Rockwell Automation 1606-XLS960F-3 User Manual

Reference Manual
egaP egaP
1.
Intended Use .......................................................3
3. AC-Input...............................................................4
4. Input Inrush Current ...........................................5
5. DC-Input...............................................................5
6. Output .................................................................6
7. Hold-up Time.......................................................8
8. DC-OK Relay Contact ..........................................9
9. Shut-down Input .................................................9
10. Remote Control of Output Voltage .................10
11. Internal Data Logging.......................................10
12. Efciency and Power Losses..............................11
13. Lifetime Expectancy and MTBF.........................12
14. Functional Diagram...........................................12
15. Terminals and Wiring........................................13
16. Front Side and User Elements...........................14
17. EMC....................................................................15
18. Environment ......................................................16
19. Protection Features ...........................................17
20. Safety Features..................................................17
21. Dielectric Strength ............................................18
22. Certications
................................................ 18
23. Physical Dimensions and Weight ..................... 19
24. Accessories ........................................................ 20
24.1. 1606-XLC - Wall mounting bracket ............20
24.2. 1606-XLSBUFFER48 module ........................20
25. Application Notes............................................. 21
25.1. Repetitive Pulse Loading .......................... 21
25.2. Peak Current Capability ...........................22
25.3. External Input Protection .........................22
25.4. Using only 2 Legs of a 3-Phase System ....23
25.5. Charging of Batteries ............................... 24
25.6. Output Circuit Breakers ............................24
25.7. Parallel Use to Increase Output Power ....25
25.8. Parallel Use for Redundancy ....................25
25.9. Series Operation ....................................... 26
25.10. Inductive and Capacitive Loads................26
25.11. Back-feeding
Loads ..................................26
25.12. Use in a Tightly Sealed Enclosure ............ 26
25.13. Mounting Orientations ............................ 27
Bulletin 1606 Switched Mode Power Supplies
Catalog Number: 1606-XLS960F-3
Index
Terminology and Abbreviations
•PE and symbol—PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
•Earth, Ground—This document uses the term “earth” which is the same as the U.S. term “ground”.
• T.b.d.—To be defined, value or description will follow later.
• AC 230V—A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%)
included. E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
• 230Vac—A figure with the unit (Vac) at the end is a momentary figure without any additional tolerances included.
• 50Hz vs. 60Hz—As long as not otherwise stated, AC100V and AC230V parameters are valid at 50Hz and AC120V parameters are valid at 60Hz
mains frequency.
•may—A key word indicating flexibility of choice with no implied preference.
•shall—A key word indicating a mandatory requirement.
•should—A key word indicating flexibility of choice with a strongly preferred implementation.
Bulletin 1606 Switched Mode Power Supplies
3AC 380-480V Wide-range Input Three Input Fuses Included Width only 110mm, Weight only 1.5kg
95.4% Full Load and Excellent Partial Load Efciencies 50% BonusPower
, 1440W for up to 4s
55A Peak Curre
nt for 25ms for Easy Fuse Tripping Active PFC (Power Factor Correction) Active Filtering of Input Transients Negligible Low Input Inrush Current Surge Full Power Between -25°C and +60°C Current Sharing Feature for Parallel Use Internal Data Logging for Troubleshooting Included. Remote Control of Output Voltage DC-OK Relay Contact Shut-down Input 3 Year Warranty
Description
The outstanding features of the 1606-XLS DIN rail
power supplies are their extremely high efciencies and small size, which are achieved through synchronous rectication and other technological breakthroughs.
Large power reserves of 150% support the starting of heavy loads such as DC motors or capacitive loads. In many cases this allows the use of a unit from a lower wattage class, thus saving space and money.
High immunity to transients and power surges as well as low electromagnetic emission makes usage in nearly every environment possible.
The integrated output power manager, the three input fuses and near zero input inrush current make installation and usage simple. Diagnostics are easy due to the DC-ok relay, a green DC-OK LED and the red overload LED.
A large international approval package for a variety of applications makes this unit suitable for nearly every application.
