2 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1
http://www.rockwellautomation.com/literature/
solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also
because of the wide variety of uses for solid-state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
WARNING: Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury or death,
property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions help you identify
a hazard, avoid a hazard and recognize the consequences.
) describes some important differences between
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor)
to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of
the product.
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 3
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as defined in
IEC publication 60664-1), at altitudes up to 2000 meters (6562 ft)
without derating.
This equipment is considered Group 1, Class A industrial equipment according
to IEC/CISPR Publication 11. Without appropriate precautions, there may be
potential difficulties ensuring electromagnetic compatibility in other
environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The enclosure must have
suitable flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if
non-metallic. The interior of the enclosure must be accessible only by the use
of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, for additional
installation requirements, Allen-Bradley publication 1770-4.1
• NEMA Standards publication 250 and IEC publication 60529, as
applicable, for explanations of the degrees of protection provided by
different types of enclosure.
.
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these guidelines
when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Publication 1790-IN011C-EN-P - January 2015
4 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
North American Hazardous Location Approval
The following information applies when
operating this equipment in hazardous
locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for
use in Class I Division 2 Groups A, B, C, D, Hazardous
Locations and nonhazardous locations only. Each product is
supplied with markings on the rating nam eplate indicating
the hazardous location temperature code. When comb ining
products within a system, the most adverse temperature
code (lowest "T" number) may be used to help determine the
overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of
installation.
EXPLOSION HAZARD
• Do not disconnect equipment unless
power has been removed or the area is
known to be nonhazardous.
• Do not disconnect connections to this
equipment unless power has been
removed or the area is known to be
nonhazardous. Secure any external
connections that mate to this equipment
by using screws, sliding latches, threaded
connectors, or other means provided with
this product.
• Substitution of components may impair
suitability for Class I, Division 2.
• If this product contains batteries, they
must only be changed in an are a known to
be nonhazardous.
Informations sur l’utilisation de cet
équipement en environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non
dangereux. Chaque produit est livré avec d es marquages sur
sa plaque d'identification qui indiquent le code de
température pour les environnement s dangereux. Lorsque
plusieurs produits sont combinés dans un système, le code
de température le plus défavorabl e (code de température le
plus faible) peut être utilisé pour déterminer le code de
température global du système. Les combinaisons
d'équipements dans le système sont sujettes à inspection
par les autorités locales qualifiées au moment de
l'installation.
RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher l'équipement.
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher les connecteurs.
Fixer tous les connecteurs externes reliés
à cet équipement à l'aide de vis, loquet s
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.
• La substitution de composants peut rendre
cet équipement inadapté à une util isation
en environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé
non dangereux avant de changer les piles.
EDS File Requirements
Current functionality of CompactBlock LDX I/O blocks require current modular EDS
file for RSNetWorx for DeviceNet™ version 3.0 or later software.
These files are easy to install and are available online at:
www.ab.com/networks/eds/
EDS files for blocks with matching catalog numbers (for both D-Shell and terminal block
versions) are the same. Thus, on the website and in RSNetWorx for DeviceNet, there is
only one EDS file for both versions of the blocks. For example, if you want the EDS file for
1790D-T8BV8B, use the EDS file labeled 1790D-8BV8B.
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 5
Example: Node
Address is set at 11
Install the CompactBlock LDX I/O
Follow these steps to install the block:
• set the node address on the base block.
• mount the base block.
• wire the terminal blocks.
•connect field wiring.
• connect the DeviceNet cable.
These steps are explained in detail in the following procedures.
Set the Node Address on the Base Block
Each base block comes with its internal program set for node address 63. To reset the node
address, adjust the switches on the front of the block. The two switches are most
significant digit (MSD) and least significant digit (LSD). The switches can be set between
00 and 63.
The base block reads the rotary switches at power up only. Switch settings between 64 and
99 cause the block to use the last valid node address stored internally.
Node Address Example
The node address may also be set through RSNetWorx for DeviceNet or a similar
configuration tool. When software configuration is used for the node address, the switches
must be set between 64 and 99.
Publication 1790-IN011C-EN-P - January 2015
6 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
IMPORTANT
CompactBlock LDX
1790-16BVOX
DC INPUTS
EXPANSION UNIT
16 INPUTS-DCPOWER
0
7
DC INPUTS
8
15
95 mm
(3.74 in.)
