Rockwell Automation 1790D-4T0, 1790D-T4T0, 1790D-T4R0, 1790D-4R0 Installation Instructions Manual

Installation Instructions
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
Catalog Numbers 1790D-4R0, 1790D-4T0, 1790D-T4R0, 1790D-T4T0
Table of Contents
Top ic Pa ge
Important User Information 2
Prevent Electrostatic Discharge 3
North American Hazardous Location Approval 4
EDS File Requirements 4
Install the CompactBlock LDX I/O 5
Set the Node Address on the Base Block 5
Mount the Base Module 6
Wire the Terminal Block 8
Connect Field Wiring 9
Connect the DeviceNet Cable 13
I/O Memory Mapping 14
Interpret the Status Indicators 15
Specifications 16
2 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O

Important User Information

Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
http://www.rockwellautomation.com/literature/
solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
) describes some important differences between
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of
the product.
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 3

Environment and Enclosure

ATTENTION: This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, for additional installation requirements, Allen-Bradley publication 1770-4.1
• NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
.

Prevent Electrostatic Discharge

ATTENTION: This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Publication 1790-IN011C-EN-P - January 2015
4 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nam eplate indicating the hazardous location temperature code. When comb ining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
EXPLOSION HAZARD
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must only be changed in an are a known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec d es marquages sur sa plaque d'identification qui indiquent le code de température pour les environnement s dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorabl e (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquet s coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une util isation en environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non dangereux avant de changer les piles.

EDS File Requirements

Current functionality of CompactBlock LDX I/O blocks require current modular EDS file for RSNetWorx for DeviceNet™ version 3.0 or later software.
These files are easy to install and are available online at:
www.ab.com/networks/eds/
EDS files for blocks with matching catalog numbers (for both D-Shell and terminal block versions) are the same. Thus, on the website and in RSNetWorx for DeviceNet, there is only one EDS file for both versions of the blocks. For example, if you want the EDS file for 1790D-T8BV8B, use the EDS file labeled 1790D-8BV8B.
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 5
Example: Node Address is set at 11

Install the CompactBlock LDX I/O

Follow these steps to install the block:
• set the node address on the base block.
• mount the base block.
• wire the terminal blocks.
•connect field wiring.
• connect the DeviceNet cable.
These steps are explained in detail in the following procedures.

Set the Node Address on the Base Block

Each base block comes with its internal program set for node address 63. To reset the node address, adjust the switches on the front of the block. The two switches are most significant digit (MSD) and least significant digit (LSD). The switches can be set between 00 and 63.
The base block reads the rotary switches at power up only. Switch settings between 64 and 99 cause the block to use the last valid node address stored internally.
Node Address Example
The node address may also be set through RSNetWorx for DeviceNet or a similar configuration tool. When software configuration is used for the node address, the switches must be set between 64 and 99.
Publication 1790-IN011C-EN-P - January 2015
6 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
IMPORTANT
CompactBlock LDX
1790-16BVOX
DC INPUTS
EXPANSION UNIT
16 INPUTS-DCPOWER
0
7
DC INPUTS
8
15
95 mm (3.74 in.)
41 mm (1.6 in.)
Expansion Cable Cover
44252

Mount the Base Module

You can mount the base block to a panel or DIN rail. We recommend that you ground the panel or DIN rail before mounting the block.
The RTD and thermocouple base blocks do not support any expansion blocks.
WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with the proper wiring method that complies with the governing electrical codes.
Dimensions
Mount on a Panel
For panel mounting, use these steps.
1. Place the block against the panel where you want it mounted.
2. Gently pull and position the expansion cover to the left.
3. Place a center punch, nail, or similar device through the mounting holes in the
block and make two marks on the panel at the lower-left and upper-right corners of the module.
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 7
Locking Lever
4. Remove the block and drill two holes in the panel to accommodate each of the mounting screws.
5. Replace the block on the panel and place a screw through each of the two mounting holes.
6. Tighten the screws until the block is firmly in place.
Mount on DIN Rail
For DIN-rail mounting, use these steps.
1. Hook the top slot of the base block over the DIN rail.
2. Pull down on the locking lever while pressing the base block against the rail.
3. Push up on the locking lever to secure the base block to the rail when the base
block is flush against the rail.
Publication 1790-IN011C-EN-P - January 2015
8 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O