Specication Quick Reference
Output voltage DC 48V nominal Adjustment range 48 - 54V Output current 20 – 17.8A continuous 30 – 26.7A short term (4s) Output power 960W continuous 1440W short term (4s) Output ripple < 150mVpp 20Hz to 20MHz Input voltage 3AC 380-480V -15%/+20% Mains frequency 50-60Hz ±6% AC Input current 1.65 / 1.35A at 3x400 / 480Vac Power factor 0.88 / 0.90 at 3x400 / 480Vac AC Inrush current typ. 4.5A peak Efciency 95.4 / 95.2% at 3x400 / 480Vac Losses 46.3 / 48.4W at 3x400 / 480Vac Temperature range -25°C to +70°C operational Derating 24W/°C +60 to +70°C Hold-up time typ. 25 / 25ms at 3x400 / 480Vac Dimensions 110x124x127mm WxHxD Weight 1500g / 3.3lb
Catalog Numbers
Power Supply 1606-XLS960F-3 48-54V Standard unit
Accessory 1606-XLC Wall mount bracket 1606-XLSBUFFER48 Buffer unit UL
Certication Marks
IND. CONT. E
Q.
508
UL 60950-1
Class I Div 2
Marine
EMC, LVD
Power Supply
Marine RINA
C-Tick GOST R
2 Rockwell Automation Publication 1606-RM032A-EN-P — April 2014
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
1. Intended Use
This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office, communication, and instrumentation equipment.
Do not use this power supply in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe personal injury or threaten human life.
This device is designed for use in non-hazardous, ordinary or unclassified locations.
2. Installation Requirements
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for inspection.
Mount the unit on a DIN rail so that the terminals are located on the bottom of the unit. For other mounting orientations, refer to derating
requirements in this document.
This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid (e.g. cable conduits) by more than 30%!
Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply).
SHOCK HAZARD: Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input
block for earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering
- Make sure that the wiring is correct by following all local and national codes
- Do not modify or repair the unit
- Do not open the unit as high voltages are present inside
- Use caution to prevent any foreign objects from entering the housing
- Do not use in wet locations or in areas where moisture or condensation can be expected
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
WARNING: EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless power has been switched off or the area is known to be non-hazardous.
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM032A-EN-P — April 2014 3
Bulletin 1606 Switched Mode Power Supplies
3. AC Input
AC input nom. 3AC 380-480V suitable for TN, TT and IT mains networks,
grounding of one phase is allowed except in UL 508
applications AC input range min. 3x 323-576Vac continuous operation Allowed voltage L to earth max. 576Vac continuous, IEC 60664-1 Input frequency nom. 50–60Hz ±6% Turn-on voltage typ. 3x 305Vac steady-state value, load independent, see Fig. 3-1 Shut-down voltage typ. 3x 275Vac steady-state value, load independent, see Fig. 3-1
3AC 400V 3AC 480V
Input current typ. 1.65A 1.35A at 48V, 20A, symmetrical phase voltages,
see Fig. 3-3 Power factor*) typ. 0.88 0.90 at 48V, 20A, see Fig. 3-4 Start-up delay typ. 500ms 600ms see Fig. 3-2 Rise time typ. 23ms 23ms at 48V, 20A, resistive load, 0mF see Fig. 3-2 typ. 47ms 47ms at 48V, 20A, resistive load, 20mF see Fig. 3-2 Turn-on overshoot max. 1V 1V see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, denitions
Turn-on
323V
Rated input range
V
IN
P
OUT
275V 576Vac
Shut-down
305V
Start-up
delay
Rise
Time
Overshoot
- 5%
Output Voltage
Input Voltage
L1 L2 L3
Fig. 3-3 Input current vs. output load at 48V Fig. 3-4 Power factor vs. output load at 48V
20A
2 4 6 8 10 12 14 16 18
0
0.2
0.4
0.6
0.8
1.0
1.2
1.6A
Input Current, typ.
1.4
Output Current
A: 3x 400Vac B: 3x 480Vac
A
B
Power Factor, typ.
