Rockwell Automation 1761-NET-DNI User Manual

DeviceNet Interface
Catalog Number 1761-NET-DNI
User Manual

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

Summary of Changes

The information below summarizes the changes to this manual since the last revision.
Revision bars in the margin identify updated information. The following changes are included in this version of the document.
Change Page
Added note that programming over a DeviceNet network is available only with RSLogix 5/500-based controllers.
21
Added note that remote access to a DeviceNet network is available only with RSLogix 5/500-based controllers.
22
3 Publication 1761-UM005B-EN-P - October 2006
4 Summary of Changes
Publication 1761-UM005B-EN-P - October 2006
Overview
Quick Start
Operation

Table of Contents

Preface
About This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Who Should Use This Publication . . . . . . . . . . . . . . . . . . . . . 7
Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chapter 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Device Compatibility. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 2
Configure Peer-to-peer Messaging . . . . . . . . . . . . . . . . . . . . 11
Configuring Master/Slave I/O . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 3
Modes of Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
DeviceNet I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Network Configuration Software . . . . . . . . . . . . . . . . . . . . . 18
Messaging Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Programming Over the DeviceNet Network . . . . . . . . . . . . . 21
Installation and Wiring
DNI Configuration Parameters and Programming Notes
Setup, Programming, and Troubleshooting
Chapter 4
European Communities (EC) Directive Compliance . . . . . . . 23
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Network Port Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Cable Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Chapter 5
Information About DNI Series B . . . . . . . . . . . . . . . . . . . . . 27
EDS Parameters for the DNI . . . . . . . . . . . . . . . . . . . . . . . . 28
Programming Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Chapter 6
DNI Software Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Setting Up Network Configuration Software . . . . . . . . . . . . . 55
Commissioning the DNI . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Programming Over the DeviceNet Network . . . . . . . . . . . . . 59
Modifying DNI Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . 60
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Fault Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
DNI Series A DeviceNet Class Codes . . . . . . . . . . . . . . . . . . 65
DNI Series B DeviceNet Class Codes . . . . . . . . . . . . . . . . . . 66
5 Publication 1761-UM005B-EN-P - October 2006
Table of Contents 6
Application Examples
Explicit Messaging (DNI Series B Only)
Specifications
Chapter 7
MicroLogix as I/O on the DeviceNet Network . . . . . . . . . . . 69
Example DNI Configuration Parameters . . . . . . . . . . . . . . . . 70
Example Ladder Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Chapter 8
Using DF1 Protocol for Explicit Messages Over a DeviceNet
Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Routing Profile Configuration. . . . . . . . . . . . . . . . . . . . . . . . 79
Explicit Messaging Examples . . . . . . . . . . . . . . . . . . . . . . . . 80
Appendix A
Physical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
DeviceNet Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Glossary
Interface Basics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Terms and Abbreviations. . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Index
Publication 1761-UM005B-EN-P - October 2006

Preface

About This Publication

Who Should Use This Publication

Conventions

This user manual introduces the DeviceNet Interface (DNI) and explains the procedures you need to install, configure, and commission the interface.
Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use Allen-Bradley controllers on a DeviceNet network.
You should have a basic understanding of Allen-Bradley programmable controllers and DeviceNet technology. You should understand programmable controllers and be able to interpret the ladder logic instructions required to control your application. If you do not, contact your local Allen-Bradley representative for information on available training courses before using this product.
Text that is Identifies
Bold Emphasis, not used within programming text
Italic Software variables and configurable catalog numbers
courier
Example programming code, shown in a monospace font so you can identify each character and space
7 Publication 1761-UM005B-EN-P - October 2006
8 Preface

Additional Resources

Resource Description
MicroMentor, publication 1761-RM001 Information on understanding and applying micro
controllers.
AIC+ Advanced Interface Converter and DeviceNet Interface Installation Instructions, publication 1761-IN002
MicroLogix 1000 Controllers User Manual, publication 1761-UM003
MicroLogix 1500 Controllers User Manual, publication 1764-UM001
SLC 500™ Modular Hardware Style User Manual, publication 1747-UM011
PLC User Manual, publication 1785-UM001
SLC 500 and MicroLogix 1000 Instruction Set Reference Manual, publication 1747-RM001
DeviceNet Manager Software User Manual, publication 1787-UM053
1747 DeviceNet Scanner Installation Instructions, publication 1747-IN058
1747 DeviceNet Scanner User Manual, publication 1747-UM655
1771 DeviceNet Scanner Configuration Manual, publication 1771-UM118
DeviceNet Cable System Planning and Installation Manual, publication DNET-UM072
Mounting instructions for the DeviceNet Interface
Information on MicroLogix 1000 Controllers
Information on MicroLogix 1500 Controllers
Information on SLC Controllers
Information on PLC
A reference manual that contains status file data and instruction set information
Information on DeviceNet Manager
Information on 1747 DeviceNet Scanner
Information on 1771 DeviceNet Scanner
Planning and installing a DeviceNet cable system
®
Controllers
Allen-Bradley Programmable Controller Grounding and Wiring Guidelines, publication 1770-IN041
Allen-Bradley Industrial Automation Glossary, publication AG-QR071
Publication 1761-UM005B-EN-P - October 2006
In-depth information on grounding and wiring Allen-Bradley programmable controllers
A glossary of industrial automation terms and abbreviations

Overview

Chapter
1

Introduction

The DeviceNet interface is a standalone, DIN-rail or panel mounted, intelligent DeviceNet-to-DF1 protocol-conversion device that lets existing DF1 devices communicate on a DeviceNet network. The DF1 device exchanges I/O data with a Master device and originates and receives DF1 encapsulated DeviceNet messages across a DeviceNet network.
The DNI provides a single DeviceNet connection point and a single RS-232 connection. The DeviceNet port is isolated from the DNI digital logic and RS-232 port.
The primary functions of the DNI are:
Collect or receive input data from the DF1 device connected on
its RS-232 port and forward that data to a connected master on DeviceNet network.
Monitor output data received from the DeviceNet master and
write that data to the DF1 device.
Allow DF1 devices to send and receive messages across the
DeviceNet network.

Operating Modes

Device Compatibility

9 Publication 1761-UM005B-EN-P - October 2006
The DNI can be used in either or both of the following modes.
Peer-to-peer
DeviceNet slave
The DNI can be used to interconnect the following devices.
MicroLogix controllers
DF1 Full Duplex compliant products, for example: PLC-5
programmable controllers, operator interface devices, and SLC 5/03™ and higher processors
10 Overview
Publication 1761-UM005B-EN-P - October 2006
Chapter
2

Quick Start

This chapter can help you to get started using the 1761-NET-DNI DeviceNet Interface (DNI). We base the procedures here on the assumption that you have an understanding of MicroLogix products. You should understand electronic process control and be able to interpret the ladder logic instructions required to generate the electronic signals that control your application.
Because this is a start-up guide for experienced users, this chapter does not contain detailed explanations about the procedures listed. It does, however, reference other chapters in this book where you can get more information.

Configure Peer-to-peer Messaging

If you have any questions or are unfamiliar with the terms used or concepts presented in the procedural steps, always read the referenced chapters and other recommended documentation before trying to apply the information.
Follow these steps to communicate with other controllers connected to DNIs on a DeviceNet network.
1. Unpack and mount the DNI.
2. Connect the DNI to the DeviceNet network.
When power is first applied to the DNI, it resides at node 63 on the network. The DNI out-of-box configuration is defaulted to Autobaud; it synchronizes to the DeviceNet network baud rate.
3. Connect a DF1 device to the DNI.
The DF1 connection automatically enters the Autobaud mode; it synchronizes to the attached DF1 device.
4. Connect to the DNI with your network configuration tool
(software such as the DNI Configuration Utility, RSNetWorx, or DeviceNet Manager) and set the DNI to the desired node number. This is called commissioning the DNI.
See Commissioning the DNI on page 58 for more details.
11 Publication 1761-UM005B-EN-P - October 2006
12 Quick Start
IMPORTANT
If your network consists entirely of DNIs (no master is present), you must disable Autobaud on at least one DNI. It is recommended that all DNIs be manually set to a specific baud rate. This is to prevent multiple DNIs from hunting for a baud rate at power-up.
5. To exchange data with other controllers over a DeviceNet
network, configure a message instruction inside each controller’s program.
See Programming Over the DeviceNet Network on page 21 for more information.
6. To send data to a specific controller on the network, enter the
destination DNI’s DeviceNet node address into the destination parameter of a message instruction. Think of each DNI/Controller pair as one unit.
EXAMPLE
To send a message from controller A (plugged into DNI number
5) to controller B (plugged into DNI number 10), controller A must have a message instruction with a destination node address of 10.
See the application example MicroLogix as I/O on the DeviceNet Network on page 69 for an example ladder program.
Publication 1761-UM005B-EN-P - October 2006
Configuring Master/Slave
Quick Start 13
I/O
IMPORTANT
Follow these steps to configure a DNI connected to a MicroLogix 1000 controller as a slave device to a DeviceNet master.
1. Unpack and mount the DNI.
2. Connect the DNI to the DeviceNet Network.
When power is first applied to the DNI, it resides at node 63 on the network. The DNI out-of-box configuration is defaulted to Autobaud; it synchronizes to the DeviceNet network baud rate.
3. Connect to the DNI with your network configuration tool
(software such as DeviceNet Manager or RSNetWorx) and set the DNI to the desired node number. This is called node commissioning.
4. Double-click on the DNI icon to open the DNI’s EDS.
You must have the DNI’s EDS (electronic data sheet) file and bitmap file (or icon) loaded into your configuration software. See DNI Software Files on page 53 and Setting Up Network Configuration Software on page 55 for more information.
5. For DNI Series A: set DNI Mode (parameter 17) to Standby mode
(0).
For DNI Series B: set I/O Scan Enable (parameter 12) to disable (0) (default).
6. Click Save to Device.
Publication 1761-UM005B-EN-P - October 2006
14 Quick Start
To configure a MicroLogix 1000 controller as a slave device to a DeviceNet master, set the parameters as shown in the following table.
MicroLogix 1000 Controller Parameter Settings
Parameter Number Description Range Default Value For this Example,
Series A Series B
4 1 Input Size Series A: 1…16
Series B: 1…32
Not Applicable 2 Input Split Point 1…32 1 word 2 words
5 3 Input Type Bit or Integer File Integer File Integer File
6 4 Input Data File 3…254 7 7
7 5 Input Word Offset 0…254 0 90
8 6 Output Size Series A: 1…16
Series B: 1…32
9 8 Output Type Bit or Integer File Integer File Integer File
10 9 Output Data File 3…254 7 7
11 10 Output Word Offset 0…254 1 95
14 11 DF1 Device 0…3:
0: Other 1: PLC 2: SLC/ Other MicroLogix 3: MicroLogix 1000
312DNI Series A:
Data Enable DNI Series B: I/O Scan Enable (Polling Enable)
12 13 DF1 Heartbeat Series A: 2…10
13 14 Data Scan Delay
(Polling Delay)
2 15 Message Timeout 0…2500 ms 0 ms 0 ms
Not Applicable 16 DF1 Substitute Address 0…64 64 = Disabled 64 = Disabled
15 17 DF1 Autobaud Disabled (0) or Enabled
16 18 DF1 Baud Rate 0…5:
1 19 DeviceNet Autobaud Disabled (0) or Enabled
17 Not
Applicable
DNI Mode Standby (0) or
Disabled (0) or Enabled (1)
Series B: 1…10
20…3000 ms 50 ms 100 ms
(1)
0: 38,400 1: 19,200 2: 9600 3: 4800 4: 2400 5: 1200
(1)
Operational (1)
1 word 2 words
1 word 2 words
3 = MicroLogix 1000 3 = MicroLogix 1000
Disabled (0) Enabled (1)
22
Enabled (1) Enabled (1)
Series A: 2 = 9600 Series B: 1 = 19,200
Enabled (1) Enabled (1)
Operational (1) Operational (1)
ENTER
n/a
Publication 1761-UM005B-EN-P - October 2006
Quick Start 15
7. Click Modified Parameter, then OK.
8. Save to the configuration to the DNI.
In this configuration, the DNI provides two words (32 bits) of data. The data is scanned (read), starting at address N7:90 of the attached MicroLogix 1000 controller, at 100 msec intervals.
Data received (DeviceNet master output) is written to the MicroLogix 1000 controller whenever new (changed) data is detected by the DNI. Two words of data will be written to Integer file 7, starting at word 95.
IMPORTANT
You must have the following rung programmed into the MicroLogix 1000 controller:
N7:95
7
N7:90
7
At this point, the DNI is configured to be a slave on DeviceNet, but it is not part of (owned by) a DeviceNet master/scanner.
To configure your DeviceNet scanner, refer to its manual. For the 1747-SDN, refer to the SLC 500 DeviceNet Scanner user manual, publication 1747-UM655. For the 1771-SDN, refer to the PLC-5 DeviceNet Scanner user manual, publication 1771-UM118.
Publication 1761-UM005B-EN-P - October 2006
16 Quick Start
Publication 1761-UM005B-EN-P - October 2006

