Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://www.ab.com/manuals/gi) describes some important differences
between solid state equipment and hard-wired electromechanical devices.
Because of this difference, and also because of the wide variety of uses for
solid state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is
acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for
indirect or consequential damages resulting from the use or application of
this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with
any particular installation, Rockwell Automation, Inc. cannot assume
responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to
use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety
considerations.
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information about practices or circumstances
that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property
damage, or economic loss.
Identifies information that is critical for successful
application and understanding of the product.
Identifies information about practices or circumstances
that can lead to personal injury or death, property
damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
Labels may be located on or inside the drive to alert
people that dangerous voltage may be present.
Labels may be located on or inside the drive to alert
people that surfaces may be dangerous temperatures.
Summary of Changes
The information below summarizes the changes to this manual since
the last printing.
To help you find new and updated information in this release of the
manual, we have included change bars as shown to the right of this
paragraph.
Information on 1761-NET-ENI and 1761-NET-ENIW, series D, has been
added throughout the manual. The table below lists the sections that
document new features and additional or updated information on
existing features.
For this information:See
how to obtain a manual from Rockwell AutomationP-2
Series D LED descriptionpage 1-3
Ethernet Settingspage 1-6
Series D Enhancementspage 1-8
Using the RSLinx Ethernet/IP driver with series B ENIs and higherpage 3-5
Download location for ENI/ENIW Configuration Utilitypage 4-1
Download location for Com Port Redirector softwarepage 4-1
Updated examples and information on making configuration settings
using the ENI/ENIW Configuration Utility, including series D
configuration options
Series D Email Authenticationpages 4-5 and
Updated information on using the ENI/ENIW Configuration Utility over
RS-232
New information on using the ENI/ENIW Configuration Utility over
Ethernet (series D only), including using the Com Port Redirector
software
Updated information on configuration node functionspage 4-12
Configuring Email Authentication options for series D ENI/ENIWspages 4-20 to
Configuring Ethernet speed and duplex settings for series D
ENI/ENIWs
Series D Web Page Enhancementschapter 7
LED sequence at power-up for series A/B/C/Dpage 9-2
Troubleshooting using the LED indicators series A/B/C/Dpage 9-3
Series C and D Ethernet specificationspage A-1
pages 4-2 to 4-4
6-2
page 4-6
pages 4-8
4-21
page 4-22
Updated information on configuration via BOOTPAppendix B
1761-NET-ENI/ENIW performance considerationsAppendix C
1Publication 1761-UM006E-EN-P - August 2005
2 Summary of Changes
Publication 1761-UM006E-EN-P - August 2005
Product Overview
Table of Contents
Preface
Who Should Use this Manual. . . . . . . . . . . . . . . . . . . . . . . P-1
Read this preface to familiarize yourself with the rest of the manual. It
provides information concerning:
• who should use this manual
• the purpose of this manual
• related documentation
• conventions used in this manual
• Rockwell Automation support
Who Should Use this
Manual
Purpose of this Manual
Use this manual if you are responsible for designing, installing,
programming, or troubleshooting control systems that use
Allen-Bradley Controllers on Ethernet.
You should have a basic understanding of Allen-Bradley
programmable controllers and Ethernet networking. You should
understand programmable controllers and be able to interpret the
ladder logic instructions required to control your application. If you
do not, contact your local Allen-Bradley representative for information
on available training courses before using this product.
This manual is a reference guide for the Ethernet Interface (ENI) and
Web-enabled Ethernet Interface (ENIW). It describes the procedures
you use to install and configure the ENI and ENIW.
1Publication 1761-UM006E-EN-P - August 2005
Preface 2
Related Documentation
The following documents contain additional information concerning
Rockwell Automation products. To obtain a copy, contact your local
Rockwell Automation office or distributor.
ForRead this DocumentDocument Number
Instructions on installing a 1761-NET-ENI or 1761-NET-ENIW Interface
Converter.