Wire the Terminal Block

The following figures show how to wire the terminal blocks.
1790D-4R0 RTD Input Module D-Shell Wiring
CH1_B
10
29
CH1_B
10
29
NC
COM
13
COM
28
COM
28
NC
14
NC
9
NC
NC
27
COM
9
27
NC
15
NC
16
NC
CH2_A
8
COM
NC
8
NC
7
26
COM
CH2_A
7
26
NC
17
18
NC
CH2_B
25
CH2_B
NC
CH3_B
CH3_A
5
6
24
23
COM
COM COM COM
CH3_B
CH3_A
5
6
24
25
23
NC
NC NC NC
NC
19
20
NC
+24V
NC
NC
CH0_B
+24V
19
37
GND
18
36
GND
+24V
17
35
GND
NC
16
15
34
33
NC
NC
CH0_A
14
32
NC
13
COM
CH1_A
11
12
30
31
COM
COM
• Wire pins 17, 18, 19 to Field Power (+) 24V DC
• Wire pins 35, 36, 37 to Field Power (-) GND
1790D-4T0 Thermocouple Module D-Shell Wiring
+24V
NC
NC
CH0_B
+24V
19
37
GND
18
36
GND
+24V
17
35
GND
NC
16
15
34
33
NC
NC
CH0_A
14
32
NC
CH1_A
11
13
12
30
31
NC
NC
• Wire pins 17, 18, 19 to Field Power (+) 24V DC
• Wire pins 35, 36, 37 to Field Power (-) GND
1790D-T4RO RTD Input Module Terminal Block Wiring
+24V
CH1_A
CH0_A
1
3
2
GND
CH0_B
• Wire pin 1 to Field Power (+) 24V DC
• Wire pin 2 to Field Power (-) GND
5
4
CH1_B
COM
6
CH2_A
7
8
COM
CH3_A
9
10
CH2_B
11
12
CH3_B
NC
NC
NC
3
4
22
4
1
2
20
21
COM
NC
NC
NC
3
1
2
22
20
21
NC
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 9
20
18
16
14
12
10
8
6
4
2
19
17
15
13
11
9
7
5
3
1
NC
NC
CH3_B
NC
CH0_B
NC
NC
CH2_B
CH1_B
GND
NC
NC
CH2_A
CH1_A
+24V
NC
NC
CH3_A
NC
CH0_A
1790D-T4T0 Thermocouple Input Module Terminal Block Wiring
• Wire pin 1 to Field Power (+) 24V DC
• Wire pin 2 to Field Power (-) GND

Connect Field Wiring

System Wiring Guidelines
Follow these guidelines when wiring your system:
• use shielded, twisted pair wire to ensure proper operation and high immunity to electrical noise
• to limit noise, locate RTD and resistance device signal wires as far away as possible from power lines, load lines and other sources of electrical noise, such as hard-contact switches, relays and AC motor drives
• under normal conditions, the drain wire and shield junction should be connected to earth ground, via a panel or DIN rail mounting screw at the block end
• keep shield connection to ground as short as possible
• to ensure optimum accuracy, limit overall cable impedance by keeping the cable as short as possible. Locate the I/O system as close to your field devices as your application will permit.
RTD Wiring Guidelines
Since the operating principle of the RTD module is based on the measurement of resistance, give special consideration when selecting the input cable. For 2-wire or 3-wire configurations, select a cable that has consistent impedance throughout its entire length.
Publication 1790-IN011C-EN-P - January 2015
10 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
IMPORTANT
IMPORTANT
The RTD block requires three wires to compensate for lead resistance error. We recommend that you do not use 2-wire RTDs if long cable runs are required, as it reduces the accuracy of the system.
However, if a 2-wire configuration is required, reduce the effect of the lead wire resistance by using a lower-gauge wire for the cable (for example, use AWG #16 instead of AWG #24). The block’s terminal strip accepts AWG #14 gauge wire.
When using a 3-wire configuration, the block compensates for resistance error due to lead wire length. For example, in a 3-wire configuration, the block reads the resistance due to the length of the wires and assumes that the resistance of the other wire is equal. If the resistance of the individual lead wires are much different, an error may exist. The closer the resistance values are to each other, the greater the amount of error is eliminated.
To ensure temperature or resistance value accuracy, the resistance difference of the cable lead wires must be equal to or less than 0.01 .
To ensure that the lead values match as closely as possible:
• keep lead resistance as small as possible and less than 25
• use quality cable that has a small tolerance impedance rating
• use a heavy-gauge lead wire which has less resistance per foot
RTD Wiring Configurations
Three configurations of RTDs can be connected to the blocks:
• 2-wire RTD, which is composed of an RTD EXC (excitation) lead wire and a RTN (ret urn) wi re
• 3-wire RTD, which is composed of a Sense and 2 RTD lead wires (RTD EXC and RTN)
• 4-wire RTD, which is composed of a Sense and 2 RTD lead wires (RTD EXC and RTN). The second sense wire of a 4-wire RTD is left open.
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 11
CH0_A
CH0_B
COM
Add Jumper
Cable Shield (to Ground)
CXE DTRCXE DTR
nruteRnruteR
CH0_A
CH0_B
COM
Cable Shield (to Ground) RTD EXC
RTD EXC
Sense
Sense
Return
Return
2-Wire RTD Configuration
3-Wire RTD Configuration
4-Wire RTD Configuration
Leave this sensor wire open
RTD EXC
Sense
Return
CH0_A
CH0_B
COM
Cable Shield (to Ground)
RTD EXC
Sense
Return

