Rockwell Automation 1788-EN2DN User Manual

Page 1
Installation Instructions
Ethernet-to-DeviceNet Linking Device
Catalog Number 1788-EN2DN
This publication tells you how to install the 1788-EN2DN Ethernet-to-DeviceNet linking device and use RSNetWorx for DeviceNet software to configure it.
Topi c Pag e
Important User Information 2
System Requirements 7
Installing and Configuring the Linking Device 8
Using Diagnostic Web Pages 44
Dimensions 49
DeviceNet Connector Pinouts 50
EtherNet/IP RJ45 Connector Pinouts 50
Specifications 51
Additional Resources 55
Page 2
2 Ethernet-to-DeviceNet Linking Device

Important User Information

Solid-state equipment has operational characteri stics differing from those of electromechanical equipment. Safety Guidelin es for the Application, Installation an d Maintenance of Solid State Controls (publication SGI-1.1 Rockwell Automationsales office or online at http://www.rockwellautomation.com/literature/ differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all pers ons responsible for applying this equipment must sati sfy themselves that each intended application of this equ ipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liab le for indirect or consequential damages resulting from the use or application of this equi pment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING : Identifies information about practices or circumstan ces that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstan ces that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or ins ide the equipment, for example, drive or motor, to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical fo r successful application and understanding of the produc t.
available from your local
) describes some important
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 3
Ethernet-to-DeviceNet Linking Device 3

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations.
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNIN G: Explosion Hazard -
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connec tions that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT: Risque d’Explosion –
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 4
4 Ethernet-to-DeviceNet Linking Device

European Hazardous Location Approval

The following applies when the product bears the Ex Marking. This equipment is intended for use in potentially explosive atmospheres as
defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
WARNING: This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2 environments.
This equipment shall be used within its specified ratings defined by Rockwell Automation.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Zone 2 environments.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 5

Environment and Enclosure

ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety cer tifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the
, for additional installation requirements
1770-4.1
degrees of protection provided by enclosures
Ethernet-to-DeviceNet Linking Device 5
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 6
6 Ethernet-to-DeviceNet Linking Device

About the Linking Device

The 1788-EN2DN Ethernet-to-DeviceNet linking device lets you seamlessly connect your information- or control-level networks with your device-level network.
The linking device provides full DeviceNet master functionality, so you can connect up to 63 DeviceNet slave devices to an Ethernet TCP/IP interface that supports the EtherNet/IP network and an HTTP web server. As examples, you could use the linking device:
as a gateway to connect information- or control-level networks to
device-level networks for programming, configuration, control, or data collection.
as a router/bridge to connect the EtherNet/IP network to the
DeviceNet network.
The linking device provides centralized data storage, or I/O tables, for data shared between the DeviceNet and EtherNet/IP networks. Data is placed into the I/O tables by one network interface, allowing the data to be read through the other network interface.
The linking device appears as a single device on either network by using standard protocol mechanisms. No special, or extended, protocol features are required for the devices on either network to read or write the data flowing through the I/O tables; all cross-network activity is transparent to the devices on either network.
All connections, whether power or fieldbus, to the linking device are made on one end of the module. Phoenix connectors are provided for power and DeviceNet connections. A RJ45 style connector is provided for EtherNet/IP connection.
The linking device can be mounted to a DIN rail.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 7
Ethernet-to-DeviceNet Linking Device 7

System Requirements

The following hardware and software components are required to use the linking device.

Required Hardware

1788-EN2DN linking device
DeviceNet cabling, power, and devices forming a DeviceNet network
Ethernet cabling and power
Computer with access to the Ethernet network
Computer running DeviceNet configuration software
The DeviceNet slave devices with which the linking device communicates are specified using a DeviceNet Configuration Software tool such as RSNetWorx for DeviceNet software.
24V DC power to the linking device
DeviceNet power may be used; however, using DeviceNet power bypasses the DeviceNet network isolation.

Required Software

DeviceNet configuration software, such as RSNetWorx for DeviceNet
software, version 4.01 or later, to configure DeviceNet devices and the linking device’s DeviceNet functionality
RSLinx
DHCP server 2.3.2 or later, which ships with RSLinx software version
software, version 2.31 or later
2.42 and later. If you are using an earlier version of RSLinx software, you will need to download the standalone server from
http://www.rockwellautomation.com/support
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 8
8 Ethernet-to-DeviceNet Linking Device

Optional Software

RSLogix5000 software, version 13 or later.