Information on DF1 open protocol.DF1 Protocol and Command Set
In-depth information on designing, implementing, and maintaining an
industrial control system using EtherNet/IP (Ethernet Industrial Protocol)
In-depth information on grounding and wiring Allen-Bradley
programmable controllers
A description of important differences between solid-state
programmable controller products and hard-wired electromechanical
devices
An article on wire sizes and types for grounding electrical equipmentNational Electrical Code - Published by the National Fire
A glossary of industrial automation terms and abbreviationsAllen-Bradley Industrial Automation
Ethernet Interface Installation
Instructions
Reference Manual
EtherNet/IP Media Planning and
Installation Manual
Allen-Bradley Programmable
Controller Grounding and Wiring
Guidelines
Application Considerations for
Solid-State Controls
Protection Association of Boston, MA.
Glossary
1761-IN007
1770-6.5.16
ENET-IN001
1770-4.1
SGI-1.1
AG-7.1
If you would like a manual, you can:
• download a free electronic version from the internet at
www.rockwellautomation.com/literature.
• purchase a printed manual by contacting your local
Allen-Bradley distributor or Rockwell Automation sales office.
Common Techniques Used
in this Manual
Publication 1761-UM006E-EN-P - August 2005
The following conventions are used throughout this manual:
• Bulleted lists such as this one provide information, not
procedural steps.
• Numbered lists provide sequential steps or hierarchical
information.
• Italic type is used for emphasis.
• ENI/ENIW is used when information and instructions are
applicable to both the 1761-NET-ENI and 1761-NET-ENIW. In
cases where information applies to only one type of interface,
the appropriate model and series is identified.
Preface 3
Your Questions or
Comments on this Manual
If you find a problem with this manual, or you have any suggestions
for how this manual could be made more useful to you, please
contact us at the address below:
Rockwell Automation
Automation Control and Information Group
Technical Communication, Dept. A602V
P.O. Box 2086
Milwaukee, WI 53201-2086
or visit our internet page at:
http://www.rockwellautomation.com
Publication 1761-UM006E-EN-P - August 2005
Preface 4
Publication 1761-UM006E-EN-P - August 2005
Chapter
1
Product Overview
This chapter gives an overview of the Ethernet Network Interface. The
following topics are covered:
• EtherNet/IP Connectivity
• Hardware Features
• Operating Modes
• Device Compatibility
• Enhancements by Series
• Ethernet Networks
• Web-Server Functionality
EtherNet/IP Connectivity
The 1761-NET-ENI and 1761-NET-ENIW provide EtherNet/IP
connectivity for all MicroLogix controllers, CompactLogix controllers,
and other DF1 full-duplex devices. The Ethernet Network Interface,
ENI or ENIW, allows you to easily connect non-Ethernet controllers
onto new or existing Ethernet networks and upload/download
programs, communicate between controllers, and generate email
messages via SMTP (simple mail transport protocol).
EtherNet/IP is an industry standard open protocol which provides
inter-device compatibility. You can exchange information with other
Allen-Bradley Ethernet controllers (SLC, PLC, and ControlLogix) in a
peer-to-peer relationship, so you do not need any master-type device.
The ENI and ENIW also support an SMTP mail service that allows an
existing controller to send email messages to any destination
connected to the network. The email can be used to initiate the
transmission of data or status information.
1Publication 1761-UM006E-EN-P - August 2005
1-2 Product Overview
Hardware Features
Ethernet Port
Series A/B: 10-Base-T
Series C/D: 10/100-Base-T
IP Address
Write-On Area
Product Drawing
RS-232
Mini-DIN Port
ETHERNET
INTERFACE
CATFRN
1761-NET-ENI2.20
ENI*B22001020001FAC. xx
LISTED IND.CONT.EQ. FOR HAZ.
