Rockwell Automation 1606-XLSPRED User Manual

Reference Manual
Bulletin 1606 Switched Mode Power Supplies
Catalog Number: 1606-XLSPRED
Index
1. Intended Use .......................................................3
2. Installation Requirements...................................3
3. Input and Output Characteristics .......................4
4. Power Losses........................................................5
5. Lifetime Expectancy and MTBF...........................6
6. Terminals and Wiring..........................................7
8. Front Side and User Elements.............................8
9. EMC......................................................................9
10. Environment ......................................................10
11. Protection Features ...........................................11
12. Safety Features..................................................11
13. Certications .................................................... 12
14. Physical Dimensions and Weight ..................... 13
15. Accessories ........................................................ 13
16. Application Notes............................................. 14
16.1. Recommendations for Redundancy .........14
16.2. Inductive and Capacitive Loads ................ 14
16.3. Example: 1+1 Redundancy .......................14
16.4. Example: N+1 Redundancy ....................... 15
16.5. Example: Battery Back-up ........................ 15
16.6. Mounting Orientations ............................16
Terminology and Abbreviations
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”.
T.b.d. To be dened, value or description will follow later.
DC 24V A gure displayed with the AC or DC before the value represents a nominal voltage with
24Vdc A gure with the unit (Vdc) at the end is a momentary gure without any additional
may A key word indicating exibility of choice with no implied preference
shall A key word indicating a mandatory requirement
should A key word indicating exibility of choice with a strongly preferred implementation
1+1 Redundancy Use of two identical power supplies in parallel to provide continued operation following most
N+1 Redundancy Use of three or more identical power
standard tolerances (usually ±15%) included. E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or at (10V)
tolerances included.
failures in a single power supply. The two power supply outputs should be isolated from each other by utilizing diodes or other switching arrangements.
ACDCACDCACDCACDCACDCAC
N+1
Redundancy
DC
1+1
Redundancy
ACDCAC
E.g. two 2.5A power supplies are needed to achieve a 2.5A redundant system.
supplies in parallel to provide continued
IN 1
IN 2 IN 1
OUT
IN 2 IN 1
OUT
OUT
IN 2
IN 1
IN 2
OUT
operation following most failures in a single power supply. All power supply outputs should be isolated from each other
+
Load
-
+
Load
-
by utilizing diodes or other switching arrangements. E.g.: To achieve a 10A redundant system, ve 2.5A power supplies are needed in a N+1 redundant system.
egaP egaP
DC
Bulletin 1606 Switched Mode Power Supplies
Redundancy Module
Cost Effective Solution to Build Redundant Systems Dual Input with Single Output Two Diodes (Common Cathode) DC12-48V (120Vdc) ±25% Wide-range Input Full Power Between -40°C and +60°C Compact Design, Width only 45mm Quick-connect Spring-clamp Terminals Easy Wiring: Distribution Terminal for Negative Pole Included 3 Year Warranty
Description
The 1606-XLPRED is a simple redundancy module that you can use to build 1+1 and N+1 redundant systems. It is equipped with two input channels, which can be connected to power supplies with up to 5A output current and one output, capable of carrying nominal currents up to 10A. The module is suitable for power supplies with constant current overload behavior as well as any kind of “Hiccup” overload behavior.
Unique quick-connect spring-clamp terminals allow for a safe and fast installation and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Specication Quick Reference
Input voltage
DC 12-48V
±25%
DC 12-120V
±25%
w/o restrictions
with restrictions Input voltage range
9-60Vdc 9-150Vdc
w/o restrictions
with restrictions Input current 2x 0-5A continuous 2x 0-8A for 5 seconds Output current 0-10A continuous 10-16A for 5 seconds
<16A at cont. overload/
short circuit Input to output
voltage drop
typ. 0.8V typ. 0.9V typ. 0.9V
input: 2x2.5A
input: 1x5A
input: 2x5A Power losses typ. 0W at no load typ. 4.0W input: 2x2.5A typ. 4.5W input: 1x5A typ. 9.0W input: 2x5A Temperature range -40°C to +70°C operational, Derating 0.25A/°C +60 to +70°C Dimensions 45x75x91mm WxHxD
Catalog Numbers
Redundancy 1606-XLPRED 12-48V (120V) Module Standard unit
Certications
IND. CONT. E
Q.