Installing and Configuring the Linking Device

WARNING: If you connect or disconnect the communication cable with power
applied to this module or any device on the network, an elec trical arc can occur. This could cause an explosion in hazardous location installations.
If you connect or disconnec t wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
When you change switch settings while field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Follow these steps to install the linking device (described in the sections that follow).
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 9
Ethernet-to-DeviceNet Linking Device 9
DeviceNet Connection
Power Connection
Configuration DIP Switch
RJ45 Port (EtherNet/IP Connection)
31480-M

Connect the Linking Device to the EtherNet/IP Network

Connect the EtherNet/IP network cable to the RJ45 port on the end of the linking device.
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 10
10 Ethernet-to-DeviceNet Linking Device
(Red) Net Power 24V DC
(White) CAN High +
CAN Shield
(Blue) CAN Low
(Black) Net Power 24V DC Common
31442-M

Connect the Linking Device to the DeviceNet Network

ATTENTION:
Do not wire more than 2 conductors on any single terminal. To comply with the CE Low Voltage Directive (LVD), this equipment must be
powered from a source compliant with Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
To comply with UL restrictions, this equipment must be powered from a source compliant with Class 2 or Limited Voltage/Current.
1. Make sure a computer running RSNetWorx for DeviceNet software is
connected to the EtherNet/IP network.
2. With power to the linking device off, connect the DeviceNet network
cable to the DeviceNet connector on the linking device.
The female terminal block connector is provided with the linking device.
3. Connect the power cable to the linking device.
The female terminal block connector is provided with the linking device.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 11
Ethernet-to-DeviceNet Linking Device 11
TIP
IMPORTANT
..
24V DC common
24V DC +
Two 120 ohm termination resistors (supplied with the linking device) may be required for proper network termination at each end of the trunk line. See the DeviceNet Specification (available from the Open DeviceNet Vendors Association at http://www.odva.org
) for specific rules on DeviceNet
connections and termination.
4. Apply power to the linking device and DeviceNet network.
The linking device defaults to Autobaud. This means that the linking device automatically finds the network communication rate at when power is applied. You must specify a master device, such as a DeviceNet Bridge Module (catalog number 1756-DNB) so that the linking device can pick up the correct communication rate. If you do not have another device installed, you must use RSNetWorx for DeviceNet software to set the communication rate, as described in Set the DeviceNet MAC ID and Communication Rate Do not attempt to commission the li nking device on a network configured at a different communication rate.
on page 21.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 12
12 Ethernet-to-DeviceNet Linking Device
IMPORTANT
ON
23456781
ON
23456
7
8
1
31421-M

Configure the Linking Device IP Address

Several methods may be used to set the IP Address. These methods include the following:
IP address configuration DIP switch
DHCP protocol
We b p ag e
RSLogix 5000 software, version 13 or later), and 1788-EN2DN Linking
Device, revision 2.x or later
Setting the IP Address with the Configuration DIP Switch
A configuration DIP switch on the end of the linking device lets you set the IP address. If the configuration DIP switch is set to 1 (in the up position, as shown in the following figure), when power is applied to the switch, the value of the switch creates the IP address of 192.168.1.1.
The numbers that appear above the switches on the DIP switch do not correspond to bit locations in the address value. The numbers on the switch are opposite the address value bit locations; for example, bit 0 is set by switch 8.
IP Address Configuration DIP Switch
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 13
Ethernet-to-DeviceNet Linking Device 13
TIP
The switch represents the binary value of the last byte in the 4-byte IP address. In this case it is n. If n = 0, the linking device obtains its IP address from the software configuration (DHCP or web page).
IP address 192.168.1.n
Subnet mask 255.255.255.0
Gateway address 0.0.0.0 (No gateway set)
Setting the IP Address By Using DHCP/BootP
The use of DHCP is the default configuration for the linking device as shipped. The IP address configuration DIP switch ships with n =0.
When DHCP/BootP is enabled and a DHCP or BootP server is found, the IP address, Subnet mask, and Gateway address are automatically configured by the DHCP server, as shown in the following figure.
Automatic Configuration
Follow these steps to change the IP address, Subnet mask, and Gateway address from this dialog box.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 14
14 Ethernet-to-DeviceNet Linking Device
1. Click New.
You see the Properties dialog box.
2. On the Properties dialog box, enter the appropriate values into the
following fields.
Ethernet address (MAC ID) [from the linking device product ID
label]
IP address
Subnet Mask
Gateway (IP address)
3. Click OK.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 15
Ethernet-to-DeviceNet Linking Device 15
TIP
31445-M
The following figure shows a flowchart describing how the IP configuration is determined when the linking device is powered up.
Start
Use received
conguration
Yes
Request cong
from DHCP/
BOOTP Server.
Timeout 30 secs
DHCP
Cong
Received?
No
Valid
Conguration
File?
No
Remain oine
Yes
Valid
Conguration
in Flash Memory?
Yes
DHCP
Enabled?
No
Use Valid (stored)
IP address
Stop
No
Yes
Yes
You can enable these values using the linking device’s IP Configuration web page. Refer to Setting the IP Address Using By Using the Web Page on
page 16.
DIP Switch = 0
No
IP = 192 168.1.n
Sub = 255.255.255.0
No Gateway
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 16
16 Ethernet-to-DeviceNet Linking Device
IMPORTANT
Setting the IP Address Using By Using the Web Page
The EtherNet/IP address can also be configured using the IP Configuration web page on the linking device, as shown in the following figure.
The IP address can be set with the web page only if the linking device already has a valid IP address. Typically, you can do this by using the DIP switch to force the linking device to use a temporary IP address after you cycle power. Follow these steps to configure the IP address with the web page.
Because the DIP switch setting overrides other IP address configurations, be sure to set the DIP switch to the 0 position before continuing.
1. Browse to the linking device by entering the temporary IP address in
your web browser’s address bar and click Enter.
2. In the left pane, click IP Configuration.
You see the Enter Network Password dialog box.
3. In the Username field, enter Administrator.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 17
4. Leave the password field blank.
5. Click OK.
You see the IP Configuration dialog box.
Ethernet-to-DeviceNet Linking Device 17
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 18
18 Ethernet-to-DeviceNet Linking Device
6. Enter the following values into the IP Configuration dialog box.
In this field Enter
IP Address Any valid value. See your system administrator for a
Subnet Mask
Gateway IP Address
DHCP enabled
valid IP address.
Any valid value.
7. Click Submit Values.
8. Follow the on-dialog box prompts.
9. Click the Reset Module button to reset the linking device.