2 4 6 8 10 12 14 16 18 20A
0.70
0.75
0.80
0.85
0.90
0.95
Output Current
A: 3x 400Vac B: 3x 480Vac
A
B
4 Rockwell Automation Publication 1606-RM032A-EN-P — April 2014
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
4. Input Inrush Current
The power supply is equipped with an active inrush current limitation circuit, which limits the input inrush current after turn-on to a negligible low value. The input current is usually smaller than the steady state input current.
3AC 400V 3AC 480V
Inrush current
*)
max. 6A
peak
6A
peak
over entire temperature range
typ. 4.5A
peak
4.5A
peak
over entire temperature range
Inrush energy max. 1.5A
2
s 1.5A2s over entire temperature range
Inrush delay typ. 500ms 600ms
*) The charging current into EMI suppression capacitors is disregarded in the rst microseconds after switch-on.
Fig. 4-1 Typical turn-on behaviour at nominal
load and 25°C ambient temperature
Input
Output
Input Current 2A/DIV
3x400Vac
48Vdc
100ms/DIV
5. DC Input
Do not operate this power supply with DC-input voltage.
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM032A-EN-P — April 2014 5
Bulletin 1606 Switched Mode Power Supplies
6. Output
Output voltage nom. 48V Adjustment range min. 48-54V guaranteed max. 56V
***)
at clockwise end position of potentiometer Factory setting typ. 48.0V ±0.2%, at full load, cold unit, in “single use” mode typ. 46.0V ±0.2%, at full load, cold unit, in “parallel use” mode typ. 48.0V at no load, cold unit, in “parallel use” mode Line regulation max. 10mV 3x323-576Vac Load regulation max. 50mV in “single use” mode: static value, 0A 20A, see Fig. 6-1
typ. 2000mV in “parallel use” mode: static value, 0A
20A,
see Fig. 6-2 Ripple and noise voltage max. 150mVpp 20Hz to 20MHz, 50Ohm Output current nom. 20A continuously available at 48V, see Fig. 6-1 and Fig. 6-2 nom. 17.8A continuously available at 54V, see Fig. 6-1 and Fig. 6-2 nom. 30A short term (4s) available BonusPower*), at 48V,
see Fig. 6-1, Fig. 6-2 and Fig. 6-4 nom. 26.7A short term (4s) available BonusPower
*)
, at 54V,
see Fig. 6-1, Fig. 6-2 and Fig. 6-4 typ. 55A up to 25ms, output voltage stays above 40V, see Fig.
6-4, This peak current is available once every second.
See section 25.2 for more peak current measurements. Output power nom. 960W continuously available at 48-54V nom. 1440W*) short term available BonusPower*) at 48-54V BonusPower
time typ. 4s duration until the output voltage dips, see Fig. 6-3 BonusPower recovery time typ. 7s overload free time to reset power manager, see Fig. 6-5 Overload behavior cont. current see Fig. 6-1 Short-circuit current
**)
min. 20A continuous, load impedance 50mOhm, see Fig. 6-1 max. 22A continuous, load impedance 50mOhm, see Fig. 6-1 min. 30A short-term (4s), load impedance 50mOhm, see Fig. 6-1 max. 34A short-term (4s), load impedance 50mOhm, see Fig. 6-1 typ. 26A continuous, load impedance <10mOhm max. 29A continuous, load impedance <10mOhm Output capacitance typ. 3 700μF included in the power supply
*) BonusPower, short term power capability (up to typ. 4s)
The power supply is designed to support loads with a higher short-term power requirement without damage or shutdown. The short­term duration is hardware controlled by an output power manager. BonusPower is repeatedly available. Detailed information can be found in section 25.1. If the power supply is loaded longer with the BonusPower than shown in the bonus-time diagram (see Fig. 6-3), the max. output power is automatically reduced to 960W.
**) Discharge current of output capacitors is not included.
***) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not
guaranteed value which can be achieved. The typical value is about 55V.
6 Rockwell Automation Publication 1606-RM032A-EN-P — April 2014
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
Fig. 6-1 Output voltage vs. output current in
“single use” mode, typ.
Fig. 6-2 Output voltage vs. output current in
“parallel use” mode, typ.