UL 508
UL 60950-1
ATEX
II 3G Ex nA IIC T4 Gc
Marine
EMC, LVD
UL Class 1 Div 2
C-Tick
Marine RINA
GOST R
2 Rockwell Automation Publication 1606-RM035A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
1. Intended Use
This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office, communication, and instrumentation equipment.
Do not use this power supply in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe personal injury or threaten human life.
This device is designed for use in hazardous, non-hazardous, ordinary or unclassified locations.
2. Installation Requirements
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for inspection.
Mount the unit on a DIN rail so that the terminals are located on the bottom of the unit. For other mounting orientations, refer to derating
requirements in this document.
This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid (e.g. cable conduits) by more than 30%!
Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply).
SHOCK HAZARD: Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input
block for earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering
- Make sure that the wiring is correct by following all local and national codes
- Do not modify or repair the unit
- Do not open the unit as high voltages are present inside
- Use caution to prevent any foreign objects from entering the housing
- Do not use in wet locations or in areas where moisture or condensation can be expected
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
WARNING: EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless power has been switched off or the area is known to be non-hazardous.
Notes for use in hazardous location areas:
The unit is suitable for use in Class I Division 2 Groups A, B, C, D locations
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM035A-EN-P — April 2014 3
Bulletin 1606 Switched Mode Power Supplies
3. Input and Output Characteristics
Number of inputs - 2 Number of outputs - 1 Input voltage nom. DC 12-48V
±25%
The input circuitry must meet the SELV requirements
stipulated by IEC/EN/UL 60950-1. Input voltage range - 9–60Vdc Input voltage with restrictions nom. DC 12-120V
±25%
See note 3 at the bottom of the table
Input voltage range with restrictions
- 9-150Vdc Restrictions apply, see note 3 at the bottom of the table.
at 2x2.5A, see Fig. 3-2Voltage drop, input to output typ. 0.8V typ. 0.9V at 1x5A, see Fig. 3-3 typ. 0.9V at 2x5A, see Fig. 3-2 Input current nom. 2x 0-5A continuous nom. 1x 0-10A continuous, see note 1 nom. 2x 5-8A for 5 seconds Peak input current max. 125A for maximal 10ms per input Output current nom. 10A continuous nom. 10-16A for 5 seconds max.
16A at continuous overload or short circuit, see note 2 Reverse current max. 0.6mA per input, -40°C to +60°C Reverse voltage max. 200Vdc voltage applied to the output, continuously allowed
Note 1: Each input can be loaded up to 10A. At currents above 10A, the other input should not be loaded. It is preferable to parallel the two
inputs in order to minimize the power loss in such cases.
Note 2: Ensure that the continuous output current does not exceed 16A. Check the short-circuit current of the power sources and if the
power source can deliver more than 16A together, use an appropriate fuse on the output.
Note 3: The redundancy module can be used with input voltages up to 150Vdc with the constraint, that it can be used only as a single input
module at voltages above 60Vdc. Both inputs need to be connected together as shown in Fig. 3-1. Ensure proper means to protect against touching this voltage.
Fig. 3-1 Restrictions for utilizing voltages between 60 and 150Vdc (See also Note 3)
AC
DC
(>60V)
+
-
Load
>60V
+
-
Power Supply
Power Supply
Diode Module
+
-
+
+
-
-
AC
DC
(>60V)
+
-
AC
DC
(>60V)
+
-
Load
>60V
+
-
Power Supply Diode Module
+
-
+
+
-
-
Diode Module
+
-
+
+
-
-
AC
DC
(>60V)
+
-
Power Supply
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
4 Rockwell Automation Publication 1606-RM035A-EN-P — April 2014
Fig. 3-2 Input to output voltage drop when both inputs draw current
(typical 1+1 redundant case, when the output voltages of the two units are equal or set into “parallel use” mode)
Voltage Drop, typ.