Register the Driver in RSLinx Software

1. In RSLinx software, choose Communications>Configure Driver.
2. In the Configure Drivers menu, choose Ethernet Devices from the
Available Driver Types pull-down menu.
3. Click Add New.
4. In the Add New RSLinx Drivers pop-up menu, click OK.
5. In the Config ure Driver window that appears, enter the IP address of the
linking device.
6. Click Close.
7. Click OK.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 19
Ethernet-to-DeviceNet Linking Device 19
IMPORTANT
(Optional)
RSNetWorx for DeviceNet software requires an electronic data sheet (EDS) to recognize a device and its capabilities. If you do not already have a registered EDS file for the device, you can download an EDS file from
http://www.rockwellautomation.com/support/downloads.html
Register the EDS file in RSNetWorx Software
.
If RSLinx or RSNetWorx for DeviceNet soft ware cannot find the EDS file for the linking device, the linking device’s icon may be labeled an unrecognizable device in the software.
1. In RSNetWorx for DeviceNet software, choose Tools>EDS Wizard.
2. Click Next.
3. Select Register an EDS File and click Next.
4. Select Register a Single File and enter or browse to the location of the
EDS file for the linking device.
5. Click Next or Finish for the remaining option dialog boxes.

Use RSNetWorx for DeviceNet Software to Locate the Module on the Network

1. In RSNetWorx for DeviceNet software, choose Network>Online.
2. In the left pane, click the RSLinx Ethernet driver you added previously.
Refer toUse RSNetWorx for DeviceNet Software to Locate the Module
on the Network on page 19.
3. In the left pane, click the + next to the 1788-EN2DN linking device
icon.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 20
20 Ethernet-to-DeviceNet Linking Device
4. In the left pane, click DeviceNet, DeviceNet.
5. When asked to upload from the network, click OK to perform a single
pass browse.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 21
Ethernet-to-DeviceNet Linking Device 21

Set the DeviceNet MAC ID and Communication Rate

1. In RSNetWorx for DeviceNet software, choose Tools>Node
Commissioning.
You see the Node Commissioning dialog box.
2. On the Node Commissioning dialog box, click Browse.
You see the Device Selection dialog box.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 22
22 Ethernet-to-DeviceNet Linking Device
3. In the left pane, click the + next to the RSLinx driver for the
1788-EN2DN linking device.
4. In the left pane of the dialog box, click the + next to the IP address for
the 1788-EN2DN linking device.
5. In the left pane, click the + next to the DeviceNet network.
You see the 1788-EN2DN linking device in the left pane.
6. Click on the 1788-EN2DN linking device in the left pane.
It appears in the right pane.
7. Click OK.
8. If a warning text box asking you if you wish to continue appears, click
Ye s .
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 23
Ethernet-to-DeviceNet Linking Device 23
IMPORTANT
TIP
9. Enter the desired MAC address or data rate, then click Apply.
10. Click Close.
The linking device will automatically reset if a new MAC ID is entered. If only the communication rate is changed you must cycle power to the linking device before the new communication rate will take effect.
When the MAC ID is changed, the linking device’s I/O configuration is cleared.
11. Restart RSNetworx for DeviceNet software and go online.
If you are using the linking device as a network gateway, you may need to restart RSNetWorx for DeviceNet software before continuing.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 24
24 Ethernet-to-DeviceNet Linking Device
(Optio nal)
If you do not want the linking device to automatically determine the network communication rate, disable Autobaud. By default, the linking device has Autobaud enabled.
Disable Autobaud
1. In RSNetWorx for DeviceNet software, highlight the linking device by
clicking on its icon.
2. From the pull-down menu, choose Device>Class Instance Editor.
3. If a warning text box appears, click Yes.
You see the Class Instance Editor dialog box.
4. From the pull-down menu, choose Description>Set Single Attribute.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 25
Ethernet-to-DeviceNet Linking Device 25
IMPORTANT
In this field Select
Object Address
Class Instance Attribute
Data Sent to Device 00 to enable Autobaud
3 1 64h
01 to disable Autobaud
Tra nsm it D ata Siz e By te
Make sure the Values in Decimal checkbox is not checked.
5. Click Execute.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 26
26 Ethernet-to-DeviceNet Linking Device
IMPORTANT
You should see a message in the Data received from device field indicating that the execution was completed.
Changes to the autobaud option configuration do not take effect until you cycle power to the linking device. You may also have to cycle power to the slave devices.
If the linking device is the only master on the DeviceNet network, do not enable autobaud. Automatic communication de tection requires traffic on the network. There is typically no traffic until the master establishes connections.
6. Click Close.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 27
Ethernet-to-DeviceNet Linking Device 27
IMPORTANT
IMPORTANT
IMPORTANT

