/16 inch (5
mm) of insulation away to expose the end of the wire.
ATTENTION
Be careful when stripping wires. Wire fragments that fall into a module could cause damage at power up.
!
3. At one end of the cable, twist the drain wire and foil shield
together.
Under normal conditions, this drain wire and shield junction must be connected to earth ground, via a panel or DIN rail mounting screw at the analog I/O module end. Keep the length of the drain wire as short as possible.
In environments where high frequency noise may be present, it may be necessary to ground the cable shields to earth at the module and via a 0.1µF capacitor at the sensor end for analog inputs and at the load end for analog outputs.
4. At the other end of the cable, cut the drain wire and foil shield
back to the cable.
Publication 1790-UM001A-EN-P - March 2002
5. Connect the signal wires to the terminal block as shown in
analog input wiring on page 2-15 and page 2-16 and analog output wiring on page 2-17 and page 2-18.
6. Connect the other end of the cable to the analog input or output
device.
7. Repeat steps 1 through 5 for each channel on the module.
Loading...
+ 74 hidden pages