0A 2A 4A 8A
200mV
400mV
600mV
800mV
1000mV
10
A
6A
Input, Output Current
0mV
Output:
2x2A2x1A
Input:
2x4A2x3A0A 2x5
A
A... 25°C B... 60°C
A
B
V
A
24V,5A
+
-
24V,5A
+
-
V
A
I
1
I
2
U
1
U
2
I1I2=
U2U1= Voltage Drop
U1=
U
OUT
-
Output
A
V
I
OUT
U
OUT
Variable
Load,
0-10A
1606-XLPRED
Input 1
Input 2
Output
Fig. 3-3 Input to output voltage drop when only one input draws current
Voltage Drop
U1=
U
OUT
-
Not used or
power supply
with lower
voltage
V
A
24V,10A
+
-
I
1
U
1
Output
A
V
I
OUT
U
OUT
Variable
Load,
0-10A
Input 1
Input 2
Output
1606-XLPRED
Voltage Drop, typ.
0A 2A 4A 8A
200mV
400mV
600mV
800mV
1000mV
10
A
6A
Output Current
0mV
A... 25°C B... 60°C
A
B
4. Power Losses
DC 24V
Power losses typ.
4.0W input: 2x2.5A
typ.
4.5W
input: 1x5A
typ.
9.0W
input: 2x5A
Standby power losses typ. 0W at no output current
Fig. 4-1 Power losses
Power Losses, typ.
0A 2A 4A 8A
2W
4W
6W
8W
10W
10
A
6A
Input, Output Current
0
Output:
2x2A2x1A
Input:
2x4A2x3A0A 2x5
A
A... 25°C
B... 60°C
A B
1606-XLS 240E
1606­XLS120E
1606­XLS120E
Bulletin 1606 Switched Mode Power Supplies
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM035A-EN-P — April 2014 5
Bulletin 1606 Switched Mode Power Supplies
5. Lifetime Expectancy and MTBF
The redundancy module has two input channels which are completely independent from each other. Each control circuit, auxiliary voltage source, or other circuitry in the module is designed separately for each input. The dual input redundancy module can be considered as two single redundancy modules combined together in one housing. The only common point is the circuit trace that ties the two separate circuits together at the output.
The MTBF gures below are for the entire dual input module. If the MTBF number of only one path is needed, simply double the value from the table.
The redundancy module does not include electrolytic capacitors. Therefore, the lifetime expectancy is extremely high.
Input / output current conditions
Input: 2x5A
Output: 10A
Lifetime expectancy *) min. 25 years at 24V and 40°C min. 25 years at 24V and 25°C MTBF
**) SN 29500, IEC 61709 84 868 000h at 24V 40°C
125 266 000h at 24V 25°C MTBF **) MIL HDBK 217F 71 454 000h at 24Vand 40°C (Ground Benign GB40) 81 453 000h at 24Vand 25°C (Ground Benign GB25)
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life). **) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF gure is a statistical representation of the likelihood of a device to fail. A MTBF gure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the eld. However, it can not be determined if the failed unit has been running for 50 000h or only for 100h.
6 Rockwell Automation Publication 1606-RM035A-EN-P — April 2014
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
6. Terminals and Wiring
Type Bi-stable, quick-connect spring clamp terminals.
Solid wire 0.3-4mm2 Stranded wire 0.3-2.5mm2 American Wire Gauge 26-12 AWG Max. wire diameter 2.8mm (including ferrule) Wire stripping length 6mm / 0.25inch Pull-out force 10AWG:80N, 12AWG:60N, 14AWG:50N,
Instructions:
a) Use appropriate copper cables that are designed for
minimum operating temperatures of: 60°C for ambient up to 45°C and 75°C for ambient up to 60°C and 90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation
regulations!
c) Ensure that all strands of a stranded wire enter the terminal
connection! d) Ferrules are allowed, but not required. e) Do not connect or disconnect the wires from the terminals
below -25°C (-13°F).