41 mm
(1.6 in.)
Expansion
Cable
Cover
44252
Mount the Base Module
You can mount the base block to a panel or DIN rail. We recommend that you ground the
panel or DIN rail before mounting the block.
The RTD and thermocouple base blocks do not support any expansion
blocks.
WARNING: When used in a Class I, Division 2, hazardous location, this
equipment must be mounted in a suitable enclosure with the proper wiring
method that complies with the governing electrical codes.
Dimensions
Mount on a Panel
For panel mounting, use these steps.
1. Place the block against the panel where you want it mounted.
2. Gently pull and position the expansion cover to the left.
3. Place a center punch, nail, or similar device through the mounting holes in the
block and make two marks on the panel at the lower-left and upper-right corners
of the module.
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 7
Locking Lever
4. Remove the block and drill two holes in the panel to accommodate each of the
mounting screws.
5. Replace the block on the panel and place a screw through each of the two
mounting holes.
6. Tighten the screws until the block is firmly in place.
Mount on DIN Rail
For DIN-rail mounting, use these steps.
1. Hook the top slot of the base block over the DIN rail.
2. Pull down on the locking lever while pressing the base block against the rail.
3. Push up on the locking lever to secure the base block to the rail when the base
block is flush against the rail.
Publication 1790-IN011C-EN-P - January 2015
8 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
Wire the Terminal Block
The following figures show how to wire the terminal blocks.
1790D-4R0 RTD Input Module D-Shell Wiring
CH1_B
10
29
CH1_B
10
29
NC
COM
13
COM
28
COM
28
NC
14
NC
9
NC
NC
27
COM
9
27
NC
15
NC
16
NC
CH2_A
8
COM
NC
8
NC
7
26
COM
CH2_A
7
26
NC
17
18
NC
CH2_B
25
CH2_B
NC
CH3_B
CH3_A
5
6
24
23
COM
COMCOM COM
CH3_B
CH3_A
5
6
24
25
23
NC
NCNCNC
NC
19
20
NC
+24V
NC
NC
CH0_B
+24V
19
37
GND
18
36
GND
+24V
17
35
GND
NC
16
15
34
33
NC
NC
CH0_A
14
32
NC
13
COM
CH1_A
11
12
30
31
COM
COM
• Wire pins 17, 18, 19 to Field Power (+) 24V DC
• Wire pins 35, 36, 37 to Field Power (-) GND
1790D-4T0 Thermocouple Module D-Shell Wiring
+24V
NC
NC
CH0_B
+24V
19
37
GND
18
36
GND
+24V
17
35
GND
NC
16
15
34
33
NC
NC
CH0_A
14
32
NC
CH1_A
11
13
12
30
31
NC
NC
• Wire pins 17, 18, 19 to Field Power (+) 24V DC
• Wire pins 35, 36, 37 to Field Power (-) GND
1790D-T4RO RTD Input Module Terminal Block Wiring
+24V
CH1_A
CH0_A
1
3
2
GND
CH0_B
• Wire pin 1 to Field Power (+) 24V DC
• Wire pin 2 to Field Power (-) GND
5
4
CH1_B
COM
6
CH2_A
7
8
COM
CH3_A
9
10
CH2_B
11
12
CH3_B
NC
NC
NC
3
4
22
4
1
2
20
21
COM
NC
NC
NC
3
1
2
22
20
21
NC
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 9
• use shielded, twisted pair wire to ensure proper operation and high immunity to
electrical noise
• to limit noise, locate RTD and resistance device signal wires as far away as possible
from power lines, load lines and other sources of electrical noise, such as
hard-contact switches, relays and AC motor drives
• under normal conditions, the drain wire and shield junction should be connected
to earth ground, via a panel or DIN rail mounting screw at the block end
• keep shield connection to ground as short as possible
• to ensure optimum accuracy, limit overall cable impedance by keeping the cable as
short as possible. Locate the I/O system as close to your field devices as your
application will permit.
RTD Wiring Guidelines
Since the operating principle of the RTD module is based on the measurement of
resistance, give special consideration when selecting the input cable. For 2-wire or 3-wire
configurations, select a cable that has consistent impedance throughout its entire length.