Operation

Chapter
3

Modes of Use

DeviceNet I/O

The DeviceNet Interface has three primary features.
DeviceNet I/O
Explicit Messaging
Programming over DeviceNet network
IMPORTANT
The DNI is capable of being owned by a master on DeviceNet. This functionality on DeviceNet is part of the I/O class of services, and allows a master device to exclusively manage (own) another device’s (a different node number) data and resources. This type of relationship is functionally the same as a PLC with remote I/O. A PLC uses the remote I/O chassis as distributed inputs and outputs. The master/slave relationship on DeviceNet is exactly the same, except it is being done over DeviceNet.
All input and output comments are referenced from the perspective of the DeviceNet Master.
The amount of data available between devices that implement I/O master/slave services is determined by the design of each device, and is not a function of DeviceNet.
The DNI on DeviceNet is capable of handling 32 I/O words of data with a DeviceNet I/O master for DNI Series A (64 for DNI Series B). This is broken up into two data images: the input image and the output image.
17 Publication 1761-UM005B-EN-P - October 2006
18 Operation

Input Image

The input image is a configurable array of 16-bit data words. The image is configurable from 1…16 data words for DNI Series A (1…32 data words for DNI Series B). The actual data that resides in the input image is delivered to the DeviceNet master by one of three mechanisms.
Polled: Where the DeviceNet Master sends a poll request with
output data and the DNI responds with its current input data.
COS (Change of State): Where the DNI detects that data has
changed within the input image and automatically sends the data to the DeviceNet Master.
Cyclic: The DNI continuously sends the input image data to the
master at a user/scanner-defined time interval, regardless of whether the data has changed.

Network Configuration Software

Output Image

The output image is a configurable array of 16-bit data words. The image is configurable from 1…16 data words for DNI Series A (1…32 data words for DNI Series B). The actual data that resides in the output image is delivered to the DNI from the master by one of two mechanisms:
Polled: Where the DeviceNet Master sends a poll request with
output data and the DNI responds with its current input data.
COS (Change Of State): Where the DeviceNet Master detects that
data has changed within its output image and automatically sends the data to the DNI.
Cyclic: The DNI continuously receives the output image data
from the master at a user/scanner-defined time interval, regardless of whether the data has changed.
All DNI I/O parameters are configured with software such as the DNI Configuration Utility, RSNetWorx, or DeviceNet Manager and stored as part of the network configuration.
Publication 1761-UM005B-EN-P - October 2006
Configuration software is covered in Setup, Programming, and Troubleshooting on page 53.
Individual settings of the DNI are covered in DNI Configuration Parameters and Programming Notes on page 27.
Operation 19

Messaging Services

The capabilities of each individual device determine what level of messaging is supported. The types of messaging supported are:
I/O Assembly Messaging (DNI responds)
PCCC encapsulated DeviceNet Messaging (peer-to-peer)
Explicit Assembly Messaging (DNI initiates, DNI Series B Only)
See Explicit Messaging (DNI Series B Only) on page 77 for more information.

I/O Assembly Messaging

Two conditions must be met to access the I/O assemblies.
Data Enable (DNI Series A) or I/O Scan Enable (DNI Series B)
must be enabled.
The DF1 Device must be servicing the Heartbeat.
See DF1 Heartbeat on page 43 for information on using the Heartbeat.
The following sections describe additional conditions based on the DNI Series.
DNI Series A
DNI Series A supports explicit messaging to the master I/O assemblies over DeviceNet at a minimal level. If the DNI is not owned by a DeviceNet master, the DNI responds to explicit messaging gets and accepts explicit messaging sets to the master I/O assembly. If the DNI is owned by a DeviceNet master, it responds to gets, but cannot accept sets. In either case, the data size must be 16 words, even if the I/O size is smaller.
See page 65 to address DNI Series A assemblies.
DNI Series B
DNI Series B provides the above described functionality, except the data size is equal to the configured I/O size. Additionally, DNI Series B can respond to explicit messages over DeviceNet to its explicit I/O assemblies whether it is owned by a DeviceNet master or not.
See page 66 to address DNI Series B assemblies.
DNI Series B can also perform get/set services with its new DeviceNet messaging capability.
See page 77 for Explicit Messaging (DNI Series B Only).
Publication 1761-UM005B-EN-P - October 2006
20 Operation

Programmable Controller Communications Commands (PCCC) DeviceNet Messaging/ DF1 (peer-to-peer)

Allen-Bradley controllers with RS-232 ports communicate via PCCC messaging. The DNI encapsulates the PCCC messages to allow PCCC messaging to operate over DeviceNet. This is an open, non-proprietary protocol that can be implemented by anyone who needs to exchange information with an Allen-Bradley controller.
The DNI is capable of receiving the DF1 protocol, and sending or receiving it over DeviceNet. This enables any existing Allen-Bradley device that is capable of DF1 communications to an Allen-Bradley controller to use the DNI to communicate over DeviceNet.
For DNI Series A, the only stipulation is that the device has to be capable of entering a destination node address (For DNI Series B, this stipulation has been removed with the addition of the DF1 Substitute Address parameter.). The DNI uses the DF1 destination node address that is embedded in the DF1 packet to determine where on DeviceNet it needs to send the information.
This DF1-to-DeviceNet capability lets you configure a peer-to-peer network. By programming standard ladder logic message instructions, with the destination address the same as the destination DNI (when not using DNI Series B address substitution), the message is routed across DeviceNet by the DNI. The following diagram illustrates the types of messaging.
Messaging Overview
Running RSLogix 500 and/or DeviceNet Manager
:
IBM Compatible
SLC Rack
Node 3
KFD
1747-SDN
5/0x
Master/Slave I/O
Peer-to-Peer Messaging
DeviceNet Network
DNI Module
Node 1
Publication 1761-UM005B-EN-P - October 2006
Node 2
Also see Explicit Messaging (DNI Series B only) on page 80 for DNI Series B.
Operation 21

Programming Over the DeviceNet Network

IMPORTANT
Programming over a DeviceNet network via the DNI is available only with RSLogix 5/500-based controllers such as PLC-5, SLC, and MicroLogix.

Local Access to a DeviceNet Network

PCCC/DF1 messaging allows programming devices to connect to a DeviceNet network, and upload/download/monitor and even edit programs if the controller attached to the destination DNI supports that functionality. Rockwell Software RSLogix 500/RSLinx (version 2 and higher) users can connect directly to the DeviceNet network using a KFD, PCD, or PCI interface.
DeviceNet
KFD
PC
Upload/Download Monitoring DNI Configuration
Cable
MicroLogix Controller
You can also use a DNI connected to the computer’s RS-232 port to upload/download to other controllers connected to DNIs on a DeviceNet network.
RS-232 Port DeviceNet Connection
RS-232 DF1
PC
Upload/Download Monitoring DNI Configuration
DeviceNet Cable
DNI Module
MicroLogix Controller
Publication 1761-UM005B-EN-P - October 2006
22 Operation

Remote Access to DeviceNet (Modems)

IMPORTANT
Remote access to a DeviceNet network via the DNI is available only with RSLogix 5/500-based controllers such as PLC-5, SLC, and MicroLogix.
If users need to dial into a DeviceNet network and have access to controllers connected to DNIs, they can plug a DNI into a modem. Now users can dial into the modem and have access to all DNI/controllers from a remote site.
Remote Access to DeviceNet
DNI Module
PC
Modem
DeviceNet Cable
MicroLogix Controller
Publication 1761-UM005B-EN-P - October 2006

Installation and Wiring

Chapter
4

European Communities (EC) Directive Compliance

This product has the CE mark and is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following additional directives.

EMC Directive

This product is tested to meet the Council Directive 89/336/EC Electromagnetic Compatibility (EMC) by applying the following standards, in whole or in part, documented in a technical construction file:
EN 50081-2 EMC — Generic Emission Standard, Part 2 —
Industrial Environment
EN 50082-2 EMC — Generic Immunity Standard, Part 2 —
Industrial Environment
This product is intended for use in an industrial environment.

Low Voltage Directive

This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 - Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the Allen-Bradley publication Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1.
This equipment is classified as open equipment and must be mounted in an enclosure during operation to provide safety protection.
23 Publication 1761-UM005B-EN-P - October 2006
24 Installation and Wiring

Safety Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only.
ATTENTION
Use only the following communication cables and replacement connectors in Class I, Division 2, Hazardous Locations.
Environment Classification Communication Cables
Class I, Division 2 Hazardous Environment 1761-CBL-PM02 Series C (or later)
Explosion Hazard
Substitution of components may impair suitability for Class I, Division 2.
Do not replace components unless power has been switched off and the area is known to be non-hazardous.
Do not disconnect connectors unless power has been switched off and the area is known to be non-hazardous.
1761-CBL-HM02 Series C (or later) 1761-CBL-AM00 Series C (or later) 1761-CBL-AP00 Series C (or later) 1761-RPL-00 DeviceNet Connector

Mounting

The DNI can be mounted in the vertical or horizontal position. There are no spacing requirements except as necessary for DIN rail latch movement.
See Physical Specifications on page 85 for operating temperature specifications.

DIN Rail Mounting

Follow these steps to mount the DNI on a DIN rail.
1. Mount your DIN rail.
2. Snap the DIN rail latch into the closed position.
3. Hook the top slot over the DIN rail.
4. While pressing the unit against the rail, snap the unit into
position.
Publication 1761-UM005B-EN-P - October 2006
Installation and Wiring 25
Side View
DIN Rail
Latch
Follow these steps to remove the DNI from the DIN rail.
1. Place a screwdriver in the DIN rail latch at the bottom of the
unit.
2. Holding the unit, pry downward on the latch until the unit is
released from the DIN rail.
Side
DIN Rail
View

Panel Mounting

Follow these steps to mount the DNI on a panel.
1. Remove the mounting template from Appendix A of this
document.
2. Secure the template to the mounting surface.
3. Drill holes through the template.
4. Remove the mounting template.
5. Mount the unit.
Mounting Template
Publication 1761-UM005B-EN-P - October 2006
26 Installation and Wiring

Network Port Wiring

DeviceNet Network

To properly design your DeviceNet network, see DeviceNet Media Design Installation Guide, publication DNET-UM072. This document provides design guidelines concerning wiring practices, connectors, grounding and power budgeting.
This publication is available from your Allen-Bradley distributor, or from the Internet at www.literature.rockwell.com.
Port Identification
NODE
DANGER
GND
V–
CAN_L
SHIELD CAN_H
V+
TX/RX
NET
MOD
DeviceNet Network
(Port 1) (Replacement connector part no. 1761-RPL-0000)
Use this write-on area to mark the DeviceNet node Address.