(Optional) Configure DeviceNet I/O

Steps 8 and 9 are required only if the linking device is used as an I/O scanner. The linking device can function as a gateway/bridge, even if no I/O is configured.
I/O Mapping
The DeviceNet I/O configuration defines the format of the Input and Output tables, or the mapping of DeviceNet slaves’ I/O data to the I/O tables. As slaves are added to the linking device’s DeviceNet scanner configuration, the location in the I/O tables of each part of the slave’s I/O data is determined and stored.
The organization of the I/O tables is very important. I/O tables define the format of the data that will be provided to the EtherNet/IP scanner. The Input and Output table formats should be planned and documented to be sure the EtherNet/IP scanner is working with the correct data from the DeviceNet network.
The size of the I/O data that can be exchanged with the EtherNet/IP scanner (and, hence, the size of the I/O tables) is restricted as explained below.
The Input table size cannot be larger than 496 bytes.
The Output table size cannot be larger than 492 bytes.
Either table may be empty (0 bytes).
To configure DeviceNet I/O, use RSNetWorx for DeviceNet software to set the linking device’s scan list and I/O table mapping.
Automap is used in this example for simplicity. In some cases, you may want to organize the I/O data in other ways; you can do this using the Advanced data table editor in the Input and Output tabs. Refer to RSNetWorx online help for complete details.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 28
28 Ethernet-to-DeviceNet Linking Device
1. In RSNetWorx for DeviceNet, go online by choosing Network>Online.
2. Select Network>Single Pass Browse. Wait for browsing to complete.
3. Select Network>Upload from Network. Wait for the device
information to be uploaded from the network.
4. Double-click the linking device icon to bring up the Module
Description dialog box.
Several tabs appear on the top of the dialog box.
5. Click the Scanlist tab.
6. In the informational text box that appears, click Upload.
The dialog box shows two columns. On the left is a list of available devices that may be added to the scan list. On the right is a list of devices that are configured in the scan list.
7. Check AutoMap on Add.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 29
Ethernet-to-DeviceNet Linking Device 29
The top portion of this dialog box gives a list of the devices in the scan list from which the linking device receives input data. The bottom shows the location in the Input table where the data will be placed for each device. This shows the format of the Input table of the linking device. This is the format of the input data that will be sent to the EtherNet/IP scanner.
8. Select the I/O devices on the left side of the dialog box and click > to
move it to the right side of the dialog box.
9. Select the Input tab.
The Input mapping dialog box is displayed.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 30
30 Ethernet-to-DeviceNet Linking Device
TIP
The top portion of this dialog box gives a list of the devices in the scan list to which the linking device will send output data. The bottom shows the location in the Output table where the data will be placed for each device. This shows the format of the Output table of the linking device. This is the format of the output data that will be sent to the linking device from the EtherNet/IP scanner.
10. Select the Output tab.
The Output mapping dialog box is displayed.
11. Click Apply, and click Yes to download the scanlist to the linking
device.
The linking device starts scanning as soon as it finds entries in its scanlist. However, in Idle mode, output data will not be sent to the devices.
12. Click OK.
(
Optional
) Add the Linking Device to an RSLogix 5000 Software Project
1. Create a new project in RSLogix 5000 software by selecting File>New.
You see the New Controller dialog box.
2. From the Type pull-down menu, choose the controller type.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 31
Ethernet-to-DeviceNet Linking Device 31
3. From the Revision pull-down menu, choose the controller version.
4. Enter a name for the controller project.
5. Click OK.
A project is created.
6. In the left pane, right-click I/O Configuration.
7. Click New Module.
8. In the Select Module Type menu, choose any EtherNet/IP Bridge
Module (such as the 1788-ENBT module).
9. Click OK.
You see the Module Properties dialog box.
10. In the Slot Number field, enter the slot number in which the device
resides.
11. Click Finish.
12. In the right pane, right-click the EtherNet/IP module you just added to
your project.
13. Click New Module.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 32
32 Ethernet-to-DeviceNet Linking Device
14. In the Select Module Type menu, choose 1788-EN2DN/A 1788
Ethernet to DeviceNet Linking Device.
15. Click OK.
16. On the Select Major Revision dialog box that appears, choose the major
revision from the drop-down box.
17. Click OK.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 33
Ethernet-to-DeviceNet Linking Device 33
If you see errors in this field when you are online, see the table following this illustration.
You see the Module Properties dialog box.
18. In the Name field, enter a module name.
19. Click the IP Address radio button and enter the IP address for which the
linking device is configured.
20. Click Next.
21. Enter the Requested Packet Interval (RPI or update rate) in a range from
2…750 ms.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 34
34 Ethernet-to-DeviceNet Linking Device
RSLogix 5000 Software Error Codes
This Error code Means So you should
16#0203 Connection timed out Check IP configuration and Ethernet cabling
16#0204 Connection Request Error: Connect
16#0103 Service Request Error: CIP transport
16#0005 Connection Request Error: Bad class. Check for correct assembly instance numbers
request timed out
class not supported
Check IP configuration and Ethernet cabling
Check for valid RPI range (for example, 2…3200ms)
in connection parameters
22. Click Next.
If an RSNetWorx for DeviceNet configuration file (filename *.dnt) already exists for the linking device, enter or browse to the appropriate filename. Doing so allows RSNetWorx for DeviceNet to launch directly from RSLogix 5000 software.