Publication 1790-IN011C-EN-P - January 2015
10 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
IMPORTANT
IMPORTANT
The RTD block requires three wires to compensate for lead resistance error.
We recommend that you do not use 2-wire RTDs if long cable runs are
required, as it reduces the accuracy of the system.
However, if a 2-wire configuration is required, reduce the effect of the lead
wire resistance by using a lower-gauge wire for the cable (for example, use
AWG #16 instead of AWG #24). The block’s terminal strip accepts
AWG #14 gauge wire.
When using a 3-wire configuration, the block compensates for resistance error due to lead
wire length. For example, in a 3-wire configuration, the block reads the resistance due to
the length of the wires and assumes that the resistance of the other wire is equal. If the
resistance of the individual lead wires are much different, an error may exist. The closer the
resistance values are to each other, the greater the amount of error is eliminated.
To ensure temperature or resistance value accuracy, the resistance
difference of the cable lead wires must be equal to or less than 0.01 .
To ensure that the lead values match as closely as possible:
• keep lead resistance as small as possible and less than 25
• use quality cable that has a small tolerance impedance rating
• use a heavy-gauge lead wire which has less resistance per foot
RTD Wiring Configurations
Three configurations of RTDs can be connected to the blocks:
• 2-wire RTD, which is composed of an RTD EXC (excitation) lead wire and a
RTN (ret urn) wi re
• 3-wire RTD, which is composed of a Sense and 2 RTD lead wires (RTD EXC
and RTN)
• 4-wire RTD, which is composed of a Sense and 2 RTD lead wires (RTD EXC
and RTN). The second sense wire of a 4-wire RTD is left open.
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 11
CH0_A
CH0_B
COM
Add Jumper
Cable Shield (to Ground)
CXE DTRCXE DTR
nruteRnruteR
CH0_A
CH0_B
COM
Cable Shield (to Ground)
RTD EXC
RTD EXC
Sense
Sense
Return
Return
2-Wire RTD Configuration
3-Wire RTD Configuration
4-Wire RTD Configuration
Leave this sensor wire open
RTD EXC
Sense
Return
CH0_A
CH0_B
COM
Cable Shield (to Ground)
RTD EXC
Sense
Return
Wire Resistance Devices (Potentiometers)
Potentiometer wiring requires the same type of cable as that for the RTD. Potentiometers
can be connected to the module as a 2-wire or 3-wire connection as shown in the
following figures:
Publication 1790-IN011C-EN-P - January 2015
12 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
TIP
A
CH0_A
CH0_B
COM
CH0_A
CH0_B
COM
Cable Shield (to Ground)
RTD EXC
Return
Potentiomete
Cable Shield (to Ground)
RTD EXC
Return
Potentiometer
Sense
Run Return and sense wires from
the module to potentiometer terminal
and tie terminal to one point
Run Return and sense wires from
the module to potentiometer terminal
and tie terminal to one point
2-Wire Potentiometer Interconnection
Add Jumper
CH0_A
CH0_B
COM
Cable Shield (to Ground)
RTD EXC
Return
Potentiometer
dd Jumper
CH0_A
CH0_B
COM
The potentiometer wiper arm can be connected to either the
EXC or return terminal, depending on whether you want
increasing or decreasing resistance.
Publication 1790-IN011C-EN-P - January 2015
Cable Shield (to Ground)
RTD EXC
Return
Potentiometer
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 13
Wiring Diagram for
1799-DNETCON
Connector
Wiring Diagram for
1799-DNC5MMS
Connector
V+ Red
V- Black
Drain/Shield
Can_H White
Can_L Blue
V+ Red
Can_H White
Drain/Shield
Can_L Blue
V- Black
44164
Connect the DeviceNet Cable
Follow these procedures when connecting the DeviceNet cable to the base block.
The required DeviceNet connector is not supplied with the block - you must purchase it
separately. There are three types of connectors that you can order directly from Rockwell
Automation or your local distributor:
• 1799-DNETCON – 5-position open style connector
• 1799-DNETSCON – 5-position open style connector with locking screws
• 1799-DNC5MMS – 5-position open style to 5-pin micro male connector with
locking screws
WARNING: If you connect or disconnect the DeviceNet cable with power
applied to this module or any device on the network, an electrical arc can
occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
1. Connect the DeviceNet wiring (drop line) to one of the DeviceNet connectors as
shown in the figure, noting that a color-coded wiring diagram is printed next to
the connector on the left side of the base block.