Cable Selection Guide

RS-232 (Port 2)
Port 2 of the DNI is an 8-pin mini-DIN RS-232 port that provides connection to DF1 compatible RS-232 devices. The table below describes the RS-232 compatible cables.
RS-232 Devices
DNI Connected to: Catalog Number Use Cable
MicroLogix (all series) 1761-CBL-AM00
1761-CBL-HM02
SLC 5/03, SLC 5/04, or SLC 5/05 Channel 0
1761-CBL-AP00 1761-CBL-PM02
PLC 5 1761-CBL-AP00
1761-CBL-PM02
Mini DIN to Mini DIN 45cm (17.7 in) 2m (6.5 ft.)
Mini DIN to D-Shell 45cm (17.7 in) 2m (6.5 ft.)
Mini DIN to D-Shell 45cm (17.7 in) 2m (6.5 ft.)
Publication 1761-UM005B-EN-P - October 2006
Chapter

DNI Configuration Parameters and Programming Notes

5

Information About DNI Series B

The following changes have been made which affect the EDS file.
The Standby/Operational parameter has been removed from the
EDS file. The operating mode is now controlled by the I/O Scan Enable parameter.
Three new parameters have been added to the EDS file. The
parameters are:
– DF1 Substitution Address - The DF1 Substitution Address
allows any DF1 device, such as the MicroView, to communicate to A-B controllers over the DeviceNet network.
– Input Split Point and Output Split Point - The split point
parameters are used to define how much data is configured as Master/Slave I/O and how much data is configured for explicit I/O assembly messaging.
ATTENTION
DNI Series A configurations are not compatible with DNI Series B. You must manually re-enter the Series A parameters into the Series B DNI. This step is required because of the enhanced functionality of DNI Series B.
TIP
27 Publication 1761-UM005B-EN-P - October 2006
DNI Series A stopped shipping in June of 1999. DNI Series B started shipping in July of 1999.
28 DNI Configuration Parameters and Programming Notes

EDS Parameters for the DNI

The following list shows the available parameters for configuring the DNI. Parameter definitions and usage information are provided in the sections following the table.
IMPORTANT
When modifying most DNI parameters, you must first disable polling (Set the Data Enable parameter to disable for DNI Series A. Set the I/O Scan Enable parameter to disable for DNI Series B). You can enable polling after setting your configuration.
For information on how to set up and modify parameters, see Setup, Programming, and Troubleshooting on page 53.
EDS Parameters for the DNI
Parameter Ty pe
I/O 4 1 Input Size Series A: 1…16
I/O Not
I/O 5 3 Input Type Bit or Integer File Integer File 33
Parameter Number Description Range Default Value For More
Series A Series B
1 word 29
Series B: 1…32
2 Input Split Point 1…32 1 word 30
Applicable
Information
I/O 6 4 Input Data File 3…254 7 33
I/O 7 5 Input Word Offset 0…254 0 34
I/O 8 6 Output Size Series A: 1…16
Series B: 1…32
I/O Not
Applicable
I/O 9 8 Output Type Bit or Integer File Integer File 38
I/O 10 9 Output Data File 3…254 7 39
I/O 11 10 Output Word Offset 0…254 1 39
I/O 14 11 DF1 Device 0…3:
I/O 3 12 DNI Series A: Data
I/O 12 13 DF1 Heartbeat Series A: 2…10
7 Output Split Point 1…32 1 word 36
0: Other 1: PLC 2: SLC/ Other MicroLogix 3: MicroLogix 1000
Disabled (0) or Enable DNI Series B: I/O Scan Enable (Polling Enable)
Enabled (1)
Series B: 1…10
1 word 35
3 = MicroLogix 1000 41
Disabled (0) 41
243
I/O 13 14 Data Scan Delay
(Polling Delay)
Publication 1761-UM005B-EN-P - October 2006
20…3000 ms 50 ms 45
DNI Configuration Parameters and Programming Notes 29
EDS Parameters for the DNI
Messaging 2 15 Message Timeout 0…2500 ms 0 ms 46
Messaging Not
Applicable
DF1 15 17 DF1 Autobaud Disabled (0) or
DF1 16 18 DF1 Baud Rate 0…5:
DeviceNet 1 19 DeviceNet Autobaud Disabled (0) or
Device 17 Not
16 DF1 Substitute
Address
DNI Mode Standby (0) or
Applicable
0…64 64 = Disabled 47
Enabled (1)
0: 38,400
1: 19,200
2: 9600
3: 4800
4: 2400
5: 1200
Enabled (1)
Operational (1)

Input Size

Input Size Parameter Definition
Parameter Ty pe
Parameter Number Description Range Default
Series ASeries B
Enabled (1) 47
Series A: 2 = 9600 Series B: 1 = 19,200
Enabled (1) 48
Operational (1) 49
48
Value
I/O 4 1 Input Size Series A: 1…16
Series B: 1…32
1
This parameter identifies the size, in words, of the data array that is read from the controller attached to the DNI’s RS-232 port.
IMPORTANT
For DNI Series B, you must also configure the Input Split Point.
See Input Split Point on page 30.
The array may contain up to 16 (16-bit) words of data for DNI Series A (32 words for DNI Series B) from a contiguous block within the attached controller.
Publication 1761-UM005B-EN-P - October 2006
30 DNI Configuration Parameters and Programming Notes
The first byte (byte 0) of the first word contains the status byte and is not available to the user.
Input Size Sample Data Array
Series A Series B
0 0 Data (8 bits) Status
1 1 Data Most Significant Byte
2 2 Data MSB Data LSB
3 3 Data MSB Data LSB
↓↓↓
14 30 Data MSB Data LSB
15 31 Data MSB Data LSB
Word Input Image
(MSB)
Data Least Significant Byte (LSB)
TIP
TIP
Byte 1 (MSB) of word 0 is available for user data.
For information on the Status Byte (byte 0), see the Status Byte section on page 50.

Input Split Point

Input Split Point Parameter Definition
Parameter Ty pe
I/O n/a 2 Input Split Point 1…32 1
IMPORTANT
Paremeter Number Description Range Default
Series A Series B
The Input Split Point parameter cannot be used with DNI Series A.
Value
Publication 1761-UM005B-EN-P - October 2006
The Input File Size within the DNI is configurable from 1…32 words. The Input Split Point defines how much data is configured as Master/Slave I/O and how much data is configured for explicit assembly messaging.
DNI Configuration Parameters and Programming Notes 31
Organization of Input Data
The following diagram describes how the Split Point parameter affects the data in the DF1 Device. The split point represents the last word of the Master data. Words above the split point are Explicit data.
Organization of Input Data
DNI Device
Explicit\ Input Assembly
Master Input Assembly
Split Point
DF1 Device
most significant word
Explicit Inputs
least significant word
most significant word
Master’s Inputs
least significant word
Higher Addresses
Input File Size
Lower Addresses
Input Split Point Example
We need 4 (3.5 data + 0.5 status) words of slave data that the master will own, and we need to configure an additional 15 words so that other DeviceNet products can read data.
Input Size = 19
Input Split Point = 4
Publication 1761-UM005B-EN-P - October 2006
32 DNI Configuration Parameters and Programming Notes
The DNI’s input image will consist of:
Word Instance ID
DNI’s Input Image
0 Master’s Slave Data and
Status
1 Master’s Slave Data 2
3 Master’s Slave Data
Split Point
4 Explicit Input Data 0x70 You can use 0x66 5 0x71 6 0x72 7 0x73 8 0x74 9 0x75 10 0x76 11 0x77 12 0x78 13 0x79 14 0x7A 15 0x7B
0x64
to access the entire configured explicit assembly.
16 0x7C 17 0x7D 18 ↓Explicit Input Data 0x7E
The minimum value allowed for the split point is 1, if the Input Size parameter is 32 (the maximum), the resulting range of explicit input words would be 0x70 to 0x8E.
See Input Assembly Data (Explicit, Split Point, and Slave) on page 67 for more information.
Publication 1761-UM005B-EN-P - October 2006

Input Type

DNI Configuration Parameters and Programming Notes 33
Parameter Ty pe
I/O 5 3 Input Type Bit or Integer File Integer File
Parameter Number Description Range Default
Series A Series B
Value
This parameter is used to identify the type of data to be read within the controller. The DNI supports data exchange with either bit or integer files.

Input Data File

Parameter Ty pe
I/O 6 4 Input Data File 3…254 7
This parameter is used to identify the data file to be read within the controller. The following table shows the files within Allen-Bradley controllers.
Parameter Number Description Range Default Value
Series A Series B
Controller Input Data Files Number Values
MicroLogix 1000 Bit 3
Integer 7
SLC/Other MicroLogix Bit 3, 10-255
Integer 7, 9-255
PLC Bit 3, 10-999
Integer 7, 9-999
TIP
The DNI can access only files 3…254.
Publication 1761-UM005B-EN-P - October 2006
34 DNI Configuration Parameters and Programming Notes

Input Word Offset

Parameter Ty pe
I/O 7 5 Input Word Offset 0…254 0
Parameter Number Description Range Default Value
Series A Series B
This parameter identifies the starting word within the input file identified by the parameter Input Data File. The value entered is the first word of data that is read from the controller attached to the DNI.
The sizes of compatible data files within Allen-Bradley controllers vary based on the DFI device selected.
Compatible Data File Sizes
Controller Input Data Files File Size
MicroLogix 1000 Bit 32 Words
Integer 105 Words
SLC/Other MicroLogix Bit 255 Words
Integer 255 Words
PLC Bit 999 Words
Integer 999 Words
TIP
IMPORTANT
The DNI can only access files 3 through 254.
You must have sufficient room in the file that you select. Make sure the Input Word Offset plus the Input Size does not exceed the boundary of the controller’s data file. For example, a MicroLogix 1000 controller has 32 words in its bit file; therefore, you could not use a Input Word Offset of 30 and a Input Size of 5 because this exceeds the file size.
Publication 1761-UM005B-EN-P - October 2006
DNI Configuration Parameters and Programming Notes 35
IMPORTANT
If you use RSNetWorx or DeviceNet Manager to configure/commission the DNI, it is up to you to select the correct values for:
Input Size
Input Split Point (DNI Series B only)
Input Type
Input Data File
Input Word Offset
Only the DNI Configuration Software Utility performs checks on the information entered.

Output Size

Parameter Ty pe
I/O 8 6 Output Size Series A: 1…16
Parameter Number Description Range Default
Series A Series B
Series B: 1…32
Value
1
IMPORTANT
For DNI Series B, you must also configure the Output Split Point. See page 36.
This parameter identifies the size, in words, of the data array that will be written to the controller attached to the DNI’s RS-232 port. The array may contain up to 16 (16-bit) words of data for DNI Series A (32 words for DNI Series B) from a contiguous block within the attached controller.
Publication 1761-UM005B-EN-P - October 2006
36 DNI Configuration Parameters and Programming Notes
The first byte (byte 0) of the first word contains the status byte and is not available to the user. A sample of the data array is shown below.
Sample Data Array
Word Output Image
Series A Series B
0 0 Data (8 bits) Status
1 1 Data Most Significant Byte
2 2 Data MSB Data LSB
3 3 Data MSB Data LSB
ØØØ Ø
14 30 Data MSB Data LSB
15 31 Data MSB Data LSB
(MSB)
Data Least Significant Byte (LSB)
TIP
TIP
Byte 1 (MSB) of word 0 is available for user data.
For information on the Status Byte (byte 0), see the Status Byte section on page 50.

Output Split Point

Parameter Ty pe
I/O n/a 7 Output Split Point 1…32 1
IMPORTANT
The Output Size within the DNI is configurable from 1…32 words. The Output Split Point defines how much data is configured as Master/Slave I/O and how much data is configured for explicit assembly messaging.
Parameter Number Description Range Default
Series A Series B
Value
The Output Split Point parameter cannot be used with DNI Series A.
Publication 1761-UM005B-EN-P - October 2006
DNI Configuration Parameters and Programming Notes 37
Organization of Output Data
The following diagram describes how the Split Point parameter affects the data in the DF1 Device. The split point represents the last word of the Master data. Words above the split point are Explicit data.
Output Data Organization
DNI Device
Explicit
Output
Assembly
Master
Output
Assembly
Split Point
DF1 Device
most significant word
Explicit Outputs
least significant word
most significant word
Master’s Outputs
least significant word
Higher
Addresses
Output
File
Size
Lower
Addresses
Output Split Point Example
We need 4 (3.5 data + 0.5 status) words of slave data that the master will own, and we need to configure an additional 15 words so that other DeviceNet products can write data.
Output Size = 19
Output Split Point = 4
Publication 1761-UM005B-EN-P - October 2006
38 DNI Configuration Parameters and Programming Notes
The DNI’s output image will consist of:
Word Instance ID
0 Master’s Slave Data and Status 0x65 1 Master’s Slave Data 2 3 Master’s Slave Data Split Point 4 Explicit Output Data 0x90 You can use 5 0x91 6 0x92 9 0x93 8 0x94 9 0x95 10 0x96 11 0x97 12 0x98 13 0x99 14 0x9A 15 0x9B 16 0x9C 17 0x9D 18 Explicit Output Data 0x9E
DNI’s Output Image
0x67 to access the entire configured explicit assembly.
The minimum value allowed for the Split Point is 1. If the Output Size is 32 (maximum), the resulting range of explicit output words would be 0x90 to 0xAE.
See Output Assembly Data (Explicit, Split Point, and Slave) on page 68 for more information.

Output Type

Parameter Ty pe
I/O 9 8 Output Type Bit or Integer File Integer File
This parameter is used to identify the type of data to be written to the controller. The DNI supports data exchange with either bit or integer files.
Parameter number Description Range Default
Series A Series B
Value
Publication 1761-UM005B-EN-P - October 2006

Output Data File

DNI Configuration Parameters and Programming Notes 39
Parameter Ty pe
I/O 10 9 Output Data File 3…254 7
Parameter Number Description Range Default
Series A Series B
Value
This parameter is used to identify the target data file where data will be written within the controller.
The sizes of compatible data files within Allen-Bradley controllers vary based on the DFI device selected.
Controller Data Files
Controller Output Data Files File Sizes
MicroLogix 1000 Bit 3
Integer 7
SLC/Other MicroLogix Bit 3, 10-255
Integer 7, 9-255
PLC Bit 3, 10-999
Integer 7, 9-999
TIP
The DNI can access only files 3…254.