Output Voltage
0
0 5 10 15 20
8
16
24
56V
32
40
48
3025 35A
Output Current
Adjustment Range
A B
A
B
A
B
Short-term (4s) BonusPower
Continuously available
Output Voltage
(Parallel Use, typ.)
42V
01020
44V
46V
48V
56V
50V
52V
54V
30A25155
Adjustment Range
Output Current
Factory setting
A
B
A
B
A
B
Short-term (4s) BonusPower
Continuously available
Fig. 6-3 Bonus time vs. output power Fig. 6-4 Dynamic overcurrent capability, typ.
ma
x
.
Bonus Time
0
100 120 130 140 150
170%
1
2
3
4
5s
110 160
Output Power
m
i
n
.
Output Voltage
(dynamic behavior, < 25ms)
0
0
8
16
24
54V
32
40
48
70A30 6010 20 40 50
Adjustment Range
Output Current
Fig. 6-5 BonusPower recovery time
Power Demand
100%
t
t
Limitation by Power Manager
Output Voltage
Bonus Power disabled
Bonus
Time
Recovery Time
The BonusPower is available as soon as power comes on and after the end of an output short circuit or output overload.
Fig. 6-6 BonusPower after input turn-on Fig. 6-7 BonusPower after output short
100%
Output Voltage
Input Voltage
Bonus
Power
Output Power
150%
Short of
Output
100%
Output Voltage
Bonus
Power
Output Power
150%
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM032A-EN-P — April 2014 7
Bulletin 1606 Switched Mode Power Supplies
7. Hold-up Time
3AC 400V
*)
3AC 480V*) Hold-up Time typ. 50ms 50ms at 48V, 10A, see Fig. 7-1 min. 40ms 40ms at 48V, 10A, see Fig. 7-1 typ. 25ms 25ms at 48V, 20A, see Fig. 7-1 min. 20ms 20ms at 48V, 20A, see Fig. 7-1
*) Curves and gures for operation on only two legs of a 3-phase system can be found in section 25.4.
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, denitions
0
10
20
30
40
50ms
320 360 400 440 3x480Vac
Input Voltage
Hold-up Time
48V, 10A, typ.
4
8
V
,
2
0
A
,
t
y
p
.
48V, 10A, min.
4
8
V
,
2
0
A
,
m
i
n
.
- 5%
Hold-up Time
Zero Transition
Output Voltage
Input Voltage
8 Rockwell Automation Publication 1606-RM032A-EN-P — April 2014
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
8. DC-OK Relay Contact
This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed voltage from a unit connected in parallel to the power supply output.
Contact closes As soon as the output voltage reaches 90% of the adjusted output voltage. Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 250ms. Dips shorter than 1ms will be ignored. Contact re-closes As soon as the output voltage exceeds 90% of the adjusted voltage. Contact ratings max 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load min 1mA at 5Vdc min. permissible load Isolation voltage See dielectric strength table in section 21.
Fig. 8-1 DC-ok relay contact behavior
V
= V
OUT
ADJ
10%
0.9* V
ADJ
open
<
1ms
>
1ms
250ms
openclosed closed
9. Shut-down Input
This feature allows a switch-off of the output of the power supply with a signal switch or an external voltage. The shut-down function ramps down and has no safety feature included. The shut-down occurs immediately while the turn-on is delayed up to 350ms. In a shut-down condition, the output voltage is <4V and the output power is <0.5W.
The voltage between different minus pole output terminals must be below 1V when units are connected in parallel. In a series operation of multiple power supplies only wiring option “A” with individual signal switches is allowed.
Please note that option C requires a current sink capability of the voltage source. Do not use a blocking diode.
Fig. 9-1 Activation of the shut-down input
Option A:
Shut-
15
down Input
OFF: linked ON : open
16
Option B:
(via open collector)
OFF: I > 0.3mA ON : I < 0.1mA
n.c.
I
15
16
-
Shut­down Input
Option C:
(via external voltage
OFF: U < 1V ON : U = 4 -29V
n.c.
+
U
16
-
down Input
Shut-
15
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM032A-EN-P — April 2014 9
Loading...
+ 19 hidden pages