Wire Resistance Devices (Potentiometers)

Potentiometer wiring requires the same type of cable as that for the RTD. Potentiometers can be connected to the module as a 2-wire or 3-wire connection as shown in the following figures:
Publication 1790-IN011C-EN-P - January 2015
12 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
TIP
A
CH0_A
CH0_B
COM
CH0_A
CH0_B
COM
Cable Shield (to Ground)
RTD EXC
Return
Potentiomete
Cable Shield (to Ground)
RTD EXC
Return
Potentiometer
Sense
Run Return and sense wires from the module to potentiometer terminal and tie terminal to one point
Run Return and sense wires from the module to potentiometer terminal and tie terminal to one point
2-Wire Potentiometer Interconnection
Add Jumper
CH0_A
CH0_B
COM
Cable Shield (to Ground)
RTD EXC
Return
Potentiometer
dd Jumper
CH0_A
CH0_B
COM
The potentiometer wiper arm can be connected to either the EXC or return terminal, depending on whether you want increasing or decreasing resistance.
Publication 1790-IN011C-EN-P - January 2015
Cable Shield (to Ground)
RTD EXC
Return
Potentiometer
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 13
Wiring Diagram for 1799-DNETCON Connector
Wiring Diagram for 1799-DNC5MMS Connector
V+ Red
V- Black
Drain/Shield
Can_H White Can_L Blue
V+ Red
Can_H White
Drain/Shield Can_L Blue
V- Black
44164

Connect the DeviceNet Cable

Follow these procedures when connecting the DeviceNet cable to the base block.
The required DeviceNet connector is not supplied with the block - you must purchase it separately. There are three types of connectors that you can order directly from Rockwell Automation or your local distributor:
1799-DNETCON – 5-position open style connector
1799-DNETSCON – 5-position open style connector with locking screws
1799-DNC5MMS – 5-position open style to 5-pin micro male connector with locking screws
WARNING: If you connect or disconnect the DeviceNet cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
1. Connect the DeviceNet wiring (drop line) to one of the DeviceNet connectors as shown in the figure, noting that a color-coded wiring diagram is printed next to the connector on the left side of the base block.
1. Attach the connector to the base block once you have properly wired the drop line to the connector.
2. Use the locking screws on the connector to fasten it to the base block, if applicable.
Publication 1790-IN011C-EN-P - January 2015
14 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O

I/O Memory Mapping

1790D-4R0, 1790D-T4R0 Input Data File
Word Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 RTD Input Data Channel 0 1 RTD Input Data Channel 1 2 RTD Input Data Channel 2 3 RTD Input Data Channel 3 4 Not used S11 S10 S9 S8 Not used S3 S2 S1 S0
Word/Bit Descriptions – 1790D-4R0, 1790D-T4R0 RTD
Word Decimal Bit Description
Read Word 0 Bits 00…15 Channel 0 input data Read Word 1 Bits 00…15 Channel 1 input data Read Word 2 Bits 00…15 Channel 2 input data Read Word 3 Bits 00…15 Channel 3 input data Read Word 4 Bits 00…03 Underrange for individual channels – Bit 00 corresponds to input
Bits 04…07 Not used: Set to 0 Bits 08…11 Overrange for individual channels – Bit 08 corresponds to input
Bits 12…15 Not used: Set to 0
1790D-4T0, 1790D-T4T0 Input Data File
Word Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Thermocouple Input Data Channel 0 1 Thermocouple Input Data Channel 1 2 Thermocouple Input Data Channel 2 3 Thermocouple Input Data Channel 3 4 Not used S11 S10 S9 S8 Not used S3 S2 S1 S0
channel 0, bit 01 corresponds to input channel 1 and so on. When set (1) the input signal is below the input channel’s minimum range.
channel 0, bit 09 corresponds to input channel 1 and so on. When set (1) the input signal is above the input channel’s maximum range, or open RTD is detected.
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 15
Word/Bit Descriptions – 1790D-4T0, 1790D-T4T0 Thermocouple
Word Decimal Bit Description
Read Word 0 Bits 00…15 Channel 0 input data Read Word 1 Bits 00…15 Channel 1 input data Read Word 2 Bits 00…15 Channel 2 input data Read Word 3 Bits 00…15 Channel 3 input data Read Word 4 Bits 00…03 Underrange for individual channels – Bit 00 corresponds to input
Bits 04…07 Not used: Set to 0 Bits 08…11 Overrange for individual channels – Bit 08 corresponds to input
Bits 12…15 Not used: Set to 0
channel 0, bit 01 corresponds to input channel 1 and so on. When set (1) the input signal is below the input channel’s minimum range.
channel 0, bit 09 corresponds to input channel 1 and so on. When set (1) the input signal is above the input channel’s maximum range, or open RTD is detected.