LOC. A196
R
CUS
OPERATING TEMPERATURE CODE T3C
CLASS I, GROUPS A,B,C, AND D, DIV 2
ETHERNET ADDRESS
FF-FF-FF-FF-FF-FF
EXTERNAL POWER REQUIREMENTS
24 V dc +10/-15% AT 100 mA
N.E.C. CLASS 2
USE EXTERNAL DC SOURCE
FOR CLASS I DIVISION 2
APPLICATIONS. SEE
INSTALLATION INSTRUCTIONS
MADE IN U.S.A.
24VDC
NEUT
DC
SER
B
N223
GND
CHS
LED Indicators
The ENI and ENIW have five LED indicators:
Ethernet Hardware
Address
Series A/B
FAULT
LINK
Ethernet TX/RX
RS-232 TX/RX
POWER
Table 1.1 Series A/B Descriptions
LEDDescriptionFunctionColor
RS-232
TX/RX
RS-232 data
transmission indicator
flashes when the RS-232 port is
transmitting or receiving data
green
POWERmodule powerlit when module is poweredgreen
LINKEthernet link statuslit when there is a valid physical
green
Ethernet connection
Ethernet
TX/RX
Ethernet data
transmission indicator
flashes when the Ethernet port is
transmitting or receiving data
green
indicates Ethernet network traffic to
and from the ENI/ENIW
FAULTfault condition indicator lit when a fault condition is presentred or
flashing
red
Publication 1761-UM006E-EN-P - August 2005
Series C
FAULT
100
RS-232 TX/RX
POWER
Table 1.2 Series C Descriptions
Product Overview 1-3
10
LEDDescriptionFunctionColor
RS-232
TX/RX
RS-232 data
transmission indicator
RS-232 port is transmitting or receiving
data
flashing
green
no RS-232 trafficoff
POWERmodule powermodule is poweredgreen
1010-Base-T Ethernet
link status and data
transmission indicator
No link or continuous data activityoff
10-Base-T Half Duplex; Link good
amber
however no data activity
10-Base-T Half Duplex; Link good with
sporadic data activity
(1)
10-Base- T Full Duplex; Link good
flashing
amber
green
however no data activity
10-Base-T Full Duplex; Link good with
sporadic data activity
100 100-Base-T Ethernet
link status and data
transmission indicator
No link or continuous data activityoff
100-Base-T Half duplex; Link good
however no data activity
100-Base-T Half Duplex; Link good
with sporadic data activity
100-Base-T Full Duplex; Link good
(1)
(1)
flashing
green
amber
flashing
amber
green
however no data activity
100-Base-T Full Duplex; Link good with
sporadic data activity
(1)
flashing
green
FAULTfault condition
lit when a fault condition is presentred or
indicator
(1) Any Ethernet network activity; not necessarily to or from the ENI/ENIW.
Publication 1761-UM006E-EN-P - August 2005
flashing red
1-4 Product Overview
Series D
FAULT
LINK
Ethernet TX/RX
RS-232 TX/RX
POWER
Table 1.3 Series D Descriptions
LEDDescriptionFunctionColor
RS-232
RS-232 data
transmission indicator
RS-232 port is transmitting or
receiving data
flashing green
TX/RX
no RS-232 trafficoff
POWERmodule powermodule is poweredgreen
LINK
Ethernet link status and
10-Base-T or
100-Base-T indicator
No linkoff
10-Base-T linkamber
100-Base-T linkgreen
Ethernet activity status
Ethernet
TX/RX
and Half Duplex or Full
Duplex status
FAULTfault condition
indicator
(1) Any Ethernet network activity; not necessarily to or from the ENI/ENIW.
No activityoff
Half Duplex activity
Full Duplex activity
(1)
(1)
lit when a fault condition is
present
flashing amber
flashing green
red or flashing
red
After out-of-box power-up, the most common reason for a flashing
red fault LED is because an IP address has not yet been assigned via
BOOTP. Either set up a BOOTP server to assign an IP address or
modify the ENI/ENIW configuration to use a specific IP address or to
obtain an IP address via a DHCP server.