23. Click Finish.
You can now use the linking device as both a bridge and a scanner.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 35
Ethernet-to-DeviceNet Linking Device 35
TIP
24. Write a user program to use the linking device on the network.
Consult Rockwel l Automation Technical Suppor t or your Rockwell Autom ation representative for assistance in writing the program.
25. To view information specific to the RSLogix 5000 tags that pertain to
the linking device, do the following: a. In the left pane of the RSLogix 5000 software window, click
Controller Tags. In the right pane, you see the 1788-EN2DN linking device controller tags.
b. Click on the + to the left of the tag name to expand it. c. Review data in the fields that appear for each tag, as described in the
section entitled Assembly Objects and Connections
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
on page 36.
Page 36
36 Ethernet-to-DeviceNet Linking Device
IMPORTANT
Assembly Objects and Connections
Three Assembly Object instances are accessible from EtherNet/IP: input, output and status. The input and output assemblies are linked to the input and output tags created in RSLogix 5000 software. The status assembly provides current status information about the linking device.
With a specific 1788-EN2DN profile, I/O tags are mapped without an offset. For example, RSLogix 5000 version13 input tag EN2DN:I:Data[0] corresponds to word 0 of the RSNetWorx for DeviceNet software input mapping table.
The assembly instances associated with these three assemblies are listed in the following tables.
Input Assembly
The input assembly contains a 32-bit status register followed by the data in the linking device’s input data table.
Input Assembly Format
DINT
Size in
Description RSLogix 5000 software
DINTs
Offset
0 1 Status register EN2DN:I.Data[0] EN2DN:I.Status Register
1Up to
Input data EN2DN:I.Data[1 - 124] EN2DN:I.Data[0 …123]
123
versio n 12 examp le tags
RSLogix 5000 software version 13 or later example tags
The input data format and content is determined by the DeviceNet scanner configuration. The data appears in the table as it is mapped from the DeviceNet input connections. The input data in the assembly is 124 DINTs long ; however, only the size of the input data table will be used. The remaining space will be filled with the value 0 (zero).
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 37
Ethernet-to-DeviceNet Linking Device 37
IMPORTANT
Output Assembly
The output assembly contains a 32-bit command register followed by the data in the linking device’s output data table.
Output Assembly Format
DINT
Size in
Offset
DINTs
01 Command
1 Up to 123 Output data EN2DN:O.Data[1 - 123] EN2DN:O.Data[0 …23]
Description RSLogix 5000 software
version 12 example tags
EN2DN:O.Data[0] EN2DN:O.Command Register
registe r
RSLogix 5000 software version 13 or later example tags
The output data format and content is determined by the DeviceNet scanner configuration. The data appears in the table as it is mapped to the DeviceNet output connections. The output data in the assembly is 123 DINT long ; however, only the size of the output data table will be used. The remaining space will be ignored.
Status Assembly
The status assembly is a collection of status and diagnostic information for the linking device’s DeviceNet network interface. The information in the assembly is updated once a second.
All information in the status assembly is stored in little endian format. The least significant byte of multi-byte values is stored first.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 38
38 Ethernet-to-DeviceNet Linking Device
Status Assembly Format
Byte Offset
0 4 UDINT Scan Counter The number of DeviceNet I/O scans
4864-bit
12 8 64-bit
20 8 64-bit
28 8 64-bit
36 4 ASCII[4] Status Display Mimics a 4-character a lpha-numeric
40 1 USINT Scanner Address The DeviceNet MAC ID of the linking
41 1 USINT Sc anner Status The current status of the DeviceNet
Size in Bytes
Data Type
Bitstring
Bitstring
Bitstring
Bitstring
Name (RSLogix 5000 software version 13 or later)
Device Failure Register Indicates which DeviceNet slaves are
Auto Verify Failure Register
Device Idle Register Indicates which DeviceNet slaves are
Active Node Register Indicates which DeviceNet nodes are
Description
that have taken place since power was applied to the linking device.
faulted. Each bit represents the status of the slave at the corresponding MAC ID.
Indicates which DeviceNet slaves are the incorrect device type. Each bit represents the status of the slave at the corresponding MAC ID.
in Idle mode. Each bit represents the status of t he slave at the corresponding MAC ID.
configured in the 1788-EN2DN’s scan list. Each bit represents the status of the slave at the corresponding MAC ID.
display. If there are no faults, the display shows the linking device’s MAC ID and its Run/Idle status.
If there are faults, the display will scroll through the MAC IDs of the faulted nodes and display the error code associated with each.
device.
scanner.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 39
Status Assembly Format (cont.)
Ethernet-to-DeviceNet Linking Device 39
Byte Offset
42 1 USINT
43 1 USINT
44 20 USINT[20] N/A
64 64 USINT[64] Device Status The current status of each DeviceNet
Size in Bytes
Data Type
Name (RSLogix 5000 software version 13 or later)
Scrolling Device Address and Status
Description
The scrolling address and status fields scroll through the address and status of all DeviceNet slaves that are faulted. This scrolling includes the linking device scanner itself.
If there are no faulted nodes, both the scrolling address and status are set to
0. The scrolling fields change once a
second.
slave node. Each array element is the status of the node at the corresponding MAC ID.
If a node is not configured in the linking device scan list, the status value will be set to 0.
The linking device scanner status appears at the entry associated with the linking device MAC ID.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 40
40 Ethernet-to-DeviceNet Linking Device