Output Word Offset

Parameter Ty pe
I/O 11 10 Output Word Offset 0…254 1
This parameter identifies the starting word within the output file identified by the Output Data File parameter. The value entered is the first word of data that is written to the controller attached to the DNI.
Parameter Number Description Range Default
Series A Series B
Value
Publication 1761-UM005B-EN-P - October 2006
40 DNI Configuration Parameters and Programming Notes
The sizes of compatible data files within Allen-Bradley controllers vary based on the DFI device selected.
Controller Data Files
Controller Output Data Files File Sizes
MicroLogix 1000 Bit 32 Words
SLC/Other MicroLogix Bit 255 Words
PLC Bit 999 Words
Integer 105 Words
Integer 255 Words
Integer 999 Words
TIP
IMPORTANT
IMPORTANT
The DNI can only access files 0…254.
You must have sufficient room in the file that you select. Make sure the Output Word Offset plus the Output Size does not exceed the boundary of the data file. For example, a MicroLogix 1000 controller has 32 words in its bit file; therefore, you could not use a Output Word Offset of 30 and a Output Size of 5 because this exceeds the file size.
If you use RSNetWorx or DeviceNet Manager to configure/commission the DNI, it is up to the user to select the correct values for:
Output Size
Output Split Point (DNI Series B only)
Output Type
Output Data File
Output Word Offset
Only the DNI Configuration Software Utility performs checks on the information entered.
Publication 1761-UM005B-EN-P - October 2006

Device Type

Device Type Parameter Definition
DNI Configuration Parameters and Programming Notes 41
Parameter Typ e
I/O 14 11 DF1 Device 0…3:
Parameter Number Description Range Default
Series A Series B
0: Other 1: PLC 2: SLC/ Other MicroLogix 3: MicroLogix 1000
Value
3 = MicroLogix 1000
Select the device connected to the DNI’s RS-232 port. If you are connecting an Allen-Bradley controller as a DeviceNet I/O slave device, this selection is used by the DNI to determine the type of communication commands used to read and write data.
To achieve the best communications performance you should use these recommended combinations.
Recommended Combinations
RS-232 Device DF1 Device
Value
MicroLogix 1000 3 N (integer) 7 SLC 5/03 or higher
Other MicroLogix (MicroLogix 1500)
2 N (integer) 9
File Type File Number
TIP
If you do not want to communicate with these specific data files, RS-232 port communications throughput will suffer marginally.

I/O Scan Enable

Parameter Ty pe
I/O 3 12 DNI Series A:
This parameter enables the DNI to scan/exchange I/O data with DF1 devices. If the DNI is being used in an application that does not use this feature, disabling this parameter improves the DNI’s messaging
Parameter Number Description Range Default
Series A Series B
Disabled (0) or Data Enable DNI Series B: I/O Scan Enable (Polling Enable)
Publication 1761-UM005B-EN-P - October 2006
Enabled (1)
Value
Disabled (0)
42 DNI Configuration Parameters and Programming Notes
performance. When this parameter is disabled, PCCC messaging still operates.
IMPORTANT
IMPORTANT
Enable this parameter to use explicit messaging to assemblies.
When modifying most DNI parameters, you must first disable polling (Set the Data Enable parameter to disable for DNI Series A. Set the I/O Scan Enable parameter to disable for DNI Series B). You can enable polling after setting your configuration.
For information on how to set up and modify parameters, see Setup, Programming, and Troubleshooting on page 53.
Publication 1761-UM005B-EN-P - October 2006
DNI Configuration Parameters and Programming Notes 43

DF1 Heartbeat

DF1 Heartbeat Parameter Definition
Parameter Ty pe
I/O 12 13 DF1 Heartbeat Series A: 2…10
Parameter Number Description Range Default
Series A Series B
Series B: 1…10
Value
2
The DF1 data heartbeat is used to detect a valid communications path between the controller and the DNI and also to detect if the connected controller is scanning its ladder logic.
The heartbeat is enabled when:
DNI Series A: Data Enable is enabled and DNI Mode is
operational
DNI Series B: I/O Scan Enable is enabled
The heartbeat consists of a bit in the first byte (byte 0, bit 7) of the data packet that is exchanged with the controller. The DNI sets this bit in the output data being sent to the controller. The user must move this bit, using ladder logic, to the corresponding bit position in the input data area where the bit is then read from the controller by the DNI.
At the heartbeat rate, once the DNI sees the bit return in its correct state, it toggles the bit to the opposite state and sends it back to the controller (this is a round robin process). If the bit state does not change, it is detected as a communication/controller error and reported to the DNI master as a zero-length packet. Refer to your scanner or master controller documentation to determine how this is detected in the master logic.
This bit should also be monitored by the controller attached to the DNI, and if the bit does not change in the output image at the heartbeat rate, it can be used within the controller to detect a problem with the DNI/DeviceNet Master.
Publication 1761-UM005B-EN-P - October 2006
44 DNI Configuration Parameters and Programming Notes
DF1 Heartbeat Rotation Example
The value entered for the heartbeat determines how often the DNI will rotate the heartbeat bit. The table below illustrates the heartbeat rotation with the default setting of two (heartbeat checked on every other read).
DF1 (RS-232) Port A DEF A DNI’s Read Sequence
DNI’s Write Sequence
A. DNI gets (reads) data from controller
B. DNI checks heartbeat and toggles bit
C. DNI sets (writes) data to controller
D. Data Scan Delay period
BC BC
E. DNI gets (reads) data from controller
F. Data Scan Delay (period)
IMPORTANT
The example above does not represent accurate timing relationships.
Consider the following with the above list.
B is done inside the DNI and is completed extremely fast,
typically less than a millisecond.
D is the only consistent time variable; the DNI waits for the
amount of time specified by the Data Scan Delay parameter.
A, C, and E are variable; the time associated with each is
dependent on a number of factors: baud rate, communication errors/retries.
If you are monitoring the heartbeat bit in the controller to
determine communications integrity, as a general rule, multiply the Data Scan Delay by the DF1 Heartbeat plus 1 to determine the preset time value for the heartbeat timer.
DF1 Heartbeat determines how many input reads are done
between heartbeat checks and toggles (step B). When the DF1 Heartbeat is set to 2, this occurs on every other read; when the DF1 Heartbeat is set to 3, this occurs on every third read.
Publication 1761-UM005B-EN-P - October 2006
See the application example DF1 Heartbeat (Bit 7) on page 51 and MicroLogix as I/O on the DeviceNet Network on page 69 for more information about using the DF1 Heartbeat.
DNI Configuration Parameters and Programming Notes 45

Data Scan Delay

Data Scan Delay Parameter Definition
Parameter Ty pe
I/O 13 14 Data Scan
Parameter Number Description Range Default
Series A Series B
20…3000 ms 50 ms Delay (Polling Delay)
Value
When Data Enable (parameter 3) is enabled (DNI Series A) or I/O Scan Enable (parameter 12) is enabled (DNI Series B), the value entered for Data Scan Delay defines the amount of time that the DNI will delay between communications. This value does not identify how often communications take place; it defines the delay between the completion (end) of one communication sequence and the beginning of the next.
IMPORTANT
It is important not to set this value too low. Setting Data Scan Delay too low limits access to the controller from other devices on the network. If this value is too low, programming terminals, other controllers, and any other devices attempting to communicate with this controller are unable to due so, because the RS-232 port communications link bandwidth is being consumed by the I/O scan feature of the DNI.
IMPORTANT
To move data from the controller to the DeviceNet master as quickly as possible, use the DNI’s input messaging feature.
See input messaging on page 49.
See the application example MicroLogix as I/O on the DeviceNet Network on page 69 for more information about using the Data Scan Delay.
Publication 1761-UM005B-EN-P - October 2006
46 DNI Configuration Parameters and Programming Notes

Message Timeout

Message Timeout Parameter Definition
Parameter Ty pe
Messaging 2 15 Message Timeout 0…2500 ms 0 MS
Parameter Number Description Range Default
Series A Series B
Value
The Message Timeout is the amount of time that a DeviceNet explicit connection is held open after message completion. The Message Timeout allows the DNI to hold open a connection with another device over the DeviceNet network. On a DeviceNet network, a connection means that two devices have established a communications path. Each time communications need to occur between devices, a connection is established; when the communications have completed, the connection is released.
The number of connections that each device can support depends on the design/capabilities of each device. The DNI has five connections available for messaging. The Message Timeout allows the user to tune how a connection behaves after communications have completed. You may want to dedicate a connection to a specific node/device to maintain a connection. This reduces the amount of time needed to re-establish communications with the device.
It is recommended that this value only be changed (from the default) if communications with another node is constant. When the timeout is set, the connection is not released back to the system until the timeout expires (where 0 ms means close immediately after use).
Publication 1761-UM005B-EN-P - October 2006
IMPORTANT
An open connection between devices over DeviceNet does not limit or inhibit communications over the network. If two devices maintain a connection, other devices continue to communicate.
DNI Configuration Parameters and Programming Notes 47

DF1 Substitute Address

DF1 Substitute Address Parameter Definition
Parameter Ty pe
Messaging n/a 16 DF1 Substitute
IMPORTANT
Parameter Number Description Range Default Value
Series A Series B
0…64 64 = Disabled
Address
The DF1 Substitute Address parameter cannot be used with DNI Series A.
If the device that is connected to the DNI is not capable of selecting a DF1 destination address of 0…63, by entering a value in this parameter, the DNI automatically routes all DF1 communications to this address with the following exceptions:
Responses to poll requests are sent to the configured address.
COS/Cyclic I/O data messages are sent to the configured device.
For example, when using a MicroView operator interface over DeviceNet, DF1 Substitute Address defines the device (node number) that the MicroView exchanges data with.
TIP
A value of 64 (default) disables this feature.

DF1 Autobaud

Parameter Ty pe
DF1 15 17 DF1 Autobaud Disabled (0)
The DNI’s RS-232 baud rate is set up to automatically synchronize to the attached RS-232 device. If you want to lock the RS-232 baud rate, disable this parameter. If this parameter is disabled (0), the DNI’s RS-232 port baud rate is set to the value specified by the DF1 Baud Rate parameter.
Parameter Number Description Range Default Value
Series A Series B
Enabled (1) or Enabled (1)
Publication 1761-UM005B-EN-P - October 2006
48 DNI Configuration Parameters and Programming Notes

DF1 Baud Rate

DF1 Baud Rate Parameter Definition
Parameter Ty pe
DF1 16 18 DF1 Baud
Parameter Number Description Range Default Value
Series A Series B
Series A: 2 = 9600 Series B: 1 = 19,200
Rate
0…5: 0: 38,400 1: 19,200 2: 9600 3: 4800 4: 2400 5: 1200
This parameter defines the baud rate for the RS-232 port when DF1 Autobaud is disabled.

DeviceNet Autobaud

DeviceNet Autobaud Parameter Definition
Parameter Ty pe
DeviceNet 1 19 DeviceNet
Parameter Number Description Range Default Value
Series A Series B
Autobaud
Disabled (0) or Enabled (1)
Enabled (1)
The DNI automatically synchronizes to the DeviceNet network that it is attached to (125K, 250K, or 500K baud). To disable this feature, set DeviceNet Autobaud to disable (0).
When set to disable, the DNI uses the DeviceNet baud rate configured during the node commissioning process. Therefore, when the DeviceNet Autobaud is disabled, the baud rate the DNI is set to may be different than the DeviceNet network baud rate.
IMPORTANT
When parameter is disabled (0), the baud rate is set using the node commissioning utility in your network configuration software, and is not set by the DNI’s EDS file.
IMPORTANT
Power cycle the DNI for baud rate changes to take effect.
Publication 1761-UM005B-EN-P - October 2006

DNI Mode

DNI Mode Parameter Definition
DNI Configuration Parameters and Programming Notes 49

Programming Notes

Parameter Typ e
Device 17 n/a DNI Mode Standby (0) or
IMPORTANT
Parameter Number Description Range Default Value
Series A Series B
Operational (1)
Operational (1)
The DNI Mode parameter only applies to DNI Series A. For DNI Series B, the operating mode is controlled by the I/O Scan Enable parameter.
This parameter defines the mode of the DNI. You must set this mode to Standby (0) when you want to change a number of DNI parameters. Once you have made the necessary changes, set this value to Operational (1).