Interpret the Status Indicators

The 1790D I/O block has these status indicators:
•Block status
•Network status
•I/O status
Status Indicators
Indicator Status Description
Module Solid red Unrecoverable fault in base unit.
Flashing red Recoverable fault Solid green Normal operation – OK Flashing green Standby Off No power.
Publication 1790-IN011C-EN-P - January 2015
16 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
Status Indicators
Indicator Status Description
Network Solid red Unrecoverable communication fault
Flashing red Recoverable communication fault Solid green Communication path complete – OK Flashing green Communication path incomplete Off Device not on line or not powered
I/O Channel LED Status Indicators
Status Description
Flashing green/red Power up Off Off line Red On line and no field power Red DeviceNet connection and no field power Flashing red Field power and open wire Green Field power and valid input Flashing red Input overrange Flashing red Input underrange Flashing red Recoverable fault

Specifications

4-Channel Input RTD Base Module - 1790D-4R0, 1790D-T4R0
Attribute Value
Number of inputs 4 channel, RTD/Resistance input Input range 1…625
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 17
4-Channel Input RTD Base Module - 1790D-4R0, 1790D-T4R0
Sensors supported
Resolution 16 bits across 625 , 0.1°C/bit or 0.1 °F/bit (RTD Sensors) 20 bit Sigma-Delta
Data format 16 bit interger (2’s compliment) Module scan time, per
channel Overall accuracy 0.2% Full scale @ 0…60 ° C Settable notch filter 10 Hz (default), 25 Hz, 50 Hz, 60 Hz, 100 Hz, 250 Hz, 500 Hz Open wire detection Out of range, open wiring Excitation current 1 mA Imput impedance 5 M
Sensor Type Degree Counts Resolution
Resistance 100 m 1…625  10…6250 100 m Resistance 10 m 1…327  100…3270 10 m 100 Pt/ =0.00385 -200…+850 °C -2000…8500 0.1 °C 200 Pt/ =0.00385 -200…+850 °C -2000…8500 0.1 °C 500 Pt/ =0.00385 -200…+650 °C -2000…6500 0.1 °C 100 Pt/ =0.003916 -200…+640 °C -2000…6400 0.1 °C 200 Pt/ =0.003916 -200…+640 °C -2000…6400 0.1 °C 500 Pt/ =0.003916 -200…+640 °C -2000…6400 0.1 °C 100 Nickel -60…+250 °C -600…2500 0.1 °C 120 Nickel -80…+260 °C -800…2600 0.1 °C 200 Nickel -60…+250 °C -600…2500 0.1 °C 500 Nickel -60…+250 °C -600…2500 0.1 °C
modulation converter
8 ms @ Notch filter = 60 Hz
4-Channel Input Thermocouple Base Module – 1790D-4T0, 1790D-T4T0
Attribute Value
Number of inputs 4 channel, Thermocouple/mV Input
Input range ±76.50 mV
Publication 1790-IN011C-EN-P - January 2015
18 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
4-Channel Input Thermocouple Base Module – 1790D-4T0, 1790D-T4T0
Attribute Value
Sensors supported
Resolution 16 bits, 0.1°C/bit or 0.1°F/bit (Thermocouple Sensors) 20 bit Sigma-Delta
Data format 16 bit Integer (2’s compliment)
Module scan time, per channel
Overall accuracy 0.2% Full scale @ 0…60 °C
Settable notch filter 10 Hz (default), 25 Hz, 50 Hz, 60 Hz, 100 Hz, 250 Hz, 500 Hz
Open wire detection Out of range, open wiring
Cold Junction Compensation range
Sensor Type Range Scaling
Voltage 10V -76.50…+76.50 mV -7650…+7650
Type B 300…1800 °C 3000…18000
Type E -270…1000 °C -2700…10000
Type J -210…1200 °C -2100…12000
Type K -270…1370 °C -2700…13700
Type R -50…1768 °C -500…17680
Type S -50…1768 °C -500…17680
Type T -270…400 °C -2700…4000
Type N -270…1300 °C -2700…13000
modulation converter
140 ms @ Notch filter = 60 Hz
0…70 °C
General Specifications
Attribute Value
DeviceNet power Supply voltage – 24V DC nom
DeviceNet power dissipation 1.2 W max @ 28.8V DC
Network length 500 m (1640 ft) max @ 125 Kbps
Voltage range – 11…28.8V DC
100 m (328 ft) max @ 500 Kbps
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 19
General Specifications
Attribute Value
Network protocol Slave messaging:
• Poll command
• Bit Strobe command
• Cyclic command
•COS command
Field power Supply voltage – 24V DC nom
Field power dissipation 1.5 W max @ 26.4V DC
Status indicators Module Status – 1 red/green