Publication 1761-UM006E-EN-P - August 2005
For more detailed information on LED operation, see Chapter 9,
Troubleshooting.
Product Overview 1-5
IMPORTANT
The IP addresses in any of the examples in this
manual were arbitrarily assigned and should only be
used on an isolated Ethernet network. Contact your
system administrator for unique IP addresses if you
are connecting your Ethernet devices to your
employer’s Ethernet network.
Default Settings
The ENI/ENIW has the following default settings:
Table 1.4 RS-232 Settings
SettingDefaultOther Options
Baud RateAutobaudsee table 4.2
Handshaking (hardware, software)nonenone
Data Bits8none
Stop Bits1none
Paritynonenone
Table 1.5 DF1 Settings
SettingDefaultOther Options
Duplicate Message DetectionEnablednone
Error DetectionAuto-detect (for
Autobaud)
Embedded Response Operation
DLE ACK Timeout1 secondnone
DLE NAK Receive3 NAK retriesnone
DLE ENQ for Response3 ENQs retriesnone
DF1 Node AddressDon’t Care
(1) Connected controllers should be configured for Embedded Responses Disabled or Auto-detect.
Disabled
(1)
Auto-detect when
Autobaud is true,
otherwise CRC
none
Publication 1761-UM006E-EN-P - August 2005
1-6 Product Overview
Table 1.6 Ethernet Settings
SettingDefaultOther Options
Ethernet Speed/Duplex
(1)
10 Mbps half-duplex
(series A, B)
Auto Negotiate (series C, D)
Factory Value - Read Only
(see the nameplate on the
Factory Value
unit)
(1) Series D only.
(2) See page 4-19.
(3) Changes to the Baud Rate take effect when the ENI/ENIW power is cycled, or the configuration is saved to
flash.
(4) TThe ENI/ENIW address, 192.168.1.254 will be replaced by the IP address assigned to the ENI/ENIW. For
example, the string may be ENI191.225.181.52@eni1761.org. If the ENI/ENIW does not have an assigned IP
address, the string will be read as ENI192.168.1.254@eni1761.org for the series D or ENI0.0.0.0@eni1761.org
for series A, B, or C.
(5) See page 4-17 for Subnet Mask auto-detect mode details.
(6) Series C and higher.
Publication 1761-UM006E-EN-P - August 2005
Product Overview 1-7
Operating Modes
Device Compatibility
Messaging
When the ENI/ENIW is connected to a programmable controller (and
connected to an Ethernet network), the controller can be accessed
from other devices on Ethernet, or initiate communications to other
EtherNet/IP devices.
Email
The ENI/ENIW also support SMTP mail service, which allows a
controller to send email messages to any email address on the
network. The email can be used to initiate the transmission of data or
status information.
The ENI/ENIW are compatible with the following devices and
applications:
• All MicroLogix, SLC, PLC-5, CompactLogix, FlexLogix, and
ControlLogix controllers, which support DF1 Full-Duplex on an
available RS-232 port
• Personal Computers using the RSLinx (V2.30.00 and higher) DF1
Full-Duplex Driver
• Other DF1 Full-Duplex compliant products that have at least one
RS-232 port, for example, operator interface devices
• RSLinx (V2.31.00 and higher) Ethernet Driver
Series B Enhancements
The 1761-NET-ENI series B features the following enhancements:
• elimination of the need for two ENIs in a CompactLogix,
FlexLogix, or ControlLogix system using RSLogix 5000
• ability to use Dynamic Host Configuration Protocol (DHCP)
• two new BOOTP options
The 1761-NET-ENIW has the same features as the 1761-NET-ENI, but
includes web-serving capabilities as discussed on page 1-9.