Input Messaging

The DNI is capable of accepting an unsolicited Input Data Message from the DF1 device. This capability allows the controller to update the DNI’s input data whenever it detects a change in its input data. With this capability, a user can increase the value of the data scan delay; this reduces the amount of communications traffic over the RS-232/DF1 port, but still maintains very high I/O throughput performance.
To utilize this feature, simply program a message instruction in the controller with a destination address of 254. The DNI accepts the message and when it sees the 254 address (which is invalid on DeviceNet), it recognizes that the message is input data. All data received by message instruction with address 254 is automatically routed to the DNI’s input data area.
See the application example MicroLogix as I/O on the DeviceNet Network on page 69 for more information about input messaging.
Publication 1761-UM005B-EN-P - October 2006
50 DNI Configuration Parameters and Programming Notes

Input Messaging Considerations

You cannot write to a specific word in the DNI’s input area.
The destination offset value in the controller’s message
The message length must equal the size specified by the Input
For MicroLogix 1000 controllers, use N7 as the destination file
instruction is ignored. Data always starts at word 0.
Size parameter. For DNI Series B only, both the Master’s Slave data and the Explicit Assembly are considered to be input. For more information, see:
Input Split Point on page 30. Input Assembly Data (Explicit, Split Point, and Slave) on
page 67.
type.
– For other controllers, see the recommended file number on
page 41.

Status Byte

The first byte (bits 0…7) of the first word of I/O data is set aside as status information. The second byte (bits 8…15) of the first word of I/O is available for user data. The DNI Input/Output Image is shown below:
Word Input/Output Image Series A Series B
0 0 Data (bits 8…15) Status Byte (bits 0…7) 1 1 Data Most Significant Byte (MSB) Data Least Significant Byte (LSB) 2 2 Data MSB Data LSB 3 3 Data MSB Data LSB
↓↓↓
14 30 Data MSB Data LSB 15 31 Data MSB Data LSB

Input Status to Master Device

Publication 1761-UM005B-EN-P - October 2006
The Input Status Byte provides the following information.
Function n/a Output Buffer Overdrive n/a
Bit Number76 543210
DNI Configuration Parameters and Programming Notes 51
Output Buffer Overdrive (Bit 6, written by the DNI)
This bit is set (1) when Master Outputs arrive at a rate faster than the DNI can forward the data to the DF1 device. When the Buffer Overdrive bit is set, the output image is being overwritten before it can be sent to the DF1 device. To resolve this, limit the data production rate in the scanner until this bit stays clear (0).

Output Status to DF1 Device

The Output Status Byte provides the following information.
Function Heartbeat Valid Data DeviceNet Node Number
Bit Number7 6 543210
DeviceNet Node Number (Bits 0 - 5)
Whenever the DNI sets (writes) output data to the DF1 device, these six bits contain the DeviceNet address that the DNI is assigned on DeviceNet. If the user program needs to know what node number its DNI is configured for, program a masked move (MVM) instruction in the ladder logic to move the node number out of this byte. The MVM should have:
its destination address located in the controller’s integer file
a masked value of 003F
the source address should match the location identified by the
Output Word Offset parameter.
DeviceNet Valid Data (Bit 6)
The DNI sets this bit (1) to the DF1 device whenever it detects that the DNI’s DeviceNet master is on-line/operational. The ladder logic program in the controller should monitor this bit and take any necessary control action.
DF1 Heartbeat (Bit 7)
The DNI writes the status of this bit to the controller, using the interval set by the DF1 Heartbeat parameter. The DNI expects the controller to move the status of bit 7 from the output data area to the input data area. The easiest way to accomplish this is by programming an XIC instruction in series with an OTE instruction as shown in the following example.
Publication 1761-UM005B-EN-P - October 2006
52 DNI Configuration Parameters and Programming Notes
Example
With the starting output word at N7:95 (Output Word Offset), and the starting input word at N7:90 (Input Word Offset), you need to program this rung in the controller’s program to move the heartbeat bit.
N7:95
7
N7:90
7
Your program should also monitor N7:95/7 for activity. If activity is lost, it represents a problem with the connection to the DNI, or the DNI has some type of error or problem.
See the application example MicroLogix as I/O on the DeviceNet Network on page 69 for more information about using the DF1 Heartbeat.
Publication 1761-UM005B-EN-P - October 2006
Chapter

Setup, Programming, and Troubleshooting

6

DNI Software Files

To configure the DNI as an I/O slave device on a DeviceNet network, you may need to obtain two software files. These two files provide your network configuration software with the information it needs to interface with the DNI.

DNI Series A Information

RSNetWorx and DeviceNet Manager (version 3.0 and higher) include the files necessary for DNI Series A.

DNI Series B Information

To configure the Series B DNI, you must have the Series B DNI EDS file installed in your DeviceNet configuration software. RSNetWorx DeviceNet Network Management software version 2.11.36 or higher includes all Series B DNI files. You can also download the new files from http://www.ab.com/micrologix.
The following table shows the old and new file filenames:
Series B DNI Files
1761-NET-DNI File Description File Name
Series B DNI Electronic Data Sheet 1761DNI3.EDS
DNI Configuration Software Utility DNIUTIL1.EXE (Rev. 2.0 or higher)
DNI Icon for Configuration Software 1761DNI.ICO or 1761DNIB.BMP
Series A DNI Electronic Data Sheet 1761DNI2.EDS
DNI Configuration Software Utility DNIUTIL1.EXE
DNI Icon for Configuration Software 1761DNI.BMP
ATTENTION
53 Publication 1761-UM005B-EN-P - October 2006
DNI Series A configurations are not compatible with DNI Series B. You must manually re-enter the Series A parameters into the Series B DNI. This step is required because of the enhanced functionality of DNI Series B.
54 Setup, Programming, and Troubleshooting
TIP
DNI Series A stopped shipping in June of 1999. DNI Series B started shipping in July of 1999.

File Descriptions

File Description
DNI Electronic Data Sheet
DNI Icon for Configuration Software
DNI Configuration Software Utility
This is a text file that is compatible with A-B network configuration software. This file, along with the 1761DNI.BMP (or 1761DNI.ICO) file, must be installed using the EDS import utility built into your network configuration software.
This is a bitmap that is used to graphically illustrate the DNI in your configuration software. For RSNetWorx, use 1761BMP.ICO. For DeviceNet Manager, use 1761DNI.BMP. The DNI Configuration Software Utility includes the DNI icon files.
The 1761-NET-DNI configuration utility can be used to configure all 1761-NET-DNI parameters, and also to commission (set node number and baud rate) of other DeviceNet compatible products for operation on a DeviceNet Network. This utility makes configuring a 1761-NET-DNI easier through the use of intuitive screens and Wizards.

Obtaining the Files

These files are routinely incorporated into your network configuration software. If they are not in your version of configuration software, these files are available from a number of sources:
Local Allen-Bradley distributor
Local Allen-Bradley Sales Office
Via the Internet at http://www.ab.com/micrologix
Publication 1761-UM005B-EN-P - October 2006
Setup, Programming, and Troubleshooting 55

Setting Up Network Configuration Software

To configure the DNI, you must set up your network configuration software and follow the configuration procedures. The initial set up is only performed once. After the files have been saved by your network configuration software, they are stored on the computer.

Setting Up DNI Configuration Software Utility

No initial set up is required to use the DNI Configuration Software Utility.

Setting Up RSNetworx

With RSNetworx open, install 1761DNI2.EDS for DNI Series A (1761DNI3.EDS for DNI Series B) and 1761DNI.ICO using the EDS install utility (in the Utilities menu of RSNetworx).
Follow these steps to load both DNI files into RSNetWorx.
1. Start RSNetWorx.
2. With RSNetWorx open, select the View Tools Menu.
3. Select EDS Wizard.
4. Select Register an EDS file and follow the prompts.
RSNetWorx is now set up to recognize and configure the DNI.
5. To locate 1761-NET-DNI in RSNetWorx file list, double-click on
the following folders:
– Rockwell Automation - Allen-Bradley Company
Publication 1761-UM005B-EN-P - October 2006
56 Setup, Programming, and Troubleshooting
Communications Adapter
Publication 1761-UM005B-EN-P - October 2006
Setup, Programming, and Troubleshooting 57

Setting Up DeviceNet Manager

With DeviceNet Manager open, install 1761DNI2.EDS for DNI Series A (1761DNI3.EDS for DNI Series B) and 1761DNI.BMP for DNI Series A (1761DNIB.BMP for DNI Series B) using the EDS install utility (in the Utilities menu of DeviceNet Manager).
Follow these steps to load both DNI files into DeviceNet Manager.
1. Start DeviceNet manager.
2. With DeviceNet manager open, select the Utilities Menu.
3. Select Install EDS Files.
4. Locate 1761DNI2.EDS for DNI Series A (1761DNI3.EDS for DNI
Series B) on your computer.
5. Highlight and load electronic data sheet into the software.
6. Confirm the prompt to attach a bitmap.
7. Locate 1761DNI.BMP (1761DNIB.BMP for DNI Series B) on your
computer.
8. Highlight and load bitmap into the software. DeviceNet manager
is now set up to recognize and configure the DNI.
9. To locate 1761-NET-DNI in DeviceNet managers file list,
double-click on the following folders:
Communications AdapterAllen-Bradley Company
Publication 1761-UM005B-EN-P - October 2006
58 Setup, Programming, and Troubleshooting

Commissioning the DNI

Your configuration software handles all interface issues for connection to a DNI over a DeviceNet network. You use exactly the same procedures to connect to a DNI as you do any other DeviceNet product.
The DNI draws power from the DeviceNet connector. When the DNI is connected to a DeviceNet network for the first time, the DNI out-of-box configuration is:
Node: 63
Baud: Autobaud
Commissioning is accomplished with network configuration software such as DNI Configuration Utility, RSNetWorx, or DeviceNet Manager. There are two parameters that need to be set during the commissioning process: the Node Address and Baud Rate.
IMPORTANT
If the tool you are using to commission the DNI is connected to the DNI with a point-to-point connection (Example: a 1770-KFD connected directly to the DNI without any other devices), the commissioning tool must not be set to Autobaud. The DNI out-of-box configuration is set to Autobaud. If both devices are set to Autobaud, they may hunt and never find each other.
TIP
Follow these steps to commission the DNI.
1. Connect the DNI to a PC through a DeviceNet interface device
(1770-KFD, 1784-PCD).
2. Execute mini-who screen to locate the target DNI.
3. If DeviceNet Autobaud is disabled, enter the DeviceNet baud
rate.
4. Enter the node address to be configured.
5. Apply changes. Status is shown in status bar.
6. Save changes.
For DNI Series B, you will be able to commission the DNI via the RS-232 port. This can be done using the DNI Configuration Software Utility version 2.001 (when available). For applications that use only DNIs, this will eliminate the need for configuration tools (such as RSNetWorx and the 1770-KFD Interface). You can simply use an RS-232 cable.
Publication 1761-UM005B-EN-P - October 2006
Setup, Programming, and Troubleshooting 59

Programming Over the DeviceNet Network

IMPORTANT
IMPORTANT
The DNI provides the ability to upload, download, or monitor the ladder logic program of controllers connected to a DNI on the network.
Configuring the baud rate is needed only when DeviceNet Autobaud is disabled. The default (out-of-box) setting for DeviceNet Autobaud is “enabled”.
The new baud rate takes effect on power cycle or when DNI is reset. Use caution when changing the baud rate on an active network.

Computer with DNI

Follow these steps to upload, download, or monitor over the network.
1. Connect a commissioned DNI to the RS-232 port on a computer
(as shown under Local Access to a DeviceNet Network on page
21).
2. Set the communications in the configuration software to DF1 full
duplex.
3. Select the DeviceNet address of the destination DNI. You can
now upload/download/monitor over the network. The functionality over the network is determined by the destination device.
EXAMPLE
IMPORTANT
If the destination device is a MicroLogix 1000 controller, you cannot perform on-line editing. If the destination device is an SLC 5/03 or later or PLC, you can edit on-line.
With a computer connected to a DNI, you cannot configure devices on the DeviceNet network. You cannot use the DNI as a replacement for a 1770-KFD.
Publication 1761-UM005B-EN-P - October 2006
60 Setup, Programming, and Troubleshooting

Computer on DeviceNet Network

You must have RSLinx version 2.O or newer to upload, download, or edit controller programs directly over DeviceNet (using a 1770-KFD, 1784-PCD, 1784-PCID or equal).
1. Open RSLinx, and select Configure Drivers.
2. Select DeviceNet Driver from the list.
3. Click Add New.
4. Open your configuration software and make sure it recognizes
and is configured to use RSLinx DeviceNet driver.
5. In the configuration software’s communications section, select
the destination DNI that you want to connect to.

Modifying DNI Parameters

Use the main configuration to set or change any of the DNI parameters. Disable Polling Enable while you are making changes. When you are finishing, click Save to File and Save to DNI.