Number of nodes 64 max - rotary switch-type node address setting
Communication rate 125 Kbps, 250 Kbps, 500 Kbps – auto baud rate selection
Dimensions (HxWxD), approx. 52 x 104 x 42 mm (2.03 x 4.07 x 1.64 in.)
Weight, approx. 0.1 kg (0.3 lb)
Enclosure type rating None (open style)
Isolation voltage I/O to logic: photocoupler isolation
Mounting DIN rail or screw
Wiring Category
Wiring 37-pin D-Shell connector
Wiring terminal screw torque, max
Removable terminal block screw torque, max
(1)
Use this Conductor Category information for p lanning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 17 70-4.1
(1)
Voltage range – 2136…26.4V DC (±10%)
Network Status – 1 red/green I/O Status – 4 red/green
Type tested @ 1250 V AC for 60 seconds between field power and DeviceNet (I/O to logic) DeviceNet to logic: non-isolated Field power: non-isolated
2
0.6 Nm (5.2 lb-in.)
0.56 Nm (5.0 lb-in.)
.
Publication 1790-IN011C-EN-P - January 2015
20 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
Operating altitude 2000 m
Vibration IEC 60068-2-6 (Test Fc, Operating):
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Shock, non-operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Emissions CISPR 11:
ESD immunity IEC 61000-4-2:
Radiated RF immunity IEC 61000-4-3:
EFT/B immunity IEC 61000-4-4:
Surge transient immunity IEC 61000-4-5:
Conducted RF immunity IEC 61000-4-6:
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0…55 °C (32…131 °F)
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
5…90% non-condensing
2 g @ 10…500 Hz
10 g
30 g
Group 1, Class A
8 kV air discharges
10V/m with 1 kHz sine-wave 80%AM from 80…1000 MHz 10V/m with 200 Hz 50% Pulse 100%AM @ 900 MHz
1 kV @ 5 kHz on power ports ±2 kV @ 5 kHz on signal ports ±2 kV @ 5 kHz on communications ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports ±2 kV line-earth(CM) on communications ports
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 21
Certifications
Certification (when product is marked)
c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
CE European Union 89/336/EEC EMC Directive, compliant with:
RCM Australian Radiocommunications Act, compliant with: AS/NZS CISPR11;
ODVA ODVA conformance tested to DeviceNet specifications
(1)
See the Product Certification lin k at http://www.rockwellautomation.com/products/certification/ for Declaration of Conformity, Certificates, and other certification details.
Valu e
(1)
certified for U.S. and Canada. See UL File E195620.
EN 50082-2; Industrial Immunity EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions
Industrial Emissions
Publication 1790-IN011C-EN-P - January 2015
22 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
Notes:
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 23
Notes:
Publication 1790-IN011C-EN-P - January 2015
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/
technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/
, you can find technical manuals, a knowledge base of FAQs,
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada
Use the Worldwide Locator
http://www.rockwellautomation.com/support/americas/phone_en.html
contact your local Rockwell Automation representative.
at
, or
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number
Outside United States Please contact your local Rockwell Automation representative for the return
(call the phone number above to obtain one) to your distributor to complete the return process.
procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
http://www.rockwellautomation.com/literature/
Allen-Bradley, Rockwell Automation, CompactBlock LDX and RSNetWorx for DeviceNet, are trademarks of Rockwell Automation, Inc. DeviceNet is a trademark of Open DeviceNet Vendor Association.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
.
Publication 1790-IN011C-EN-P - January 2015 PN-297580
Supersedes Publication 1790-IN011B-EN-P - April 2003 Copyright © 2015 Rockwell Automation, Inc. All rights reserved. Printed in Korea.
, available at
Loading...