Reference Manual
Bulletin 1606 Switched Mode Power Supplies
Catalog Numbers: 1606-BATASSY1, 1606-XLSBAT1, 1606XLSBATBR1
Terminology and Abbreviations
•DC-UPS—Uninterruptible power supply with DC Input.
•Normal mode—Describes a condition in which the battery is charged, the input voltage is in range and the output is loaded within the
allowed limits.
• Buffer mode—Describes a condition where the input voltage is below the transfer threshold level, the unit is running on battery (buffering)
and the output is loaded within the allowed limits.
• Charging mode—Describes a condition where the battery is in the process of charging, the input voltage is in range and the output is loaded
within the allowed limits.
• Inhibit mode—Describes a condition where buffering is intentionally disabled by using the inhibit input of the DC UPS (e.g. to perform
service actions or to save battery capacity).
•Buffer time—This term is equivalent to “hold-up time.”
• T.b.d.—To be defined, value or description will follow later.
Bulletin 1606 Switched Mode Power Supplies
Battery Modules
A modular concept allows the user to meet individual
application demands and is available with two dierent
options:
You can order the module with an assembled battery or
you can choose only the bracket allowing the mounting
of individual batteries – such a long life or higher current
which achieves a longer buer-time. The mounting
bracket allows you to assemble the battery just in time,
thus avoiding outdated batteries due to limited shelf life.
Two mounting options:
DIN rail or panel/wall mounting
Easy access to the terminals and the fuse
Heavy duty fuse holder and spare fuse included
Description
Specication Quick Reference
Battery
Maintenance free valve regulated lead acid battery
Battery voltage nom 12Vdc
Battery capacity nom 7Ah
Self-discharge typ 3%/ month at 20°C
Design life (EUROBAT) 3 to 5 years
Fuse
Blade terminal fuse nom 30A ATO
®
)esuflettiL 030 752(
Terminals and Wiring
Type Screw terminals
Solid wire nom 2.5-4mm
2
Stranded wire nom 2.5-4mm
2
American wire gauge max 12 AWG
Wire stripping length nom 7mm / 0.275”
Tightening torque nom 0.8Nm / 7lb.in
Ambient Temperature
Operation min +0°C to +40°C
Storage and transport min -20°C to +50°C
Instructions for Use and Disposal of the Battery
Place the battery module outside the cabinet or in the
coolest area when used inside the cabinet.
Use wires no smaller than 2.5mm2 (or 12 AWG) and no
longer than 2x1.5m (cord length 1.5m).
Disconnect battery fuse before working on the battery
or on the DC-UPS.
To replace battery, loosen screw with only one turn and
slide the mounting bracket up.
For storage, installation and operation, the
requirements of the EN 50272-2 as well as other
national regulations must be observed.
Ensure sucient ventilation for the battery.
Always dispose the batteries through a recycling
organisation. Batteries must be completely discharged
before recycling.
Dimensions and Weight (1606-XLSBATASSY1)
Widtt nom 155mm / 6.1“
Height nom 124mm / 4.88“
Depth nom 112mm / 4.41“
Weight max 3200g / 7.06lb
The DIN rail height when used must be added to the depth
to calculate the total required installation unit depth.
Warranty
3 Year limited warranty except battery as battery is
considered as a service part. Special conditions are part of
our general terms and conditions. Do not store the battery
longer than 9 month without supplementary charge or
performance might change.
Catalog Numbers
Certication Marks
1606-XLSBATASSY Battery module with battery
1606-XLSBATBR1 Mounting kit without battery
1606-XLSBAT1
Battery replacement
GL
Marine
Battery, terminal block,
cables, fuse and fuse
holder are UL-approved
components.
GOST R
All parameters are specified at 25°C ambient unless noted otherwise.