Publication 1761-UM006E-EN-P - August 2005
1-8 Product Overview
Series C Enhancements
Series D Enhancements
The 1761-NET-ENI/ENIW series C features the following
enhancements:
• 10/100-Base-T Ethernet port that auto-negotiates between
10 Megabits per second and 100 Megabits per second, either
half-duplex or full-duplex.
• increased temperature range up to 60°C (140°F)
• increased messaging performance
The ENI/ENIW series D features the following enhancements:
• Ability to configure the ENI/ENIW over Ethernet
• Email user authentication for open mail servers
• Ability to force 10 Mbps or 100 Mbps and half-duplex or
full-duplex Ethernet configuration
• Diagnostic web-page for Ethernet connections in use
• Revised web-page formats for ENIW
Ethernet Networks
Basic Ethernet Topology
The ENI/ENIW Ethernet connectors conform to ISO/IEC 8802-3 STD
802.3 and utilizes 10/100 Base-T media. Connections are made directly
from the ENI/ENIW to an Ethernet switch. The network setup is
simple and cost effective. Typical network topology is pictured below.
Ethernet
Switch
to PC Ethernet Card or
other Ethernet Device
RJ45 connectors on
both ends of cable
(10/100 Base-T)
to ENI or ENIW
Publication 1761-UM006E-EN-P - August 2005
Product Overview 1-9
Web Server Functionality
IMPORTANT
The ENIW enhances operation with web server functionality, enabling
it to:
• display 40 data table values on 4 standard Data View web pages
consisting of 7 integer and 3 floating-point values on each page,
• display 10 user-configurable data description strings on each
Data View web page,
• display a diagnostic page with status and IP Address of active
Ethernet connections (series D only),
• password protect writable data files to prevent unauthorized
modification, and
• provide 10 user-configurable web page links.
The ENI/ENIW provides a 10/100 Base-T, RJ45
Ethernet connector which connects to standard
Ethernet hubs and switches via an 8-wire twisted
pair straight-through cable. To access other Ethernet
mediums, use 10/100 Base-T media converters or
Ethernet switches that can be connected together via
fiber, thin-wire, or thick-wire coaxial cables, or any
other physical media commercially available with
Ethernet switches. See page 2-6 for more cable
information.
You can access information about the ENI/ENIW via your web
browser. Simply enter it’s TCP/IP address into the address field of
your browser.
See Chapter 7 for details on using the ENIW’s web server capabilities.
Publication 1761-UM006E-EN-P - August 2005
1-10 Product Overview
Publication 1761-UM006E-EN-P - August 2005
Chapter
Installation and Wiring
This chapter covers installation and wiring for the ENI/ENIW. It is
divided into the following sections:
• European Communities (EC) Directive Compliance
• Safety Considerations
• Mounting
• External Power Supply Wiring
• ENI/ENIW Port Identification
• Ethernet Connections
• RS-232 Port Connections
2
European Communities (EC)
Directive Compliance
This product has the CE mark. It is approved for installation within the
European Union and EEA regions. It has been designed and tested to
meet the following directives.
EMC Directive
This product is tested to meet the Council Directive 89/336/EC
Electromagnetic Compatibility (EMC) by applying the following
standards, in whole or in part, documented in a technical construction
file:
• EN 50081-2 EMC — Generic Emission Standard, Part 2 —
Industrial Environment
• EN 50082-2 EMC — Generic Immunity Standard, Part 2 —
Industrial Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low
Voltage, by applying the safety requirements of EN 61131-2
Programmable Controllers, Part 2 - Equipment Requirements and
1Publication 1761-UM006E-EN-P - August 2005
2-2 Installation and Wiring
Tests. For specific information required by EN 61131-2, see the
appropriate sections in this publication, as well as the Allen-Bradley
publication Industrial Automation Wiring and Grounding Guidelines
For Noise Immunity, publication 1770-4.1.