Understanding Status Indicators

A group of status indicators on the front panel of the linking device shows the current status of the linking device and the network interfaces, as shown in the following figures.
The following tables provide information on status indicator states.
For Information about the See Page
I/O status indicator 42
DeviceNet Network status indicators 42
Module status indicators 43
Ethernet Link status indicators 43
EtherNet Network status indicators 43
CIP Link status indicators 44
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 41
Status Indicators
TIP

I/O Status Indicator

DeviceNet Network Status Indicator
CIP Link Status Indicator
Ethernet Link Status Indicator
Module Status Indicator
EtherNet Network Status Indicator
31441-M
Ethernet-to-DeviceNet Linking Device 41
I/O Status Indicator
If the I/O status indicator is flashing red and green for an extended period of time, count the number of red and green flashes and call Rockwell Automation technical support. Refer to the back cover of this publication for details on contacting technical support.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 42
42 Ethernet-to-DeviceNet Linking Device
I/O Status Indicator States
Indicator Status Description
Flashing green Idle Module is in Idle mode.
Solid green Running Module is in Run mode.
Solid orange Hardware Initialization The status indicator will be in this state immediately
Flashing red/green Error A fault has been detected.
Off No I/O No DeviceNet I/O configured.
after power is applied.

DeviceNet Network Status Indicator

DeviceNet Network Status Indicator States
Indicator Status Description
Solid green Online and
Flashing green Online, no
Solid red DeviceNet interface
Flashing red Connection time-out A connection with at least one slave device has
communicating
communication
fault
The linking device is on the DeviceNet network and communicating with at least one device.
The linking device is on the DeviceNet network and is not currently communicating with any devices.
A major fault in the DeviceNet interface has been detected. Possible causes include Bus-off or duplicate MAC ID.
timed out.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 43
Ethernet-to-DeviceNet Linking Device 43

Module Status Indicator

DeviceNet Module Status Indicator States
Indicator Status Description
Flashing green Standby or not
Solid green Normal Normal operation.
Solid red Unrecoverable major
Flashing red Recoverable minor
configured
fault
fault
The module has not been configured and is currently using default values.
This status indicator state is also used to indicate that the module is in a standby state. This could occur during initialization or DeviceNet autobaud.
A fault the requires user intervention has been detected. Correct the problem and reset the linking device.
A fault that can be corrected and does not require a linking device reset has been detected.

Ethernet Link Status Indicator

The Ethernet Link status indicator indicates that the module is connected to an Ethernet network. The status indicator displays green if the link is active. The status indicator will flash when Ethernet packets are received and transmitted.

Ethernet Network Status Indicators

Ethernet Network Status Indicator States
Indicator Status Descrip tion
Off No IP address The module has no IP address assigned.
Solid green Network OK and
Flashing green Network OK There are no active connections.
communicating
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
There is at least one EtherNet/IP connection.
Page 44
44 Ethernet-to-DeviceNet Linking Device
Ethernet Network Status Indicator States
Indicator Status Description
Solid red Address conflict The module’s IP address is already in use by
Flashing Red Connection time-out One or more of the connections in which this
Red,Green alternate flashing
Self test A self-test of the module is in progress.
another module.
module is the target has timed out. This state is only left if all timed out connections are re-established or if the module is reset.

CIP Link Status Indicator

The CIP Link status indicator indicates bridged and gateway activity between EtherNet/IP and DeviceNet networks. The status indicator will flash green when a CIP message is bridged from EtherNet/IP to DeviceNet networks. The status indicator will be solid green if an EtherNet/IP I/O connection is active.

Using Diagnostic Web Pages

Status

The Status page displays the linking device identification information, current status, and IP configuration. The module status is updated approximately every
2.5 seconds.