Publication 1761-UM005B-EN-P - October 2006
Setup, Programming, and Troubleshooting 61

Using RSNetWorx to Modify Parameters

Once a DNI is placed on the network, double-click to open the EDS file. All adjustable parameters that configure the DNI for operation are set up through this configuration utility. The illustration below shows the RSNetWorx Device Configuration screen with each DNI configurable parameter.
Perform this procedure to configure any of the parameters.
1. Highlight the parameter.
2. Click the Modify Parameter button, or double-click on the
parameter.
3. For DNI Series A, set DNI mode to Standby. For DNI Series B,
set I/O Scan Enable to Disable.
4. Change the parameter data as needed.
5. For DNI Series A, set DNI mode to Operational. For DNI Series
B, set I/O Scan Enable to Enable.
6. For more detailed information click on Help.
Once a parameter is changed or after all parameters are changed, click Download to Device.
Publication 1761-UM005B-EN-P - October 2006
62 Setup, Programming, and Troubleshooting

Using DeviceNet Manager to Modify Parameters

Once a DNI is placed on the network, double-click to open the EDS file. All adjustable parameters that configure the DNI for operation are set up through this configuration utility. The illustration below shows the DeviceNet Manager Device Configuration screen with each DNI configurable parameter.
To configure any of the parameters, perform this procedure.
1. Highlight the parameter.
2. Click the Modify Parameter button, or double-click on the
parameter.
3. For DNI Series A, set DNI mode to Standby. For DNI Series B,
set I/O Scan Enable to Disable.
4. Change the parameter data as needed.
5. For DNI Series A, set DNI mode to Operational. For DNI Series
B, set I/O Scan Enable to Enable.
6. For more detailed information, click on Help.
Once a parameter is changed or after all parameters are changed, click Save to Device.
Publication 1761-UM005B-EN-P - October 2006
Setup, Programming, and Troubleshooting 63

Troubleshooting

The DeviceNet Interface has three LED indicators.
LED Indicators
LED Color
Module Status LED bicolor - red/green Network Status LED bicolor - red/green RS-232 LED green

Module Status LED (MOD LED)

The module status LED provides information specific to the DNI.
Module Status LED
LED Condition DNI State Problem/Indication
Off Not Powered The device may not be powered or
firmware unable to run.
(1)
Green
Flashing Green
DNI Series A: Device Operational
DNI Series B: Device Scanning
(1)
DNI Series A: Device in Standby
The device is operating in a normal condition.
For DNI Series A only, the device may be in Standby Mode; set to operational.
For DNI Series B, I/O Scan (Polling
DNI Series B: Device Not Scanning
Flashing Red Minor Fault Recoverable fault.
Red Unrecoverable Fault The device has an unrecoverable fault
Flashing Red-Green Device Self Testing The device is in self test and should occur
(1)
Normal condition.
Enable) may need to be set (1).
DNI may need to be commissioned (the DNI will not operate when set to the out-of-box defaults).
The device needs commissioning due to missing, incomplete, or incorrect configuration.
EEPROM may be corrupt, re-commission the DNI.
which requires the power to be cycled, or the DNI may need to replaced.
only at power up or reset.
Publication 1761-UM005B-EN-P - October 2006
64 Setup, Programming, and Troubleshooting

Network Status LED (NET LED)

The network status LED provides information specific to the DeviceNet network.
Network Status LED
LED Condition DNI State Problem/Indication
Off Not Powered/Not
On-Line
Flashing Green
(1)
Green
Flashing Red Connection
Red Critical Link Failure Failed communication device. The DNI has
Flashing Red-Green Communication
(1)
Normal condition.
(1)
On-Line, Not Connected
On-Line, Connected The DNI has one or more valid established
Time-O ut
Faulted
DNI is not on-line.
DNI has not completed the
Dup_MAC_ID test yet.
DNI may not be powered.
DNI has passed the Dup_MAC_ID test, is on-line, but has not established connections to other nodes.
connections. This can be either I/O or Messaging
I/O connection(s) are in the timed-out state.
detected an error that has rendered it incapable of communicating on the network (Bus-Off error). If the error is Duplicate MAC ID, the DNI only communicates via the Group 4 off-line connection set.
A specific communication fault recovery stage or self-test.

RS-232 Port LED Indicator

The DNI has a green LED next to the RS-232 connector to provide communications activity status. The LED is lit whenever data is being transmitted or received. When communications are occurring, this LED will appear to be flashing.

Fault Conditions

Fault Conditions
MOD LED NET LED Fault Condition DeviceNet Standard Fault Available Recovery Options
Solid Red Not Applicable Self-Test Failure Module - Major Unrecoverable Fault Power Cycle Flash Red Not Applicable Invalid Configuration
Parameter Flash Red Not Applicable EEPROM Invalid Module - Major Recoverable Fault Re-commission the DNI. Not Applicable Solid Red Duplicate Node Detected Communication Fault Power Cycle, Group 4 Fault Recovery Not Applicable Solid Red Bus-Off Error Communication Fault Power Cycle, set bus-off attribute of
Publication 1761-UM005B-EN-P - October 2006
The following table defines causes of faults in the DNI.
Module - Minor Recoverable Fault Modify Invalid Parameter
DeviceNet object to 1.
Setup, Programming, and Troubleshooting 65

DNI Series A DeviceNet Class Codes

Identity Object

Class Code: 0x01
Service Name Service Code
Get Attribute Single 0x0E Set Attribute Single 0x10 Reset 0x05
Instance = 0x01
Name Attribute Data Access Value
Vendor ID 0x01 UINT Get 1 Device Type 0x02 UINT Get 12 Product Code 0x03 UINT Get 2 Revision 0x04 STRUCT of: Get Major Revision USINT Get 1 Minor Revision USINT Get 2 Status 0x05 WORD Get N/A Serial Number 0x06 UDINT Get N/A Product Name 0x07 SHORT_STRING Get 1761-NET-DNI DNI Mode
(parameter 17)
0x64 BOOL Get/Set 0 or 1

Slave I/O Assembly Data

Class Code: 0x04
Name Access Instance Data
Ty pe Va l ue
Input Assembly Get/Set Input 100 (64H) 3
Output Assembly Get/Set Output 101 (65H) 3
Attribute
Publication 1761-UM005B-EN-P - October 2006
66 Setup, Programming, and Troubleshooting

DNI Series B DeviceNet Class Codes

Identity Object

Class Code: 0x01
Service Name Service Code
Get Attribute Single 0x0E Set Attribute Single 0x10 Reset 0x05
Instance = 0x01
Name Attribute Data Access Value
Vendor ID 0x01 UINT Get 1 Device Type 0x02 UINT Get 12 Product Code 0x03 UINT Get 32 Revision 0x04 STRUCT of: Get Major Revision USINT Get 2 Minor Revision USINT Get 1 Status 0x05 WORD Get N/A Serial Number 0x06 UDINT Get N/A Product Name 0x07 SHORT_STRING Get 1761-NET-DNI
Publication 1761-UM005B-EN-P - October 2006
Setup, Programming, and Troubleshooting 67

Input Assembly Data (Explicit, Split Point, and Slave)

Class Code: 0x04
Name Access Instance Data Attribute Inputs Type Value
Slave Assembly Get/Set Input 100 (64h) 3
Input Split Point
Explicit Assembly Explicit word 0 Get/Set Input 112 (70h) 3 Explicit word 1 Get/Set Input 113 (71h) 3 Explicit word 2 Get/Set Input 114 (72h) 3 Explicit word 3 Get/Set Input 115 (73h) 3 Explicit word 4 Get/Set Input 116 (74h) 3 Explicit word 5 Get/Set Input 117 (75h) 3 Explicit word 6 Get/Set Input 118 (76h) 3 Explicit word 7 Get/Set Input 119 (77h) 3 Explicit word 8 Get/Set Input 120 (78h) 3 Explicit word 9 Get/Set Input 121 (79h) 3 Explicit word 10 Get/Set Input 122 (7Ah) 3 Explicit word 11 Get/Set Input 123 (7Bh) 3 Explicit word 12 Get/Set Input 124 (7Ch) 3 Explicit word 13 Get/Set Input 125 (7Dh) 3 Explicit word 14 Get/Set Input 126 (7Eh) 3 Explicit word 15 Get/Set Input 127 (7Fh) 3 Explicit word 16 Get/Set Input 128 (80h) 3 Explicit word 17 Get/Set Input 129 (81h) 3 Explicit word 18 Get/Set Input 130 (82h) 3 Explicit word 19 Get/Set Input 131 (83h) 3 Explicit word 20 Get/Set Input 132 (84h) 3 Explicit word 21 Get/Set Input 133 (85h) 3 Explicit word 22 Get/Set Input 134 (86h) 3 Explicit word 23 Get/Set Input 135 (87h) 3 Explicit word 24 Get/Set Input 136 (88h) 3 Explicit word 25 Get/Set Input 137 (89h) 3 Explicit word 26 Get/Set Input 138 (8Ah) 3 Explicit word 27 Get/Set Input 139 (8Bh) 3 Explicit word 28 Get/Set Input 140 (8Ch) 3 Explicit word 29 Get/Set Input 141 (8Dh) 3 Explicit word 30 Get/Set Input 142 (8Eh) 3
(1)
The split point determines the size of the slave assembly and the explicit assembly. If the input size (parameter
1) is set to 32, and the split point (parameter 2) is the minimum size (1), the remaining words are explicit inputs. The example above illustrates the maximum amount of explicit inputs that can be configured. For more information about using the split point parameter, see Input Split Point on page 30 or Output Split Point on page
36.
(2)
A get of this instance will return the entire set of Explicit Assembly Data.
(1)
(2)
Get/Set Input 102 (66h) 3
Publication 1761-UM005B-EN-P - October 2006
68 Setup, Programming, and Troubleshooting

Output Assembly Data (Explicit, Split Point, and Slave)

Class Code: 0x04
Name Access Instance Data Attribute Outputs Type Value
Slave Assembly Get/Set Output 101 (65h) 3
Output Split Point
Explicit Assembly Explicit word 0 Get/Set Output 144 (90h) 3 Explicit word 1 Get/Set Output 145 (91h) 3 Explicit word 2 Get/Set Output 146 (92h) 3 Explicit word 3 Get/Set Output 147 (93h) 3 Explicit word 4 Get/Set Output 148 (94h) 3 Explicit word 5 Get/Set Output 149 (95h) 3 Explicit word 6 Get/Set Output 150 (96h) 3 Explicit word 7 Get/Set Output 151 (97h) 3 Explicit word 8 Get/Set Output 152 (98h) 3 Explicit word 9 Get/Set Output 153 (99h) 3 Explicit word 10 Get/Set Output 154 (9Ah) 3 Explicit word 11 Get/Set Output 155 (9Bh) 3 Explicit word 12 Get/Set Output 156 (9Ch) 3 Explicit word 13 Get/Set Output 157 (9Dh) 3 Explicit word 14 Get/Set Output 158 (9Eh) 3 Explicit word 15 Get/Set Output 159 (9Fh) 3 Explicit word 16 Get/Set Output 160 (A0h) 3 Explicit word 17 Get/Set Output 161 (A1h) 3 Explicit word 18 Get/Set Output 162 (A2h) 3 Explicit word 19 Get/Set Output 163 (A3h) 3 Explicit word 20 Get/Set Output 164 (A4h) 3 Explicit word 21 Get/Set Output 165 (A5h) 3 Explicit word 22 Get/Set Output 166 (A6h) 3 Explicit word 23 Get/Set Output 167 (A7h) 3 Explicit word 24 Get/Set Output 168 (A8h) 3 Explicit word 25 Get/Set Output 169 (A9h) 3 Explicit word 26 Get/Set Output 170 (AAh) 3 Explicit word 27 Get/Set Output 171 (ABh) 3 Explicit word 28 Get/Set Output 172 (ACh) 3 Explicit word 29 Get/Set Output 173 (ADh) 3 Explicit word 30 Get/Set Output 174 (AEh) 3
(1)
The split point determines the size of the slave assembly and the explicit assembly. If the output size (parameter 6) is set to 32, and the split point (parameter 7) is the minimum size (1), the remaining words are explicit outputs. The example above illustrates the maximum amount of explicit outputs that can be configured. For more information about using the split point parameter, see Input Split Point on page 30 or Output Split Point on page 36.
(2)
A get of this instance will return the entire set of Explicit Assembly Data.
(1)
(2)
Get/Set Output 103 (67h) 3
Publication 1761-UM005B-EN-P - October 2006
Chapter
7

Application Examples

All examples are for illustration and information purposes only. Because of the many variables and requirements associated with any particular installation, Rockwell Automation cannot assume responsibility or liability for the actual use based on the examples and diagrams.