Input and output
IP20 Finger safe construction. Suitable for eld- and factory installation.
16AWG:40N (according to UL486E)
Bulletin 1606 Switched Mode Power Supplies
Terminals shipped in open
position.
Fig. 6-1 Connecting a wire
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM035A-EN-P — April 2014 7
Bulletin 1606 Switched Mode Power Supplies
7. Functional Diagram
Fig. 7-1 Functional diagram
Input 1
+
-
Input 2
+
-
8. Front Side and User Elements
Fig. 8-1 Front side
Output terminals
A
B Input terminals for input 1
C
Input terminals for input 2
+ +
-
-
Output
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
8 Rockwell Automation Publication 1606-RM035A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
9. EMC
The redundancy module is suitable for applications in industrial environment as well as in residential, commercial and light industry environment without any restrictions. A detailed EMC report is available upon request.
EMC Immunity
According generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV 15kV
Criterion A
Criterion A Electromagnetic RF eld EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A Fast transients (Burst) EN 61000-4-4 Input lines
Output lines
2kV 2kV
Criterion A
Criterion A Surge voltage on input lines EN 61000-4-5 + - 200V Criterion A Surge voltage on output line EN 61000-4-5 + - 200V Criterion A Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A Power-frequency magnetic
eld *)
EN 61000-4-8 50Hz 30A/m Criterion A
Criteria: A: Redundancy module shows normal operation behavior within the dened limits. Notes: *) A test is not applicable according to EN 61000-6-2, since the device does not contain components susceptible to magnetic elds, e.g. hall
elements, electrodynamic microphones, etc.
EMC Emission
According generic standards: EN 61000-6-3 and EN 61000-6-4 Conducted emission IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 Class B, input lines *) IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 Class B, output lines *) Radiated emission EN 55011, EN 55022 Class B This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
*) Provided, that power sources connected on the inputs fulll the class B requirements as well.
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM035A-EN-P — April 2014 9
Bulletin 1606 Switched Mode Power Supplies
10. Environment
Operational temperature Output de-rating 0.25A/°C 60-70°C (140°F to 158°F), see Storage temperature -40 to +85°C (-40°F to 185°F) for storage and transportation Humidity **) 5 to 95% r.H. IEC 60068-2-30 Vibration sinusoidal 2-17.8Hz: ±1.6mm
Shock 15g 6ms, 10g 11ms
Altitude 0 to 2000m (0 to 6 560ft) without any restrictions 2000 to 6000m (6 560 to 20 000ft) reduce output power or ambient temperature,
Altitude de-rating 0.7A/1000m or 5°C/1000m > 2000m (6500ft), see Fig. 10-2 Over-voltage category not applicable The concept of the overvoltage category is
Degree of pollution 2 IEC 62103, EN 50178, not conductive LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
*) Operational temperature is the same as the ambient temperature and is dened as the air temperature 2cm below the unit. **) Do not energize in the presence of condensation.
Fig. 10-1 Output current vs. ambient temp. Fig. 10-2 Output current vs. altitude
Allowed Output Current
17.5A
t
a
15.0
12.5
10.0
7.5
5.0
2.5
0
Ambient Temperature
-40 0 20 40
*) -40°C to +70°C (-40°F to 158°F) Reduce output power above +60°C
IEC 60068-2-6
17.8-500Hz: 2g 2 hours / axis
IEC 60068-2-27 3 bumps / direction 18 bumps in total
see Fig. 10-2
used for equipment energized directly from
the low voltage mains (IEC 60664-1 §4.3.3.2.1).
use in paint shops.