Active Nodes

The Active Nodes page indicates which DeviceNet nodes are currently configured as slaves to the linking device’s DeviceNet scanner. Each node that is configured as a slave will be displayed with ‘Active’ next to the node’s MAC ID.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 45
Ethernet-to-DeviceNet Linking Device 45

Idle Nodes

The Idle Nodes page indicates which DeviceNet nodes are currently in the Idle state. If a node is Idle, the page will display ‘Idle’ next to the node’s MAC ID. Note that only nodes configured as slaves to the linking device and the linking device itself are updated on this page.

Faulted Nodes

The Faulted Nodes page indicates which DeviceNet nodes are currently in a faulted state. If a node is faulted, the page will display “Faulted” next to the node’s MAC ID. Note that only nodes configured as slaves to the linking device and the linking device itself are updated on this page.
A node is considered faulted if the linking device has lost communication or is unable to establish communications with the node. The actual problem can be determined by viewing the Node Status web page.

Invalid Nodes

The Invalid Nodes page indicates which DeviceNet nodes are not the correct device type. If a node’s device type is different than that configured in the scan list, the page will display ‘Invalid’ next to the node’s MAC ID. Note that only nodes configured as slaves to the linking device are updated on this page.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 46
46 Ethernet-to-DeviceNet Linking Device

Node Status

The Node Status page displays the current status of all DeviceNet nodes that are configured as slaves to the linking device and the linking device itself. The status of each node is displayed next to the node’s MAC ID. Note that only nodes configured as slaves to the linking device and the linking device itself are updated on this page.
The page will display the status textually for many of the common status values. However, to save web page size, many of the status values are only displayed numerically. The table below describes the meaning of each status value.
Node Status Codes
This status code Means So you should
0OK Do nothing.
60 Duplicate MAC ID test in progress Do nothing.
70 Module failed Duplicate Node Address check Change the module address to
71 Illegal data in scan list table Reconfigure the scan list table
72 Slave device stopped communicating Inspect the field devices and
73 Device’s identity information does not match
74 Data overrun on port detected Modify your configuration and
75 No traffic detected on the network Check the network configuration.
76 No direct network traffic for module detected None. The module hears other
electronic key in scan list table entry
another available one. The node address you selected is already in use on that network.
and remove any illegal data.
verify connections.
Verify that the correct device is at this node number. Make sure that the device at the scrolling node address matches the desired electronic key (such as vendor, product code, and product type).
check for invalid data. Check network communication traffic.
network communication.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 47
Ethernet-to-DeviceNet Linking Device 47
Node Status Codes (cont.)
This status code Means So you should
77 Data size expected by the device does not
78 Slave device in scan list table does not exist Add the device to the network, or
79 Module has failed to transmit a message Make sure that your module is
80 Module is in IDLE mode Put controller in RUN mode.
81 Module is in FAULT mode Check Module Command Register
82 Error detected in sequence of fragmented I/O
83 Slave device is returning error responses when
84 Module is initializing the DeviceNet network None. This code clears itself once
85 Data size was incorrect for this device at
86 Device is producing zero length data (idle
87 The primary owner has not allocated the slave Put the primary owner on line.
match scan list entry
messages from device
module attempts to communicate with it
runtime
state) while module is in Run mode
Reconfigure your module for the correct transmit and receive data sizes.
delete the scan list entry for that device.
connected to a valid network. Check for disconnected cables.
Enable RUN bit in module command register.
for fault bit set.
Check scan list table entry for slave device to make sure that input and output data lengths are correct. Check slave device configuration.
Check accuracy of scan list table entry. Check slave device configuration. Slave device may be in another master’s scan list. Reboot slave device.
module attempts to initialize all slave devices on the network.
Slave device is transmitting incorrect length data. Try replacing the device.
Check device configuration and slave node s tatus.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 48
48 Ethernet-to-DeviceNet Linking Device
Node Status Codes (cont.)
This status code Means So you should
88 The connection choices (such as polled or
89 Slave device initialization using Auto Device
90 User has disabled communication port Check Module Command Register
91 Bus-off condition detected on comm port.
92 No network power detected on
95 Application nonvolatile memory update in
96 COMM port in Test mode Do nothing.
97 Module operation halted by user command Check Module Command Register
98 Gen eral firmware e rror Replac e module.
99 System failure Replace module.
strobed) between the primary connection and the shared input only connection do not match
Replacement parameters failed
Module is detecting communication errors
communication port
progress
Reconfigure the shared input only connection's choices to be the same as, or a subset of, the primary connection's choice(s).
Put the slave device into configurable mode.
Check the slave's EDS file, if the slave is configured offline.
Check to see if the slave device has been replaced with an incompatible device.
for DISABLE bit set.
Check DeviceNet connections and physical media integrity. Check system for failed slave devices or other possible sources of network interference.
Provide network power. Make sure that module drop cable is providing network power to module comm port.
Do nothing. Do not disconnect the module while application nonvolatile memory update is in progress. You will lose any existing data in the module’s memory.
for HALT bit set.
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 49
Ethernet-to-DeviceNet Linking Device 49
100.2 mm
4.3 in.
52.7 mm 2 in.
10 mm
0.425 in.
63 mm
2.4 in.
68.2 mm
2.69 in.
31444-M

IP Configuration

The IP Configuration web page is used to change the IP configuration of the linking device.