MicroLogix as I/O on the DeviceNet Network

MicroLogix controllers are incapable of being true slave I/O products. But, they are capable of behaving like slave I/O and more by adding logic (user program). This example turns a MicroLogix controller into an I/O block on the DeviceNet network. The MicroLogix input data is sent up to the DeviceNet master as input data, and the DeviceNet master output data is sent to the MicroLogix outputs.
The example logic is a user program that monitors the communications link between the MicroLogix and the DeviceNet master and makes sure it is operational. If problems occur with the communications link, the MicroLogix controller turns off the outputs. If the connection is restored, the controller recovers and behaves like an I/O block.
If you would prefer to have the MicroLogix maintain the outputs when a communications fault is detected, remove or disable some of the logic in this application (review the comments for each rung to determine which logic to remove). Or, if you prefer to have the controller behave differently on a communications fault, simply add the corresponding logic that you require.
69 Publication 1761-UM005B-EN-P - October 2006
70 Application Examples

Example DNI Configuration Parameters

Parameter Number Description Range Default Value For this Example, Series A Series B
4 1 Input Size Series A: 1…16
Not Applicable
5 3 Input Type Bit or Integer File Integer File Integer File 6 4 Input Data File 3…254 7 7 7 5 Input Word Offset 0…254 0 90 8 6 Output Size Series A: 1…16
Not Applicable
9 8 Output Type Bit or Integer File Integer File Integer File 10 9 Output Data File 3…254 7 7 11 10 Output Word Offset 0…254 1 95 14 11 DF1 Device 0…3:
312DNI Series A:
12 13 DF1 Heartbeat Series A: 2…10
13 14 Data Scan Delay
2 15 Message Timeout 0…2500 ms 0 ms 0 ms Not
Applicable 15 17 DF1 Autobaud Disabled (0) or Enabled (1) Enabled (1) Enabled (1)
2 Input Split Point 1…32 1 word 4 words
7 Output Split Point 1…32 1 word 4 words
Data Enable DNI Series B: I/O Scan Enable (Polling Enable)
(Polling Delay)
16 DF1 Substitute
Address
All example ladder logic programs in this section use the following DNI configuration.
ENTER
1 word 4 words
Series B: 1…32
1 word 4 words
Series B: 1…32
3 = MicroLogix 1000 3 = MicroLogix 1000
0: Other 1: PLC 2: SLC/ Other MicroLogix 3: MicroLogix 1000
0 or 1 Disabled (0) Enabled (1)
22
Series B: 1…10 20…3000 ms 50 ms 100 ms
0…64 64 = Disabled 64 = Disabled
Publication 1761-UM005B-EN-P - October 2006
Application Examples 71
Parameter Number Description Range Default Value For this Example, Series A Series B
16 18 DF1 Baud Rate 0…5:
Series A: 2 = 9600
ENTER
0 = 38,400
1 19 DeviceNet Autobaud Disabled (0) or Enabled (1) Enabled (1) Enabled (1) 17 Not
Applicable

Example Ladder Logic

0: 38,400
1: 19,200
2: 9600
3: 4800
4: 2400
5: 1200
DNI Mode Standby (0) or
Operational (1)
Series B: 1 = 19,200
Operational (1) Operational (1)
The ladder program example is used to monitor the integrity of the communications link with the DNI. If something happens and communications are lost (cable is cut or removed, DNI loses power or faults) this logic detects that condition. The user can program the controller to respond to a loss of communications, if desired.
The example ladder logic shown below is available for download from http://www.ab.com/micrologix. The sample is compatible with RSLogix 500 programming software. The file name is DNI I-O.RSS and contains two programs.
DNI MicroLogix Heartbeat Logic, DNI I-O.RSS Ladder 2 - Main
Program
Monitors the communications link for integrity. This is considered to be part of the Heartbeat logic associated with the DNI.
DNI - COS (change of state) I/O Messaging, DNI I-O.RSS Ladder
6 - COS ML DNI
Moves the Input and Output data inside the controller, for correct operation with the DNI.
Publication 1761-UM005B-EN-P - October 2006
72 Application Examples

DNI - MicroLogix Heartbeat Logic

TIP
Rung 9 in this example resets (0) all outputs to off if communications are lost. If you prefer your application to have the controller maintain the outputs in their last state, remove this rung. Or, if you want additional logic to control your outputs, remove this rung and program the outputs as your application requirements warrant.
Publication 1761-UM005B-EN-P - October 2006
0000
0001
0002
0003
Application Examples 73
DNI I-O.RSS Ladder 2 - Main Program
This rung sets status file bit S2:0/8. When this bit is set, it allows a program written for a 32-point MicroLogix 1000 controller to run without an I/O mismatch error on a 10, 16, or 25-point controller.
This rung detects an off-to-on transition of bit N7:95/7. Bit N7:95/7 is the communication’s Heartbeat that is received from the DNI.
N7:95
7
B3:31
OSR
15
This rung detects an on-to-off transition of bit N7:95/7. Bit N7:95/7 is the communication’s Heartbeat that is received from the DNI.
N7:95
7
B3:31
OSR
13
This rung resets the communications watchdog whenever the DNI Heartbeat changes state (off-to-on or on-to-off).
DNI Heartbeat Pulse On Detected
B3:31
14
DNI Heartbeat Pulse Off Detected
B3:31
12
Extend I/O Configuration
S:0
8
DNI Heartbeat Pulse On DetectedOff-to-On MemoryHeartbeat Bit from DNI
B3:31
14
DNI Heartbeat Pulse Off DetectedOn-to-Off MemoryHeartbeat Bit from DNI
B3:31
12
DNI Communications Watchdog
T4:39
RES
0004
Timer 39 is the communications watchdog for DNI/MicroLogix communications. If this timer ever “times out”, the outputs directly controlled by the MicroLogix turn off. This timer is constantly being reset by the status of bit N7:95/7 (toggle on, toggle off). Bit N7:95/7 is controlled by communications received from the DNI. The amount of time (preset) the timer should be set to is dependent on the DF1 Heartbeat, Data Scan Delay, and the baud rate of the RS-232 port. Using this logic with a Series D MicroLogix 1000 controller, set T4:39 to a preset value of 350 ms. If communications are lost with the DNI, the MicroLogix 1000 turns off its outputs after 350 ms.
TON
TIP
TON Timer On Delay Timer T4:39 Time Base 0.01 Preset 350< Accum 22<
Subroutine 6 (COS ML DNI) is covered in the following section.
EN
DN
Publication 1761-UM005B-EN-P - October 2006
74 Application Examples

DNI - COS (change of state) I/O Messaging

The ladder logic shown below is an example of how to send input data to the DNI (COS input messaging). This procedure is recommended because the latency issue associated with polling devices is minimized. Polling is a mechanism that is used to acquire data from a device. The DNI reading data from a controller at a set interval is an example of a polled relationship. The problem with polling is that usually the data does not change, so the communications are consumed by reading the same data over and over. Another problem is that information cannot be received quicker than the polled rate, and depending on when the data changes, worst case update can take up to twice the polled rate.
One solution to this problem is to allow for COS (change of state) messaging. What this allows is for the device (MicroLogix for example) to send input data to the DNI when it detects new/changed data. Many also call this type of relationship unsolicited communications. This can significantly improve system throughput because the polling interval is eliminated.
The way the MicroLogix controllers can get input data into the DNI is to message to node address 254. Address 254 is an invalid address on the DeviceNet network. When the DNI detects an incoming message, it looks at the destination address and size; if it reads 254 for the address and the size is equal to the configured input size, it knows the data in the message is input data destined for the DNI (For DNI Series B, the size includes master and explicit input data). The data is then placed into the DNI’s input image and is delivered to the DeviceNet master using the polled or COS connection that was configured in the DeviceNet master by the user.
Publication 1761-UM005B-EN-P - October 2006
0000
Application Examples 75
DNI I-O.RSS Ladder 6 - COS ML DNI
This rung checks to see if the input data has changed from the previous ladder scan. If the input data has changed, bit B3:31 is set.
MicroLogix 1000 Inputs Input Data has Changed Flag
NEQ Not Equal Source A I:0.0 341< Source B N7:89 341<
NEQ Not Equal Source A I:0.1 0< Source B N7:80 0<
The Time Out bit (TO) associated with each message instruction is used to clear the controller’s communications buffer and message instruction. Setting the TO bit places the controller’s communication section in the same condition as when the controller powers up. This rung detects if a message instruction is currently being processed and, when input data changes, the existing message is terminated allowing a new transmission to start. It also terminates the message if the message instruction does not complete (T4:38/DN).
B3:31
11
0001
0002
MicroLogix to DNI Message Input Data has Changed Flag MicroLogix to DNI Message Timeout
N7:82
13
B3:31
11
N7:82
8
Retry Message
T4:38
DN
This is the message instruction that writes data to the DNI. It is recommended that you use 485CIF as the target device. CIF is the most efficient type of communications. This message instruction also has a destination address of 254. This value is entered into the Setup Screen area of the message instruction.
MSG Read/Write Message Read/Write Write Target Device 485CIF Control Block N7:82 Control Block Length 7
Setup Screen
EN
DN
ER
Publication 1761-UM005B-EN-P - October 2006
76 Application Examples
Publication 1761-UM005B-EN-P - October 2006
Chapter
8

Explicit Messaging (DNI Series B Only)

Explicit messaging is the mechanism that is used to move data over the DeviceNet network. Every device on the DeviceNet network either initiates or responds to some type of explicit message to either read (get) or write (set) data.
In the network shown below, node 5 is a master (scanner) that owns slave I/O data on the DeviceNet network. When the master interacts with its slaves (either through strobed, polled, cyclic or COS connections), the communications used are specific types of I/O messages. If the MicroLogix controllers at nodes 10 and 30 want to exchange data, they message through the DNIs to each other using explicit messages.
Node 5
Node 15
Node 25
The functionality of each device determines how it can interact with other devices on the network. Many devices can respond only to requests. Some devices can be configured to respond, but they can also initiate messages to others. One example is the PanelView operator interface that has DeviceNet technology built in. It can be owned by a master as slave I/O, and can also get or set data to other devices on the network.
Node 10
Node 20
Node 30
77 Publication 1761-UM005B-EN-P - October 2006
78 Explicit Messaging (DNI Series B Only)
The Series B DNI also has the ability to exchange data with other DeviceNet devices using explicit messaging, provided those devices are capable of interacting. The following list provides some of the requirements.
If a device is Unconnected Message Manager (UCMM) capable,
it should be 100 percent compliant with or without a master being present on the network.
If a device is not UCMM capable, it will need a master to be
present on the network, and it should be owned by the master.
If a device is not UCMM capable and a master is not present (or
a master is present but the device is not owned by the master), the device will not be compatible with the DNI using explicit messaging.

Using DF1 Protocol for Explicit Messages Over a DeviceNet Network

The DNI is an intelligent bridge between DF1 full duplex (Allen-Bradley open protocol) and DeviceNet. All Allen-Bradley controllers that use DF1 protocol (basically any Allen-Bradley controller with an RS-232 port) use the historical source/destination model to move data.
The problem with this is that DeviceNet technology uses the newer producer/consumer model and is not compatible with the source/destination model. So, to allow controllers that use the source/destination model (MicroLogix, SLC, PLC) access to devices on the DeviceNet network, the DNI can act as an intermediary.
To act as an intermediary, the DNI must allow the historical DF1 message format to be compatible with the newer DeviceNet producer/consumer object model. This is accomplished by creating a routing profile. The routing profile basically takes the DF1 message and converts it to DeviceNet. Each routing profile contains the information needed to get or set data to other DeviceNet devices.
Each routing profile has the following five components.
Node - the address of the Device on a DeviceNet network
Class - the DeviceNet class code
Instance - the DeviceNet instance code
Attribute - the DeviceNet attribute code
Size - the amount of data to be read or written
Publication 1761-UM005B-EN-P - October 2006
Explicit Messaging (DNI Series B Only) 79
The DNI can store up to 10 profiles. These profiles can be changed at any time, and they are not backed up with a battery. If the power to the DeviceNet network is lost, the profiles are cleared and must be reloaded. This can be done with a subroutine.

Routing Profile Configuration

TIP
A message instruction returning an error code of 0xD0H is an indication that profiles need to be re-configured.
The 10 profiles are stored within the DNI in profile registers. To configure a routing profile, the user creates a write message in the controller’s ladder logic with a destination node address of 240…249. The write message must have a data length of five words. Each word corresponds to one of the five components in the routing profile.
Word Title Function
0 Target Node Node number (0…63) of the target device on a DeviceNet
network that communications will be established with. 1 Class Class of the target DeviceNet object. 2 Instance Instance of the target DeviceNet object. 3 Attribute Attribute of the target DeviceNet object that will be read from or
written to (get/set). 4 Size Amount of data to be read or written in bytes.
When the DNI receives a write message with a destination address of 240…249, it stores the five words of data in the corresponding profile register, location 240…249.
Publication 1761-UM005B-EN-P - October 2006
80 Explicit Messaging (DNI Series B Only)

Explicit Messaging Examples

Once the profiles are correctly loaded into the DNI, getting data from a DeviceNet device is as simple as reading data from another controller. The procedure is illustrated by the following examples.