Allowed Output Current
o
v
e
r
l
d
o
a
s
/
h
o
r
c
t
r
c
u
i
t
i
n
o
r
m
l
a
o
m
d
e
70°C
60-25
17.5A
o
v
e
r
l
15.0
12.5
10.0
n
7.5
5.0
A
.
T
.
.
m
a
b
2.5
B C
T
.
.
.
m
a
b
T
.
.
.
b
m
a
0
0 2000 4000
o
a
d
s
/
h
o
r
t
o
r
a
m
m
l
o
d
<
°
0
6
C
<
°
0
5
C
<
°
0
C
4
c
r
c
u
i
t
i
e
A
Altitude
C
B
6000m
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
10 Rockwell Automation Publication 1606-RM035A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
11. Protection Features
Output over-current protection not included Reverse input polarity protection included unit does not start when input voltage is reversed Degree of protection IP 20 EN/IEC 60529 Penetration protection > 2.5mm e.g. screws, small parts Over-temperature protection not included Input transient protection not included Output transient protection not included Internal input fuse not included
12. Safety Features
Input / output separation no galvanic separation 200V epitaxial diode between input and output Safety level of output voltage The output voltage is regarded to be SELV (EN 60950-1) or PELV (EN 60204-1, EN
50178, IEC 60364-4-41) if the input voltage fullls the requirements for a SELV source or PELV source.
Class of protection III plastic housing, PE connection not required
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM035A-EN-P — April 2014 11
Bulletin 1606 Switched Mode Power Supplies
13. Certications
EN 60950-1, EN 61204-3
Complies with
- CE EMC directive
- CE Low-Voltage Directive
The CE mark indicates conformance with the
- ATEX directive 94/9/EC (Equipment and protection systems intended for use in potentially explosive atmospheres)
UL 508
IND. CONT. EQ.
LISTED E56639 for use in the U.S.A. (UL 508) and Canada (C22.2 No. 14-95) Industrial Control Equipment
UL 60950
RECOGNIZED E168663 for use in the U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950); Information Technology Equipment, Level 3
CSA 22.2 No107.1-01, 60950-1
CSA Certied under File Number 240020
II 3G Ex nA IIC T4 Gc
ATEX
II 3G Ex nA IIC T4 Gc
Marine GL
GL (Germanischer Lloyd) classied for marine and offshore applications. Environmental category: C, EMC2. See below for link to the Certicate.
ISA 12.12.01, CSA C22.2 No. 213
RECOGNIZED UNDER FILE NUMBER E244404 for use in the U.S.A. (ISA 12.12.01) and Canada (C22.2 No. 213) Hazardous Location Class I Div. 2, Groups A, B, C, D
Marine RINA
RINA (Registro Italiano Navale) certied. See below for the link to the Certicate.
GOST R
GOST R certication is applicable for products intended for sale and use within Russia. See below for the link to the Certicate.
C-TICK
C-Tick compliance is for products intended for sale and use within the Australian market. See below for the link to the C-Tick Declarations of Conformity
Product certification information (including Certificates and Declarations of Conformity) can be found at www.ab.com/certifications.
12 Rockwell Automation Publication 1606-RM035A-EN-P — April 2014
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
14. Physical Dimensions and Weigth
Weight 140g / 0.31lb DIN Rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN rail height must be added to the unit depth (91mm) to calculate the total required installation depth.
Installation clearances See section 2.
Fig. 14-1 Front view Fig. 14-2 Side view
15. Accessories
DIN rail bracket for wall or panel mount:
A suitable DIN rail bracket is available upon request.
The picture of the power supply is for representation only.
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM035A-EN-P — April 2014 13
Bulletin 1606 Switched Mode Power Supplies
16. Application Notes
16.1. Recommendations for Redundancy
Recommendations for the conguration of redundant power systems:
Use separate input fuses for each power supply.
Use three-phase power supplies to gain functional safety if one phase fails.
When single-phase power supplies are utilized connect them to different phases or mains circuits if possible.
Set the power supply in “Parallel-Use” mode if this feature is available
It is desirable to set the output voltages of all power supplies to the same value.