Security

Use the Security web page to change the security password.

Dimensions

Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 50
50 Ethernet-to-DeviceNet Linking Device
1
23
4
5
31422-M
31423-M

DeviceNet Connector Pinouts

DeviceNet Pinouts
Pin Signal
1V-
2CAN_L
3Shield
4CAN_H
5V+

EtherNet/IP RJ45 Connector Pinouts

EtherNet/IP Pinouts
Pin Signal
1TD+
2TD-
3RD+
4Termination
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
5Termination
Page 51
Ethernet-to-DeviceNet Linking Device 51
EtherNet/IP Pinouts
Pin Signal
6RD-
7Termination
8Termination

Specifications

Technical Specifications - 1788-EN2DN
Attribute 1788-EN2DN
Enclosure type rating None (open style)
Supply power and current rating DeviceNet network:
Operating voltage: 12…30V DC (24 V DC nom)
100 mA at 24V DC, Class 2
Input power Operating Voltage: 12…30V DC (24V DC
nom) 300 mA at 24V DC, Class 2
Isolation voltage 50V (continuous), basic insulation type
Torque 0.5… 0.8 N•m (5…7 lb•in)
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 52
52 Ethernet-to-DeviceNet Linking Device
Technical Specifications - 1788-EN2DN
Attribute 1788-EN2DN
Wire size DeviceNet connections:
See appropriate system-level installation manual
Ethernet network connections: RJ45 connector according to IEC 60603-7, 2
or 4 pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702
Wirin g categor y
DC Power connections:
0.2… 3.3 mm stranded copper wire rated at 75 °C (167 °F), or greater, 1.2 mm (3/64 in.) insulation max
(1)
2 - on power ports
(24…12 AWG) solid or
2 - on communication ports
North American temp code T4
IEC temp code T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
.
Environmental Specifications - 1788-EN2DN
Attribute 1788-EN2DN
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shoc k)
0…60 °C (32…140 °F)
-40…85 °C (-40…185 °F)
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 53
Ethernet-to-DeviceNet Linking Device 53
Environmental Specifications - 1788-EN2DN
Attribute 1788-EN2DN
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibrat ion
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
ESD immunity
IEC 61000-4-2
Radiated RF immunity
IEC 61000-4-3
EFT/B immunity
IEC 61000-4-4
Surge transient immunity
IEC 61000-4-5
Conducted RF immunity
IEC 61000-4-6
5…95% noncondensing
5 g @ 10…500 Hz
30 g
50 g
6 kV contact discharges 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
±2 kV at 5 kHz on power ports ±2 kV at 5 kHz on communication ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±2 kV line-earth(CM) on communication ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 54
54 Ethernet-to-DeviceNet Linking Device
Certifications - 1788-EN2DN
Certification (when product is marked)
c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D
CE European Union 2004/108/EC EMC Directive,
C-Tick Australian Radiocommunications Act,
Ex Eu ropean Union 94/9/EC ATEX Di rective,
ODVA ODVA conformance tested to DeviceNet
EtherNet/IP ODVA conformance tested to EtherNet/IP
KC Korean Registration of Broadcasting and
(1) See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification
details.
(1)
1788-EN2DN
Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
compliant with:
EN 61326-1; Meas./Control/Lab.,
Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers
(Clau se 8, Zone A & B)
compliant with:
AS/NZS CISPR 11; Industrial Emissions
compliant with:
EN 60079-15; Potentially Explosive
Atmospheres, Protection “n”
EN 60079-0; General Requirements
II 3 G Ex nA nL IIC T4 X
specifications
specifications
Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 55
Ethernet-to-DeviceNet Linking Device 55

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication
ENET-UM001
DeviceNet Network Configuration User Manual, publication DNET-UM004
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website,
http://www.ab.com
You can view or download publications at
http://www.rockwellautomation.com/literature/
technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Provides information about how to use EtherNet/IP modules with various Logix5000 controllers.
Describes how to use DeviceNet modules with your Logix5000 controller and communicate with various devices on the DeviceNet network.
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
. To order paper copies of
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Page 56
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation Support
Rockwell Automation provides technical i nformation on the Web to assist you in using its prod ucts. At
http://www.rockwellautomation.com/support/
application notes, sample code and links to software service packs, and a MySuppor t feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/support/
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the informatio n that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufact uring facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs bette r. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
, you can find technical manuals, a knowledge base of FAQs, technical and
.
Use the Wor ldwi de Loc ator
http://www.rockwellautomation.com/support/americas/phone_en.html
local Rockwell Automation representative.
Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.
at
, available at http://www.rockwellautomation.com/literature/.
, or contact your
Allen-Bradley, Rockwell Software, Rockwell Automation, RSLinx , RSLogix, RS NetWorx, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to R ockwell Automation are property of their respective companies.
Publication 1788-IN055C-EN-P - September 2011 PN-122467
Supersedes Publication 1788-IN055B-EN-P - June 2004 Copyright © 2011 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...