Open style devices must be provided with environmental and safety
protection by proper mounting in enclosures designed for specific
application conditions. See NEMA Standards publication 250 and IEC
publication 529, as applicable, for explanations of the degrees of
protection provided by different types of enclosure.
Safety Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, D, or non-hazardous locations only. The following WARNING
statement applies to use in hazardous locations.
WARNING
Explosion Hazard
• Substitution of components may impair suitability
for Class I, Division 2.
• Do not replace components or disconnect
equipment unless power has been switched off
and the area is known to be non-hazardous.
• Do not connect or disconnect connectors or
operate switches while circuit is live unless the
area is known to be non-hazardous.
• This product must be installed in an enclosure.
All cables connected to the product must remain
in the enclosure or be protected by conduit or
other means.
• The ENI/ENIW must be operated using the
external power source. The DC power source
switch must be in the EXTERNAL position.
• All wiring must comply with N.E.C. article
501-4(b).
Publication 1761-UM006E-EN-P - August 2005
Use only the following communication cables and replacement
connectors in Class I Division 2 Hazardous Locations.
Environment ClassificationCommunication Cable and Connectors
Class I, Division 2 Hazardous
Environment
1761-CBL-PM02 Series C 2707-NC8 Series B
1761-CBL-HM02 Series C 2707-NC9 Series B
1761-CBL-AM00 Series C 2707-NC10 Series B
1761-CBL-AP00 Series C2707-NC11 Series B
External Power Supply
Wiring
WARNING
Installation and Wiring 2-3
EXPLOSION HAZARD
In Class I Division 2 applications, an external, Class 2
power supply must be used. The DC Power Source
selector switch on the ENI/ENIW must be set to
EXTERNAL before connecting the power supply to
the ENI/ENIW.
Mounting
IMPORTANT
• In non-hazardous locations, external power is not
required. Some devices (such as a MicroLogix
24
VDC
DC
NEUT
CHS
GND
controller) provide power to the ENI/ENIW via a
cable connected to the ENI/ENIW’s port 2. Be
sure to set the DC power source selector switch
to match your particular configuration, CABLE or
EXTERNAL.
Bottom View
• Always connect the CHS GND (chassis ground)
terminal to the nearest earth ground. This
connection must be made whether or not an
external 24V dc supply is used.
The ENI/ENIW must be mounted in the vertical position, as shown.
Horizontal mounting is not recommended due to thermal considerations. Allow 50 mm
(2 in.) of space on all sides for adequate ventilation. See page A-1 for
operating temperature specification.
protective debris strip
ETHERNET
FAULT
top
RS232
ATTENTION
TX/RX
sideside
IP
CABLE
EXTERNAL
PWR
bottom
Do not remove the protective debris strip until after
all the equipment in the panel is mounted and wiring
is complete. Once wiring is complete, remove the
protective debris strip. Failure to remove strip before
operating can cause overheating.
Publication 1761-UM006E-EN-P - August 2005
2-4 Installation and Wiring
DIN Rail Mounting
Installation
1. Mount your DIN rail.
2. Snap the DIN rail latch into the closed
position.
3. Hook the top slot over the DIN rail.
4. While pressing the unit against the rail,
snap the unit into position.
Removal
1. Place a screwdriver in the
DIN rail latch at the bottom
of the unit.
DIN
Rail
2. Holding the unit, pry
downward on the latch until
the unit is released from the
DIN rail.
Panel Mounting
DIN
Rail
Latch
Side
View
Publication 1761-UM006E-EN-P - August 2005
Temp la te
See Appendix A for panel mounting dimensions.
Installation
ATTENTION
Be careful of metal chips when drilling mounting
holes for your equipment within the enclosure or
panel. Drilled fragments that fall into the equipment
could cause damage. Do not drill holes above
mounted equipment if the protective debris strip has
been removed.
ENI/ENIW Port
Identification
1. Remove the mounting template from
the back of the installation instructions.