Reading (Get) Data Example

Node 5
Node 15
Node 25
Node 10
Node 20
Node 30
For the DeviceNet network shown above, we want to read data from the proximity sensor at node 15. The proximity sensor has specific DeviceNet parameters that are accessible via the DeviceNet network. In this example, profile register 240 within the DNI (node 10) has been configured to access specific data within the proximity sensor.
TIP
Devices must be UCMM capable. The proximity switch and tower light are not UCMM capable. But, because they are owned by the 1747-SDN scanner in the SLC chassis, the DNI can explicit message to them.
TIP
Any devices parameters should be identified in their respective documents.
Publication 1761-UM005B-EN-P - October 2006
Explicit Messaging (DNI Series B Only) 81
DNI Profile Register 240:
DeviceNet Node:15
Class: 14 (0x0E)
Instance: 1
Attribute: 1
Size: 1 byte
To read data from the proximity sensor, a read message is initiated from the controller to node address 240. The DNI receives the node 240 read request and then generates the appropriate DeviceNet explicit message to get (read) data from the proximity sensor at node 15.
TIP
The profiles size parameter must match the DeviceNet device.
In this example, the amount of data (size) being read over DeviceNet (in bytes) is 1. The DNI receives the byte of information from the sensor and replies to the controller read request with a word of data. The actual byte of data from the sensor resides in the low order byte of the data word within the controller.
In this example, the read message instruction has N7:10 identified as the data table address, so the sensor data will appear in low order byte of N7:10. The message instruction setup screen is shown below.
Publication 1761-UM005B-EN-P - October 2006
82 Explicit Messaging (DNI Series B Only)

Writing (Set) Data Example

In this example we want to write data to the light tower at node 20. The light tower has specific parameters that are accessible via the DeviceNet network. In this example, profile register 241 within the DNI (node 10) has been configured to set data in the light tower.
DNI Profile Register 241:
DeviceNet Node:20
Class: 9
Instance: 1
Attribute: 3
Size: 1 byte
Node 5
Node 15
Node 25
Node 10
Node 20
Node 30
To set DeviceNet data, a write message is initiated from the controller to node address 250. The first data word of the write message identifies which profile register to use (240…249). The remaining data words in the message contain the data that is transmitted to the DeviceNet device, in this example the light tower.
Publication 1761-UM005B-EN-P - October 2006
The size specified in the DNI’s profile register is in bytes. The data being sent by the controller is in words. In this example N7:0 contains the profile register to be used (241). Location N7:1 contains the data to be sent to the light tower.
Explicit Messaging (DNI Series B Only) 83
The message instruction setup screen is shown below.
The actual data portion of the controller’s write message (N7:1)
must match the size parameter in the respective profile register. In this example:
the size of profile register 241 is 1
the controller’s write message has a length of 2
the first word identifies the profile register to be usedthe second word is the actual data
To verify that this is a valid routing profile, we see that the data portion of this message is 1, which corresponds to the profile’s size of
1. So, this example is valid. If the sizes do not match, the controller’s write message will result in an error.
Publication 1761-UM005B-EN-P - October 2006
84 Explicit Messaging (DNI Series B Only)
Publication 1761-UM005B-EN-P - October 2006

Specifications

Appendix
A

Physical Specifications

DeviceNet Specifications

Description Specification
24V dc Power Source Required 11…25V dc Current Draw 200 mA at 24V dc
350 mA at 11V dc (400 mA maximum inrush for 30 ms at 24V dc)
Internal Isolation 500V dc Ambient Operating Temp. 0° C…+60° C (+32° F…+140° F) Storage Temperature -40° C…+85° C (-40° F…+175° F) Agency Certification UL 1604
C-UL C22.2 No. 213 Class I Division 2 Groups A,B,C,D CE compliant for all applicable directives ODVA Conformance Version 2.0
Feature Y/N Comments
Peer to Peer Messaging Y Only to other Controllers/DNI’s I/O Assembly Explicit
Messaging I/O Peer to Peer Messaging
(also known as Dynamic I/O) UCMM Y Configuration Consistency
Value Deferred Delete Y Faulted Node Recovery Y DeviceNet Auto-Baud Y Flash Upgradeable N Baud Rate All 125K, 250K, 500K Master/Scanner N I/O Slave:
Bit Strobe Polling COS (change of state)
Flat cable TBD
Y Output sets only when I/O connection set is
unowned
N
Y
Y N Y Y
85 Publication 1761-UM005B-EN-P - October 2006
86 Specifications

Dimensions

52.07 mm (2.05 in.)
118 mm (4.64 in.)
Allow 15 mm (0.6 in.) clearance for DIN rail latch movement during installation and removal.
27.7 mm (1.09 in.)
107 mm (4.20 in.)
64.8 mm (2.55 in.)
Publication 1761-UM005B-EN-P - October 2006

Mounting Template

Specifications 87
52.07 mm (2.05 in)
118 mm (4.64 in)
27.7 mm (1.09 in)
107 mm (4.20 in)
Allow 15 mm (0.6 in.) clearance for DIN rail latch movement during installation and removal.
Publication 1761-UM005B-EN-P - October 2006
88 Specifications
Publication 1761-UM005B-EN-P - October 2006

Glossary

Interface Basics

The 1761-NET-DNI (DNI) is a smart interface that provides DF1 full-duplex capable devices a connection to the DeviceNet network. To understand how the DNI operates, you need to become familiar with certain terms. This figure illustrates the relationship between the DF1 Device, the DNI function, and the DeviceNet network.
1761-NET-DNI Interface Diagram
DeviceNet
Input Image (To Master)
Output Image (From Master)
Messaging
DNI Configuration, Parameters, Operating Systems

Terms and Abbreviations

MicroLogix or other DFI Device
The following terms and abbreviations are specific to this product. For a complete listing of Allen-Bradley terminology, refer to Allen-Bradley Industrial Automation Glossary, publication AG-7.1.
Autobaud
A feature that allows a communications port to automatically synchronize to the device or network that it is attached to. This feature typically minimizes the amount of configuration required, and also makes it easier to replace devices.
Connection Set
These methods of communication relate to how data is communicated between master and slave. For example, a master allocates a slave I/O connection set. The ownership allows the master to read (get) and/or write (set) data to the slave.
COS (Change Of State)
Communication method that does not send or receive data until a change in data is detected.
89 Publication 1761-UM005B-EN-P - October 2006
90 Glossary
DeviceNet Master
A product capable of owning input/output (I/O) on a DeviceNet network.
DeviceNet Slave
A product whose data (or portion of) can be owned by DeviceNet master.
DF1 Full Duplex
DF1 is a standard (open) point-to-point communication protocol. Virtually all Allen-Bradley controllers (PLC-3, PLC-5R, SLC, MicroLogix) that support an RS-232 communication port support DF1.
Explicit Messaging
A DeviceNet message that gets/sets device configuration information.
Heartbeat
A mechanism that lets a device, set of devices, or a connection check for operation or integrity. Also known as a watchdog.
Input Buffer
A set of 16-bit words that is available to a master on a DeviceNet network. The input buffer in DNI Series A is configurable from 1… 16 data words (DNI Series B is configurable from 1…32). The data in the input buffer originates from the device connected to the RS-232 port (either by the DNI reading the data, or the RS-232 device writing the data to the DNI). The input buffer terminology is used because the data is input data to the DeviceNet master.
Messaging
A general term that identifies the exchange of data between devices. The two major types of DeviceNet messaging are:
I/O - DeviceNet master and DeviceNet slave.
Peer-to-peer - Between compatible devices without a master’s
involvement.
Publication 1761-UM005B-EN-P - October 2006
Output Buffer
A set of 16-bit data words that is available to a Master on a DeviceNet network. The output buffer in DNI Series A is configurable from 1…16
Glossary 91
data words (DNI Series B is configurable from 1…32). Output data received from the DeviceNet master is forwarded (written) to the RS-232 device.
Peer-To-peer
A type of communication where both devices are equal. These devices communicate to each other without a third device to manage the transaction.
Profile Register
The location within the DNI where routing profile configurations are stored.
PCCC
Programmable Controller Communication Commands
UCMM
Unconnected Message Manager
Publication 1761-UM005B-EN-P - October 2006
92 Glossary
Publication 1761-UM005B-EN-P - October 2006

Index

Numerics

1761-NET-DNI
agency certification commissioning 58 compliance to EC directives 23 configuration parameters 27 configuration software 53 interface diagram 89 new features 27 port identification 26 specifications 85
85
A
application examples 69, 78 autobaud 47, 48
B
baud rate 48
C
cables 24 CE 85 commissioning the DNI 58 configuration parameters 27, 28 configuring master/slave I/O 13 configuring peer-to-peer messaging 11 C-UL 85
DeviceNet valid data 51 DF1 autobaud 47 DF1 baud rate 48 DF1 heartbeat 43 DF1 substitute address 27, 47 dimensions 86
mounting template 87
DIN rail mounting 24 DNI Configuration Utility 54, 55 DNI mode 49 DNI-COS I/O Messaging 74 DNI-MicroLogix heartbeat logic 71
E
EDS file 27, 28 example
explicit messaging MicroLogix as I/O on DeviceNet 69 reading (get) data 80 writing (set) data 82
explicit messaging 19, 77
example 80 I/O assembly messaging 19 PCCC encapsulated DeviceNet
Messaging
using DF1 protocol 78
80
20
F
fault conditions 64
D
data enable 41 data scan delay 45 definitions 89 device compatibility 9 device type 41 DeviceNet autobaud 48 DeviceNet class codes
I/O assembly data identity object 65, 66 Series A 65 Series B 66
DeviceNet I/O 17
input image 18 output image 18
DeviceNet Manager 57, 62 DeviceNet node number 51
67, 68
G
getting started 11
H
hazardous location operation 24, 85
I
I/O scan enable 41 input image 18 input messaging 49 input size 29 input split point 30 input word offset 34 installation
DNI software files getting started 11 mounting 24 mounting template 87
Publication 1761-UM005B-EN-P - October 2006
53
94 Index
network port wiring 26 safety considerations 24 setting up network configuration
software
53
L
LED
module status network status 64 RS-232 port 64
63
M
master/slave I/O configuration 13 message timeout 46 modes of use 17
DeviceNet I/O 17 explicit messaging 17 programming over DeviceNet network
17
mounting
DIN rail mounting enclosure 23 mounting template 87 panel mounting 25
24
O
ODVA 85 operating modes 9 operation 17 output image 18 output size 35 output split point 36 output type 38 output word offset 39
P
parameter
data enable data scan delay 45 device type 41 DeviceNet autobaud 48 DF1 autobaud 47 DF1 baud rate 48 DF1 heartbeat 43 DF1 substitute address 47 DNI mode 27, 49 I/O scan enable 41
41
input data file 33 input size 29 input split point 30 input type 33 input word offset 34 message timeout 46 output size 35 output split point 36 output type 38 output word offset 39 polling delay 45 polling enable 41
peer-to-peer messaging configuration
11
polling delay 45 polling enable 41 product overview
description
programming notes 49 programming over DeviceNet 21, 59
computer on DeviceNet 60 computer with DNI 59 local access 21 remote access 22
9
R
routing profile 78
configuration 79
RSNetWorx 55, 61
S
safety considerations 24 software
DeviceNet Manager DNI Configuration Utility 18, 55 RSNetWorx 18, 55, 61
specifications 85
DeviceNet 85 dimensions 86 physical 85
split point 27, 30, 36 standby/operational parameter 27, 49 start-up instructions 11 status
input status to master device output status to DF1 device 51
status byte 50 substitute address 47
18, 57, 62
50
Publication 1761-UM005B-EN-P - October 2006
T
terms 89 troubleshooting
LED indicators
U
UL 85 W wiring
26
cables 24
Index 95
62
Publication 1761-UM005B-EN-P - October 2006
96 Index
Publication 1761-UM005B-EN-P - October 2006
Index 97
Publication 1761-UM005B-EN-P - October 2006
98 Index
Publication 1761-UM005B-EN-P - October 2006
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com
, you can
.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running.
United States 1.440.646.3223
Monday – Friday, 8am – 5pm EST
Outside United States
Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return
Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning, it may need to be returned.
United States Contact your distributor. You must provide a Customer Support case
number (see phone number above to obtain one) to your distributor in order to complete the return process.
Outside United States
Allen-Bradley, CompactLogix, ControlLogix, PowerFlex, Rockwell Automation, RSLinx, RSLogix, MicroLogix, Panelview, RSNetWorx, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Please contact your local Rockwell Automation representative for return procedure.
Publication 1761-UM005B-EN-P - October 2006 100
Supersedes Publication 1761-UM 005A-EN-P - June 1999 Copyright © 2006 Rockwell Automation, Inc . All rights reserved. Printed in the U.S.A.
Loading...