16.2. Inductive and Capacitive Loads
The unit is designed to supply any kind of load, including unlimited inductive and capacitive loads.
16.3. Example: 1+1 Redundancy
A 1+1 redundancy up to 2.1A requires two 1606-XLP50E power supplies (each 2.1A output current) and one 16060-XLPRED redundancy module.
Fig. 16-1 Wiring diagram, 1+1 Redundancy, 2.1A output current
XLPRED
IN 1
+
-
+
-
L N
II
XLP50E
Power
Supply
L N
Output
Input
+ +
- -
DC OK
XLP50E
Power
Supply
L N
Output
Input
Load
+
- -
+
-
IN 2
Alarm
Monitor
Output
+ +
- -
DC
OK
+
Note: Whenever possible, use separate mains systems for each power supply.
14 Rockwell Automation Publication 1606-RM035A-EN-P — April 2014
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
16.4. Example: N+1 Redundancy
A N+1 redundancy up to 6.3A requires four 16060-XLP50E power supplies (each 2.1A output current) and two 1606-XLPRED redundancy modules.
Fig. 16-2 Wiring diagram, N+1 Redundancy, 6.3A output current
L
N
I
XLP50E
Power
Supply
L N
Input
Output
+ +
- -
DC
OK
XLP50E
Power
Supply
L N
Output
Input
+ +
- -
DC OK
XLPRED
IN 1
+
-
+
-
Output
+
- -
IN 2
+
Alarm
Monitor
Load
+
-
XLP50E
Power
Supply
L N
Input
Output
+ +
- -
DC OK
XLP50E
Power Supply
L N
Output
Input
+ +
- -
DC OK
XLPRED
IN 1
+
-
+
-
Output
+
- -
IN 2
+
II I
Note: Whenever possible, use separate mains systems for each power supply.
16.5. Example: Battery Back-up
A battery back-up requires one power supply and one 1606-XLPRED redundancy module.
Please note: Set output voltage of power supply to 26.5Vdc minimum to ensure that the load current is delivered from the power supply and not from the charger (battery). Use a fuse between the battery and the 1606-XLPRED module!
Fig. 16-3 Wiring diagram, 10A Battery back-up
L N
PE
24V Battery
I
Battery
Charger
+
-
Failure
Monitor
Load
XLP50E
Power
Supply
L N
Input
Output
+ +
- -
DC OK
XLPRED
IN 1
+
-
+
-
Output
+
- -
IN 2
+
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM035A-EN-P — April 2014 15
Bulletin 1606 Switched Mode Power Supplies
16.6. Mounting Orientations
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature.
Fig. 16-4
Mounting Orientation A
(Standard orientation)
Redundancy
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°C
2
6
8
10A
50
4
Ambient Temperature
Fig. 16-5 Mounting Orientation B
(Upside down)
Redundancy
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°C
2
6
8
10A
50
4
Ambient Temperature
Fig. 16-6 Mounting Orientation C
(Table-top mounting)
Output Current
0
10 20 30 40
60°C
2
6
8
10A
50
4
Ambient Temperature
Fig. 16-7 Mounting Orientation D
(Horizontal cw)
Redundancy
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°C
2
6
8
10A
50
4
Ambient Temperature
Fig. 16-8 Mounting Orientation E
(Horizontal ccw)
Redundancy
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°C
2
6
8
10A
50
4
Ambient Temperature
16 Rockwell Automation Publication 1606-RM035A-EN-P — April 2014
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. You can also visit our Knowledgebase at http://
www.rockwellautomation.com/knowledgebase for FAQs, technical information, support chat and forums,
software updates, and to sign up for product notification updates.
, you can find technical manuals, technical and application
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer Tech Con ne ct representative, or visit http://www.rockwellautomation.com/support/
SM
support programs. For more information, contact your local distributor or Rockwell Automation
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Wo rldw ide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local
Rockwell Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Publication 1606-RM035A-EN-P — April 2014
, available at http://
Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...