2. Secure the template to the mounting
surface.
3. Drill holes through the template.
4. Remove the mounting template.
5. Mount the unit.
Installation and Wiring 2-5
Mounting
Tem pl at e
Ethernet Connections
Ethernet Port (Port 1)
Write-on area for
Ethernet IP address
RS-232 Mini-DIN (Port 2)
Ethernet 8-Pin 10/100-Base-T Connector (Port 1)
The Ethernet connector is an RJ45, 10/100-Base-T connector. The
pin-out for the connector is shown below:
PinPin Name
1Tx+
2Tx-
3Rx+
4not used
5not used
6Rx-
7not used
8not used
Publication 1761-UM006E-EN-P - August 2005
2-6 Installation and Wiring
When to use straight-through and cross-over cables:
• ENI/ENIW Ethernet port to 10/100-Base-T Ethernet switch cables
utilize a straight-through pin-out (1-1, 2-2, 3-3, 6-6).
• Direct point-to-point 10/100-Base-T cables connecting the
ENI/ENIW Ethernet port directly to another ENI/ENIW Ethernet
port (or a computer 10/100-Base-T port) require a cross-over
pin-out (1-3, 2-6, 3-1, 6-2).
Ethernet Cables
Shielded and non-shielded twisted-pair 10/100-Base-T cables with
RJ45 connectors are supported. The maximum cable length between
an ENI/ENIW Ethernet port and a 10/100-Base-T port on an Ethernet
switch (without repeaters or fiber) is 100 meters (323 feet). However,
in an industrial application, the cable length should be kept to a
minimum.
With media converters or Ethernet switches, you can also connect to
the following media:
• fiber optic
• broadband
• thick-wire coaxial cable (10-Base-5)
• thin-wire coaxial cable (10-Base-2)
Maintain ENI and ENIW Cable Connections
The unshielded twisted pair (UTP) patch cable on a switch should be
labeled and treated as dedicated. Be careful when moving any cables,
as port identity may be effected. If you are using a switch and must
move the ENI/ENIW to a new port for any reason, power-cycle the
interface. The power cycle forces a new Address Resolution Protocol
(ARP) sequence which should immediately associate the ENI/ENIW’s
IP address with the port it is connected to.
To help prevent problems with network communications affected by
moving cables, discourage any field personnel from treating the ports
of a switch as “all the same”.
Publication 1761-UM006E-EN-P - August 2005
Installation and Wiring 2-7
RS-232 Port Connections
RS-232 Connector
7
6
8-pin mini-DIN
Table 2.1 RS-232 Connector Pin Assignments
PinPort 2
124V dc
2ground (GND)
3no connection
4ENI/ENIW input data, RxD
5no connection
6no connection
5
4
2
8
3
1
7ENI/ENIW output data, TxD
8ground (GND)
RS-232 Cables
Port 2 of the ENI/ENIW is an 8-pin mini-DIN RS-232 port that provides
connection to DF1 compatible RS-232 devices. The table below
describes the RS-232 compatible cables.
ENI/ENIW Connected to:Catalog NumberUse Cable
MicroLogix 1000, 1100, 1200, and
1500, Channel 0 (all series)1761-CBL-AM00
1761-CBL-HM02
SLC 5/03, SLC 5/04, or
SLC 5/05, Channel 0
MicroLogix 1500 LRP, Channel 1
CompactLogix, FlexLogix, or
ControlLogix serial ports
1761-CBL-AP00
1761-CBL-PM02
Mini DIN to Mini DIN
45 cm (17.7 in)
2m (6.5 ft.)
Mini DIN to D-Shell
45 cm (17.7 in)
2m (6.5 ft.)
See page 2-2 for the list of cables that can be used in a hazardous
environment.
Publication 1761-UM006E-EN-P - August 2005
2-8 Installation and Wiring
Publication 1761-UM006E-EN-P - August 2005
Loading...
+ 114 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.