1. Attach the connector to the base block once you have properly wired
the drop line to the connector.
2. Use the locking screws on the connector to fasten it to the base block,
if applicable.
Publication 1790-IN011C-EN-P - January 2015
14 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
I/O Memory Mapping
1790D-4R0, 1790D-T4R0 Input Data File
Word Bit Position
15 14 13 12 11 10 9876543210
0RTD Input Data Channel 0
1RTD Input Data Channel 1
2RTD Input Data Channel 2
3RTD Input Data Channel 3
4Not usedS11 S10 S9 S8 Not usedS3 S2 S1 S0
Word/Bit Descriptions – 1790D-4R0, 1790D-T4R0 RTD
WordDecimal BitDescription
Read Word 0 Bits 00…15Channel 0 input data
Read Word 1 Bits 00…15Channel 1 input data
Read Word 2 Bits 00…15Channel 2 input data
Read Word 3 Bits 00…15Channel 3 input data
Read Word 4 Bits 00…03Underrange for individual channels – Bit 00 corresponds to input
Bits 04…07Not used: Set to 0
Bits 08…11Overrange for individual channels – Bit 08 corresponds to input
Bits 12…15Not used: Set to 0
1790D-4T0, 1790D-T4T0 Input Data File
Word Bit Position
15 14 13 12 11 10 9876543210
0Thermocouple Input Data Channel 0
1Thermocouple Input Data Channel 1
2Thermocouple Input Data Channel 2
3Thermocouple Input Data Channel 3
4Not usedS11 S10 S9 S8 Not usedS3 S2 S1 S0
channel 0, bit 01 corresponds to input channel 1 and so on.
When set (1) the input signal is below the input channel’s
minimum range.
channel 0, bit 09 corresponds to input channel 1 and so on.
When set (1) the input signal is above the input channel’s
maximum range, or open RTD is detected.
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 15
Read Word 0 Bits 00…15Channel 0 input data
Read Word 1 Bits 00…15Channel 1 input data
Read Word 2 Bits 00…15Channel 2 input data
Read Word 3 Bits 00…15Channel 3 input data
Read Word 4 Bits 00…03Underrange for individual channels – Bit 00 corresponds to input
Bits 04…07Not used: Set to 0
Bits 08…11Overrange for individual channels – Bit 08 corresponds to input
Bits 12…15Not used: Set to 0
channel 0, bit 01 corresponds to input channel 1 and so on.
When set (1) the input signal is below the input channel’s
minimum range.
channel 0, bit 09 corresponds to input channel 1 and so on.
When set (1) the input signal is above the input channel’s
maximum range, or open RTD is detected.
16 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
Status Indicators
IndicatorStatusDescription
NetworkSolid redUnrecoverable communication fault
Flashing redRecoverable communication fault
Solid greenCommunication path complete – OK
Flashing greenCommunication path incomplete
OffDevice not on line or not powered
I/O Channel LED Status Indicators
StatusDescription
Flashing green/redPower up
OffOff line
RedOn line and no field power
RedDeviceNet connection and no field power
Flashing redField power and open wire
GreenField power and valid input
Flashing redInput overrange
Flashing redInput underrange
Flashing redRecoverable fault
Specifications
4-Channel Input RTD Base Module - 1790D-4R0, 1790D-T4R0
AttributeValue
Number of inputs4 channel, RTD/Resistance input
Input range1…625
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 17
4-Channel Input RTD Base Module - 1790D-4R0, 1790D-T4R0
Sensors supported
Resolution16 bits across 625 , 0.1°C/bit or 0.1 °F/bit (RTD Sensors) 20 bit Sigma-Delta
Data format16 bit interger (2’s compliment)
Module scan time, per
channel
Overall accuracy0.2% Full scale @ 0…60 ° C
Settable notch filter10 Hz (default), 25 Hz, 50 Hz, 60 Hz, 100 Hz, 250 Hz, 500 Hz
Open wire detection Out of range, open wiring
Excitation current1 mA
Imput impedance5 M
Sensor TypeDegreeCountsResolution
Resistance 100 m1…625 10…6250100 m
Resistance 10 m1…327 100…327010 m
100 Pt/ =0.00385-200…+850 °C-2000…85000.1 °C
200 Pt/ =0.00385-200…+850 °C-2000…85000.1 °C
500 Pt/ =0.00385-200…+650 °C-2000…65000.1 °C
100 Pt/ =0.003916-200…+640 °C-2000…64000.1 °C
200 Pt/ =0.003916-200…+640 °C-2000…64000.1 °C
500 Pt/ =0.003916-200…+640 °C-2000…64000.1 °C
100 Nickel-60…+250 °C-600…25000.1 °C
120 Nickel-80…+260 °C-800…26000.1 °C
200 Nickel-60…+250 °C-600…25000.1 °C
500 Nickel-60…+250 °C-600…25000.1 °C
modulation converter
8 ms @ Notch filter = 60 Hz
4-Channel Input Thermocouple Base Module – 1790D-4T0, 1790D-T4T0
AttributeValue
Number of inputs4 channel, Thermocouple/mV Input
Input range±76.50 mV
Publication 1790-IN011C-EN-P - January 2015
18 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
4-Channel Input Thermocouple Base Module – 1790D-4T0, 1790D-T4T0
AttributeValue
Sensors supported
Resolution16 bits, 0.1°C/bit or 0.1°F/bit (Thermocouple Sensors) 20 bit Sigma-Delta
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 19
General Specifications
AttributeValue
Network protocolSlave messaging:
• Poll command
• Bit Strobe command
• Cyclic command
•COS command
Field powerSupply voltage – 24V DC nom
Field power dissipation1.5 W max @ 26.4V DC
Status indicatorsModule Status – 1 red/green
Number of nodes64 max - rotary switch-type node address setting
Communication rate125 Kbps, 250 Kbps, 500 Kbps – auto baud rate selection
Dimensions (HxWxD), approx. 52 x 104 x 42 mm (2.03 x 4.07 x 1.64 in.)
Weight, approx.0.1 kg (0.3 lb)
Enclosure type ratingNone (open style)
Isolation voltageI/O to logic: photocoupler isolation
MountingDIN rail or screw
Wiring Category
Wiring37-pin D-Shell connector
Wiring terminal screw torque,
max
Removable terminal block
screw torque, max
(1)
Use this Conductor Category information for p lanning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 17 70-4.1
(1)
Voltage range – 2136…26.4V DC (±10%)
Network Status – 1 red/green
I/O Status – 4 red/green
Type tested @ 1250 V AC for 60 seconds between field power and
DeviceNet (I/O to logic)
DeviceNet to logic: non-isolated
Field power: non-isolated
2
0.6 Nm (5.2 lb-in.)
0.56 Nm (5.0 lb-in.)
.
Publication 1790-IN011C-EN-P - January 2015
20 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
ODVAODVA conformance tested to DeviceNet specifications
(1)
See the Product Certification lin k at http://www.rockwellautomation.com/products/certification/ for Declaration of
Conformity, Certificates, and other certification details.
Valu e
(1)
certified for U.S. and Canada. See UL File E195620.
EN 50082-2; Industrial Immunity
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
Industrial Emissions
Publication 1790-IN011C-EN-P - January 2015
22 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
Notes:
Publication 1790-IN011C-EN-P - January 2015
DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O 23
Notes:
Publication 1790-IN011C-EN-P - January 2015
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/
technical and application notes, sample code and links to software service packs, and a MySupport feature
that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we
offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/
, you can find technical manuals, a knowledge base of FAQs,
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting
your product up and running.
contact your local Rockwell Automation representative.
at
, or
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from
the manufacturing facility. However, if your product is not functioning and needs to be returned, follow
these procedures.
United StatesContact your distributor. You must provide a Customer Support case number
Outside United StatesPlease contact your local Rockwell Automation representative for the return
(call the phone number above to obtain one) to your distributor to complete the
return process.
procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002
http://www.rockwellautomation.com/literature/
Allen-Bradley, Rockwell Automation, CompactBlock LDX and RSNetWorx for DeviceNet, are trademarks of Rockwell Automation, Inc.
DeviceNet is a trademark of Open DeviceNet Vendor Association.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
.
Publication 1790-IN011C-EN-P - January 2015PN-297580